Product Data Sheet 6ES7315-2AH14-0AB0
Product Data Sheet 6ES7315-2AH14-0AB0
SIMATIC S7-300,
CPU 315-2DP CPU WITH MPI INTERFACE INTEGRATED
24 V DC POWER SUPPLY 256 KBYTE WORKING
MEMORY 2. INTERFACE DP-MASTER/SLAVE MICRO
MEMORY CARD NECESSARY
General information
Hardware product version 01
Engineering with
Programming package STEP 7 V5.5 + SP1 or higher or STEP7 V5.2 + SP1 or higher with
HSP 218
Supply voltage
24 V DC Yes
Mains buffering
Repeat rate, min. 1s
Input current
Current consumption (rated value) 850 mA
I²t 1 A²·s
Power losses
Memory
Type of memory other
Work memory
Integrated 256 kbyte
expandable No
Load memory
pluggable (MMC) Yes
Backup
present Yes ; Guaranteed by MMC (maintenance-free)
CPU-blocks
Number of blocks (total) 1024 ; (DBs, FCs, FBs); the maximum number of loadable blocks
can be reduced by the MMC used.
DB
Number, max. 1024 ; Number range: 1 to 16000
FB
Number, max. 1024 ; Number range: 0 to 7999
FC
Number, max. 1024 ; Number range: 0 to 7999
OB
Description see instruction list
Nesting depth
per priority class 16
S7 counter
Number 256
Retentivity
can be set Yes
lower limit 0
preset Z 0 to Z 7
Counting range
lower limit 0
IEC counter
present Yes
Type SFB
S7 times
Number 256
Retentivity
can be set Yes
lower limit 0
preset No retentivity
Time range
lower limit 10 ms
IEC timer
present Yes
Type SFB
Flag
Number, max. 2048 byte
Retentivity preset MB 0 to MB 15
Data blocks
Number, max. 1024 ; Number range: 1 to 16000
Local data
per priority class, max. 32 kbyte ; Max. 2 KB per block
Address area
of which, distributed
Inputs 2048 byte
Process image
Inputs 2048 byte
Subprocess images
Number of subprocess images, max. 1
Digital channels
Inputs 16384
Outputs 16384
Analog channels
Inputs 1024
Outputs 1024
Hardware configuration
Expansion devices, max. 3
Number of DP masters
Integrated 1
Via CP 4
CP, point-to-point 8
CP, LAN 10
Rack
Racks, max. 4
Time of day
Clock
Hardware clock (real-time clock) Yes
Behavior of the clock following POWER-ON Clock continues running after POWER OFF
Behavior of the clock following expiry of backup period Clock continues to run with the time at which the power failure
occurred
Number/Number range 0
Granularity 1 hour
Clock synchronization
supported Yes
in AS, slave No
Digital inputs
Number of digital inputs 0
Digital outputs
Analog inputs
Number of analog inputs 0
Analog outputs
Number of analog outputs 0
Interfaces
Number of USB interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Functionality
MPI Yes
DP master No
DP slave No
Point-to-point connection No
MPI
Transmission rate, max. 187.5 kbit/s
Services
PG/OP communication Yes
Routing Yes
S7 communication, as client No
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Functionality
DP master Yes
DP slave Yes
Point-to-point connection No
DP master
Transmission rate, max. 12 Mbit/s
Services
PG/OP communication Yes
Routing Yes
S7 communication, as client No
SYNC/FREEZE Yes
DPV1 Yes
Address area
Inputs, max. 2048 byte
DP slave
GSD file The latest GSD file is available at: http://www.siemens.com/profibus-
gsd
Services
PG/OP communication Yes
S7 communication, as client No
DPV1 No
Transfer memory
Inputs 244 byte
Isochronous mode
Isochronous operation (application synchronized up to Yes
terminal)
Communication functions
PG/OP communication Yes
S7 basic communication
supported Yes
User data per job (of which consistent), max. 76 byte ; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT
or X_GET as server)
S7 communication
supported Yes
as server Yes
User data per job (of which consistent), max. 240 byte ; as server
S5-compatible communication
supported Yes ; via CP and loadable FC
Number of connections
overall 16
S7 message functions
Number of login stations for message functions, max. 16 ; Depending on the configured connections for PG/OP and S7
basic communication
Number of breakpoints 4
Status/control
Status/control variable Yes
Forcing
Forcing Yes
Diagnostic buffer
present Yes
can be set No
Of which powerfail-proof 100 ; Only the last 100 entries are retained
preset 10
Service data
Ambient conditions
Configuration
Configuration software
STEP 7 Yes ; V5.2 SP1 or higher with HW update
programming
Command set see instruction list
Nesting levels 8
Programming language
LAD Yes
FBD Yes
STL Yes
SCL Yes
CFC Yes
GRAPH Yes
HiGraph® Yes
Know-how protection