TESTING 

AND COMMESSIONING OF MEDIUM VOLTAGE EQUIPMENT
11/23/2020 ENG‐SAYED TAHA ELSHEIKH 138
11/23/2020 139
11/23/2020 140
‫‪1.Reduce power system voltages to lower value for ‬‬
‫‪measurement.‬‬
‫ﺗﺧﻔﻳﺽ ﻗﻳﻣﺔ ﺍﻟﺟﻬﻭﺩ ﺇﻟﻰ ﻗﻳﻡ ﻣﻧﺎﺳﺑﻪ ﻳﻣﻛﻥ ﻗﻳﺎﺳﻬﺎ ﺑﺄﺟﻬﺯﺓ ﺍﻟﻘﻳﺎ ﺱ ﺃﻭ ﺍﻟﻭﻗﺎﻳﻪ‬

‫‪2.Insulate secondary circuits from the primary.‬‬
‫ﻋﺯﻝ ﺍﻟﺩﻭﺍﺋﺭ ﺍﻟﻣﻭﺟﻭﺩﻩ ﻓﻰ ﺍﻟﺟﺎﻧﺏ ﺍﻟﺛﺎﻧﻭﻯ ) ﺃﺟﻬﺯﺓ ﻗﻳﺎﺱ ‪ /‬ﻭﻗﺎﻳﻪ ( ﻋﻥ‬
‫ﺍﻟﺟﺎﻧﺏ ﺍﻹﺑﺗﺩﺍﺋﻰ ﺫﻯ ﺍﻟﺗﻳﺎﺭﺍﺕ ﺍﻟﻌﺎﻟﻳﻪ‬

‫‪3.Permit the use of standard voltage ratings (110,100)volt ‬‬
‫‪for secondary equipment.‬‬
‫ﺇﺳﺗﺧﺩﺍﻡ ﻗﻳﻡ ﺟﻬﺩ ﻗﻳﺎﺳﻳﻪ )‪(110,100‬ﻟﻸﺟﻬﺯﻩ ﺍﻟﻣﻭﺟﻭﺩﻩ ﻓﻰ ﺍﻟﺟﺎﻧﺏ ﺍﻟﺛﺎﻧﻭﻯ‬

‫‪11/23/2020‬‬ ‫‪141‬‬
11/23/2020 142
Electromagnetic  Capacitor VT`s (CVT)
VT`s
Similar to a power transformer. Used at high voltages

Main difference is that CVT 
May not be economical above 132kV has a capacitor divider on
the front end.

11/23/2020 143
11/23/2020 144
11/23/2020 145
11/23/2020 146
11/23/2020 147
Groups of V.T

Measurement  Protection 
V.T.s V.T.s
100 VA , 0.1) (100VA , 3P )
11/23/2020 148
11/23/2020 149
11/23/2020 150
11/23/2020 151
11/23/2020 152
INSULATION 
CONTINUTI  RESISTANCE 
CHECK TEST IR 
• FLUKE 87  • MEGGER 
MTI515

VT TEST  VT TESTS
CPC100  CTA 

11/23/2020 153
11/23/2020 154
• Never shorten  • Fuses and switches  • The voltage 
the voltage  should be used in  transformer is 
transformer  voltage transformer  well grounded on 
secondary circuits  secondary circuits. the primary and 
for any reason. ‫ﻳﺟﺏ ﺃﻥ ﺗﺳﺗﺧﺩﻡ‬ secondary side ‫ﻳﺗﻡ‬
‫ﻻﻳﺗﻡ ﻋﻣﻝ ﻗﺻﺭ ﻋﻠﻰ‬ ‫ﺍﻟﻔﻳﻭﺯ ﻭﺍﻟﻣﻔﺎﺗﻳﺢ ﻓﻰ‬ ‫ﺗﺄﺭﻳﺽ ﻣﺣﻭﻝ ﺍﻟﺟﻬﺩ‬
‫ﺍﻟﺩﻭﺍﺋﺭ ﺍﻟﺛﺎﻧﻭﻳﺔ ﻟﻣﺣﻭﻝ‬ ‫ﺍﻟﺩﻭﺍﺋﺭ ﺍﻟﺛﺎﻧﻭﻳﺔ ﻟﻣﺣﻭﻝ‬ ‫ﺟﻳﺩﺍ ﻣﻥ ﺍﻟﺟﺎﻧﺑﻳﻥ‬
‫ﺍﻟﺟﻬﺩ ﻣﻬﻣﺎ ﻛﺎﻧﺕ‬ ‫ﺍﻟﺟﻬﺩ‬ .‫ﺍﻹﺑﺗﺩﺍﺋﻰ ﻭﺍﻟﺛﺎﻧﻭﻯ‬
.‫ﺍﻷﺳﺑﺎﺏ‬

11/23/2020 155
VT 
TESTS

Visual 
Inspection

Insulation Resistance of C.T.  Polarity  WINDING 


Ratio check RESISTANCE
secondary windings check

11/23/2020 156
11/23/2020 157
1.Insulation Resistance of C.T. 
secondary windings

Mode of Connection

PRIMARY‐GROUND 5000 
VDC

PRIMARY‐SECONDARY 2500
VDC

SECONDARY‐GROUND 500
VDC

11/23/2020 158
11/23/2020 159
11/23/2020 160
VOLTAGE TRANSFORMER TEST REPORT
03. Voltage Transformer Test Report.pdf
guha_191110‐100342‐2ac1.pdf

11/23/2020 161
CONTRACTOR CLIENT
OMAN SHAPOORJI COMPANY LLC

Voltage Transformer Test


Report
Client MEDC Date 24-6-2020
CONVENTION CENTRE- OMRAN
Tender No (PACKAGE-3)
Equipment 11 kV VT
Location GALA Feeder Details 11 kV Distribution
Manufacturer VOLTAMP Switchgear No. 1 TO

1.0 Panel No.3 Incomer -1(INC-1):


1.1 VT Specifications:
Sec. Winding Sec. Winding-1 Sec. Winding-2 Sec. Winding-3
Function Metering Protection Protection
Class 0.5 3P 3P
VA 100 50 50
Ratio 11000/√3:110/√3

1.2 VT Serial No.:


Phase Serial No.
R 16/006947
Y 16/006948
B 16/006949

1.3 Insulation resistance Test:


Applied Voltage Measured IR Value (GΩ)
Circuit Reference
(V) R Y B
5000 Primary to Earth
5000 Primary to Secondary-1 8.01 8.54 8.62
5000 Primary to Secondary-2 8.10 8.32 8.45
5000 Primary to Secondary-3 NOT UES
500 Sec-1 to Sec-2 32.1 11.3 10.5
500 Sec-1 to Sec-3 23.54 14.3 12.66
500 Sec-2 to Sec-3 21.6 15.1 16.86
500 Secondary-1 to Earth 17.6 14.44 22.1
500 Secondary-2 to Earth 16.0 10.6 20.1
1

500 Secondary-3 to Earth 9.8 8.5 12.46


Page

1.4 VT Primary & Secondary Winding Resistance:

Tested By Witnessed By
Name SAYED TAHA AHMED AL ZEIDI

Signature

Organization/License GGPL / PE 003/2019 MEDC


Date 24.06.2020 24.06.2020
CONTRACTOR CLIENT
OMAN SHAPOORJI COMPANY LLC

Voltage Transformer Test


Report
Measured WR Value (mΩ) @ 34° C
Core Terminals
R Y B
Sec. Winding-1 1a-1n 393.8 391.8 388.7
Sec. Winding-2 2a-2n 790.3 753.0 750.7

1.5 VT Polarity Check:


Core Terminals R Y B
Sec. Winding-1 1a-1n OK OK OK
Sec. Winding-2 2a-2n OK OK OK

1.6 VT Ratio Test:


PHASE/CORE CORE-1 CORE-2 CORE-3
Pri.Volt.(mV) 402.2 402.5 NOT USE
R Sec.Volt. (V) 40.00 40.00 NOT USE
Ratio 99.46 99.3 NOT USE
Pri.Volt. (V) 401.8 402.0 NOT USE
Y Sec.Volt. (V) 40.00 40.00 NOT USE
Ratio 99.55 99.3 NOT USE
Pri.Volt (V) 401.5 402.6 NOT USE
B Sec.Volt (V) 40.0 40.0 NOT USE
Ratio 99.62 99.35 NOT USE

1.7 VT Visual Check:


Description Remarks
VT Fixing OK
VT Fuses Continuity OK
Secondary terminal OK
No Any mechanical damage OK
2
Page

Tested By Witnessed By
Name SAYED TAHA AHMED AL ZEIDI

Signature

Organization/License GGPL / PE 003/2019 MEDC


Date 24.06.2020 24.06.2020