225 kV Guinea-Mali Power Interconnection Project
Lot n ° P6: 225/30 kV Beyla and Nzérékoré substations
International Bidding Document / PART 2 - Project Owner s Requirements
Section VII. Specifications
5.6 Power transformers
DATA SHEET
20 MVA 225/30/11 kV transformer
Item Designation Units Specified Value Guaranteed value
General features
1 Manufacturer
2 Model To indicate
3 Installation
4 Type of transformer immersed in oil
5 Core Type 3 columns
6 Number of phases 3
7 Rated frequency Hz 50
8 Rated power
HV winding (primary) MVA 20
LV winding (secondary) MVA 20
9 Maximum operating voltage kV 245
10 Group symbol YNyn0 + d
11 Nominal current at the nominal voltage tap
and in ONAF operation
HV winding (primary) A
LV winding (secondary) A
12 System of cooling ONAN
13 Transformation Report
HV winding (primary) kV 225 ± 12x1.25%
LV winding (secondary) kV 30
stabilizing winding kV 11
Insulation level of windings
14 Power frequency withstand voltage
net kV 460
BT kV 70
Neutral HT kV 185
LV neutral kV 70
15 Surge withstand voltage (BIL):
net kV 1050
BT kV 170
Neutral HT kV 450
LV neutral kV 170
16 Switching impulse withstand voltage:
net kV 850
BT NA
Neutral HT NA
LV neutral NA
17 Limits of temperature rise at maximum
operating voltage and for a maximum
ambient temperature of 50 ° C
Page VII-24