3RW44366BC34 Datasheet en
3RW44366BC34 Datasheet en
3RW44366BC34 Datasheet en
Power Electronics
Product designation Soft starter
Control electronics
Type of voltage of the control supply voltage AC
Control supply voltage frequency 1 rated value Hz 50
Control supply voltage frequency 2 rated value Hz 60
Mechanical data
Width mm 170
Height mm 200
Depth mm 270
Mounting type screw fixing
Mounting position with vertical mounting surface +/-90° rotatable, with
vertical mounting surface +/- 22.5° tiltable to the front
and back
Required spacing with side-by-side mounting
● upwards mm 100
● at the side mm 5
● downwards mm 75
Wire length maximum m 500
Number of poles for main current circuit 3
Connections/Terminals
Type of electrical connection
● for main current circuit busbar connection
● for auxiliary and control current circuit screw-type terminals
Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 3
Number of CO contacts for auxiliary contacts 1
Type of connectable conductor cross-sections for
main contacts for box terminal using the front
clamping point
● finely stranded with core end processing 16 ... 70 mm²
● finely stranded without core end processing 16 ... 70 mm²
● stranded 16 ... 70 mm²
Type of connectable conductor cross-sections for
main contacts for box terminal using the back
clamping point
● finely stranded with core end processing 16 ... 70 mm²
Ambient conditions
Installation altitude at height above sea level m 5 000
Environmental category
● during transport acc. to IEC 60721 3K6 (no formation of ice, no condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices),
3M6
● during storage acc. to IEC 60721 3K6 (no formation of ice, no condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices),
3M6
● during operation acc. to IEC 60721 3K6 (no formation of ice, no condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices),
3M6
Ambient temperature
● during operation °C 60
● during storage °C -25 ... +80
Derating temperature °C 40
Protection class IP IP00
other
Confirmation
UL/CSA ratings
Yielded mechanical performance [hp] for three-phase
AC motor
● at 200/208 V
— at inside-delta circuit at 50 °C rated value hp 75
● at 220/230 V
— at standard circuit at 50 °C rated value hp 50
— at inside-delta circuit at 50 °C rated value hp 100
● at 460/480 V
— at standard circuit at 50 °C rated value hp 100
— at inside-delta circuit at 50 °C rated value hp 200
Contact rating of auxiliary contacts according to UL B300 / R300
Further information
Simulation Tool for Soft Starters (STS)
https://support.industry.siemens.com/cs/ww/en/view/101494917
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RW4436-6BC34
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RW4436-6BC34
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RW4436-6BC34
120 269.7
198
148
180
7.5
153
10
100
6.5
167
7
6.5
SYS
OVERLOAD/FAILURE