3RW44366BC34 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Data sheet 3RW44 36-6BC34

SIRIUS soft starter Values at 460 V, 50 °C Standard:


145 A, 100 hp Inside-delta: 251 A, 200 hp 200-460 V
AC, 115 V AC Screw terminals

General technical data


Product brand name SIRIUS
Product feature
● integrated bypass contact system Yes
● Thyristors Yes
Product function
● Intrinsic device protection Yes
● motor overload protection Yes
● Evaluation of thermistor motor protection Yes
● External reset Yes
● Adjustable current limitation Yes
● inside-delta circuit Yes
Product component Motor brake output Yes
Reference identifier acc. to DIN EN 61346-2 Q
Reference indentifier acc. to DIN 40719 extended G
according to IEC 204-2 acc. to IEC 750

Power Electronics
Product designation Soft starter

3RW44 36-6BC34 Subject to change without notice


Page 1/7 04/10/2018 © Copyright Siemens
Operating current
● at 40 °C rated value A 162
● at 50 °C rated value A 145
● at 60 °C rated value A 125
Operating current for three-phase motors at inside-
delta circuit
● at 40 °C rated value A 281
● at 50 °C rated value A 251
● at 60 °C rated value A 217
Mechanical power output for three-phase motors
● at 230 V
— at standard circuit at 40 °C rated value W 45 000
— at inside-delta circuit at 40 °C rated value W 90 000
● at 400 V
— at standard circuit at 40 °C rated value W 90 000
— at inside-delta circuit at 40 °C rated value W 160 000
Yielded mechanical performance [hp] for three-phase hp 40
AC motor at 200/208 V at standard circuit at 50 °C
rated value
Operating frequency rated value Hz 50 ... 60
Relative negative tolerance of the operating % -10
frequency
Relative positive tolerance of the operating frequency % 10
Operating voltage at standard circuit rated value V 200 ... 460
Relative negative tolerance of the operating voltage % -15
at standard circuit
Relative positive tolerance of the operating voltage at % 10
standard circuit
Operating voltage at inside-delta circuit rated value V 200 ... 460
Relative negative tolerance of the operating voltage % -15
at inside-delta circuit
Relative positive tolerance of the operating voltage at % 10
inside-delta circuit
Minimum load [%] % 8
Adjustable motor current for motor overload A 32
protection minimum rated value
Continuous operating current [% of Ie] at 40 °C % 115
Power loss [W] at operating current at 40 °C during W 95
operation typical

Control electronics
Type of voltage of the control supply voltage AC
Control supply voltage frequency 1 rated value Hz 50
Control supply voltage frequency 2 rated value Hz 60

3RW44 36-6BC34 Subject to change without notice


Page 2/7 04/10/2018 © Copyright Siemens
Relative negative tolerance of the control supply % -10
voltage frequency
Relative positive tolerance of the control supply % 10
voltage frequency
Control supply voltage 1 at AC
● at 50 Hz rated value V 115
● at 60 Hz rated value V 115
Relative negative tolerance of the control supply % -15
voltage at AC at 60 Hz
Relative positive tolerance of the control supply % 10
voltage at AC at 60 Hz
Display version for fault signal Display

Mechanical data
Width mm 170
Height mm 200
Depth mm 270
Mounting type screw fixing
Mounting position with vertical mounting surface +/-90° rotatable, with
vertical mounting surface +/- 22.5° tiltable to the front
and back
Required spacing with side-by-side mounting
● upwards mm 100
● at the side mm 5
● downwards mm 75
Wire length maximum m 500
Number of poles for main current circuit 3

Connections/Terminals
Type of electrical connection
● for main current circuit busbar connection
● for auxiliary and control current circuit screw-type terminals
Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 3
Number of CO contacts for auxiliary contacts 1
Type of connectable conductor cross-sections for
main contacts for box terminal using the front
clamping point
● finely stranded with core end processing 16 ... 70 mm²
● finely stranded without core end processing 16 ... 70 mm²
● stranded 16 ... 70 mm²
Type of connectable conductor cross-sections for
main contacts for box terminal using the back
clamping point
● finely stranded with core end processing 16 ... 70 mm²

3RW44 36-6BC34 Subject to change without notice


Page 3/7 04/10/2018 © Copyright Siemens
● finely stranded without core end processing 16 ... 70 mm²
● stranded 16 ... 70 mm²
Type of connectable conductor cross-sections for
main contacts for box terminal using both clamping
points
● finely stranded with core end processing max. 1x 50 mm², 1x 70 mm²
● finely stranded without core end processing max. 1x 50 mm², 1x 70 mm²
● stranded max. 2x 70 mm²
Type of connectable conductor cross-sections at
AWG conductors for main contacts for box terminal
● using the back clamping point 6 ... 2/0
● using the front clamping point 6 ... 2/0
● using both clamping points max. 2x 1/0
Type of connectable conductor cross-sections for
DIN cable lug for main contacts
● finely stranded 16 ... 95 mm²
● stranded 25 ... 120 mm²
Type of connectable conductor cross-sections for
auxiliary contacts
● solid 2x (0.5 ... 2.5 mm²)
● finely stranded with core end processing 2x (0.5 ... 1.5 mm²)
Type of connectable conductor cross-sections at
AWG conductors
● for main contacts 4 ... 250 kcmil
● for auxiliary contacts 2x (20 ... 14)
● for auxiliary contacts finely stranded with core 2x (20 ... 16)
end processing

Ambient conditions
Installation altitude at height above sea level m 5 000
Environmental category
● during transport acc. to IEC 60721 3K6 (no formation of ice, no condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices),
3M6
● during storage acc. to IEC 60721 3K6 (no formation of ice, no condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices),
3M6
● during operation acc. to IEC 60721 3K6 (no formation of ice, no condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices),
3M6
Ambient temperature
● during operation °C 60
● during storage °C -25 ... +80
Derating temperature °C 40
Protection class IP IP00

3RW44 36-6BC34 Subject to change without notice


Page 4/7 04/10/2018 © Copyright Siemens
Certificates/approvals
General Product Approval EMC Declaration of
Conformity

Test Certificates Shipping Approval


Special Test Type Test
Certificate Certificates/Test
Report

other
Confirmation

UL/CSA ratings
Yielded mechanical performance [hp] for three-phase
AC motor
● at 200/208 V
— at inside-delta circuit at 50 °C rated value hp 75
● at 220/230 V
— at standard circuit at 50 °C rated value hp 50
— at inside-delta circuit at 50 °C rated value hp 100
● at 460/480 V
— at standard circuit at 50 °C rated value hp 100
— at inside-delta circuit at 50 °C rated value hp 200
Contact rating of auxiliary contacts according to UL B300 / R300

Further information
Simulation Tool for Soft Starters (STS)
https://support.industry.siemens.com/cs/ww/en/view/101494917
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RW4436-6BC34
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RW4436-6BC34
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RW4436-6BC34

3RW44 36-6BC34 Subject to change without notice


Page 5/7 04/10/2018 © Copyright Siemens
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RW4436-6BC34&lang=en
170

120 269.7

198

148
180
7.5

153

10

100

6.5

167
7

6.5

3RW44 36-6BC34 Subject to change without notice


Page 6/7 04/10/2018 © Copyright Siemens
-Q1 1/L1 3/L2 5/L3 A1 PE 95 L+ L- IN1 IN2 IN3 IN4

SYS
OVERLOAD/FAILURE

OUT 1 OUT 2 OUT 3

2/T1 4/T2 6/T3 A2 96 98 13 14 23 24 33 34 T1 T2

last modified: 04/06/2018

3RW44 36-6BC34 Subject to change without notice


Page 7/7 04/10/2018 © Copyright Siemens

You might also like