2 Stages Comp.1 - CRLT
2 Stages Comp.1 - CRLT
2 Stages Comp.1 - CRLT
2-STAGE
SEMI-HERMETIC
AIR COOLED REFRIGERATION CONDENSING UNITS
CRLT Series
Example:
X
CR L T - 1500 - F Z
UNIT MODELS
CRLT-1500 - FX 15 F CRLT-1500 - FZ 15 F
CRLT-2000 - FX 20 F CRLT-2000 - FZ 20 F
CRLT-2500 - GX 25 G CRLT-2500 - GZ 25 G
CRLT-3000 - GX 30 G CRLT-3000 - GZ 30 G
1
STANDARD FEATURES
2
STANDARD FEATURES
COMPRESSOR
• Electronic motor protection with
thermal monitoring with PTC sensors
• Integrated differential pressure relief valve to protect the compressor against high discharge
pressures.
• Discharge gas temperature sensor (optional).
• Terminal box enclosure class is IP54 (as per standard IEC34)
FAN MOTOR
• Thermal protection.
• Protection grill on propeller side for safety of personnel conforms to machinery directive (CE).
• Class F insulation as per standards NFC 51200-11 and CEI 34-1.
• Terminal box enclosure class is IP55 (as per standard IEC34)
CRANKCASE HEATER
• To guard compressor against flood back conditions and to eliminate oil fluffing on start up.
• Insertion type
HIGH / LOW PRESSURE CONTROL
• To protect the compressor against high discharge pressures and low suction pressures.
• Terminal box enclosure class is IP44 (as per standards IEC529/EN60529)
OIL PRESSURE DIFFERENTIAL CONTROL
• To protect compressor against lack of oil.
• Connected to the oil pump discharge outlet and the crankcase pressure.
The oil pressure control breaks the control circuit when the pressure difference between the oil
pump outlet and the crankcase drops below 0.7 bar, then the compressor will be stopped after
a 120 seconds delay after having solved the problem, the control has to be reset manually.
• Terminal box enclosure class is IP44 (as per standards IEC529/EN60529).
THE UNITS COMPLY WITH CE DIRECTIVES:
• Low Voltage Directive (LVD).
• Machinery Directive (MD).
• Electro-Magnetic Compatibility (EMC).
3
LAYOUT OF 2- STAGE SYSTEM WITH LIQUID SUBCOOLER AND INTERSTAGE COOLING
BY INTERSTAGE THERMOSTATIC EXPANSION VALVE
17 16 15 7 8
5
6
13
12 14
11 10 9
18 3 2 1 4
Legend
1 Compressor
2 Low pressure cylinder heads
3 High pressure cylinder heads
4 Thermostatic expansion valve with external equalizer
5 Interstage liquid subcooler
6 Oil separator
7 Condenser
8 Liquid receiver
9 Inter stage filter drier
10 Interstage solenoid valve
11 Interstage sight glass
12 Filter for oil return line
13 Solenoid valve for oil return line
14 Sight glass for oil return line
15 Expansion valve (evaporator)
16 Evaporator
17 Suction accumulator (Field installed)
18 Suction line filter (Field installed)
4
PIPING DIAGRAM OF 2-STAGE SYSTEM WITH LIQUID SUBCOOLER AND INTERSTAGE
COOLING BY INTERSTAGE THERMOSTATIC EXPANSION VALVE
Legend
DL Discharge line
SL Suction line
ML Intermediate pressure mixing line
FL Liquid line
1 High pressure connection (HP)
3 Low pressure connection (LP)
17 Interstage liquid subcooler
19 Oil separator ( oil return )
20 Interstage thermostatic expansion valve
21 Interstage solenoid valve
23 Interstage filter drier
24 Valve sensor / sensor pocket
25 External equalizer of thermostatic expansion valve
26 Interstage sight glass
5
REFRIGERATING CAPACITY AND POWER INPUT
CONDENSING UNITS LOW TEMPERATURE CRLT SERIES
R22 CRLT 50Hz
AMBIENT EVAPORATING TEMPERATURE (ºC)
MODEL
°C -20 -25 -30 -35 -40 -45 -50
CRLT-1500-FX 27 30310 25345 20945 17050 13590 10490 7660
32 29980 25090 20740 16875 13420 10295 7405
37 29665 24845 20545 16710 13260 10110
Q
42 29365 24605 20370 16570 13125
46 29150 24435 20240 16475
27 14.26 13.09 11.90 10.72 9.53 8.36 7.19
32 15.19 13.91 12.63 11.35 10.07 8.79 7.51
P 37 16.11 14.73 13.35 11.97 10.58 9.17
42 17.03 15.53 14.05 12.56 11.05
46 17.76 16.17 14.61 13.02
CRLT-2000-FX 27 35130 29380 24275 19760 15750 12160 8880
32 34750 29085 24040 19560 15555 11935 8585
37 34385 28795 23815 19370 15370 11720
Q
42 34040 28520 23605 19205 15215
46 33785 28320 23460 19095
27 16.53 15.17 13.79 12.42 11.05 9.69 8.34
32 17.61 16.12 14.64 13.15 11.67 10.19 8.71
P 37 18.68 17.07 15.47 13.87 12.26 10.63
42 19.74 18.00 16.29 14.56 12.80
46 20.6 18.74 16.63 15.10
CRLT-2500-GX 27 40330 33730 27840 22685 18085 13960 10195
32 39895 33390 27600 22455 17855 13700 9855
37 39480 33060 27345 22240 17650 13455
Q
42 39080 32745 27105 22050 17470
46 38790 32515 26935 21925
27 18.98 17.41 15.84 14.26 12.68 11.12 9.57
32 20.2 18.51 16.81 15.10 13.40 11.70 10.00
P 37 21.4 19.60 17.76 15.92 14.07 12.20
42 22.7 20.7 18.70 16.72 14.70
46 23.6 21.5 19.44 17.33
CRLT-3000-GX 27 48255 40355 33350 27145 21635 16705 12200
32 47735 39950 33025 26865 21365 16395 11790
37 47235 39555 32715 26610 21115 16100
Q
42 46755 39180 32430 26380 20900
46 46410 38900 32225 26230
27 22.7 20.8 18.95 17.06 15.18 13.30 11.45
32 24.2 22.1 20.1 18.07 16.03 13.99 11.96
P 37 25.7 23.4 21.2 19.05 16.84 14.60
42 27.1 24.7 22.4 20.0 17.59
46 28.3 25.7 23.3 20.7
NOTES
(1) Performance data are based on 20°C suction gas temperature with system inherently liquid subcooling
based on liquid subcooler according to European Standard EN 13215 .
(2) Q = Refrigerating Capacity in watts.
(3) P = Power Input in KW according to DIN 8971: including Fans.
6
REFRIGERATING CAPACITY AND POWER INPUT
CONDENSING UNITS LOW TEMPERATURE CRLT SERIES
R404A CRLT 50Hz
AMBIENT EVAPORATING TEMPERATURE (ºC)
MODEL
°C -20 -25 -30 -35 -40 -45 -50
CRLT-1500-FZ 27 27070 23295 19740 16450 13450 10785
32 26505 22810 19325 16095 13165 10575
37 25955 22320 18905 15750 12900 10380
Q
42 25495 21865 18500 15425 12660 10195
46 25245 21555 18210 15190 12475 10045
27 15.05 13.74 12.47 11.24 10.05 8.91
32 16.00 14.58 13.21 11.90 10.63 9.42
P 37 16.94 15.42 13.96 12.65 11.21 9.93
42 17.83 16.23 14.68 13.20 11.78 10.41
46 18.48 16.83 15.24 13.70 12.22 10.78
CRLT-2000-FZ 27 31275 26925 22830 19020 15550 12470
32 30585 26340 22325 18595 15215 12220
37 29895 25740 21810 18185 14900 11995
Q
42 29310 25175 21320 17790 14615 11780
46 2478 20960 17500 14395 11605
27 17.47 15.95 14.47 13.04 11.66 10.33
32 18.53 16.90 15.32 13.79 12.32 10.92
P 37 19.60 17.85 16.17 14.55 12.99 11.50
42 20.6 18.79 17.01 15.30 13.65 12.07
46 19.51 17.67 15.88 14.16 12.51
CRLT-2500-FZ 27 35585 30710 26080 21750 17800 14280
32 34860 30065 25505 21265 17405 13990
37 34110 29380 24915 20780 17040 13725
Q
42 33420 28715 24335 20325 16705 13475
46 32965 28230 23900 19980 16450 13270
27 20.0 18.32 16.64 15.00 13.41 11.87
32 21.3 19.40 17.59 15.85 14.16 12.55
P 37 22.5 20.5 18.56 16.70 14.92 13.20
42 23.7 21.6 19.53 17.56 15.67 13.85
46 24.6 22.4 20.3 18.25 16.27 14.35
CRLT-3000-GZ 27 42495 36585 31025 25870 21180 17015
32 41455 35705 30285 25255 20700 16660
37 40411 34805 29530 24660 20255 16345
Q
42 39475 33950 28810 24105 19850 16040
46 38890 33343 28280 23690 19540 15785
27 23.9 21.9 19.89 17.94 16.04 14.21
32 25.2 23.1 21.0 18.96 16.95 15.00
P 37 26.6 24.4 22.2 19.98 17.85 15.80
42 28.1 25.7 23.3 21.7 18.75 16.57
46 29.3 26.8 24.3 21.8 19.46 17.18
NOTES
(1) Performance data are based on 20°C suction gas temperature with system inherently liquid subcooling
based on liquid subcooler according to European Standard EN 13215 .
8
IMPORTANT INFORMATION
Only qualified personnel should install and repair compressors. The electrical connection of the compressor
and of its accessories is also to be done by authorized personnel only.
Delivery
Please check whether the delivery is complete and intact. Deficiencies should be immediately reported in writing.
Installation Guidance
• Do not use the units outside of the operating limits specified.
• Install only in a properly ventilated area.
• Check tightness of all screw terminals.
• Check that the electrical supply to the installation is suitable and that the motor is connected correctly.
• Check the currents drawn.
• The refrigerant circuit must be perfectly clean, dry and installed according to best refrigeration practice.
• Check settings of all safety devices.
• Limit the superheat of the suction gas to 20K for low temperature operation.
Compressor Motor of Part Winding Construction
With this type of motor the stator winding is separated into two parts - normally in Y/YY connection. The
both coil packets lay parallel to each other in the stator slots and the winding crown. They are insulated
from each other. With this construction it is possible to switch the part windings one after the other (with
a time delay), resulting in a significantly reduced starting current.
Electrical Connections
Closely observe part-winding
1. Part winding (contactor K1): Connections 1U1, 1V1, 1W1
2. Part-winding (contactor K2): Connections 2U1, 2V1, 2W1
Time delay before connection of the second part-winding 0.5 seconds
Attention!
Danger of compressor damage!
Wrong wiring results in opposing or displaced rotating fields due to changed phase angle. This leads to
locked rotor conditions. Mount connections correctly.
Attention!
Compressor motor is equipped with electronic protection device!
• The electrical connections should be made according to the wiring diagram.
• When the protection device cuts out, this indicates either an overload or impermissible operating
conditions:
Determine the source of the problem and correct it!
• Terminals B1-B2, M1-M2 and cables 1-2 must not come into contact with supply or control voltage!
System Cleanness
Braze only when using inert gas. Only materials and components approved by refrigeration engineering are
suitable.
It is absolutely necessary that all impurities (dirt, brazing scale, flux, scobs etc.) are removed from the
system before operation in order to avoid breakdowns. Many of these impurities are so small that they can
pass through the filter built into the suction side of the compressor. Other blockages can occur in the
suction filter situated in the compressor. A high pressure drop can even damage the filter. For this reason
we strongly recommend the use of a large suction tube filter (which causes only a minimal drop of pressure)
for all installations which are to be assembled on site or in cases where the required cleanness cannot be
guaranteed.
Pipe Connections
The pipe connections are designed to , accept tubes with standard millimeter or inch dimensions. Solder
connections have stepped diameters. According to the size the tube can be pushed more or less into the
fitting. If not required the end with the largest diameter can be cut off.
Warning!
Compressor is under pressure with holding charge.
Injury of skin and eyes possible. Wear safety goggles while working on compressor:
Do not open connections before pressure has been1'eleased.
Attention!
Absolutely avoid penetration of air!
The shut-off valves should remain closed until evacuating.
Pipelines
Only use tubes and components which are
• Clean and dry inside (free from slag, swart, rust, and phosphate coatings) and
• Which are delivered with an air tight seal.
Leak Test
The suction shut-off valve and discharge shut-off valve on the compressor remain closed during pressure
testing to prevent air and moisture from entering. The test pressure (dried nitrogen) must not exceed 20.5
bar provided no other system component’s pressure is lower; in these cases the lower pressure is the test
pressure.
10
COMMISSIONING
Evacuation (Drying)
Energize the crankcase heater.
Open all shut-off valves and solenoid valves. Evacuate the entire system including compressor using a
vacuum pump connected to the high and low pressure sides.
When the pump is switched off a "standing vacuum" of less than 1.5 mbar must be maintained.
If necessary repeat this procedure several times.
Attention!
Danger of motor and compressor damage!
Do not start compressor under vacuum!
Do not apply any voltage - not even for test purposes!
Charging Refrigerant
Charge only permitted refrigerants
• Before refrigerant is charged:
- Energize the crankcase heater.
- Check the compressor oil level.
- Do not switch on the compressor!
• Liquid refrigerant must be filled through the charge fitting in the receiver shut-off valve or in the liquid
line. The use of a filter drier in the charging line is highly recommended.
• For systems with flooded evaporator refrigerant can be also charged into the evaporator.
• After commissioning it may be necessary to add refrigerant:
Charge the refrigerant from the suction side while the compressor is in operation. Charge preferably
at the evaporator inlet.
Blends must be taken from the charging cylinder as "solid liquid".
If liquid is charged:
Attention!
Danger of wet operation!
Charge small amounts at a time!
Keep the oil temperature above 40°C.
Danger!
Explosion risk of components and pipelines by hydraulic overpressure.
Avoid absolutely overcharging of the system with refrigerant!
11
CHECKS BEFORE STARTING
Ensure that all service valves are in the open
position before start-up. A closed discharge or suction service valve may cause serious damage to
the compressor and/or compromise safety device operation, thereby resulting in potential injury to
personnel.
• Oil Level
Each compressors is delivered with sufficient oil charge for normal operation.
The optimum oil level should be checked by operating the compressor until the system is stable and
then comparing the sight glass reading with the appropriate diagram.
The oil level can also be checked within 10 seconds of compressor shut-down.
• Check that all safety devices are operational and properly set.
• For high-pressure switches the setting must not exceed maximum service pressure of any system
component. Refer to the Application Guidelines for relevant compressor pressure safety limits.
• A low-pressure switch is recommended to prevent operation under vacuum. Use a minimum setting of
1.1 bar (absolute).
• Verify that all electrical connections are properly fastened and in compliance with local safety
regulations.
• Ensure that the crankcase heater of compressor has been energized for a minimum of 12 hours before
initial start-up and/or after prolonged shutdown periods.
12
START-UP PROCEDURE
Never start the system in the absence of a refrigerant charge.
Do not bypass the safety switches during start up.
Attention!
During pull down operation:
Danger of extreme suction gas superheat and therefore thermal overload of the compressor!
Ensure sufficient refrigerant charge bubble - free at intake of interstage expansion valve and subcooler.
Attention!
Danger of wet operation!
Keep the discharge temperature at least 30 K ( R22 ) or at least 20 K ( R404A ) above condensing
temperature.
Attention!
Danger of liquid slugging!
Check the oil return.
Vibrations
The whole plant especially the pipe lines must be checked for abnormal vibrations.
If necessary additional protective measures must be taken.
Attention!
Pipe fractures and leakages at compressor and other components of the plant possible !
Avoid strong vibrations!
Switching Frequency
The compressor should not be started more than 8 times per hour. Thereby a minimum running time
should be guaranteed:
Unit model min. running time
CRLT 1500-2000-2500-3000 5 min
13
START-UP PROCEDURE (CONT.)
• Avoid refrigerant migration (high pressure to low pressure side) during longer shut-off periods.
- Application of a crankcase heater.
- Pump down system (especially if evaporator can get warmer than suction line or compressor).
- Automatic sequence change for systems with multiple refrigerant circuits.
14
SERVICE / MAINTENANCE
Electric Shock Hazard
Disconnect the main power supply before servicing the system or handling any internal parts of the unit.
Regular Checks
Examine regularly the plant according to national regulations.
Check the following points:
• Operating data.
• Oil supply.
• Protection devices and all compressor monitoring (parts differential oil pressure switch, high / low
pressure switch).
• Check electrical cable connections on tight fitting.
• Check tightening torques.
• Refrigerant charge, tightness test.
• Update data protocol.
Oil Changing
Oil changing is not normally necessary for factory assembled plants. For "field installations" and for
applications near the operating limits a first oil change is recommended after approx.
100 operating hours.
This includes cleaning the oil filter and magnetic plug.
After that the oil has to be replaced approx. every 3 years or 10000 - 12000 operating hours. Clean also oil
filter and magnetic plug.
Attention!
Ester oils are strongly hygroscopic.
Moisture is chemically compounded with these oils. It cannot be, or only insufficiently, removed by
evacuation.
Handle very carefully:
Avoid air admission into the plant and oil can. Use only originally closed oil drums.
15
DE-COMMISSIONING
Standstill
Keep the crankcase heater switched on until dismantling the compressor! This prevents increased
refrigerant solution in the compressor oil.
Dismantling Compressor
For repair work, that makes dismantling necessary, or when decommissioning them:
Close the shut-off valves at the compressor. Pump-off the refrigerant. Do not release the refrigerant but
dispose it properly!
Warning!
Compressor can be under pressure!
Severe injuries possible. Wear safety goggles!
Open the threaded joints or flanges at the compressor valves. Remove the compressor if necessary with a
hoisting tool.
Disposing Compressor
Drain the oil at the compressor.
Dispose of waste oil properly!
Chlorinated oil is pollutive waste.
Attention!
Oil is already in the system,
Therefore it may be necessary to drain a part of the oil charge. If there are large quantities of oil in the
circuit (possibly from a preceding compressor damage), there is also a risk of liquid slugging at start.
Adjust oil level within the marked sight glass range!
16
DIMENSIONS (mm)
R22 MODELS R404A MODELS
Fig (1) H
D
H
Fig (2)
17
DIMENSIONS (mm)
R22 MODELS R404A MODELS
Fig (1) H
D
H
Fig (2)
www.miraco.com.eg
Carrier is committed to continuously improving its products according to national and international standards
to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
All specifications subject to change without prior notice according to Carrier policy of continuous development.