Sondex A/S PHE - Design & Datalist
___________________________________________________________________ V1044A
Anh Minh 4/23/2019
009 Item: 1
_____________________________________________________________________________
PHE-Type S9A-IG10-32-TM-STEAM Hot side Cold side
Flowrate (kg/s)/(m3/h) 0.31 60.00
Inlet temperature (°C) 130.00 102.00
Outlet Temp. Cond./Fluid (°C) 130.00 (129) 112.00
Pressure drop (bar) 0.02 / 60.47 0.89
Heat exchanged (kW) 671
Thermodynamic properties: Steam Water
Density (kg/m³) 953.63
Specific heat (kJ/kg*K) 4.22
Thermal conductivity (W/m*K) 0.68
Mean viscosity (mPa*s) 0.26
Wall viscosity (mPa*s) 0.21
Fouling factors (m²*K/kW) 0.00
Dimensioning factor % 1.33
Inlet branch F1 F3
Outlet branch F4 F2
_____________________________________________________________________________
Design of Frame / Plates:
Plate arrangement (passes*channel) 1 x 15 + 0 x 0
Plate arrangement (passes*channel) 1 x 16 + 0 x 0
Number of plates 32
Effective heat surface (m²) 3.08
Overall K-value Duty/Clean (W/m²*K) 9,621.19 9,748.89
Plate material 0.5 mm AISI 316
Gasket material / Max. temp. EPDM HT HANG ON (H) / 140
Max. design temperature (°C) 140.00
Max. Working/test pressure (bar) 10.00 13.00
Max. Differential pressure (bar) 10.00
Design according to PED 2014/68/EU(EN13445)
Liquid volume (liter) 9
Frame length (mm) 438 Max. No. of Plates 57
Net weight (kg) 138
Frame type IG
Connections HOT side : DN 65 Flange rubberlind HT PN10/PN16
Connections COLD side: DN 65 Flange rubberlind HT PN10/PN16
_____________________________________________________________________________
Category C2L BLUE RAL 5010
Sondex A/S Marsvej 5 DK-6000 Kolding
Tel: +45 76306100 Fax: +45 75538968/75505019