WB4 Short Form - Dual Branding - 10-24-19
WB4 Short Form - Dual Branding - 10-24-19
WB4 Short Form - Dual Branding - 10-24-19
CAFCO® SprayFilm® WB 4
(Americas)
ISOLATEK® Type WB 4
(Worldwide)
This is an abbreviated guide and is not intended as a substitute for the Long Form CAFCO SprayFilm WB 4 / ISOLATEK Type WB 4 Application &
Installation Manual. Applicator shall completely and fully read and understand the Long Form Application & Installation Manual prior to applying
this product.
PUMP REQUIREMENTS: Pneumatic, electric or gas-powered airless spray pump operating with a minimum fluid
pressure of 3,000 psi (207 bar, 20.7mPa, 211 kq/cm2) and 1.25gpm (4.7 L/m). Remove all
filters and rock catcher screens. A direct immersion pump is required. Pumps that utilize
siphon hoses at the material intake are not recommended. Recommended pump is a Graco
Mark V or equivalent.
MIXING REQUIREMENTS: Standard shielded drywall mixing paddle or Jiffy style mixer, thoroughly mix for 3-5 minutes
prior to use.
HOSE SET-UP: High pressure, minimum 3/8 in. (10mm) I.D. hose rated to exceed the maximum pump
capacity. An optional 1/4 in. (6.35mm) I.D. whip hose is allowable at a maximum of 2 ft.
(61cm) in length. Overall hose length is dependent on the application equipment being used.
SPRAY GUN: A Graco HD Texture Spray Gun Model #241-705, Series B or equivalent with diffuser tip
removed capable of handling a minimum 3,000 psi (207 bar, 20.7mPa, 211 kq/cm2) fluid
pressure.
SPRAY TIP: Reversible type. Tip size minimum is 225 and maximum is 431.
BRUSH: Use a high-grade soft bristle latex paint brush. Brush lightly in one direction using as few
strokes as possible. Do not roll the material.
TROWEL: For use only with SprayFilm WB 4 TG / Type WB 4 TG (Trowel Grade), use a straight edge
trowel to apply to a smooth even finish.
SURFACE PEPARATION: All structural steel to be coated with SprayFilm WB 4 / Type WB 4 must first be primed with
an approved primer. Primed surface must be free from any grease oil, dirt, loose mill scale,
rust or any other contaminant that would inhibit the bond of the product to the primer. Primer
must be fully cured and installed in accordance with the primer manufacturer’s application
instructions before application. A complete list of approved primers can be found on our
website www.isolatek.com.
GALVANIZED AND ZINC-RICH SprayFilm WB 4 / Type WB 4 cannot be applied directly to galvanized steel or directly
PRIMERS: over Zinc-Rich primers. An approved tie-coat must be applied in accordance with
manufacturer’s instructions. Contact Isolatek Technical Services for more information.
The distance between the spray gun and substrate must be a minimum 18 in (45 cm).
SPRAY GUN DISTANCE:
Typical spray gun distance from the substrate is between 24 in. and 36 in. (61 cm and 92
cm).
APPLICATION TEMPERATURE: Apply product when the ambient air temperature is between 50°F (10°C) and 100°F (38°C).
A minimum ambient and substrate temperature of 50°F (10°C) must be maintained during
and a minimum of 72 hours after application. Steel surface temperature must be a minimum
4°F (2°C) above the dew point to prevent condensation from forming. The maximum steel
temperature is 100°F (38°C).
HUMIDITY: Do not exceed a relative humidity of 85%. Precautions must be taken to avoid condensation
forming on the steel during application. Do not apply product if condensation is present.
High humidity levels will increase drying times and may promote sagging. Reduce the
maximum wet film thickness per coat.
WEATHER PROTECTION: SprayFilm WB 4 / Type WB 4 must be protected from any and all weather exposure during
the application and after the product has fully cured. Tarps may be used to enclose work
areas. This procedure, in addition to jobsite heat, will help maintain proper substrate and
ambient temperatures
MASKING Required on all areas not to receive SprayFilm WB 4 / Type WB 4. Masking typically
consists of lightweight polyethylene plastic and the appropriate tape/adhesive. It is installed
to protect all surfaces not to receive product
1 of 2
For initial coat, apply a “catch coat” between 3 mils and 5 mils (0.076 mm and 0.13 mm) Wet
CATCH COAT: Film Thickness (WFT), sufficient to cover the primer. The “catch-coat” must dry 1 to 2 hours
before subsequent coats can be applied.
SUBSEQUENT COATS: Product can be applied at the wet film thicknesses shown in the table below. A second coat
may be applied within one spray day, provided a minimum drying time of 4 hours is allowed
between coats. A maximum of 2 coats can be applied per spray day (24 hrs). The thickness
applied per coat is dependent on relative humidity, air and steel temperature, and airflow:
VENTILATION: Provide a minimum of 4 complete air exchanges per hour until the material is dry
A minimum of 5 days must be allowed prior to applying a top coat over SprayFilm WB 4 /
DRY TIME: Type WB 4. Alternatively, achieving a minimum Shore D value of 50 is recommend prior
to applying a topcoat. Increased drying time may be required under conditions of low air
flow and/or high humidity.
TOPCOATING: A topcoat is not required by UL for Conditioned Interior Space Purpose and /or Interior
General Purpose. Refer to our Finish Coat Materials data page for additional information
regarding finish coats.
NOTE: DO NOT APPLY THE TOPCOAT UNTIL THE FINAL THICKNESS OF THE
SPRAYFILM WB 4 / Type WB 4 IS VARIFIED AND THE FINISH OF THE INSTALLED
PRODUCT IS ACCEPTABLE.
EXTERIOR USE: For exterior use, UL requires that SprayFilm WB 4 / Type WB 4 be coated with CAFCO®
SprayFilm® Topseal® / ISOLATEK® Type Topseal® at a total DFT of 14 mils (0.35mm),
applied in two coats. Refer to the SprayFilm WB 4 / Type WB 4 application guide for
additional information.
Isolatek International requires that for exterior use, an approved exterior finish coat be
EXTERIOR FINISH COAT: applied to a minimum DFT of 7 mils over the surface of the SprayFilm Topseal / Type
Topseal within 14 days of the final application. A minimum of 24 hours shall be allowed prior
to the application of the exterior finish coat. The exterior finish coat must be installed in
accordance with manufacturers written application and installation instructions.
TERMINATION POINTS: All exposed product edges/termination points of the SprayFilm WB 4 / Type WB 4 system
shall be sealed in order to avoid intrusion of moisture. To properly seal the
edges/terminations, SprayFilm Topseal / Type Topseal shall extend from all
edges/terminations of the SprayFilm WB 4 / Type WB 4 onto the adjacent substrate a
minimum of 2 inches at a minimum DFT of 7 mils (0.17mm). In locations where SprayFilm
Topseal / Type Topseal cannot extend beyond the protected substrate, a high-grade exterior
silicone caulk shall the be installed onto the adjacent or adjoining substrate in a manner
suitable to completely seal the termination point.
SAFETY PRECAUTIONS: Safety glasses, gloves, and a dust mask should be worn in cases where individuals are
exposed to airborne mists of the material. Refer to the SDS for complete health and
safety information.
STORAGE/SHELF LIFE: Product must be stored in a dry environment with temperatures between 33°F (1°C) and
100°F (38°C). The shelf life of the material is 12 months in unopened, sealed containers,
properly stored.
NOTE: Only the listed equipment and procedures are approved for applying CAFCO SprayFilm WB 4 / ISOLATEK Type WB 4. Deviations from these
requirements will result in product not meeting claims as published in the literature. For additional information, please contact the Technical Service
Department.
10/18 – 071 072