A/A DC Inverter U-MATCH Air Conditioners Service Manual: T1/R410A/50Hz
A/A DC Inverter U-MATCH Air Conditioners Service Manual: T1/R410A/50Hz
A/A DC Inverter U-MATCH Air Conditioners Service Manual: T1/R410A/50Hz
CONTENTS
PRODUCT .................................................................................................................................................. 1
1 MODELS LIST................................................................................................................................ 2
1.1 Outdoor Unit .............................................................................................................2
1.2 Indoor Unit................................................................................................................3
2 NOMENCLATURE ......................................................................................................................... 4
3 FUNCTION...................................................................................................................................... 5
4 PRODUCT DATA ...............................................................................................................6
4.1 Product Data at Rated Condition..............................................................................6
4.2 Operation Range ....................................................................................................19
4.3 Electrical Data ........................................................................................................20
5 PIPING DIAGRAM....................................................................................................................... 21
CONTROL ................................................................................................................................................ 23
1 OPERATION FLOWCHART ...................................................................................................... 23
1.1Cooling/Dry Operation.............................................................................................23
1.2 Heating Operation ..................................................................................................24
2 MAIN LOGIC................................................................................................................................. 25
2.1 Cooling ...................................................................................................................25
2.2 Dry Mode................................................................................................................26
2.3 Heating Mode .........................................................................................................27
2.4 Defrosting...............................................................................................................28
2.5 Fan Mode ...............................................................................................................29
3 WIRELESS REMOTE CONTROLLER..................................................................................... 30
3.1 Operation View.......................................................................................................30
4 WIRED REMOTE CONTROLLER ............................................................................................ 33
4.1 Operation View.......................................................................................................33
4.2 Buttons ...................................................................................................................34
4.3 Installation of Wired Controller and Project Debugging ..........................................36
4.4 Instruction to Operation ..........................................................................................38
4.5 Error Display ..........................................................................................................50
4.5 Dimension ..............................................................................................................51
5 CENTRALIZED CONTROLLER................................................................................................ 52
5.1 Centralized Controller-not with week timer.............................................................52
5.2 Centralized Controller-week timer ..........................................................................53
5.3 Smart Zone Controller ............................................................................................55
INSTALLATION ....................................................................................................................................... 61
1 INDOOR UNIT INSTALLATION................................................................................................. 61
1.1 Installation of Duct Type .........................................................................................61
1.2 Installation of Ceiling Type......................................................................................71
1.3 Installation of Cassette Type ..................................................................................75
2 OUTDOOR UNIT INSTALLATION ............................................................................................ 84
2.1 Before Installation...................................................................................................84
2.2 Installation Site .......................................................................................................84
2.3 Caution for Installation............................................................................................85
2.4 Dimension Data......................................................................................................86
3 REFRIGERATION PIPING WORK .......................................................................................... 86
3.1 Refrigeration Piping Work Procedures ...................................................................86
3.2 Caution in Connecting Pipes ..................................................................................89
3.3 Specification of Connection Pipe............................................................................91
4 ELECTRIC WIRING WORK ....................................................................................................... 91
4.1 Wiring Principle ......................................................................................................91
4.2 Electric Wiring Design ............................................................................................95
4.3 Specification of Power Supply Wire and Air Switch ................................................98
MAINTENANCE ....................................................................................................................................100
1 TROUBLE TABLE .....................................................................................................................100
2 FLOW CHART OF TROUBLESHOOTING............................................................................104
2.1 System Troubleshooting.......................................................................................104
2.2 Typical Troubleshooting for C series Outdoor Unit Drive (Inverter) by Single-phase
1
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
Motor ..........................................................................................................................113
2.3 Typical Troubleshooting for C series Outdoor Unit Drive (Inverter) by Single-phase
Motor ..........................................................................................................................117
2.4 Typical Troubleshooting Outdoor Unit Drive (Inverter) by Three-phase Motor......124
3 WIRING DIADRAM....................................................................................................................132
3.1 Outdoor unit..........................................................................................................132
3.2 Indoor unit ............................................................................................................136
4 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS ...............................138
4.1 Outdoor Unit .........................................................................................................138
4.2.Indoor Unit............................................................................................................203
5 EXPLODED VIEWS AND SPARE PART LIST .....................................................................221
5.1 Outdoor Unit .........................................................................................................221
5.2 Indoor Unit............................................................................................................234
2
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
PRODUCT
1
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
PRODUCT
1 MODELS LIST
1.1 Outdoor Unit
Power supply
Model Name Ref. Appearance
(V, Ph, Hz)
2
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
3
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
NOTES:
The universal outdoor units means that the customer can choose any of three kind of indoor unit to match the
outdoor unit without any change with it.
2 NOMENCLATURE
G U H D 09 N K 3 A O
1 2 3 4 5 6 7 8 9 10
C=Cool Only
3 Product Type H=Heat Pump without Aux Electric
Heaters
N=Constant Frequency
Compressor Power Supply
4 D=DC Inverter
Type Code
A=AC Inverter
N=Climate T1 Condition
6 Climate Type
T= Climate T3 Condition
1 =R22
8 Refrigerant 2=R407C
3=R410A
4
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
3 FUNCTION
Function Description
when unit restarts after power off, it will run on former status, the mode and
Memory function
parameter are kept the same
wireless controller and remote controller can be selected, and the maximum
Remote control function
control distance of remote controller is 10m.
it can timing ON/ OFF separately, meanwhile, it can also timing on circularly
Timing function
Self-diagnosis with Once the unit has malfunction, the malfunction code will be indicated and alarm
alarm function rings immediately
Sleep function it can self control for saving energy in energy saving mode.
the fan of indoor unit can adjust fan speed automatically based on actual
Automatic function
demand when cooling or heating under automatic mode
the fan starts only when the temperature of indoor unit heat exchanger is higher
Cool air proof function
than indoor temperature under heating mode
Centralized Control and Weekly Timer Functions: The centralized controller and
the weekly timer are integrated in the same wire controller. The system has both
the centralized control and the week timing functions. Up to 16 sets of units can
Weekly Time be controlled simultaneously by the centralized controller (weekly timer). The
weekly timer has the function of invalidating the lower unit. The weekly timing
function is able to realized four timing ON/OFF periods for any unit every day, so
as to achieve fully automatic operation. No timing control can be set for holidays.
High/low pressure when suction pressure is too low or discharge pressure is too high, compressor
protection will stop and unit display malfunction code
compressor has its own overheat protection.Once the temperature of
Overload protection compressor is higher than allowable level, compressor will stop and only when
temperature recovery, compressor restart
once the current of compressor is higher than normal level, compressor will stop
Over current protection
and unit display malfunction code
Discharge high once the discharge temperature of compressor is higher than allowable value,
temperature protection compressor will stop and unit display malfunction code
Reverse (open) phase once the phase sequence of power supply is incongruent or the phase is absent,
protection unit can’t work.
Anti-high temperature once the heat exchanger temperature of indoor unit is too high, the outdoor fan
protection motor will stop.
display and timing turn ON/OFF time(only with wired controller have this
Timing ON/OFF display
function)
display the speed (high,medium,low) of fan(only with wired controller have this
Fan speed display
function)
cooling mode,dry mode,heating mode,fan mode(only with wired controller have
Function model display
this function)
Testing display display testing mode(only with wired controller have this function)
display room temperature and set temperature(only with wired controller and
Temperature display
remoter board have this function)
5
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
4 PRODUCT DATA
4.1 Product Data at Rated Condition
4.1.1 Duct Type
Indoor unit GFH09K3CI GFH12K3CI
Model
Outdoor unit GUHD09NK3CO GUHD12NK3CO
kW 2.7 3.5
Cooling
Btu/h 9212 12000
Nominal Capacity
kW 2.9 3.8
Heating
Btu/h 9895 12600
Cooling kW 0.83 1.077
Power Input
Heating kW 0.803 0.974
EER/COP W/W 3.25/3.61 3.25/3.9
Indoor Unit GFH09K3CI GFH12K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil Cross Fin Coil
Type - Centrifugal fan Centrifugal fan
Drive - direct direct
Fan Motor Output kW 0.04×1 0.06×1
3
Air Flow m /h 800 840
Ext. Static Pressure Pa 25 25
Sound Pressure Level(H/M/L) dB(A) 37/35/33 37/35/33
Air Filter - Standard washable synthetic
Drain Piping mm Φ30×1.5 Φ30×1.5
Dimensions (W×H×D) 880×250×665 980×266×721
mm
(Outline/Package) 1020 ×320×745 1120×323×795
Weight(Net/Gross) kg 26/32 34/41
Outdoor Unit GUHD09NK3CO GUHD12NK3CO
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Axial fan
Fan Motor Output kW 0.75×1 0.75×1
Fan Motor Speed rpm 850 850
Type - ROTARY ROTARY
Compressor
Power Input W 1070 1070
Type - R410A
Refrigerant Control - Capillary Tube
Charge kg 1.2 1.35
Dimensions (W×H×D) 776×540×320 776×540×320
mm
(Outline/Package) 848×580×360 848×580×360
Weight(Net/Gross) kg 28/32 30/34
Liquid Inch Φ1/4" Φ1/4"
Piping Connections Gas Inch Φ3/8" Φ3/8"
Max. Length m 20 20
Max. Height Difference m 15 15
6
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued
Indoor unit GFH18K3CI GFH24K3CI GFH30K3CI
Model
Outdoor unit GUHD18NK3CO GUHD24NK3CO GUHD30NK3CO
kW 5.3 7 8.2
Cooling
Nominal Btu/h 18000 24000 28000
Capacity kW 6.15 7.5 8.8
Heating
Btu/h 21000 25500 30000
Power Cooling kW 1.65 2.19 2.56
Input Heating kW 1.7 2.08 2.44
EER/COP W/W 3.21/3.61 3.20/3.60 3.20/3.61
Indoor Unit GFH18K3CI GFH24K3CI GFH30K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil Cross Fin Coil Cross Fin Coil
Type - Centrifugal fan Centrifugal fan Centrifugal fan
Drive - direct direct direct
Fan Motor Output kW 0.07×1 0.15×1 0.15×1
Air Flow m3/h 1000 1600 1500
Ext. Static Pressure Pa 25 25 37
Sound Pressure Level(H/M/L) dB(A) 42/39/36 47/44/42 47/44/42
Air Filter - Standard washable synthetic
Drain Piping mm Φ30×1.5 Φ20×1.2 Φ20×1.2
7
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued: 2
Indoor unit GFH36K3CI GFH42K3CI GFH36K3CI
Model
Outdoor unit GUHD36NK3CO GUHD42NK3CO GUHD36NM3CO
kW 10.3 11 10.3
Cooling
Nominal Btu/h 35140 37530 35140
Capacity kW 11.5 13.2 11.5
Heating
Btu/h 39238 45038 39238
Heat Exchange - Cross Fin Coil Cross Fin Coil Cross Fin Coil
Type - Centrifugal fan Centrifugal fan Centrifugal fan
Drive - direct direct direct
Motor Output kW 0.5×1 0.5×1 0.5×1
Fan
Air Flow m3/h 2300 2300 2300
Ext. Static
Pa 37 37 37
Pressure
Sound Pressure Level(H/M/L) dB(A) 53/50/46 53/50/46 53/50/46
Air Filter - Standard washable synthetic
Drain Piping mm Φ26×2 Φ26×2 Φ26×2
8
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued: 3
Indoor unit GFH42K3CI GFH48K3CI GFH48K3CI
Model
Outdoor unit GUHD42NM3CO GUHD48NM3CO GUHD48NK3CO
kW 11 14 14
Cooling
Nominal Btu/h 37530 48000 48000
Capacity kW 13.2 16.5 16.5
Heating
Btu/h 45038 56000 56000
Cooling kW 3.4 4.35 4.35
Power Input
Heating kW 3.4 4.5 4.5
EER/COP W/W 3.24/3.88 3.21/3.67 3.21/3.67
Indoor Unit GFH42K3CI GFH48K3CI GFH48K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Centrifugal fan
Drive - direct
9
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued:4
Indoor unit GFH60K3CI
Model
Outdoor unit GUHD60NM3CO
kW 17
Cooling
Nominal Btu/h 58000
Capacity kW 18
Heating
Btu/h 61400
Cooling kW 5.3
Power Input
Heating kW 5
EER/COP W/W 3.20/3.60
Indoor Unit GFH60K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Centrifugal fan
Drive - direct
Fan Motor Output kW 0.33×1
Air Flow m3/h 3150
Ext. Static Pressure Pa 50
Sound Pressure Level(H/M/L) dB(A) 54/51/48
Air Filter - Standard washable synthetic
Drain Piping mm Φ30×1.5
10
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
11
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued 1
Indoor unit GKH30K3CI GKH36K3CI GKH42K3CI
Model
Outdoor unit GUHD30NK3CO GUHD36NK3CO GUHD42NK3CO
kW 8.8 10.3 11
Cooling
Nominal Btu/h 30000 35140 37532
Capacity kW 9.5 11.2 12.4
Heating
Btu/h 32400 38210 42300
Power Cooling kW 2.75 3.2 3.427
Input Heating kW 2.64 3 3.434
EER/COP W/W 3.20/3.60 3.22/3.73 3.21/3.61
Indoor Unit GKH30K3CI GKH36K3CI GKH42K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Centrifugal fan
Drive - direct direct direct
Fan
Motor Output kW 0.060×1 0.06 0.06
Air Flow m3/h 1660 1660 1660
Sound Pressure Level(H/M/L) dB(A) 53/51/48 53/51/48 53/51/48
Air Filter - Standard washable synthetic
Drain Piping mm Φ32×3 Φ32×3 Φ32×3
Indoor Unit Dimensions 840×320×840 840×320×840/ 840×320×840/
mm
(Outline/Package) (W×H×D) 960×394×960 960×394×960 960×394×960
Weight(Net/Gross) kg 32/43 32/43 32/46
Panel Dimensions 950×60×950/ 950×60×950/ 950×60×950/
mm
(Outline/Package) (W×H×D) 1025×115×1040 1025×115×1040 1025×115×1040
Panel Weight(Net/Gross) kg 6.5/10 6.5/10 6.5/10
Outdoor Unit GUHD30NK3CO GUHD36NK3CO GUHD42NK3CO
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Axial fan
Fan Motor Output kW 0.09×1 0.75×1
Fan Motor Speed rpm 780±20 820±20
12
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued: 2
Indoor unit GKH36K3CI GKH42K3CI
Model
Outdoor unit GUHD36NM3CO GUHD42NM3CO
kW 10.3 11
Cooling
Nominal Btu/h 35140 37530
Capacity kW 11.2 12.4
Heating
Btu/h 38210 42300
Cooling kW 3.18 3.3
Power Input
Heating kW 3.1 3.3
EER/COP W/W 3.24/3.61 3.33/3.75
Indoor Unit GKH36K3CI GKH42K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil Cross Fin Coil
13
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
kW 3.0 3.4
Cooling
Nominal Btu/h 10236 11600
Capacity
kW 3.0 3.8
Heating
Btu/h 10236 13000
Power Cooling kW 0.857 1.059
Drive - Direct
Fan
Motor Output kW 0.008×1 0.015×1
Air Flow m3/h 650 700
Type - R410A
Refrigerant Control - Capillary Tube
Charge kg 1.2 1.35
Dimensions (W×H×D) 776 x540x320 776 x540x320
mm
(Outline/Package) 848×580×360 848 ×580×360
14
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued
Indoor unit GTH18K3CI GTH24K3CI GTH30K3CI
Model
Outdoor unit GUHD18NK3CO GUHD24NK3CO GUHD30NK3CO
kW 5.3 7 8.8
Cooling
Nominal Btu/h 18000 24000 30000
Capacity kW 6.15 8 9.5
Heating
Btu/h 21000 27000 32400
15
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued:2
Indoor unit GTH36K3CI GTH42K3CI GTH36K3CI
Model
Outdoor unit GUHD36NK3CO GUHD42NK3CO GUHD36NM3CO
kW 10.6 11.9 10.6
Cooling
Nominal Btu/h 36160 40600 36167
Capacity kW 12 13.5 12
Heating
Btu/h 40940 46060 40940
Power Cooling kW 3.26 3.707 3.262
Input Heating kW 3.16 3.3 3.077
EER/COP W/W 3.25/3.8 3.21/4.09 3.25/3.9
Indoor Unit GTH36K3CI GTH42K3CI GTH36K3CI
Power Supply - 220-240V-50Hz-1Ph 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil Cross Fin Coil
Type - Centrifugal fan Centrifugal fan
Drive - Direct Direct Direct
Fan
Motor Output kW 0.15 0.15 0.15
Air Flow m3/h 2000 2000 2000
Sound Pressure Level(H/M/L) dB(A) 54/51/48 54/51/48 54/51/48
Air Filter - Standard washable synthetic
Drain Piping mm Φ17×2.5 Φ17×2.5 Φ17×2.5
16
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued: 3
Indoor unit GTH42K3CI GTH48K3CI GTH48K3CI
Model
Outdoor unit GUHD42NM3CO GUHD48NM3CO GUHD48NK3CO
kW 11.9 14 14
Cooling
Nominal Btu/h 40600 48000 48000
Capacity kW 13 16.5 16.5
Heating
Btu/h 44356 56000 56000
Power Cooling kW 3.6 4.2 4.2
Input Heating kW 3.3 4.4 4.4
EER/COP W/W 3.3/3.94 3.33/3.75 3.33/3.75
Indoor Unit GTH42K3CI GTH48K3CI GTH48K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Centrifugal fan
Drive - Direct
Fan
Motor Output kW 0.15 0.25 0.18
Air Flow m3/h 2000 2300 2300
Sound Pressure Level(H/M/L) dB(A) 54/51/48 58 58
Air Filter - Standard washable synthetic
Drain Piping mm Φ17×2.5 Φ17×1.75 Φ17×1.75
Dimensions (W×H×D) 1420×245×700 1700×245×700
mm
(Outline/Package) 1545×330×825 1825×330×825
Weight(Net/Gross) kg 55/63 64/72 64/72
Outdoor Unit GUHD42NM3CO GUHD48NM3CO GUHD48NK3CO
Power Supply - 380-415V-50Hz-3Ph 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Axial fan
17
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Continued:4
Indoor unit GTH60K3CI
Model
Outdoor unit GUHD60NM3CO
kW 16
Cooling
Btu/h 54500
Nominal Capacity
kW 17.5
Heating
Btu/h 59700
Cooling kW 5
Power Input
Heating kW 4.86
EER/COP W/W 3.20/3.60
Indoor Unit GTH60K3CI
Power Supply - 220-240V-50Hz-1Ph
Heat Exchange - Cross Fin Coil
Type - Centrifugal fan
Drive - Direct
Fan
Motor Output kW 0.25×1
Air Flow m3/h 2300
Sound Pressure Level(H/M/L) dB(A) 58/55/52
Air Filter - Standard washable synthetic
Drain Piping mm Φ17×1.75
Dimensions (W×H×D) 1700×245×700
mm
(Outline/Package) 1825×330×825
Weight(Net/Gross) kg 65/73
Outdoor Unit GUHD60NM3CO
Power Supply - 380-4150V-50Hz-3Ph
Heat Exchange - Cross Fin Coil
Type - Axial fan
Fan Motor Output kW 0.082×2
Fan Motor Speed rpm 800±20
Type - ROTARY
Compressor
Power Input W 4220
Type - R410A
Refrigerant Control - Electronic Expansion Valve
Charge kg 5.5
Dimensions (W×H×D) 1085×1365×427
mm
(Outline/Package) 1140×1390×475
Weight(Net/Gross) kg 127/133
Liquid mm Φ3/8"
Piping Connections Gas mm Φ3/4"
Max. Length m 50
Max. Height Difference m 30
18
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
Note:
① Nominal capacities are based on the follow conditions.
② The air volume is measured at the relevant standard external static pressure.
③ Noise is tested in the Semianechoic room, so it should be slightly higher in the actual operation due to
environmental change.
4.2 Operation Range
Mode Range of Outdoor Temperature℃ (℃)
Cooling 18℃-48℃
Heating -7℃-24℃
19
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
20
A/A DC INVERTER U-MATCH AIR CONDITIONERS PRODUCT
5 PIPING DIAGRAM
Outdoor Heat Exchange
4-way Valve
Compressor Throttle
Heating
Cooling
Vapour Liquid Separator
Outdoor
Indoor
Throttling Method:
GUHD09NK3CO~GUHD12NK3CO:Capillary Tube
GUHD18NK3CO~GUHD48NK3CO:Electronic expansion valve
GUHD36NM3CO~GUHD60NM3CO:Electronic expansion valve
21
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
CONTROL
22
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
CONTROL
1 OPERATION FLOWCHART
1.1Cooling/Dry Operation
23
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
24
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
2 MAIN LOGIC
2.1 Cooling
Cooling mode
Acc.to control
ON logic
OFF
compressor Acc.to control
ON logic
OFF
Outdoor fan 60s
30s
Xsteps 180steps
150s atfer the compressor is stoped
EXV
Firstly switch off to step 0 and
60s
then switch off step 60
OFF
4-way valve
ON
After the cooling command is sent out, the indoor fan will run at high speed for 5 seconds before it is put into
operation according to the setting. Then, it is started to calculate the system load demand value. If the load is 0, the
other loads except the indoor fan will not be put into operation (The water pump will run according to the pump
control logic behind). If the load is >0, the EXV will be firstly opened to step X; then the indoor fan is started. After 30
seconds, the compressor is started at initial frequency 40Hz and will be maintained for 3 minutes. After that, the
compressor, EXV and outdoor fan will adjust according to logic.
25
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Acc.to controll
ON logic
OFF
Compressor
Acc.to controll
ON logic
OFF 60s
Outdoor fan
30s
Xsteps 180steps
150s atfer the compressor is stoped
EXV
Firstly switch off to step 0
150s
OFF and then switch off step 60
4-way valve
ON
Indoor fan OFF
(cooling)
3s
The dry mode is basically same as cooling mode. The difference is that:
① The indoor fan is fixed at low speed.
② Max. capacity output: A×90%
26
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
capacity
demand>0
When the heating command is sent out, it is started to calculate the system load demand value. If the load is 0,
all the loads will not be put into operation. If the load is >0, the EXV will be firstly opened to step Y; then the outdoor
fan is started. After 30 seconds, the compressor will increase its frequency to the required initial frequency 40Hz
before it started. It is started to count the time when the compressor frequency is increased to 20Hz. After 10
seconds, the 4-way valve is energized and then the indoor fan will run as per cold air prevention mode. The
compressor will keep running at initial frequency for 3 minutes. After that, the compressor, EXV and outdoor fan will
adjust according to logic.
27
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
2.4 Defrosting
H e a tin g /D e fro s tin g T im e s e q u e n c e c h a rt
C o n d itio n fo r e n d in g
th e d e fro st
D e fro stin g D e fro stin g
m a rk in g D e fro stin g fre q u e n cy ends
A d ju s t p e r P I
C o m p re ss o r
10s
10s
35H z
35H z
ON H ig h fa n A c c. to o u td o o r fa n c o n tro l lo g ic
O u td o o r fa n
OFF
3 m in
F ix e d ste p Y A d ju s t a c co rd in g to c o n tro l lo g ic
EXV
E n e rg ize d
4 -w a y v a lve
D e -e n e rg iz e d
C o ld a ir p re ve n tio n
ON
In d o o r fa n
OFF
A cc .to th e c o n d itio n s fo r
s ta rtin g th e a u xilia ry p o w e r
ON
A u xila ry p o w e r
O FF
T im e
M e e t th e co n d itio n s fo r
e n d in g th e d e fro s t
28
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Fan Mode
OFF
Compressor
OFF OFF
Outdoor fan
Run at present
High fan
speed
OFF OFF
Indoor fan
OFF
4-way valve
Time
5s
The indoor fan will run at high speed for 5 seconds before running at preset speed
29
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
SWING FAN
AUTO FAN
OPER
AUTO
AIR
SWING
MODE ON/OFF
1 ON/OFF button Press the button to set turning on/off the unit
Press the button to select the mode,
2 Mode button
cooling , heating , fan or auto mode.
3 Increase/Decrease button Press this button to increase/decrase the setup temp
30
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
TIMER TIMER
ON/OFF HR ON/OFF
HR
SLEEP AIR
LIGHT HUMID
31
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
SWING FAN
TIMER
ONOFF HR
32
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
33
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
34
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Press Mode and ▲for 5s under off state of the unit to enter/cancel key
4 Mode memory function (If memory is set, indoor unit will resume original
and Memory function setting state after power failure and then power recovery. If not, indoor
2▲ unit is defaulted to be off after power recovery. Memory function is
defaulted to be off before outgoing.)
Upon startup of the unit without malfunction or under off state of the unit,
2▲
press ▲ ▼ key at the same time for 5s in to lock state. In this case, any
and Lock
other buttons won’t respond the press. Repress ▲ ▼ key for 5s to quit
6▼
lock state.
35
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Fig.4.3.1: Fig.1 Surface mounting of Cable Fig.4.3.2: Fig.2 Concealed mounting of Cable
No. 1 2 3 4 5
Socket’s base
Soleplate of Front panel of
Description box installed in Screw M4X25 Screw ST2.2X6.5
controller controller
the wall
Fig.4.3.3: Sketch for Installation of Wired Controller. Pay attention to the following items during installation of wired
controller:
1. Cut off power supply of heavy-current wire embedded in mounting hole in the wall before installation. It is
prohibited to perform the whole procedure with electricity.
2. Pull out 4-core twisted pair line in mounting hole and then make it through the rectangle hole at the back of
controller’s soleplate.
3. Joint the controller’s soleplate on wall face and then fix it in mounting hole with screws M4X25.
4. Insert the 4-core twisted pair line through rectangle hole into controller’s slot and buckle the front panel and
soleplate of controller together.
5. At last, fix the controller’s front panel and soleplate with screws ST2.2X6.5.
36
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Caution:
During connection of wirings, pay special attention to the following items to avoid interference of electromagnetism
to unit and even failure of it.
1. To ensure normal communication of the unit, signal line and wiring (communication) of wired controller should be
separate from power cord and indoor/outdoor connection lines. The distance between them should be kept 20cm
in min.
2. If the unit is installed at the place where there is interference of electromagnetism, signal line and wiring
(communication) of wired controller must be shielded by twisted pair lines.
4.3.2 Project Debugging
Enquiry of wired controller’s address: Press Function and Mode buttons at the same time for 5s under off state
of the unit, and then LCD displays wired controller’s address number.
Setting of wired controller’s address: Press Function and Mode buttons at the same time for 5s.In this case,
LCD displays address number. Then press ▲ or ▼ button to adjust address (address no.:1-16) .After that, press
Enter/cancel button to confirm.
Addresses of the wired controller are used for centralized control of wired controller. Enquiry and setting of
wired controller’s address is shown as Fig.4.3.4 below:
37
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note: The state shown in Fig.4.4.1 indicates off-state of the unit after energization.
The state shown in Fig.4.4.2 indicates on-state of the unit after energization.
38
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Fig 4.4.3
Fig.4.4.4
39
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Fig. 4.4.5
4.4.6Timer Setting
Press Timer button to set timer off of the unit. Under off-state of the unit, press Timer button to set timer on of
the unit in the same way.
Timer on setting: Under off-state of the unit without timer setting, if Timer button is pressed, LCD will display xx.
Hour, with ON blinking. In this case, press▲ or ▼ button to adjust timer on and then press Timer to confirm. If Mode
button is pressed before pressing Timer button to confirm, timer mode will be switched to timer off setting mode. In
this case, LCD displays xx. Hour, with OFF blinking. In this case, press▲ or ▼ button to adjust timer off and then
press Timer to confirm. When LCD displays xx. Hour On Off, xx. Hour means time of timer on, but time of timer off
won’t be displayed.
Timer off setting: Under on-state of the unit without timer setting, if Timer button is pressed, LCD will display xx.
Hour, with OFF blinking. In this case, press▲ or ▼ button to adjust timer on and then press Timer to confirm. If
Mode button is pressed before pressing Timer button to confirm, timer mode will be switched to timer on setting
mode. In this case, LCD displays xx. Hour, with ON blinking. In this case, press▲ or ▼ button to adjust timer on and
then press Timer button to confirm. When LCD displays xx. Hour On Off, xx. Hour means time of timer off, but time
of timer on won’t be displayed.
Cancel timer: After setting of timer, if Timer button is pressed, LCD won’t display xx. Hour so that timer
setting is canceled.
Timer off setting under on-state of the unit is shown as Fig.4.4.6
40
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Timer range: 0.5-24hr. Every press of▲ or ▼ button will make setting time increased or decreased by 0.5hr.If press
either of them continuously, setting time will automatically increase/ decrease by 0.5hr every 0.5s.
Note:
1. If both timer on and timer off are set in unit on interface, the wired controller only display time of time off. If both of
them are set in unit off-state, only time of timer on is displayed.
2. Timer on in unit on-state is timed from the time of unit off and timer off in unit off-state is timed from the time of unit
on.
41
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note: In air exchange mode, press Function button or there is not any operation within 5s after the last button
operation, the system will be quit from air exchange setting and current energy-saving data won’t be
memorized.
42
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note: In cooling and dry mode, if the unit with sleep function has run for 1 hour, the preset temperature will be
increased by 1°C and 1°C in another 1 hour. After that, the unit will run at this temperature. In heating mode,
if the unit with sleep function has run for 1 hour, the preset temperature will be decreased by 1°C and 1°C in
another 1 hour. After that, the unit will run at this temperature.
4.4.9 Turbo Function Setting
TURBO function: The unit at high fun speed can realize quick cooling or heating so that room temperature can
quickly approach setting temperature.
In cooling or heating mode, press Function button till the unit enters TURBO function and then press
Enter/cancel button to turn on TURBO function.
During TURBO function, press Function button till the unit enters TURBO function and then press
Enter/cancel button to cancel TURBO function.
TURBO function setting is shown in Fig.4.4.9 :
43
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note:
1. TURBO function will be turned off after power failure and then recovery. In dry, fan and auto mode, TURBO
function can not be set and TURBO mark won’t be displayed.
2. TURBO function will be automatically canceled after setting of quiet function.
44
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note:
1. In Auto running mode with save function on, the unit will be forcibly quit Auto running Mode and change to current
operation mode, After setting of save, sleep function will be canceled.
2. In save mode, if Function button is pressed or there is not any operation within 5s after the last button operation,
the system will be quit from save function setting and current data won’t be memorized.
3. After power failure and then recovery, save function setting will be memorized.
4. The lower limited value in cooling mode is 16°C and the upper limited value in heating mode is 30°C.
5. After save setting, if the setting temperature is out of the range in the mode, the limited value will prevail.
45
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note:
E-HEATER can not be set in cooling, dry and fan mode, E-HEATER mark won’t be displayed. The setting is
shown in Fig.4.4.11.
46
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note:
1.After setting BLOW function, turn off the unit by pressing On/Off button on remote controller, indoor fan will run at
low fan speed for 10 min. (BLOW shows).Meanwhile, if BLOW function is canceled indoor fan will be turned off
directly.
2.There is not BLOW function in fan or heating mode.
47
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
48
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Note:
1. This function will be shielded after energization of 12hr for some models of the units without outdoor ambient
sensors. Please refer to Instruction for details.
2. If malfunction of outdoor ambient sensor occurs, this function will be shielded in 12hr.
49
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Under off-state of the unit, press Mode and ▼ at the same time for 5s, the displayer panel will switch between
Centigrade and Fahrenheit.
4.5 Error Display
If there is malfunction during running of the system, LCD will display error code at temperature–displayed
location. Once there is more than one malfunction, error codes will be displayed circularly. If there are multiple circuit
systems, the system number of failed system will be displayed before the colon (not for single system).
If malfunction occurs, turn off the unit and contact nearest dealer for help.
As shown in Fig.4.5.1, it means high pressure protection of system 2 under unit on.
Fig.4.5.1
50
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Error code meaning:
E6 Communication malfunction
4.5 Dimension
51
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5 CENTRALIZED CONTROLLER
5.1 Centralized Controller-not with week timer
5.1.1 Function
Centralized Controller-not with week timer only control on-off function of every unit. Up to 16 sets of units can be
controlled simultaneously by the centralized controller-not with week timer.
5.1.2 Operation View
52
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.1.4 Dimensions
53
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
Press “▲” and selected the unit or a certain day in one week or specific value.
2 Increasing button
Press “▲” can set week part of time.
Press “ ” and selected the unit or a certain day in one week or specific value.
3 Decreasing button
Press “ ” can set week part of time.
CANCEL/DELETE short-press “cancel/delete” to back to default page or last process, long-press
4
button “cancel/delete” to cancel timer of a certain time period in a certain day.
SINGLLE/GROUP short-press “single/group” to enter single control setting. “SINGLE” displayed.
5
button long-press “single/group” to enter group control setting. “GROUP” displayed
TIMER/TIME Short-press “timer/time” to enter timer setting.
6
button Long-press “timer/time” under default page can begin time setting.
7 On/off button Press the button to set start or close the unit.
54
DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
5.2.4 Dimensions
55
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
1. Under the single/centralized control status:It is used to set the running temperature
4 ▲ of the indoor unit with max.30℃ anmin.16℃.
2. Under the timing setting status:It is used to set the timing period with max.24 hours
and min.0 hour.
5 ▼ 3. Under the clock setting status: it is used to set the hour (max.:23, min.: 0) and minute
(max.:59, min.: 0) of the clock.
Mon It is used for the switchover between unit 1 and unit 9;
6
1/9 Under the timing or clock setting status, it indicates Monday.
Tue It is used for the switchover between unit 2 and unit 10;
7
2/10 Under the timing or clock setting status, it indicates Tuesday.
Wed It is used for the switchover between unit 3 and unit 11
8
3/11 Under the timing or clock setting status, it indicates Wednesday.
Thu It is used for the switchover between unit 4and unit 12
9
4/12 Under the timing or clock setting status, it indicates Thursday.
Fri It is used for the switchover between unit 5and unit 13
10
5/13 Under the timing or clock setting status, it indicates Friday.
Sat It is used for the switchover between unit 6 and unit 14;
11
6/14 Under the timing or clock setting status, it indicates Saturday.
Sun It is used for the switchover between unit 7 and unit 15
12
7/15 Under the timing or clock setting status, it indicates Sunday.
13 8/16 It is used for the switchover between unit 8 and unit 16
It is used to set the timing or on/off time of the selected indoor unit as well as to set the
14 Timer/Time
clock of the system.
15 Central It is used for the switchover between single and centralized control modes.
16 Shield It is used to deactivate some or all functions of a single or a group the indoor unit(s).
56
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
Functions of Press Buttons
Table 2: Functions of Press Buttons
No. Name Function Description
1 Mode It is used for the switchover among different modes
2 Fan It is used to set the fan speed, high, medium, low or auto.
1. Under the single/centralized control status:It is used to set the running temperature
4 ▲ of the indoor unit with max.30℃ anmin.16℃.
2. Under the timing setting status:It is used to set the timing period with max.24 hours
and min.0 hour.
5 ▼ 3. Under the clock setting status: it is used to set the hour (max.:23, min.: 0) and minute
(max.:59, min.: 0) of the clock.
Mon It is used for the switchover between unit 1 and unit 9;
6
1/9 Under the timing or clock setting status, it indicates Monday.
Tue It is used for the switchover between unit 2 and unit 10;
7
2/10 Under the timing or clock setting status, it indicates Tuesday.
Wed It is used for the switchover between unit 3 and unit 11
8
3/11 Under the timing or clock setting status, it indicates Wednesday.
Thu It is used for the switchover between unit 4and unit 12
9
4/12 Under the timing or clock setting status, it indicates Thursday.
Fri It is used for the switchover between unit 5and unit 13
10
5/13 Under the timing or clock setting status, it indicates Friday.
Sat It is used for the switchover between unit 6 and unit 14;
11
6/14 Under the timing or clock setting status, it indicates Saturday.
Sun It is used for the switchover between unit 7 and unit 15
12
7/15 Under the timing or clock setting status, it indicates Sunday.
13 8/16 It is used for the switchover between unit 8 and unit 16
It is used to set the timing or on/off time of the selected indoor unit as well as to set the
14 Timer/Time
clock of the system.
15 Central It is used for the switchover between single and centralized control modes.
16 Shield It is used to deactivate some or all functions of a single or a group the indoor unit(s).
57
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
Introduction to Symbols on the LCD
1 Fan speed It displays the fan speed of the indoor unit, high, medium, low and auto.
2 Running mode It displays the running mode of the indoor unit, auto, cool, dry, fan and heat.
It displays the current time (hour and minute) in 24-hour time system and
3 System clock
also the week day.
4 Shield It displays the shield status, “ALL’, “TEMP”, “MODE” and ‘On/Off”.
5 Weekly timer It displays the timing period (unit: 0.5 hour) which will circulate every week.
Set temperature It displays the set temperature, indoor unit code (01-16), and symbols of
6
Indoor unit code Celsius and Fahrenheit scale.
It displays “CENTER” under the centralized control mode and no display
7 Control mode
under the single control mode.
Ambient temperature It displays the ambient temperature, serial port as well as symbols of Celsius
8
Serial port and Fahrenheit scale.
Numbers indicate the indoor unit codes which will be displayed when the
Indoor unit code
9 corresponding indoor unit is online; “ ” indicates the on/off status of the
On/off status
indoor unit, its flashing for “on” or else for “off”
Error It displays the error codes when some error(s) arises and also “CHILD
10
Child lock LOCK” when this function is activated.
58
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
5.3.7 Dimensions
59
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
INSTALLATION
60
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
INSTALLATION
1 INDOOR UNIT INSTALLATION
1.1 Installation of Duct Type
1.1.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or internal damage,
please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list. Ensure that
the model is correct and the machine is in good condition. Please also check if the specification and quantity of
accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing possible hazard.
For the sake of protection and safety, it is suggested to move the unit with the packaging box. Even though it is
not permitted to do like this under special occasions, do not remove the packaging box, thus to avoid loosening
or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the building,
make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive substances are
stored, thus to avoid possible explosion or fire due to leakage.
1.1.2 Installation Site
Ensure the top hanging piece has strong strength to withstand the weight of the unit.
The drainage pipe has convenient flow of water.
There is no obstacle blocking the return air inlet and exhaust outlet, so as to ensure sound air circulation.
The installation spaces required by the drawing must be ensured, so as to provide enough space for the
service and maintenance.
The installation site must be far away from heat source, leakage of inflammable gas or smoke.
The indoor unit is of ceiling mount (indoor unit is hidden inside the ceiling).
The indoor and outdoor units, the power cable and the connecting electrical lines must be at least 1 meter from
any TV set or radio. This is to avoid image interference or noise of the TV set or radio. (Even if the distance is 1
meter, noise can also exist if there is strong electric wave.)
1.1.3 Caution for Installation
1) Generally, the unit is installed indoor on ceiling. For ceiling mounting, ensure that the hangers on ceiling have
adequate strength to support the weight of the unit.
2) To meet the noise and vibration requirements, the unit shall be installed by using rubber pad (thickness ≥20mm)
and rubber connector.
3) Insert a M10 expansion bolt into the hole. Drive a nail into the bolt. Refer to the profile dimensions drawing of
the indoor unit for the distance between the holes. Refer to Figure 1 for the installation of the expansion bolt,
as Figure 1-1-1 shows.
61
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-1-3
4) Install the hanger onto the indoor unit as Figure 1-1-2 and Figure 1-1-3 shows.
5) Install the indoor unit at the ceiling as Figure 1-1-5 shows.
mm
Screw
I
Hanger
Nut
62
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
7) Level inspection of the indoor unit
After the indoor unit is installed, it is required to check the level of the whole unit. The unit
must be placed horizontally, but the condensate pipe shall be installed obliquely, so as to
facilitate the drainage of condensate.
Level Instrument
i
Air Intake Air Supply
Condensate Drainpipe
Enlarged View
As the inside of the unit is in the negative
Condensate Drainpipe pressure status, it is required to set up a
backwater elbow. The requirements is:
A=B≥P/10+20(mm)
P is the absolute pressure inside the unit.
The unit of the pressure is Pa.
Figure 1-1-6
Be suit for :
GFH09K3CI
GFH12K3CI
GFH18K3CI
63
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Be suit for :
GFH24K3CI
GFH30K3CI
GFH36K3CI
GFH42K3CI
GFH48K3CI
64
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Item
A B C D E F G H I J
Model
GFH09K3CI 840 561 635 790 880 665 738 125 203 250
GFH12K3CI 932 430 738 892 980 721 738 125 203 266
GFH18K3CI 932 430 738 892 980 721 738 125 203 266
GFH24K3CI
1101 515 820 1159 1270 530 1002 160 235 268
GFH30K3CI
GFH36K3CI
1011 748 820 1115 1226 775 979 160 231 290
GFH42K3CI
GFH48K3CI 1015 788 820 1115 1226 815 979 160 261 330
GFH60K3CI 1353 632 992 1150 192 343 1463 385 799 --
Unit:mm
Insulation materials for gas pipe 1 Used for gas pipe connector on indoor unit
Insulation materials for liquid pipe 1 Used for liquid pipe connector on indoor unit
4
4 sets, used for ceiling mounting of the indoor unit
Nut and spring gasket 4
Strap 4 or 8 pcs 4 pcs for 18KBtu/h unit and 8 pcs for others
Wired controller 1
Remote controller 1
Battery 2
Power cord 1 – 2 pcs 2 pcs for36-45 KBtu/h unit and 1 pc for others
Connection wire
65
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.1.5 Installation Clearance Data
Be suit for :
GFH09K3CI
GFH12K3CI
GFH18K3CI
Be suit for:
GFH24K3CI
GFH30K3CI
GFH36K3CI
GFH42K3CI
GFH48K3CI
Be suit for :
GFH60K3CI
Fig.36
Warning:The height of installation for the indoor unit should be 2.5m above.
66
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.1.6 Drain Piping Work
1) Installation of Drainage Pipeline
A drainage outlet is located at both the left and right sides of the indoor unit. After selecting one drainage outlet,
the other outlet shall be blocked by rubber plug. Bundle the blocked outlet with string to avoid leakage, and
also use thermal insulation materials to wrap the blocked outlet.
When shipped out from factory, both the Drainage outlets are blocked by rubber plugs.
When connecting the drainage pipe with the unit, do not apply excessive force to the pipeline at the side of the
unit. The fixing position of the pipeline shall be near the unit.
Purchase general-purpose hard PVC pipe locally to be used as the drainage pipeline. When carrying out
connection, place the end of the PVC pipeline into the drainage hole. Use flexible drainage tube and tighten it
with thread loop. Never use adhesive to connect the drainage hole and the flexible drainage tube. (As shown in
Figure 1-1-9)
When the laid drainage pipe is used for multiple units, the common pipe shall be about 100mm lower than the
drainage outlet of each set of unit. A pipe with thicker wall shall be used for such purpose.
Sponge(attachment)
Clamp Clamp(attachment)
Figure 1-1-9
2) Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system.
During the test, check if the water correctly flows through the pipelines. Carefully observe the joints to ensure
that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating the
ceiling.
3) Matters of Attention
The joint of Drainage Pipeline must not have leakage.
The Drainage Pipeline shall be installed with an inclining angel of 5~10°, so as to facilitate the drainage of
condensate. The joints of the Drainage Pipeline must be covered by thermal insulation materials to avoid
generation of exterior condensate. (As shown in Figure 1-1-10)
Pipe cover
Figure 1-1-10
1.1.7 Installation of air duct and round duct for duct-type unit
Caution:
The supply air duct, the return air duct and the fresh air duct must be covered with a layer of thermal insulation,
so as to avoid thermal leakage and condensation. Firstly apply liquid nail on the duct, and then attach the
thermal insulation cotton with a layer of tinfoil. Use the liquid nail cover to fix it. Lastly use tinfoil adhesive tape
to carefully seal the joints; other good thermal insulation materials can also be used.
The supply air duct and the return air duct shall be fixed to the prefabricated boards of the ceiling by using iron
67
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
supports. The joints of the pipes must be sealed by glue so as to avoid leakage.
The design and installation of air duct must be in conformity with the relevant state engineering criteria.
The edge of the return air duct must be at least 150mm away from the wall. The return air inlet must be
covered with filter.
Silencing and shock absorption shall be considered in the design and installation of the air duct. Additionally,
the noise source must be far away from where people stay. The return air inlet shall not be located above the
place where users stay (offices and rest places, etc.).
1) Installation of supply air duct
Installation of rectangular air duct, as shown in Fig. 1-1-11
Figure 1-1-11
Serial No. Name Serial No. Name
1 Hanger rod 5 Filter
2 Return air duct 6 Main supply air duct
3 Canvas air duct 7 Supply air outlet
4 Return air inlet
68
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-1-12
Number Name Number Name
1 Hanger rod 6 Transition air duct
2 Return air duct 7 Supply air duct
3 Canvas air duct 8 Diffuser
4 Return air louver 9 Diffuser joint
5 Supply air outlet
Notes:
The above two figures only indicate the installation of back return return air inlet. Down return air
inlet may also be used as needed for actual installation. The installation method is similar to that of
back return air inlet. Among all the Supply air outlets, at least one shall be kept open. Round air
duct can also be used, in which a thermally insulated round hose is used to supply the air to the
room. Both the supply air duct and return air duct shall be thermally insulated.
2) Installation of fresh air duct (Limited to excessive residual pressure unit with a cooling capacity
over 6000W)
Cut off the fresh air baffle when connecting the fresh air duct, as shown in Fig. 1-1-13(a). If not using the fresh
air duct, please use sponge to seal the fresh air baffle clearance.
Mount the round flange for connection of the fresh air duct, as shown in Fig. 1-1-14(b).
Both the air duct and round flange shall be well sealed and thermally insulated.
(a) (b)
Figure 1-1-13
3) Installation of return air duct
The square flange is mounted on rear section when it is shipped. The return air inlet cover plate is mounted
69
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
beneath, as shown in Fig. 1-1-14.
Figure 1-1-14
If down return air inlet is to be used, just change the position between square flange and cover plate of return
air inlet.
Rivet the return air duct to the return air inlet of indoor unit and connect another end to return air window. For
free adjustment of the height, you may fabricate a section of canvas air duct and reinforce with 8# iron wire in
folded form. You may select the installation methods in overall consideration of the building and maintenance
conditions, as shown in Fig. 1-1-15.
Supply air
Supply air
Figure 1-1-15
70
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
4) Installation of round Supply air outlet
Figure 1-1-16
1.2 Installation of Ceiling Type
1.2.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or internal damage,
please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list. Ensure that
the model is correct and the machine is in good condition. Please also check if the specification and quantity of
accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing possible hazard.
For the sake of protection and safety, it is suggested to move the unit with the packaging box. Even though it is
not permitted to do like this under special occasions, do not remove the packaging box, thus to avoid loosening
or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the building,
make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive substances are
stored, thus to avoid possible explosion or fire due to leakage.
1.2.2 Installation Site
Such a place where cool air can be distributed throughout the room.
Such a place where condensation water is easily drained out.
Such a place that can handle the weight of indoor unit.
Such a place which has easy access for maintenance.
Such a place where is permitting easy connection with the outdoor unit.
Such a place where is 1m or more away from other electric appliances such as television, audio device, etc.
Avoid a location where there is heat source, high humidity or inflammable gas.
Do not use the unit in the immediate surroundings of a laundry, a bath, a shower or a swimming pool.
Be sure that the installation conforms to the installation dimension diagram.
The space around the unit is adequate for ventilation
1.2.3 Caution for Installation
Adjust the distance from the unit to the ceiling slab beforehand (Refer to Figure 1-2-1).
Fix the hanger bracket to the suspension bolt (Refer to Figure 1-2-2).
Make sure that extended suspension bolt from the ceiling stays inside the arrowed position. Readjust the
hanger bracket when it is outside the arrowed position. (Refer to Figure 1-2-3)
Suspension bolt stays inside the cap of indoor unit .Never remove the cap. Lift the unit and slide forward unit
the dent. (Refer to Figure 1-2-4)
Screw tightly both hanger bracket setting bolts (M8) (Refer to Figure 1-2-2)
Screw tightly both hanger bracket fixing bolts (M6) to prevent the movement of the indoor unit. (Refer to Figure
71
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1-2-2)
Adjust the height by turning the nut with a spanner. Insert the spanner from the hanger bracket opening. (Refer
to Figure 1-2-5)
INNARD
Figure 1-2-3 Hanger bracket BOLT POSITION Figure 1-2-4
In case of hanging:
It is possible to install using inward facing hanger bracket by not removing the brackets from the indoor unit.
(Refer to Figure 1-2-6) Be sure to use only the specified accessories and parts for installation work.
72
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.2.4 Dimension Data
Figure 1-2-7
Unit: mm
Model A B C D E
GTH09K3CI
GTH12K3CI
1220 225 1158 700 280
GTH18K3CI
GTH24K3CI
GTH30K3CI
GTH36K3CI 1420 245 1354 700 280
GTH42K3CI
GTH48K3CI
GTH60K3CI 1700 245 1634 700 280
150cm or more
60cm or more
60cm or more
Fixing screw(M4.2)
Figure 1-2-8
73
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Clamp(attachment)
Clamp
Figure 1-2-9
2) Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system.
During the test, check if the water correctly flows through the pipelines. Carefully observe the joints to ensure
that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating the
ceiling.
3) Matters of Attention
The drain pipe outlet direction can be chosen from either the right rear or right.
The diameter of the drain pipe should be equal to or greater than the diameter of the connecting pipe. (Vinyl
tube; pipe size: 20mm; outer dimension: 26mm)
Keep the drain pipe short and incline downwards at a gradient of at least 1/100 to prevent air pockets. (Refer to
Figure 1-2-10)
74
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-2-10
No folding of drain hose inside the indoor unit. (Refer to Figure 1-2-11)
Confirm that smooth drainage is achieved after the piping work. Pour 600 cc of water into the drain pan from
the air outlet for confirming drainage. (Refer to Figure 1-2-12)
After receiving the machine, please check for any transport damage. If finding any surface or internal damage,
please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list. Ensure that
the model is correct and the machine is in good condition. Please also check if the specification and quantity of
accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing possible hazard.
For the sake of protection and safety, it is suggested to move the unit with the packaging box. Even though it is
not permitted to do like this under special occasions, do not remove the packaging box, thus to avoid loosening
or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the building,
make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive substances are
stored, thus to avoid possible explosion or fire due to leakage.
Obstruct should put away from the intake or outlet vent of the indoor unit so that the airflow can be blown
though all the room.
Make sure that the installation had accord with the requirement of the schematic diagram of installation spaces.
Select the place where can stand 4 times of the weight of the indoor unit and would not increase the operating
75
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
noise and oscillate.
Select the place where is easy to drain out the condensate water, and connect with outdoor unit.
Make sure that there are enough space for care and maintenance. Make sure that the weight between the
indoor unit and ground is above 2300mm.
When installing the steeve bolt, check if the install place can stand the weight 4 times of the
unit’s. If not, reinforce before installation. (Refer to the install cardboard and find where should be reinforced)
The appliance shall not be installed in laundry.
Cautions:
There will be lots of lampblack and dust stick on the acentric, heat exchanger and water pump in dining room
and kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal operation of the
water pump.
Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the indraft of
the lampblack by the air conditioner.
Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air conditioner.
1) Important notice:
To guarantee the good performance, the unit must be installed by professional personnel according with this
instruction.
Please contact the local Gree special nominated repair department before installation. Any malfunction caused
by the unit that is installed by the department that is not special nominated by Gree would not deal with on time
by the inconvenience of the business contact.
76
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
2) Dimension of ceiling opening and location of the hoisting screw (M10)
(□650mm)(Grille measurement)
□25-15/32"(650mm)
(Hanging bolt position)
15-3/4"(400mm)
17-5/16"(440mm)
2-19/32"(66mm)
GKH12K3CI
Figure 1-3-1
Refrigerant pi pe
780(Gaps between hoisting screw rods)
950(Decorated surface boards)
890*( Ceiling opening)
Indoor unit)
840(
Hoisting s crew(X 4)
77
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-3-3
Cautions:
The dimension for the ceiling openings with * marks can be as large as 910mm. But the overlapping sections of
the ceiling and the decorated surface boards should be maintained at no less than 20mm.
2)Main body of hoisting air conditioner
Nut (supplied at scene)
Gasket (attachment)
Insert
Hoisting stand
Tighten (double nuts) Gasket anchor board (attachment)
Water lever
Polyethylene pipe Bolt (attachment)
Bolt(attachment) [Fix the install cardboard]
Figure
1-3-4
The primary step for install the indoor unit.
When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and lower of
the hoisting stand to fix it. The use of gasket anchor board can prevent gasket break off.
Use install cardboard
Please refer to the install cardboard about the dimension of ceiling opening.
The central mark of the ceiling opening is marked on the install cardboard.
Install the install cardboard on the unit by bolt (3 piece), and fix the angle of the drainage pipe at the outlet vent
by bolt.
Adjust the unit to the suitable install place.
Check if the unit is horizontal.
Inner drainage pump and bobber switch are included in the indoor unit, check if 4 angle of every unit are
horizontal by water lever. (If the unit is slant toward the opposite of the coagulate water flow, there may be
malfunction of the bobber switch and lead water drop.)
Backout the gasket anchor board used to prevent gasket break off and tighten the nut on it.
Backout the install cardboard.
Cautions:
Please do tighten the nuts and bolts to prevent air conditioner break off.
78
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.3.4Dimension Data
Model A B C D E F
GKH12K3CI 710 650 400 606 160 250
Model A B C D E F G
GKH18K3CI 950 890 840 780 680 160 240
GKH24K3CI 950 890 840 780 680 160 240
GKH30K3CI
GKH36K3CI 950 890 840 780 680 160 320
GKH42K3CI
79
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
1.3.5 Installation Clearance Data
>20
H
≥ 1500
≥ 1500
≥1800
Unit:mm
Figure 1-3-5
Models H(mm)
GKH12K3CI 250
GKH18K3CI
260
GKH24K3CI
GKH30K3CI
GKH36K3CI 340
GKH42K3CI
Clamp Clamp(attachment)
Figure 1-3-7
2) Testing of Drainage System
After the electrical installation is completed, carry out the testing of the drainage system.
During the test, check if the water correctly flows through the pipelines. Carefully observe the joints to ensure
that there is no leakage. If the unit is to be installed in a new house, carry out testing before decorating the
ceiling.
3) Matters of Attention
The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The diameter of
80
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
polythene pipe: Outer diameter 25mm Surface thickness ≥1.5mm)
Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air bubble.
If drain hose cannot has enough drooping gradient, drain raising pipe should be added.
To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m. (As shown in Figure
1-3-8)
1-1.5m
Clamp(attachment)
Figure 1-3-9
The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t has to
endure the unnecessary outside force. (As shown in Figure 1-3-10)
Drain hose(attachment)
Below500mm
Below75mm
.
Figure 1-3-10
Please install the drain hose according to the following process if several drain hoses join together. (As shown
in Figure 1-3-11)
T-tie in join drain hose
.
Above100mm
The specs of the selected join drain hose should fits the running capacity of the unit.
Figure 1-3-11
Check the smoothness of drain after installation.
Check the drain state by immiting 600cc water slowly from the outlet vent or test hole. (As shown in Figure
1-3-12)
Check the drain in the state of refrigerating after installation of the electric circuit.
81
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
[Way of immiting]
Drain hose
Test hole cover
Drain vent for repair use (plastic
stopper is included) (drain the water
in waterspout by this outlet vent) Test hole
Figure 1-3-13
Hang the latch, which is located on the opposite side of the swing flap motor on the panel, temporarily to the
book of the indoor unit. (2 Positions)
Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be careful not to let the
82
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 1-3-14
If gap is still left between the ceiling and the panel after screwing the screws, readjust the height of the indoor
unit body (Refer to Figure 1-3-15)
No gap is allowed
Figure 1-3-15
After fixing be sure no gap left between the ceiling and the panel
3) Wiring of the decoration panel.
Connect the joints for swing flap motor lead wire (at 2 places) installed on the panel (Refer to Figure 1-3-16)
Figure 1-3-16
83
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
After receiving the machine, please check the unit and accessories in reference to the packing list. Ensure that
the model is correct and the machine is in good condition. Please also check if the specification and quantity of
accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing possible hazard.
For the sake of protection and safety, it is suggested to move the unit with the packaging box. Even though it is
not permitted to do like this under special occasions, do not remove the packaging box, thus to avoid loosening
or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of the building,
make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive substances are
stored, thus to avoid possible explosion or fire due to leakage.
Outdoor unit shall be installed so that the air discharged by outdoor unit will not return and that sufficient space
for repair shall be provided around the machine.
The installation site must have good ventilation, so that the outdoor unit can take in and exhaust enough air.
Ensure that there is no obstacle for the return air inlet and exhaust of the outdoor unit. If there is any obstacle
blocking the return air inlet or exhaust, remove it.
Place of installation shall be strong enough to support the weight of outdoor unit, and it shall be able to insulate
noise and prevent vibration. Ensure that the wind and noise from the unit will not affect your neighbors.
Avoid direct sunshine over the unit. It is better to set up a sun shield as the protection.
Place of installation must be able to drain the rainwater and defrosting water.
Place of installation must ensure the machine will not be buried under snow or subject to the influence of
rubbish or oil fog.
The installation site must be at a place where the air exhaust outlet does not face strong wind.
he outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect the air
conditioner and avoid knocking the metal parts, thus to prevent rusting in the future.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using rubber damping pad
or spring damper.
The installing dimension shall comply with the installation requirements in these instructions. The outdoor unit
must be fixed at the installing position.
84
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
The installing position shall be in good ventilation, so that the machine can breathe and exhaust enough air.
Ensure that there is no obstruction at the inlet and outlet of the machine. If any, please remove the obstructions
blocking the air inlet and outlet.
If the outdoor unit is installed on concrete or solid ground, it shall be fixed by using M10 bolts and nuts. And
ensure that the machine is kept vertical and horizontal.
The outdoor unit must be lifted by using the designated lift hole. During lifting, take care to protect the air
conditioner and avoid knocking the metal parts, thus to prevent rusting in the future.
To meet the noise and vibration requirements, the outdoor unit shall be installed by using rubber damping pad
or spring damper.
To install the drainage pipe, please insert the drainage joint to the drainage hole on the outdoor chassis and
connect a drainage pipe on the drainage joint. (The installing height of outdoor unit shall be at least 5cm if
drainage joint is to be used).
To insert the pipe through the wall, the wall-cross tube must be installed.
The installing dimension shall comply with the installation requirements in these instructions. The outdoor unit
must be fixed at the installing position.
85
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure3-17 Unit:mm
GUHD36NK3CO
Model
GUHD24NK3CO GUHD36NM3CO
GUHD12NK3CO GUHD18NK3CO
GUHD30NK3CO GUHD42NK3CO
tem
GUHD42NM3CO
A 776 955 980 1107
B 320 396 427 440
C 540 700 790 1100
D 510 560 610 631
E 286 360 395 400
Figure 2-5-1
3 REFRIGERATION PIPING WORK
3.1 Refrigeration Piping Work Procedures
1) Connection Pipe
The connection pipe must meet the following requirements. The three basic principles are that the pipe shall be
kept dry, clean and no leakage.
86
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Figure 3-1-1
Align the flared end of copper pipe with the center of threaded connector and use your hands to securely
tighten the flared nuts.
Tighten the flared nuts with torque wrench, until you hear a ‘KATA” sound from the torque wrench, as shown in
Fig. 3-1-1. See Table 3-1-1 for the torque required for tightening the nuts.
Figure 3-1-2
Form 3-1-1 the tightening torque needed for tightening nut
Pipe diameter Tightening Torque
Generally, the pipe shall be welded with the weld junction upward or horizontal. Avoid welding with the pipe
opening downward. (Downward welding is easy to cause defects, which may affect the weld quality or even
cause leakage, as show in Fig. 3-1-3).
Figure 3-1-3
Use sponge to wrap the connection pipes and connectors that are not thermally insulated, and tighten with
plastic tapes.
2) Vacuum and Leakage Detection
Remove the cap from liquid valve and gas valve.
Align with the pipe center and tighten the jointing nuts adequately with your hand.
Tighten the nuts with wrench.
Remove the 1-way cap from the gas valve.
87
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Use the hexagonal socket spanner to rotate the element of liquid valve for 1/4 turns and use the screwdriver to
prop up the element of gas valve to discharge the gas.
Discharge the gas for 15 seconds, until refrigerant gas appears. The, immediately close the 1-way valve and
tighten the valve cap.
Open the element of liquid valve and gas valve to full (See Fig. 3-1-4).
Figure 3-1-4
Tighten the valve cap and then use soap water or leakage detector to check the connection between outdoor
unit and pipe for any leakage.
Caution:
If possible, it is best to discharge the air out of the machine from the valve by using vacuum pump. To establish
vacuum by using vacuum pump, please operate as follows:
Take out the nut cover of the inlet for refrigerant.
Connect the tube of the vacuum watch with the vacuum pump, having the low-pressure end linking to the inlet
for refrigerant. (As shown in Figure 3-1-5)
Figure 3-1-5
Starting the vacuum pump, when the indicator turns to-1 bar, closing the low pressure handle and stopping
vacuumize. Keep for 15 minutes, ensuring the pressure of the vacuum watch remains.
Take out the valve cover of the gas valve together with the liquid valve.
Loosing the cord of liquid valve until the pressure rise to 0 bar.
Dismantle the tube from the cover of the inlet for refrigerant then, tighten the cover.
Loose the valve cord of the gas valve as well as the liquid valve entirely.
88
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Tighten the valve cover of the gas valve and liquid valve so as to check whether leakage occurred.
3) Installation of Protective Layer of Connecting Pipe
To avoid generation of condensate on the connecting pipe and avoid leakage, the big pipe and the small pipe
of the connecting pipe must be covered by thermal insulation materials, be bundled by adhesive tape, and be
isolated from air.
The joint connecting to the indoor unit must be wrapped by thermal insulation material. There shall be no gap
between the connecting pipe joint and the wall of the indoor unit. Refer to Figure 3-1-6.
89
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
meters.
When the indoor and outdoor units are on different height, please refer to Fig. 30201 for pipe layout.
Liquid pipe (i.e. fine pipe)
- - - - - -Gas pipe (i.e. coarse pipe)
Outdoor unit
Gas pipe
Liquid pipe
Intdoor unit
Figure 3-2-1
90
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
3.3 Specification of Connection Pipe
Size of Fitting Pipe(Inch) Max. Height Amount of
Item Max. Difference Additional
Pipe between Refrigerant to
Liquid Gas Length Indoor Unit be Filled (For
Model
(m ) and Outdoor Extra Length
Unit m of Pipe)
GUHD09NK3CO 1/4” 3/8”
GUHD24NK3CO
3/8” 5/8”
GUHD30NK3CO
30 15 60g/m
GUHD36NK3CO
3/8” 5/8”
GUHD36NM3CO
GUHD42NK3CO
3/8” 5/8”
GUHD42NM3CO
50 30 60g/m
GUHD48NK3CO
3/8” 5/8”
GUHD48NM3CO
GUHD60NM3CO 3/8” 3/4” 50 30 60 g/m
91
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
The on spot connection should refer to the circuit diagram, which is stuck on the unit body.
The unit should be reliably earth, if it is improperly earthed that may cause electric shock or fire.
Air conditioner is the “I” class electric appliance, thus please do conduct reliable grounding measure.
The yellow-green two-color wiring of air conditioner is grounding wire and cannot be used for other purposes. It
cannot be cut off and be fixed by screw, otherwise it would cause electric shock.
The user must offer the reliable grounding terminal. Please don’t connect the grounding wire to the following
places:
① Water pipe;
② Gas pipe;
③ Blowing pipe;
④ Other places that professional personnel consider them unreliable.
4.1.2 Connection between power cables and wiring terminals
Caution
Before installing the electrical equipment, please pay attention to the following matters which have been
specially pointed out by our designers:
① Check to see if the power supply used conforms to the rated power supply specified on the nameplate.
② The capacity of the power supply must be large enough. The section area of fitting line in the room shall be
2
larger than 2.5mm .
③ The lines must be installed by professional personnel.
④ An electricity leakage protection switch and an air switch with gap between electrode heads larger than 3 mm
shall be installed in the fixed line.
1) Connection of single wire
① Use wire stripper to strip the insulation layer (25mm long) from the end of the single wire.
② Remove the screw at the terminal board of the air-conditioning unit.
③ User pliers to bend the end of the single wire so that a loop matching the screw size is formed.
④ Put the screw through the loop of the single wire and fix the loop at the terminal board.
2) Connection of multiple twisted wires
① Use wire stripper to strip the insulation layer (10mm long) from the end of the multiple twisted wires.
② Remove the screw at the terminal board of the air-conditioning unit.
③ Use crimping pliers to connect a terminal (matching the size of the screw) at the end of the multiple twisted
wires.
④ Put the screw through the terminal of the multiple twisted wires and fix the terminal at the terminal board.
Warning:
If the power supply flexible line or the signal line of the equipment is damaged, only use special flexible line to
replace it.
Before connecting lines, read the voltages of the relevant parts on the nameplate. Then carry out line
92
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
The air-conditioning unit shall have special power supply line which shall be equipped with electricity leakage
The air-conditioning unit must have grounding to avoid hazard owing to insulation failure.
All fitting lines must use crimp terminals or single wire. If multiple twisted wires are connected to terminal board,
All line connections must conform to the schematic diagram of lines. Wrong connection may cause abnormal
Do not let any cable contact the refrigerant pipe, the compressor and moving parts such as fan.
Do not change the internal line connections inside the air-conditioning unit. The manufacturer shall not be
liable for any loss or abnormal operation arising from wrong line connections.
③ Connect the power supply cable to the “L, N” terminals and the grounding screw.
④ Connect the power cable to the terminal and earthing screws marked “L1, L2, L3 & N”.
Caution:
For air-conditioner with auxiliary heater, it is required to connect the power cable to the “L1, L2 L3”terminals
Take great care when carrying out the following connections, so as to avoid malfunction of the
The signal line of the wire controller must be separated from the power line and the connecting line between
In case the unit is installed in a place vulnerable by electromagnetic interference, it is better to use shielded
Pull the signal cable of the wire controller through the rubber ring.
Plug the signal line of the wire controller onto the 4-bit pin socket at the circuit board of the indoor unit.
Use cable fastener to bundle and fix the signal cable of the wire controller.
93
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
loop.
② Remove the cable clamp. Connect the power cable to the terminal and fix it.
③ Fix the power cable and signal control wire with cable clamp. Then, connect to corresponding connector
properly.
94
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
GUHD09NK3CO + GFH09K3CI
GUHD12NK3CO + GFH12K3CI
GUHD18NK3CO + GFH18K3CI
GUHD24NK3CO + GFH24K3CI
GUHD30NK3CO + GFH30K3CI
GUHD36NK3CO + GFH36K3CI
GUHD42NK3CO + GFH42K3CI
GUHD48NK3CO + GFH48K3CI
GUHD18NK3CO + GFH18K3CI
2
①Power cord 3×4 mm (H07RN-F) ②Power cord 3×1.0 mm2(H05VV-F)
③ Communication Cords
GUHD24NK3CO + GFH24K3CI
2
①.Power cord 3×4 mm (H07RN-F) ②Power cord 3×1.5 mm2(H05VV-F)
③Communication Cords
GUHD36NM3CO+ GFH36K3CI
GUHD42NM3CO+ GFH42K3CI
GUHD48NM3CO+ GFH48K3CI
GUHD60NM3CO+ GFH60K3CI
95
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Fig.54
GUHD09NK3CO + GTH09K3CI
GUHD12NK3CO + GTH12K3CI
GUHD18NK3CO + GTH18K3CI
GUHD24NK3CO + GTH24K3CI
GUHD30NK3CO + GTH30K3CI
GUHD36NK3CO + GTH36K3CI
GUHD42NK3CO + GTH42K3CI
GUHD48NK3CO + GTH48K3CI
GUHD18NK3CO + GTH18K3CI
2
①Power cord 3×4 mm (H07RN-F) ②Power cord 3×1.0 mm2 (H05VV-F)
③Communication Cords
GUHD24NK3CO + GTH24K3CI
①Power cord 3×4 mm2 (H07RN-F) ②Power cord 3×1.5 mm2 (H05VV-F)
③Communication Cords
Fig.55
GUHD36NM3CO+ GTH36K3CI
GUHD42NM3CO+ GTH42K3CI
GUHD48NM3CO+ GTH48K3CI
GUHD60NM3CO+ GTH60K3CI
96
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
Fig.56
GUHD12NK3CO + GKH12K3CI
GUHD18NK3CO + GKH18K3CI
GUHD24NK3CO + GKH24K3CI
GUHD30NK3CO + GKH30K3CI
GUHD36NK3CO + GKH36K3CI
GUHD42NK3CO + GKH42K3CI
GUHD12NK3CO + GKH12K3CI
①Power cord 3x2.5mm2 (H07RN-F) ②Power cord 3x1.0mm2 (H05V V-F)
③Communication Cords
GUHD18NK3CO + GKH18K3CI
①Power cord 3x4.0mm2 (H07RN-F) ②Power cord 3x1.0mm2 (H05V V-F)
③Communication Cords
GUHD24NK3CO + GKH24K3CI
①Power cord 3x4.0mm2 (H07RN-F) ②Power cord 3x1.5mm2 (H05V V-F)
③Communication Cords
GUHD30NK3CO + GKH30K3CI
GUHD36NK3CO + GKH36K3CI
GUHD42NK3CO + GKH42K3CI
①Power cord 3x6.0mm2 (H07RN-F) ②Power cord 3x1.5mm2 (H05V V-F)
③Communication Cords
Fig.57
GUHD36NM3CO + GKH36K3CI
GUHD42NM3CO + GKH42K3C
GUHD36NM3CO + GKH36K3CI
GUHD42NM3CO + GKH42K3CI
①Power cord 5x 6.0mm2 (H07RN-F) ②Power cord 3x1.5mm2 (H05V V-F)
③Communication Cords
97
A/A DC INVERTER U-MATCH AIR CONDITIONERS INSTALLATION
4.3 Specification of Power Supply Wire and Air Switch
Minimum Sectional
Minimum Sectional
Capability of Air Area
Power Area
Model Switch(A) Of power Wire
Supply Of Earth Wire (mm2)
(Outdoor/Indoor) (mm2)
(Outdoor/Indoor)
(Outdoor/Indoor)
GUHD09NK3CO 16/6 2.5/1.0 2.5/1.0
Note:
The parameters of the power cord listed above are only applicable to the BV single-core power cord which is laid
within the plastic bushing and used at 40℃, and those of the air switch are applicable to the one which also is used
at 40℃. If the actual installation conditions changes, please refer to the instructions of the power cord and the air
switch.
98
GREE COMMERCIAL AIR CONDITION A/A DC INVERTER U-MATCH AIR CONDITIONERS
MAINTENANCE
99
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
MAINTENANCE
1 TROUBLE TABLE
Table 1 Fault Display on Indoor Wired Controller:
Trouble Trouble Origin of
Control Description
Code Name Trouble Signal
If the water-full protection cannot be recovered after 2 hours, it is
Water Pump
E0 Water pump believed that the water pump is failed, in which case all the loads will
Malfunction
be switched off and cannot be recovered automatically.
When high pressure protection is detected for 3 seconds successively,
all the loads (except the heating 4-way valve) will be switched off, in
High Pressure
High-pressure which case all the keys and remote control signals except ON/OFF
E1 Protection of
Switch function will be disabled and cannot be recovered automatically. To
Compressor
eliminate the fault, it is needed to switch off and on the machine or
recover from power failure.
If detecting that the evaporator sensor is lower than protective temp.
value after the unit has been running for a period of time under cooling
Indoor Indoor
or dry mode, the unit will report this fault, in which case the compressor
E2 Anti-frozen evaporator
and outdoor fan will be stopped. The unit will not run until this
Protetion sensor
temperature exits the pretective temperature value and the compressor
is stopped for 3 minutes.
If it is detected within 30 seconds successively that the low-pressure
switch is cut off under ON or standby state (If the compressor is started,
Low Pressure
Low-pressure the detection will start 3 minutes after the compressor has run), the unit
E3 Protection of
Switch will report this fault. For the first two faults within 30 minutes, the unit
Compressor
can be recovered automatically. If over three times, the unit cannot be
recovered automatically.
After the compressor is started, if it is detected within 30 seconds
successively that the exhaust temperature is 130℃ or higher, E4 will be
Air Discharge
Exhaust displayed, in which case all the loads (except the 4-way valve of
High-temperatur
E4 Overtemperatur heating) will be stopped. The complete unit can only be recovered until
e Protection of
e Protection the compressor has stopped for 3 minutes and the exhaust
Compressor
temperature is lower than 90℃. For this protection occurs three times,
the complete unit cannot be recovered automatically.
After the unit is energized, if it is detected within 3 seconds
successively that the compressor overload switch is cut off, it will be
deemed compressor overload protection. In this case, all the loads will
be stopped (except the 4-way valve of heating) and E5 will be
displayed. If the fault is eliminated, the compressor will be restarted
Overload after 3 minutes. If three compressor overload protections are detected
E5 Proection of Compressor successively in 30 minutes from the first detection to the occurrence of
Compressor fault, the compressor cannot be recovered automatically and the
buzzer will alarm. You shall need to press ON/Off to stop the unit and
clear the sound alarm before pressing ON/OFF again. The unit will be
restarted if the high pressure protection disappears; otherwise the fault
code will be displayed. Besides, “E5” also will also be displayed on the
controller in the event of an error of the compressor drive module.
If the outdoor unit does not receive data from indoor unit for 30 seconds
successively once energized, this indicates indoor communication
failure. In this case, the compressor and outdoor fan will be stopped.
Under heating mode, the 4-way valve will be stopped if the compressor
Communication has been stopped for 2 minutes. If the indoor unit does not receive
Communication between indoor message from outdoor unit for 1 minute, this indicates communication
E6
s Failure and outdoor failure. In this case, the indoor unit will be stopped and the indicator will
mainboard blink. If the display board does not receive message from outdoor unit
in 1 minute, it can be judged that it is communication failure, in which
case the fault will be displayed and the machine will not function. After
the communication is resumed to normal, the system will run as per the
working mode before. This can recover automatically.
Full Water Liquid level If “full water” is detected for 8 seconds successively once energized,
E9
Protection switch the system will enter into full water protection and the indicator will blink
100
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Trouble Trouble Origin of
Control Description
Code Name Trouble Signal
(or display E9): Under cooling and dry mode, the outdoor fan and
compressor will be stopped, while the indoor fan will be stopped after 1
minute. Under heating mode, the outdoor fan and compressor will be
stopped, the 4-way valve will maintain its original state, and the indoor
unit will be stopped after 1 minute. Under fan mode, the indoor loads
will not be stopped.
If the indoor sensor is detected of open circuit or short circuit for 5
Malfunction Of seconds successively, the indoor room temperature will forcibly set to
Indoor 24℃. In this case, the system will not perform any treatment, only the
Indoor room
F0 Environment indicator will blink or display the fault code. The system can
sensor
Sensor at automatically resume after the failure is eliminated. Under fan mode,
Return air Vent only the fault will be displayed, but the indoor unit will run normally. The
fault disappears after it is eliminated.
If the evaporator sensor is detected of open circuit or short circuit for 5
seconds successively: When under cooling and dry mode, the system
will be stopped. When under heating mode, all of the loads except the
Evaporator Outdoor
4-way valve will be stopped, while the indicator will blink or display the
F1 Temp. Sensor evaporator
fault code F1. After the fault is eliminated, the system can automatically
Malfunction sensor
resume to operation and clear the fault display. Under fan mode, only
the fault will be displayed, and the indoor unit will run normally. The
fault disappears after it is eliminated.
If the condenser sensor is detected of open circuit or short circuit for 5
seconds successively: When under cooling and dry mode, the system
will be stopped. When under heating mode, all of the loads except the
4-way valve will be stopped, while the indicator will blink or display the
Condenser Outdoor fault code F2. After the fault is eliminated, the system can automatically
F2 Temp. Sensor condenser resume to operation and clear the fault display. Under fan mode, only
Malfunction sensor the fault will be displayed, and the indoor unit will run normally. The
fault disappears after it is eliminated.
For cooling-only unit, the other units except the duct type will not detect
the condenser sensor fault.
If the outdoor environment sensor is detected of open circuit or short
circuit for 5 seconds successively: When under cooling and dry mode,
Outdoor the system will be stopped. When under heating mode, all of the loads
Outdoor
Environment except the 4-way valve will be stopped, while the indicator will blink or
F3 environment
Sensor display the fault code F3. After the fault is eliminated, the system can
sensor
Malfunction automatically resume to operation and clear the fault display. Under fan
mode, only the fault will be displayed, and the indoor unit will run
normally. The fault disappears after it is eliminated.
If the outdoor temperature sensor is detected of open circuit for 5
seconds successively after the compressor is started: When under
cooling and dry mode, all the loads will be stopped. When under
heating mode, all of the loads except the 4-way valve will be stopped,
while the indicator will blink or display the fault code F4 and the buzzer
Malfunction of Exhaust will alarm. After the fault is eliminated, the system can automatically
F4 Exhaust Temp. temperature resume to operation and clear the fault code.
Sensor sensor If the outdoor temperature sensor is detected of short circuit: When
under cooling and dry mode, all the loads will be stopped. When under
heating mode, all of the loads except the 4-way valve will be stopped,
while the indicator will blink or display the fault code F4 and the buzzer
will alarm. After the fault is eliminated, the system can automatically
resume to operation and clear the fault code.
If the wired controller is detected of open circuit or short circuit for 5
Malfunction Of seconds successively, the indoor room temperature will forcibly set to
Indoor 24℃. In this case, the system will not perform any treatment, only the
F5 Environment Wired controller indicator will blink or display the fault code. The system can
Sensor at Wire automatically resume to operation after the failure is eliminated. Under
Controller fan mode, only the fault will be displayed, but the indoor unit will run
normally. The fault disappears after it is eliminated.
101
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Trouble Trouble Origin of
Control Description
Code Name Trouble Signal
All of The
Terminal Air
FF Valve Colsed System The air valve on end will be fully closed.
(not failure)
Wire Controller
Invalid the units is remotely monitored or controlled by centralized controller
CC wire controller
and the wire controller’s functions are invalidated (not failure)
(not failure)
Keys Locked
EE wire controller keys on wire controller are locked (not failure)
(not failure)
102
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
When the unit has error,it will display error code,
Its error code as the same as Table 1 Fault Display on Indoor Wired Controller.
Table3 This section is applicable to the electric control box of the GUHD09NK3CO
/GUHD12NK3CO A/A DC inverter air conditioners
NO Running Status Yellow Lamp Red Lamp Green Lamp
1 Compressor started Flash once
2 Defrosting Flash twice Displayed
3 Anti-freezing protection Flash 3 times E2
4 IPM protection Flash 4 times E5
5 Over-current protection Flash 5 times E5
Heat exchanger overload
6 Flash 6 times /
protection
7 Discharge protection Flash 7 times E4
Compressor overload
8 Flash 8 times E5
protection
9 Power protection Flash 9 times E5
Module overheating
10 Flash 10 times E5
protection
11 EEPROM reading error Flash 11 times E5
12 Low voltage protection Flash 12 times E5
13 High voltage protection Flash 13 times E5
14 PFC over-current protection Flash 14 times E5
Unmatched indoor and
15 Flash 16 times /
outdoor units
16 Limited frequency(current) Flash once /
Limited frequency
17 Flash twice /
(discharge)
18 Limited frequency (overload) Flash 3 times /
Reduced frequency
19 Flash 4 times /
(anti-freezing)
Outdoor ambient
20 Flash 6 times F3
temperature sensor error
Outdoor pipe temperature
21 Flash 5 times F2
sensor error
Outdoor discharge
22 Flash 7 times F4
temperature sensor error
Up to the startup
23 Flash 8 times /
temperature
Limited frequency
26 Flash 11 times /
(module temperature)
Flash 13
28 Limited frequency (power) /
times
Flash
31 Communication normal /
continuously
32 Communication error Black out E6
Indoor ambient temperature
33 F0
sensor error
Indoor pipe temperature
34 F1
sensor error
103
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Table 4 Main board dual 8 numeral tube Display Codes for Outdoor Unit
Note:This table except GUHD09NK3CO/GUHD12NK3CO
104
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: E1 Compressor High Pressure Protection
105
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: E3 Compressor Low Pressure Protection
106
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: E4 Compressor Exhaust High Temperature Protection
107
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: E5 Compressor Overheat (Please check the corresponding method of drive protection)
108
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: E9 Full Water Protection
109
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: F1 Failure of Evaporator Temp. Sensor
F a i l u r e o f Evaporator
Temp. sensor
Failure of condenser
Temp. sensor
110
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: F3 Failure of Outdoor Ambient Sensor
Failure of outdoor
Ambient sensor
Failure of Exhaust
Temp. sensor
111
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Malfunction display: F5 Failure of Indoor Room Sensor at Wire Controller
112
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
2.2 Typical Troubleshooting for C series Outdoor Unit Drive (Inverter) by Single-phase
Motor
(Applicable to GUHD09NK3CO,GUHD12NK3CO)
2.2.1Brief Introduction to the Electric Control Box of the Outdoor Unit
1.Schematic of Outdoor Unit Electric Control Box (Control board on the left; filter plate board on the right)
2. Testing Method to the Key Points on the Outdoor Unit’s Electric Control Box
2.1Test Points and Testing Method of 15V/12V/5V Power Supplies
113
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
114
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
3 Status Indicating Lamp of the Electric Control Box of the Outdoor Unit
There are three independent indicating lamps on the electric control box of the outdoor unit, and they will flash
on for five seconds and then black out for another five seconds, which is called a round. Once the lamp blacks out
for more than 1 seconds, it means this round is over and the next round begins as it flashes on again.
3. IPM Protection(H5)
a.Pull out the power plug for three minutes and then plug it again, in which case, if H5 appears in no time, check
if the terminals of the compressor are improperly connected or loosened; if not, replace the electric control box of the
outdoor unit; if the fault still exists, then it indicates the compressor is defective and should be replaced.
b. When H5 appears after the unit has run for a period of time, then it is necessary to see if the running
environment is really badly (e.g. the condenser is blocked with filth). If not, there is a need of a further check to see if
the wiring of the compressor is reverse, the screws of the module is tightened, or if the compressor is defective etc;
If the fault is beyond the statement above, please replace the electric control box of the outdoor unit.
4. Heating Failure
1. Under the heating status, measure the voltage between two wires of the four-way valve with a universal
meter. The testing points are 4V and AC-L2. If the measured voltage is not about AC230V, then it indicates that the
electric control box of the outdoor unit is defective and should be replaced.
2. If the measured voltage is about AC230V, then cut off the power supply and pull out these two wires of the
four-way valve and measure the resistance between the test points to see if it is about 1-2K. If it is much larger, it
indicates that there is a open circuit among the coils of the four-way valve which then should be replaced.
3. If the coils of the four-way valve is normal, then the failure may be caused by the system abnormity.
5. Cooling Failure
The cooling failure is posed generally when the Relay K5’s contactor of the four-way valve of the outdoor unit’s
electric control box is bonded, and it can be checked out by the universal meter.
2.2.3 Solutions to the Unsolved Faults after the Replacement of the Electric Control Box
1 .After the Replacement of the Electric Control Box of the Outdoor Unit
If the faults still exist after the replacement of the electric control box of the outdoor unit, please take a check to
see if the communication line, temperature sensor, reactor, fan motor, or compressor is normal or not.
Communication line: check if the communication line, live line, or neutral line are connected improperly or the
contactor of the terminals are not good. If the line is extended, then check if the joint is in good condition.
115
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Temperature sensor: measure the grounding resistance between the points 3.3V and IPM15V (the testing
method is same as above); if the grounding is shortcut, please check if each temperature sensor is damaged or if
there is arcing trace on its outer housing or metal ends
Reactor: if the communication error remains after the replacement of the electric control box, then pull out the
two terminals of the reactor and measure the resistance between them with a universal meter; if the measure valve
is about several ohms, it indicates the terminals of the reactor is likely to break off.
Fan motor: pull out the terminals of the fan motor and measure the resistance between the red, brown and black
wires with a universal meter; The normal value is about several hundreds ohms, if the measure value is beyond this
range, it indicates there is a open circuit or the fan motor is defective.
Compressor: apart from the badly running environment, improper connection, or systematic abnormity, if H5 still
occurs frequently after the replacement of the electric control box, then it indicates that the compressor is probably
defective.
Four-way valve: pull out two purple wires and measure the resistance between them with a universal meter to
see if it is about 1~2K. If it is much larger, it indicates that there is a open circuit among the coils of the four-way
valve which then should be replaced.
If the fault is beyond the statement above, then please check the indoor unit.
2 .After the Replacement of the Electric Control Box of the Indoor Unit
If the fault remains after the replacement of the electrical control box of the indoor unit, then there is a need to
check if the wiring is proper and the fan motor and temperature sensor is in good condition. Besides, if the fault is
beyond the statement above, please check the outdoor unit.
2.2.4 Precautions
1. Prior to the replacement of the main board of the outdoor unit’s control box, it must be certain that it is the qualified
product and necessary tests as follows should be taken:
a, test if there is a short circuit between any two of three IGBI pins. If so, the main board can not be used.
b. test if there is a short circuit between the points P and N of the DC bus. If so, the main board can not be used.
c. test if there is a short circuit between any U/V/W and P, U/V/W and N. If so, the main board can not be used.
d. see the section 1.2.3 for the test point and testing method of IGBT and IPM module.
2. Each compressor is matched with only certain type main board of the electric control box, so prior to the
replacement of the main board, it must be sure what model the main board is; otherwise the main board would fail to
match with the compressor.
3 .As for the replacement of the compressor, it also must be sure what model the compressor is ( it can be found on
the label of the fan motor capacitor); otherwise the compress would failed to match with the piping system and the
electric control box.
4. Never allow any wire to contact the pipes, four-way valve, compressor, and sharp edge of the metal sheet. And
the earth leads of the compressor, fan motor and electric control box must be inside a separate screw hole.
5. Necessary measurers should be taken to against water, moisture and static electricity. Besides, during the
dismantlement and installation of the electrical control box, a antistatic strip must be put on and do not touch the
component as much as possible.
6.The wiring should be done strictly according to the wiring diagram labeled on the electric control box and each
wiring terminal should be on the right place. Besides the wires can not be stretched too tightly or else it would break
away from the socket, connector or the insulating bushing. The bonding tie should be kept 3mm~5mm long, as the
longer one would cause unusual sound by the friction with the cover plate.
116
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
2.3 Typical Troubleshooting for C series Outdoor Unit Drive (Inverter) by Single-phase
Motor
(Applicable to GUHD18NK3CO,GUHD24NK3CO, GUHD30NK3CO, GUHD36NK3CO,
GUHD42NK3CO, and GUHD48NK3CO)
117
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆IPM module protection
118
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆DC busbar overvoltage protection
119
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆DC busbar undervoltage protection
120
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Abnormal noise from PFC inductor
121
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Radiator overheat protection
122
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆Tripping
123
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Y
Yes
Yes
124
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
P
W
V U
125
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
E5 is displayed
on the wired
controller.
Radiator
Overheating P8
Protection
Yes
No
126
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆ Tripping
127
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
E5 is displayed
on the wired
controller.
Main Board 88
Monitor Display Indicating Lamp
No
No
Yes
If the reactor is
tightened?
If the malfunction is
Yes
eliminated after the
reactor is tightened
securely?
If the input terminals L1,
L2, L3 are connected
No Yes properly?
No
No
128
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Wired
Controller
Display E5
Monitor
Dispay Main Board 88
Indicating Lamp
No
129
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆ Open Phase
E5 is displayed on
the wired controller
Main Board 88
Monitor Display Indicating Lamp
Open Phase LD
Yes
Yes No
130
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
◆ Communication Error between the Indoor and Outdoor Units
131
A/A DC INVERTER U-MATCH AIR CONDITIONERS CONTROL
3 WIRING DIADRAM
3.1 Outdoor unit
(The actual wiring should always refer to the wiring diagram of the unit.)
Model: GUHD09NK3CO/ GUHD12NK3CO
Model: GUHD18NK3CO
132
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GUHD24NK3CO /GUHD30NK3CO
133
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GUHD48NK3CO
134
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GUHD48NM3CO
Model:GUHD60NM3CO
135
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
3.2 Indoor unit
(The actual wiring should always refer to the wiring diagram of the unit.)
Model:GFH09K3CI/GFH12K3CI/GFH18K3CI/GFH24K3CI/GFH30K3CI/GFH36K3CI/ GFH42K3CI/
GFH48K3CI/ GFH60K3CI
136
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GTH09K3CI/ GTH12K3CI/ GTH18K3CI/ GTH24K3CI/ GTH30K3CI/ GTH36K3CI/
/GTH42K3CI /GTH48K3CI /GTH60K3CI
137
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
138
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
139
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Removal and Installation of Gas-liquid Separator and Compressor
Remark: Before removing the compressor, make sure that there is no refrigerant inside the pipe system and that
the power has been cut off.
Step Illustration Handling Instruction
4. Remove the
Remove the compressor
compressor
away from its base.
away
140
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
a. Connect the
suction/discharge pipes of
the compressor by means of
gas welding.
6. Connect the b. During the welding,
suction/discharge nitrogen should be inflated
pipes of the and its pressure should be
compressor with 0.5±0.1kgf/c ㎡ (relative
the system pressure)
piping. c. Attention should be taken
during the heating to avoid
the surrounding objects
burnt due to the high
temperature.
8. Establish
Establish vacuum inside the
vacuum through
system through liquid valve.
liquid valve
141
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
142
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Recharge the
refrigerant to the
7 Recharge the system through liquid
refrigerant to the valve.
system through liquid ● The charge volume
valve. must be identical to
the indications on
nameplate.
143
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Note: Before the dismantlement of the motor, make sure the unit is powered off
Step Illustration Handling Instruction
●Use screwdriver to
loosen the screws on
4. Remove the
electric box cover.
electric box cover
●Remove the cover
from electric box.
144
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
145
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
146
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
●Assemble the
electric box cover to
15. Assemble the correct position
electric box cover ● Use screwdriver to
fix the cover onto
electric box.
147
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
148
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
149
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
150
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
a. Dismantle the
gas-liquid separator
through heating its
inlet/outlet pipe by the
means of gas welding.
3. Disconnect the b. During the welding,
suction and nitrogen should be
discharge pipes inflated and its pressure
of the should be 0.5±0.1kgf/c
compressor ㎡ (relative pressure)
c. Attention should be
taken during the heating
to avoid the surrounding
objects burnt due to the
high temperature.
151
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
a. Connect the
suction/discharge pipes
of the compressor by
means of gas welding.
b. During the welding,
6. Connect the nitrogen should be
suction/discharge
inflated and its pressure
pipes of the should be 0.5±0.1kgf/c
compressor with
㎡ (relative pressure)
the system piping
c. Attention should be
taken during the heating
to avoid the surrounding
objects burnt due to the
high temperature.
152
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
13. Establish
Establish vacuum inside
vacuum through
the system through
liquid valve
liquid valve.
a.Recharge the
refrigerant to the system
14. Charge through liquid valve.
refrigerant
through liquid b. The charge volume
valve must be identical to the
indications on
nameplate.
153
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
154
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Recharge the
refrigerant to the system
7 Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through liquid
must be identical to the
valve.
indications on
nameplate.
155
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
●Use screwdriver to
loosen the screws on
4. Remove the
electric box cover.
electric box cover
●Remove the cover
from electric box.
156
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
157
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
158
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
A.用气焊加热电子膨胀
阀两端连接管路后拔离电
子膨胀阀组件
3 Disassemble electric B.焊接时要充氮保护,
expansion valve 氮气压力为 0.5±0.1kgf/c
㎡(相对压力)
C.加热时注意,以防周
围物料因高温烧毁
将旧的电子膨胀阀组件移
4 移开电子膨胀阀
开
A.用气焊焊接电子膨胀
阀组件
B.焊接时要充氮保护,
5 移上新的电子膨胀阀
氮气压力为 0.5±0.1kgf/c
组件与系统管路相连
㎡(相对压力)
C.加热时注意,以防周
围物料因高温烧毁
159
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Recharge the
refrigerant to the system
7Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through liquid
must be identical to the
valve.
indications on
nameplate.
160
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
161
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
162
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
163
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
a. Connect the
suction/discharge pipes of
the compressor by means of
gas welding.
6. Connect the b. During the welding,
suction/discharge nitrogen should be inflated
pipes of the and its pressure should be
compressor with 0.5±0.1kgf/c ㎡ (relative
the system piping. pressure)
c. Attention should be taken
during the heating to avoid
the surrounding objects burnt
due to the high temperature.
164
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassembly and Assembly of 4-way valve
Note: Before removing the 4-way valve, make sure that there is no refrigerant inside the pipe system and that the
power has been cut off.
Step Illustration Handling Instruction
165
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Install the new 4-way
valve to correct position.
●When welding the
4-way valve, please
wrap the valve body with
wet cloth, thus to
prevent the guide inside
5. Connect the new the valve body from
4-way valve to the pipe. burn. Also take care to
prevent any water from
flowing into the pipe.
● Weld by charging
nitrogen, with the
nitrogen pressure kept at
0.5±0.1kgf/c(relative
pressure).
● Recharge the
refrigerant to the system
7 Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through liquid
must be identical to the
valve.
indications on
nameplate.
166
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
167
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
用手或者钳子将主板上
7.拆卸电机电源线
的电机电源线拔出
168
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
169
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
1.拆除电子膨胀阀线 用手松动电子膨胀阀
圈 线圈
将电子膨胀阀线圈从
2.移开电子膨胀阀线
电子膨胀阀上去下、
圈
移开
170
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
A.用气焊加热电子膨胀
阀两端连接管路后拔离电
子膨胀阀组件
B.焊接时要充氮保护,
3 拆除电子膨胀阀 氮气压力为 0.5±0.1kgf/c
㎡(相对压力)
C.加热时注意,以防周
围物料因高温烧毁
将旧的电子膨胀阀组件移
4 移开电子膨胀阀
开
A.用气焊焊接电子膨胀
阀组件
b. During the welding,
nitrogen should be inflated
and its pressure should be
5 移上新的电子膨胀阀 0.5±0.1kgf/c ㎡ (relative
组件与系统管路相连 pressure)
c. Attention should be
taken during the heating to
avoid the surrounding
objects burnt due to the
high temperature.
171
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Recharge the
refrigerant to the system
7Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through liquid
must be identical to the
valve.
indications on
nameplate.
172
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
3. Loosen the screws between the Loosen the screws between the
electric box and side panel and electric box and side panel and
motor base. motor base with a screw driver.
173
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
用手或者钳子拔掉电器盒电源
2. 拆卸电器盒电源连接线
线
174
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
3. Loosen the screws between the Loosen the screws between the
electric box and side panel and electric box and side panel and
motor base. motor base with a screw driver.
175
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
176
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
177
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
用螺丝刀将汽液分离
2. 拆除汽液分离
器与隔板之间的固定
器固定螺钉
螺钉拆除。
178
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
A.用气焊加热汽液
分离器进出管路后拔
离汽分;
B.焊接时要充氮保
3. 拆除汽液分离 护,氮气压力为
器进出管 0.5±0.1kgf/c ㎡(相
对压力)
C.加热时注意,以
防周围物料因高温烧
毁
4. 移开汽液分离 将汽液分离器从机组
器 上移开
用扳手将压缩机与压
5. 拆除压缩机固
缩机支架间固定螺母
定螺钉
拆除
A.用气焊加热汽液
分离器进出管路后拔
离汽分;
B.焊接时要充氮保
6. 拆除压缩机吸
护,氮气压力为
排气管
0.5±0.1kgf/c ㎡(相
对压力)
C.加热时注意,以
防周围物料因高温烧
毁
179
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
将压缩机从压缩机支
7. 移开压缩机
架上移开
A.将新压缩机放到
准确位置;
8. 移上新的压缩
B.用扳手拧紧压缩
机固定在压缩机
机固定螺母;
支架上
C.压缩机安装时不
能倒置
A.用气焊焊接压缩
机吸排气管;
B.焊接时要充氮保
9. 将压缩机吸排 护,氮气压力为
气管与系统管路 0.5±0.1kgf/c ㎡(相
相连 对压力)
C.加热时注意,以
防周围物料因高温烧
毁
A.将汽液分离器放
到准确位置;
10 移上汽液分离 B.用螺丝刀拧紧汽
器并固定 液分离器与隔板固定
螺钉
180
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
A.用气焊焊接汽液
分离器进出管;
B.焊接时要充氮保
11. 将 汽 液 分 离 护,氮气压力为
器进出管与系统 0.5±0.1kgf/c ㎡(相
管路相连 对压力) ;
C.加热时注意,以
防周围物料因高温烧
毁。
A.将电源线按照拆
12. 将 压 缩 机 电 卸的反顺序插到接线
源线接好 片上;
B.用螺丝刀拧紧压
缩机盖
● Recharge the
refrigerant to the
system through
14. Charge liquid valve.
refrigerant
through liquid ● The charge
valve volume must be
identical to the
indications on
nameplate.
A. 先切断电源。
B. 妥善回收冷媒
1.拆除电磁阀
C. 用 扳 手 松 掉 固 定
电磁阀螺栓
将电磁阀从四通阀上
2.移开电磁阀
取下,移开。
182
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Install the new 4-way
valve to correct position.
●When welding the
4-way valve, please
wrap the valve body with
wet cloth, thus to prevent
the guide inside the
5. Connect the new
valve body from burn.
4-way valve to the
Also take care to prevent
pipe.
any water from flowing
into the pipe.
● Weld by charging
nitrogen, with the
nitrogen pressure kept at
0.5±0.1kgf/c(relative
pressure).
6.Establish vacuum
● Establish vacuum
inside the system
inside the system
through liquid
through liquid valve.
valve.
● Recharge the
refrigerant to the system
7 Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through
must be identical to the
liquid valve.
indications on
nameplate.
用螺丝刀将格栅与
1.拆除格栅
面板固定螺钉松掉
183
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
将格栅从面板上取
2.移开格栅
下、移开
用螺丝刀松掉顶盖
3.拆除顶盖
周围的固定螺钉
●Use screwdriver to
loosen the screws on
4. Remove the electric
electric box cover.
box cover
●Remove the cover
from electric box.
184
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
将电器盒盖从电器盒上
6.移开电器盒盖
移开
用手或者钳子将主板上
7.拆卸电机电源线
的电机电源线拔出
185
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
186
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
1.拆除电子膨胀阀线 用手松动电子膨胀阀
圈 线圈
将电子膨胀阀线圈从
2.移开电子膨胀阀线
电子膨胀阀上去下、
圈
移开
A.用气焊加热电子膨胀
阀两端连接管路后拔离电
子膨胀阀组件
B.焊接时要充氮保护,
3 拆除电子膨胀阀 氮气压力为 0.5±0.1kgf/c
㎡(相对压力)
C.加热时注意,以防周
围物料因高温烧毁
187
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
将旧的电子膨胀阀组件移
4 移开电子膨胀阀
开
A.用气焊焊接电子膨胀
阀组件
B.焊接时要充氮保护,
5 移上新的电子膨胀阀
氮气压力为 0.5±0.1kgf/c
组件与系统管路相连
㎡(相对压力)
C.加热时注意,以防周
围物料因高温烧毁
● Recharge the
refrigerant to the system
7Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through liquid
must be identical to the
valve.
indications on
nameplate.
188
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassembly and Assembly of electrical parts box
Remark : Before removing the electric box or electric box sub-assembly, make sure that the power has been cut off.
Step Illustration Handling Instruction
用手或者钳子拔掉电器盒
2. 拆卸电器盒电源连接线
电源线
用螺丝刀松掉电器盒与侧
3. 拆除电器盒与侧板、电机
板、电机支架之间的固定螺
支架之间的固定螺钉
钉
189
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
190
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
A.先切断电源;
B.妥善回收冷媒;
1.Diassemble the top cover.
C.再用螺丝刀拧下固定顶盖板
的螺钉。
2.Remove the top cover Move the top cover from the
unit.
191
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
4. 移开前侧板 将前侧板从机组上移开
用螺丝刀将后侧板固定螺钉松
5. 拆卸后侧板
掉
6.移开后侧板 将后侧板从机组上移开
192
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Removal and Installation of Gas-liquid Separator and Compressor
Remark: Before removing the compressor, make sure that there is no refrigerant inside the pipe
system and that the power has been cut off.
Step Illustration Handling Instruction
A.先用扳手拧开压缩
机电源盒盖;
1. 拆除压缩机电源连接 B.然后用钳子拔离压
线 缩机电源线
C.再将压缩机电源插
片拔掉
用螺丝刀将汽液分离
2. 拆除汽液分离器固定
器与隔板之间的固定
螺钉
螺钉拆除。
A.用气焊加热汽液分
离器进出管路后拔离
汽分;
B.焊接时要充氮保护,
3. 拆除汽液分离器进出
氮 气 压 力 为
管
0.5±0.1kgf/c ㎡(相对
压力)
C.加热时注意,以防
周围物料因高温烧毁
将汽液分离器从机组
4. 移开汽液分离器
上移开
193
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
用扳手将压缩机与压
5. 拆除压缩机固定螺钉 缩机支架间固定螺母
拆除
A.用气焊加热汽液分
离器进出管路后拔离
汽分;
B.焊接时要充氮保护,
6. 拆除压缩机吸排气管 氮 气 压 力 为
0.5±0.1kgf/c ㎡(相对
压力)
C.加热时注意,以防
周围物料因高温烧毁
将压缩机从压缩机支
7. 移开压缩机
架上移开
A.将新压缩机放到准
确位置;
8. 移上新的压缩机固定 B.用扳手拧紧压缩机
在压缩机支架上 固定螺母;
C.压缩机安装时不能
倒置
194
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
A.用气焊焊接压缩机
吸排气管;
9. 将压缩机吸排气管与 B.焊接时要充氮保护,
系统管路相连 氮 气 压 力 为
0.5±0.1kgf/c ㎡(相对
压力)
C.加热时注意,以防
周围物料因高温烧毁
A.将汽液分离器放到
准确位置;
10 移上汽液分离器并 B.用螺丝刀拧紧汽液
固定 分离器与隔板固定螺
钉
A.用气焊焊接汽液分
离器进出管;
B.焊接时要充氮保护,
11. 将汽液分离器进出 氮 气 压 力 为
管与系统管路相连 0.5±0.1kgf/c ㎡(相对
压力);
C.加热时注意,以防
周围物料因高温烧毁。
A.将电源线按照拆卸
的反顺序插到接线片
12. 将压缩机电源线接 上;
好 B.用螺丝刀拧紧压缩
机盖
195
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Establish vacuum
13. Establish vacuum
inside the system
through liquid valve
through liquid valve.
● Recharge the
refrigerant to the
system through liquid
14. Charge refrigerant valve.
through liquid valve ● The charge volume
must be identical to
the indications on
nameplate.
196
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
● Recharge the
refrigerant to the system
5 Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through liquid
must be identical to the
valve.
indications on
nameplate.
用螺丝刀将格栅与面
1.拆除格栅
板固定螺钉松掉
197
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
将格栅从面板上取
2.移开格栅
下、移开
用螺丝刀松掉顶盖周
3.拆除顶盖
围的固定螺钉
●Use screwdriver to
loosen the screws on
4. Remove the electric
electric box cover.
box cover
●Remove the cover from
electric box.
198
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
用手或者钳子将主板上的
7.拆卸电机电源线
电机电源线拔出
199
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
A.用气焊加热电子膨胀
阀两端连接管路后拔离电
子膨胀阀组件
B.焊接时要充氮保护,
1. 拆除电子膨胀阀组件 氮气压力为 0.5±0.1kgf/c
㎡(相对压力)
C.加热时注意,以防周
围物料因高温烧毁
200
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
将旧的电子膨胀阀组件移
2. 移开电子膨胀阀组件
开
A.用气焊焊接电子膨胀
阀组件
B.焊接时要充氮保护,
3. 移上新的电子膨胀阀
氮气压力为 0.5±0.1kgf/c
组件与系统管路相连
㎡(相对压力)
C.加热时注意,以防周
围物料因高温烧毁
● Recharge the
refrigerant to the system
5 Recharge the
through liquid valve.
refrigerant to the
● The charge volume
system through liquid
must be identical to the
valve.
indications on
nameplate.
201
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
用手或者钳子拔掉电器盒电
2. 拆卸电器盒电源连接线
源线
202
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
4.2.Indoor Unit
4.2.1 Duct type
For GUHD09K3CI /GUHD12K3CI
Removal and Assembly of Fan Motor
Remarks: Before removing the fan, make sure to cut off the power firstly.
Step Illustration Handling Instruction
◆ Cut off the power supply of indoor unit.
1. Unplug the motor Use screwdriver to remove the electric
cables box cover and unplug the motor cables
in electric box.
203
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
3. Remove the
◆Remove the screws on fan
screws on fan
sub-assembly.
sub-assembly.
For GUHD18K3CI/GUHD24K3CI/GUHD30K3CI/GUHD36K3CI/GUHD42K3CI/GUHD48K3CI/GUHD60K3CI
Disassembly of filter screen for return air
Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during
disassembly. Do not put filter screen near the high temperature heat source
Step Illustration Handling Instruction
204
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassembly of electrical parts box cover panel and electrical parts box
Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during
disassembly, especially the electrical components. Do not dampen or hit them
Step Illustration Handling Instruction
205
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassembly of evaporator
Remark: Make sure that the power supply is cut off and protect the copper tube and aluminum fin. If the time for
disassembly shall be long, put the copper tube under pressurized condition.
Step Illustration Handling Instruction
Disassemble of fixing screws on the side panels of
evaporator
206
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
4.2.2Cassette-type Unit
Removal and Assembly of Fan Motor
Step Illustration Handling Instruction
207
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
208
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
3 . Pull out the water 2. Loosen the screws fixing the water pump
outlet pipe and ●Pull out the water outlet pipe and
loosen the screws use screwdriver to loosen the
fixing the water screws fixing the water pump.
pump.
4 Take out the pump and ●Take out the pump and replace
replace it it
209
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
4.2.3 Floor Ceiling Type
210
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
●Remove the screws
shown by the arrow in
the graph with
screwdriver (two on
both right and left and
4 in the front) and
Remove then remove the
panel parts panel parts.
212
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
●Remove the fixing
screws of fan wheel
with inner hexagonal
and remove the
wheel. The inner
hexagonal and its
2. Remove fans direction of effect are
shown by the arrow
in the graph.
●Remove 4 screws
on the bearing fixing
plates with
screwdriver. (As
shown in the box in
the graph)
3. Remove
bearing fixing
plates
GTH30K3CI/ GTH36K3CI/GTH42K3CI
Disassembly of panel grating module
Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during
disassembly. Do not put filter screen near the high temperature heat source.
Step Illustration Handling Instruction
●Disassemble the
screws as shown in
the graph with
screwdriver and then
Disassembly of push upward to
right and left remove the right and
finishing plates left finishing
plates.(As is shown
in the graph, arrow
represents the
position of screws.)
213
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
●Unscrew the 3
sides’ screws on
Disassembly of
the cover to
panel parts
remove the cover.
●Disassemble 3
Disassembly screws as shown by
of electric the arrow in the graph
box cover on left and remove the
electric box cover.
214
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassemble
of ●remove the
water-containi water-containing plate
ng plate modules.
modules
215
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
●Disassemble the
bolts on right and
Disassembly of
left fixing plates with
right and left fixing
tools. (As is shown
plates
by the arrow in the
graph.)
216
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GTH48K3CI 、GTH60K3CI
Disassembly of panel grating module
Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during
disassembly. Do not put filter screen near the high temperature heat source.
Step Illustration Handling Instruction
●Disassemble the
screws as shown in the
graph with screwdriver
Disassembly of and then push upward
right and left to remove the right and
finishing plates left finishing plates.(As
is shown in the graph,
arrow represents the
position of screws.)
217
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassembly of sub-assy of electric box
Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during
disassembly, especially the components inside the box in case of water and hit.
Step Illustration Handling Instruction
●Disassemble 3 screws
1. Disassembly as shown by the arrow in
of electric box the graph on left and
cover remove the electric box
cover.
218
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassembly of evaporator components
Remark: Make sure that the power supply is cut off and protect the copper tube and aluminum fin. If the time for
disassembly shall be long, seal the copper tube .
Step Illustration Handling Instruction
219
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Disassembly of fan and motor components
Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during
disassembly, especially the fastening screws for fans.
Step Illustration Handling Instruction
●Unscrew the 2 screws of
coupling, take out the
rotating shaft and louver,
then loosen the tighten
screw of louver to
2. Disassembly remove the louver.
of fans
Disassembly of
right and left
fixing plates
220
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
5 EXPLODED VIEWS AND SPARE PART LIST
5.1 Outdoor Unit
Model: GUHD09NK3CO/GUHD12NK3CO
Exploded View
221
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
NO. Name of Part Part Code Qty
20 Front grill 22413433 1
21 Small Handle '26233100 1
22 Electric Box Assy 01395860 1
23 Radiator 49013027 1
24 Electric Box 20113014 1
25 Filter Board 30033073 1
30228206①
26 Main Board 1
30228207②
27 Reactor 43130184 1
28 Capacitor '33010026 1
29 Terminal Board 42011154 1
①GUHD09NK3CO
②GUHD12NK3CO
Model: GUHD18NK3CO
Exploded View
222
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
11 Strainer '07220019 1
18 Handle '26235254 1
21 Inductance '4312002001 1
22 Supporter '01805405 1
38 Radiator 49018114 1
223
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GUHD24NK3CO
Exploded View
224
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Spare Parts list
NO. Name of Part Part Code Qty
1 Top Cover '01255006P 1
2 Top Cover Sub-Assy '01255007 1
3 Electric Box Cover '01425281 1
4 Condenser Assy '01125394 1
5 Rear Grill '01475008 1
6 4-way Valve '4300008201 1
7 Temperature Sensor '3900028010 1
8 Electronic Expansion Valve '07334193 1
9 StrainerA '07210022 2
10 Right Side Plate '01305044P 1
11 Big Handle '26235001 1
12 Valve Support Sub-Assy '01715012P 1
13 Cut-off Valve '07133157 1
14 Valve '07100005 1
15 Pressure Protect Switch '460200061 1
16 electrical heater '76518732 1
17 Chassis Sub-assy '01195307P 1
18 Compressor Gasket '76710207 3
19 Compressor and fittings '00105036 1
20 Clapboard '01245237 1
21 Motor Support Sub-Assy '01805362 1
22 Fan Motor '15705224 1
23 Axial Flow Fan '10335005 1
24 Front Side Plate '01305072P 1
25 left handle '26235401 2
26 Cabinet '01435004P 1
27 Front Grill '22415003 1
28 Left Side Plate '01305043P 1
29 Condenser support plate '01175092 1
30 Electric Box Assy '01395898 1
31 Radiator '49018112 1
32 Electric Box '26905211 1
33 Main Board '30224306 1
34 Capacitor CBB61 '33010009 1
35 Electric Box Sub-Assy '01395787 1
36 PFC Inductance '43128003 1
37 Electric Box Cover '01425279 1
225
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GUHD30NK3CO
Exploded View
226
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GUHD36NK3CO/GUHD42NK3CO
Exploded View
227
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
①GUHD36NK3CO
②GUHD42NK3CO
Model: GUHD48NK3CO
Exploded View
228
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Spare Parts List
NO. Name of Part Part Code Qty
1 Condenser Assy '01025396 1
2 Rear Grill '01575205 1
3 Temp. Sensor sleeving '05212423 1
4 Strainer '07210037 1
5 Temperature Sensor '3900028002 1
6 Pressure Protect Switch '460200061 1
7 4-way Valve '43000338 1
8 Strainer '07210037 1
9 Handle '26235253 1
10 Valve Support Sub-Assy '01715001 1
11 Gas Valve Sub-Assy '07103030 1
12 Cut-off Valve '07130209 1
13 Electronic Expansion Valve '07334309 1
14 Electric expand valve fitting '4300010810 1
15 Bidirection Strainer '07220016 1
16 Pressure Protect Switch '46020007 1
17 electrical heater '765152123 1
18 Compressor Gasket '76815204 3
19 Compressor and fittings '00205224 1
20 Liquid Accumulator Clamp '01745001 1
21 Gas-liquid Separator Sub-Assy '07225018 1
22 Fan Motor '1501506105 2
23 Axial Flow Fan '10335008 2
24 Front Side Plate '01315364P 1
25 Handle '26235253 1
26 Front grill '22415002 2
27 Left Side Plate '01315366P 1
28 left handle '26235401 1
29 Electric Box Assy '01395965 1
30 Radiator '49010252 1
31 Main Board '30224311 1
32 Electric Box '26904131 1
33 High Frequency Transformer '43110030 1
34 Relay '44020378 2
35 Main Board '30224304 1
36 Capacitor CBB61 '33010010 2
37 Inductance '44020378 2
38 Breaker '46020018 1
39 Terminal Board '42011242 1
229
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GUHD36NM3CO/GUHD42NM3CO
Exploded View
230
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Spare Parts List
NO. Name of Part Part Code Qty
1 Top Cover '01255009P 1
2 Air Guard '01355204 1
01125373①
3 Condenser Assy 1
'01125392②
4 Rear Grill '01475012 1
04145342①
5 4-way Valve Assy 1
'04145362②
6 4-way Valve '43000338 1
7 Pressure Protect Switch '46020006 1
8 Temperature Sensor '3900028002 1
9 Electronic Expansion Valve '07334194 1
07335263①
10 Electric Expansion Valve Sub-Assy 1
'07335271②
11 Cut-off Valve '07133157 1
071302391
12 Cut-off Valve 1
'07133185
13 Right Side Plate Sub-Assy '01305441P 1
14 Handle '26235253 2
15 Valve Support Sub-Assy '01715257P 1
16 clamp '02145008 1
17 electrical heater '76518732 1
18 Gas-liquid Separator Sub-Assy '07255201 1
19 Compressor and fittings '00205236 1
20 Inhalation Tube 1 '04655520 1
21 Retaining Plate Sub-Assy '01845235P 1
22 Chassis Sub-assy '01195244P 1
23 Motor Support Assy '01805396 1
24 Motor Support Sub-Assy '01705111 1
25 Fan Motor '150154516 1
26 Axial Flow Fan '10335010 1
27 Insulated board (cover of electric box) '20113003 1
28 Front Side Plate Sub-Assy '01305508 1
29 Cabinet '01435007P 1
30 Front Grill '22415005 1
'01895309①
31 Condenser support plate 1
'01795020②
32 Left Side Plate '01305064P 1
33 left handle '26235401 1
34 Electric Box Assy '01395956 1
35 Radiator '49018113 1
36 Reactor '43130178 1
37 Main Board '30228806 1
38 Electric Box '26905211 1
39 XY Capacitor '33030013 1
40 Main Board '30224311 1
41 High-frequency transformer '43110030 1
42 Filter Board '30228118 1
43 Relay '44020378 1
44 Terminal Board '42011103 1
45 Capacitor CBB61 '33010009 1
42011221①
46 Terminal Board 1
'42011043②
①GUHD36NM3CO
②GUHD42NM3CO
231
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model: GUHD48NM3CO/GUHD60NM3CO
Exploded View
232
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
①GUHD48NM3CO
②GUHD60NM3CO
233
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
234
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
19 Fan Motor Mounting Plate Sub-Assy '01324341 1
NO. Name of Part Part Code Qty
20 Display Board '30294219 1
21 Remote Controller '305050031 1
22 Lower Cover Plate Sub-Assy '01264178 1
23 Water Tray Assy 01284153 1
24 Terminal Board '42010194 1
25 Transformer '43110239 1
26 Capacitor '33010027 1
27 Main Board '30228205 1
28 Electric Box Assy '01395886 1
29 Choke Plug of Drain Pipe '76712455 1
30 Tube Sensor '390000596 1
31 Room Sensor '39000191 1
32 Electric Box Cover 01424319 1
Model:GFH12K3CI/GFH18K3CI
Exploded View
235
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
236
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
①GFH12K3CI
②GFH18K3CI
Model:GFH24K3CI
Exploded View
237
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
238
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GFH36K3CI/GFH42K3CI
Exploded View
239
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
240
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
241
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GKH12K3CI
Exploded View
242
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Spare Parts List
NO. Name of Part Name Code Qty
243
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GKH18K3CI
Exploded View
244
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Spare Parts List
NO. Name of Part Name Code Qty
1 Tube Exit plate Assy '01382715 1
2 Body Fixing Plate '01332701 4
3 Front Side Plate Assy '01302718 1
4 Left Side Plate Assy '01302715 1
5 Base Plate Assy '01222701 1
6 Rear Side Plate Assy '01302714 1
7 Motor Support '10312701 1
8 Fan Motor '15012703 1
9 Centifugal Fan '10312705 1
10 Evaporator Linkage '01074042 1
11 Tube sensor '390001921 1
12 Evaporator Assy '01029435 1
13 Water Tray Assy '20182701 1
14 Electric Base Plate '01412721 1
15 Flow-guide Loop '10372701 1
16 Terminal Board '42010258 1
17 Electric Box '26909439 1
18 Transformer '43110233 1
19 Electric Box Cover I '20102702 1
20 Ambient Temperature Sensor '390001911 1
21 Electric Box Cover II '20102703 1
22 Main Board '30227111 1
23 Capacitor '33010010 1
24 Electric Box Assy '01399604 1
25 Evaporator Support Assy '01072703 2
245
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GKH24K3CI
Exploded View
ON/OF
TIMER
SWING
FAN
MODE
TJ_01
246
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Spare Parts List
NO. Name of Part Part Code Qty
247
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GKH30K3CI
Exploded View
TJ_01
MODE
FAN
SWING
TIMER
F
ON/OF
248
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GKH36K3CI/ GKH42K3CI
Exploded View
249
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Spare Parts List
No Name of Part Part Code Qty
1 Tube Exit Plate '01382715 1
2 Body Fixed Plate 1332701 1
3 Front Side Plate 01302713 1
4 Left Side Plate '01302711 1
5 Base Plate '01222701 1
6 Rear Side Plate '01302709 1
7 Motor Support '01702701 1
8 Motor FN60T 15012706 1
9 Centifugal Fan '10310101 1
10 Evaporator Linkage '01072732 1
11 Tube sensor '390001921 1
1029423①
12 Evaporator Assy 1
1029422②
13 Water Tray Assy '20182701 1
14 Electric Base Plate '01412721 1
15 Flow-guide Loop '10372722 1
'01399610①
16 Electric Box 1
1399509②
17 Terminal Board '42010258 1
18 Transformer '43110233 1
19 Electric Box Cover I '20102702 1
20 Room Sensor '390001911 1
21 Remote Controller '305125063 1
22 Electric Box Cover II '20102703 1
23 Main PCB '30227111 1
24 Capacitor '33010012 1
25 Drainage Plastic '05232044 1
26 Evap Support '01072707 2
27 Fan Fixer '10312701 1
28 Water Pump '43130324 1
29 Water Level Switch '45010201 1
30 Pump Drainpipe '05230026 1
31 Right Side Plate '01302712 1
32 Pump Cover Plate '01252713 1
33 Display Board '30294219 1
①GKH36K3CI
②GKH42K3CI
250
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GTH09K3CI/GTH12K3CI/ GTH18K3CI/ GTH24K3CI
Exploded View
'01399501④
'33010089①②
17 Capacitor 1
'33010025④③
18 Terminal Board '42010178 1
19 Left Cover '26909443 1
251
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
①GTH09K3CI
②GTH12K3CI
③GTH18K3CI
④GTH24K3CI
252
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GTH30K3CI
Exploded View
253
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
254
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GTH36K3CI
Exploded View
255
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
256
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GTH42K3CI
Exploded View
16 Transformer '4311023701 1
257
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
22 Capacitor '33010014 1
258
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
Model:GTH48K3CI/ GTH60K3CI
Exploded View
259
A/A DC INVERTER U-MATCH AIR CONDITIONERS MAINTENANCE
①GTH48K3CI
②GTH60K3CI
260
JF00300705
261