This document provides specifications for sizing the busbars for a 415V low voltage switchgear for a 2 x 685MW thermal power plant in Raipur, Chhattisgarh, India. It specifies the required busbar sizes and enclosure dimensions for various current ratings ranging from up to 500A to 3200/4000A based on a fault level of 50kA for 1 second and 105kA peak. Notes provide information on ambient temperature, temperature rise limits, and permissible final temperature for the busbars after a fault.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
138 views1 page

Busbar Selection Chart

This document provides specifications for sizing the busbars for a 415V low voltage switchgear for a 2 x 685MW thermal power plant in Raipur, Chhattisgarh, India. It specifies the required busbar sizes and enclosure dimensions for various current ratings ranging from up to 500A to 3200/4000A based on a fault level of 50kA for 1 second and 105kA peak. Notes provide information on ambient temperature, temperature rise limits, and permissible final temperature for the busbars after a fault.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

OWNER :

OWNER ENGINEER`S :

CLIENT :

MANUFACTURER : C& S ELECTRIC, NOIDA

PROJECT : 2 x 685MW THERMAL POWER PLANTAT RAIPUR,CHHATTISGARH


DOOSAN DOCUMENT NO. : T10107-YT10-P0BF-141402 DATE- 19.07.11

C&S DOCUMENT NO. : DOOSAN/J2754/703 REV : P1


DESCRIPTION : BUSBAR SIZING CALCULATION FOR 415V LV SWITCHGEAR

SIZE OF ENCLOSURE
Sr.
RATING (AMP) SIZE OF BUS BAR (Al.) FAULT LEVEL OF BUS BAR REMARKS
No.
CHAMBER (HXD)

A MAIN BUSBAR
2(50.8x6.35) Sq.mm/ PHASE & 50KA FOR 1SEC,
1 UP TO 500A 365(H)X1000(D)
NUETRAL 105KA PEAK
2(76.2X6.35) Sq.mm/PHASE & 50KA FOR 1SEC,
2 600 / 800A 365(H)X1000(D)
NUETRAL 105KA PEAK
2(101.6X6.35) Sq.mm/ PHASE & 50KA FOR 1SEC,
3 1000A 365(H)X1000(D)
NUETRAL 105KA PEAK
2(152.4X6.35) Sq.mm/ PHASE 50KA FOR 1SEC,
4 1250A 1(152.4X6.35) Sq.mm/ NUETRAL 365(H)X1000(D)
105KA PEAK
3(152.4X6.35) Sq.mm/PHASE 50KA FOR 1SEC,
5 1600/2000A 2(152.4X6.35) Sq.mm/NUETRAL 365(H)X1000(D)
105KA PEAK
6(152.4X6.35) Sq.mm/PHASE 50KA FOR 1SEC,
6 3200/4000A 3(152.4X6.35)Sq.mm/NUETRAL 365(H)X1200(D)
105KA PEAK

NOTES -:
1 Ambient temperature of switchgear =50˚C
2 Max.temp.rise due to normal full load current = 35˚C
3 Operating tempreature of busbar = 85˚C
4 Permissible final busbar tempreature after fault = 185˚C