Portable Emergency Unit: Compact, Robust and Easy To Handle

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Compact, Robust and

Easy to Handle
The Portable Emergency Unit is designed to be
used in situations with main DC power failure,
system replacement, battery replacement or
maintenance. Its easy handling, durability and
many configuration options should make this
unit a must to all service staff.

PORTABLE EMERGENCY UNIT


FP2 24V-48V -60V/ 2kW-3kW
Doc: M204EP.000.DS3 – rev4

GENERAL DESCRIPTION APPLICATIONS KEY FEATURES


The Portable Emergency Unit is configurable • Typically used by Telecom service staff • EASY TO HANDLE
with up to four Flatpack2 24V, 48V or 60V in situations like: • ROBUST
modules and one Smartpack controller. All o maintenance • CONFIGURABLE WITH ALL
housed in a hard case with removable lids in o replacing batteries or systems
FLATPACK2 24V, 48V AND 60V
back and front for maximum protection o failure on DC power
• OUTPUT POWER FROM 2kW TO12kW
during transport. By removing the lids you
have easy access to connections, modules, • SMARTPACK CONTROLLER
MCB and controller. Individual AC input feed • INDIVIDUAL AC INPUT FEED
and one protected DC output provides • DC OUTPUT BUSBARS WITH LUG
multiple connection options. CONNECTIONS
• ONE NEGATIVE DC OUTPUT
PROTECTED BY 150A MCB
• EXTENSION ALARM CARD

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2016 – www.eltek.com
PORTABLE EMERGENCY UNIT
(FP2 24V-48V-60V / 2kW-3kW)

TECHNICAL HARD CASE WITH REMOVABLE LIDS


SPECIFICATIONS
Model Portable Emergency Unit
Part number M204EP.0001)
INPUT DATA
Voltage 85-300VAC single phase (individual feed)
230VAC 3 phase IT network
230/400VAC 3 phase TN network
Connections Individual feed by terminal blocks 10mm2

Current (maximum) See datasheet for selected modules


AC upstream fuse See Quick Start Guide for selected
(not included) modules
OUTPUT DATA FP2 2kW FP2 3kW

Voltage 24/48/60VDC 48VDC


Power (maximum) 8kW 12kW
Current (maximum) 250A
Connections Busbars with 8mm2 cable lugs
Protection One output (negative) protected by
150A MCB
(See datasheet for selected modules)
OTHER
SPECIFICATIONS EASY ACCESSIBILITY
2)
Controller Smartpack (242100.110)
Alarm Alarm card Extension

Space for Smartpack 150A MCB for


controller protected DC out
Weight 12 kg (26,5 lbs) without modules

Dimensions[WxHxD] 530 x 140 x 510mm (21,0 x 5.5 x 20,25”)


DESIGN
STANDARDS
Electrical safety See datasheet for selected modules

EMC See datasheet for selected modules

Environment See datasheet for selected modules


4 position power shelf

1) Modules not included


2) Controller set to 48V as default, change settings for other voltages
AC input 10mm2
terminal blocks

W:530mm

DC output busbars 150 A protected


H: 140mm D: 510mm 8mm2 lug connection output (neg.)

Eltek — Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway Phone: +47 32 20 32 00 Eltek © 2016 – www.eltek.com