Transformer Datasheet Part 1

This document specifies the requirements for a 20 MVA 225/30/11 kV power transformer to be used in substations in Guinea and Mali. It lists 17 key technical specifications for the transformer including its manufacturer, type, cooling system, voltage levels, insulation levels, temperature rise limits and more. The transformer must be able to withstand various voltage levels and meet specified temperature rise limits when operating at maximum voltage in an ambient temperature of 50 degrees C.

Uploaded by

amulya00428
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views1 page

Transformer Datasheet Part 1

This document specifies the requirements for a 20 MVA 225/30/11 kV power transformer to be used in substations in Guinea and Mali. It lists 17 key technical specifications for the transformer including its manufacturer, type, cooling system, voltage levels, insulation levels, temperature rise limits and more. The transformer must be able to withstand various voltage levels and meet specified temperature rise limits when operating at maximum voltage in an ambient temperature of 50 degrees C.

Uploaded by

amulya00428
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

225 kV Guinea-Mali Power Interconnection Project

Lot n ° P6: 225/30 kV Beyla and Nzérékoré substations


International Bidding Document / PART 2 - Project Owner s Requirements
Section VII. Specifications

5.6 Power transformers

DATA SHEET

20 MVA 225/30/11 kV transformer

Item Designation Units Specified Value Guaranteed value


General features
1 Manufacturer
2 Model To indicate
3 Installation
4 Type of transformer immersed in oil
5 Core Type 3 columns
6 Number of phases 3
7 Rated frequency Hz 50
8 Rated power
HV winding (primary) MVA 20
LV winding (secondary) MVA 20
9 Maximum operating voltage kV 245
10 Group symbol YNyn0 + d
11 Nominal current at the nominal voltage tap
and in ONAF operation
HV winding (primary) A
LV winding (secondary) A
12 System of cooling ONAN

13 Transformation Report
HV winding (primary) kV 225 ± 12x1.25%
LV winding (secondary) kV 30
stabilizing winding kV 11
Insulation level of windings
14 Power frequency withstand voltage

net kV 460
BT kV 70
Neutral HT kV 185
LV neutral kV 70
15 Surge withstand voltage (BIL):
net kV 1050
BT kV 170
Neutral HT kV 450
LV neutral kV 170
16 Switching impulse withstand voltage:
net kV 850
BT NA
Neutral HT NA
LV neutral NA
17 Limits of temperature rise at maximum
operating voltage and for a maximum
ambient temperature of 50 ° C

Page VII-24