Sheet (1) - Electrical Power System-Transmission Line

This document contains 6 practice problems related to calculating electrical parameters for transmission lines. Problem 1 involves calculating values for a 160-km, 132 kV transmission line delivering 30 MW at 0.9 power factor lagging using the T-model. Problem 2 derives expressions relating sending and receiving end voltage and current for a medium line. Problem 3 calculates ABCD parameters, power, voltage regulation and efficiency for a 345 kV, 200 km line delivering 700 MW at 0.99 power factor leading.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
284 views2 pages

Sheet (1) - Electrical Power System-Transmission Line

This document contains 6 practice problems related to calculating electrical parameters for transmission lines. Problem 1 involves calculating values for a 160-km, 132 kV transmission line delivering 30 MW at 0.9 power factor lagging using the T-model. Problem 2 derives expressions relating sending and receiving end voltage and current for a medium line. Problem 3 calculates ABCD parameters, power, voltage regulation and efficiency for a 345 kV, 200 km line delivering 700 MW at 0.99 power factor leading.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Electrical Power System (1)

Sheet (1)

Problem 1

A 60 Hz, three-phase 160-km transmission line has r =0.1 Ω/km, L=1.25 mh/km
and C=0.01 μf/km. The line delivers 30 MW at 132 KV with 0.9 p.f lag. Using
the T-model (medium Line), Calculate the following:
a-The sending end voltage, current, power and sending power factor.
b- The regulation and efficiency of this operation.

Problem 2
a-Derive an expression relating sending end voltage and current with receiving
end in case of medium transmission line (п-section).

b- A 132 KV, three-phase, 50-Hz, 200 Km transmission line has the following
distributed parameters:
R= 0.157 Ω/Km; L=1.265x10-3 H/Km; C= 8.75x10-9 F/Km.
Calculate: a-the sending end voltage, current, power, and power factor,
b- the voltage regulation and the efficiency. When delivering 50 MVA, at 0.8 pf.
lagging. Assume-medium line (п-section).

Problem 3
A three-phase, 60 Hz, completely transposed 345 KV, 200 Km line has two
795000 cmil 26/2 ACSR conductors per bundle and the following positive-
sequence line constants:
z=0.032 +j 0.35 Ω/km
-6
y= j 4.2x10 S/km.
Full load at the receiving end of the line is 700 MW at 0.99 p.f. leading and at
95% of rated voltage. Assuming a medium-length line, determine the following:
i-ABCD parameters of the nominal π -circuit.
ii-Sending-end voltage VS, current IS and real power PS.
iii-Percent voltage regulation.
iv-Transmission line efficiency at full load.
Problem 4
a-Derive an expression relating sending end voltage and current with receiving
end in case of long transmission line.

b-A three-phase 765 KV, 60 Hz, 300 km, completely transposed line has the
following positive- sequence impedance and admittance:
z= 0.0165 + j 0.3306 = 0.331 87.14 0 Ω/km
y=j 4.674 x 10-6 S/km.
Assuming positive-sequence operation, calculate the exact ABCD parameters of
the line. Compare the exact B parameter with that of the nominal π -circuit.

Problem 5
a- Derive a formula for sending end and receiving end power flow in transmission
line in terms of ABCD constants.
b- Calculate the real and reactive power loss in the transmission line of problem 1.

a-Derive an expression relating sending end voltage and current with receiving
end in case of medium transmission line (T-section).

b- A 220 KV, three-phase, 50-Hz, 150 Km transmission line has the following
distributed parameters:
R= 0.157 Ω/Km; L=1.265x10-3 H/Km; C= 8.75x10-9 F/Km.
Calculate: a-the sending end voltage, current, power, and power factor,
b- the voltage regulation and the efficiency. When delivering 50 MW, at 0.85 pf.
lagging. Assume Π –section.

Problem 6
a- Derive an expression relating sending end voltage and current with receiving
end in case of medium transmission line (Π-section). b-A three-phase 132 KV, 50
Hz, 100 km, completely transposed line has the following positive- sequence
impedance and admittance:
z= 0.0165 + j 0.3306 = 0.331 87.14 0 Ω/km
y=j 4.674 x 10-6 S/km.
Calculate: a-the sending end voltage, current, power, and power factor,
b- the voltage regulation and the efficiency. When delivering 50 MW, at 0.85
pf. lagging. Assume T–section.