Evaluation Condition of Transformer Based On Infrared Thermography Results
Evaluation Condition of Transformer Based On Infrared Thermography Results
Evaluation Condition of Transformer Based On Infrared Thermography Results
bushing shared be three side, top, middle, and bottom. isolation 7 layer to
~I streaming
layer/ flux well
In normal condition the thermal pattern of the winding to I
~ .
I
transformer tank and radiators is cooler at the bottom High Temperature winding I
Authorized licensed use limited to: Universidad de chile. Downloaded on November 09,2020 at 11:37:24 UTC from IEEE Xplore. Restrictions apply.
3. Dielectric System 50
2. Radiator
I
' - -_ _- - " L . . -_ _----I On radiator, methodthat used is comparing temperature
---------
I
I
on each radiator fins. The position on each radiatorfins
Fig 3. Rootcausesfunctional failure in paperisolation when measured shouldbe the same.
1056
Authorized licensed use limited to: Universidad de chile. Downloaded on November 09,2020 at 11:37:24 UTC from IEEE Xplore. Restrictions apply.
ANALYSIS MEASURING METHOD Table 2. Paek Load of Transformer 2 BalarajaApril
The concept of thermography monitoring transformer 2009
are evaluating condition each parts of transforrner, is
there any abnormality or not based on pattern Dates Times A MW MVAR Temp," C
temperature results and find position of abnormality. 1 10:00 1080 3 11 76.67
2 10:00 1170 39 13 81.6
3 10:00 1200 40 13 83.74
Unusually high external temperatures or unusual 4 10:00 960 32 7 72.64
thermal patterns of transformer tanks indicate problems 5 11 :00 600 20 0 57.55
6 9:00 1140 38 11 77.68
inside the transformer, Abnormally high temperatures 1110
7 10:00 37 37 78.7
can damage or destroytransformer insulation and, thus, 8 11:00 870 29 11 76.67
reduce life expectancy. Thermal patterns oftransfonner 9 10:00 360 12 -5 55.54
tanks should be cooler at the bottom and gradually 10 10:00 570 19 1 55.54
11 10:00 840 28 6 61.55
wanner ascending to the top[3] . When temperature at 12 10:00 600 20 0 56.54
the bottom or middle of transformer tank is hotter than 13 11:00 1110 37 12 84.74
the top, means that there are problems inside the 14 9:00 1170 39 11 82.72
15 9:00 1200 40 13 86.76
maintank. Next analysis are compare the thermography
16 10:00 1290 43 15 91.8
monitoring results with other tests, such as DGA and 17 9:00 1260 42 14 88.7
oil Quality. 18 10:00 900 30 6 79.63
19 10:00 630 21 2 60.56
Evaluation Thermograph Monitoring Results. 20 11:00 1110 37 10 85.66
21 11:00 1080 36 11 82.74
In Balaraja high voltage substation, there are two 22 9:00 1140 38 12 81.73
transformers, They have same manufacturer and same 23 9:00 1200 40 13 83.74
capacity. But abnormality in transformer I . When both 24 10:00 1170 37 12 81.72
25 10:00 102 34 8 75.66
transformer have same load, the temperature of winding 26 10:00 660 22 2 60.58
indicator in transformer 2 will be higher than 27 10:00 1080 36 11 85.68
transformer I. 28 11 :00 1050 35 9 80.72
Table I.Paek Load ofTransfonner I BalarajaApril Basedon data of paek load of transformer 1 and 2, in 16
2009 April 2009, paek load is 1290. Temperature of
transformer 1 is 60,74°C and temperature oftransfonner
Dates Times A MW MVAR Temp," C 2 is 91,8°C. Defference temperature is 31,06 -c. Due to
I 10:00 750 25 17 61.75 the fact that, we do investigation to know root causes of
2 10:00 1020 34 14 60.71
3 10:00 1410 47 19 62.78 that abnormality.
4 10:00 810 27 13 56.59
5 10:00 690 23 7 55.55 Most of measuring that shoulddo are off-line conditions.
6 9:00 1320 44 20 57.62 Due to the fact that, we do thermographic measuring to
7 9:00 870 29 9 54.58
8 9:00 930 31 10 51.52 check parts of transformer. This method is practice due
9 10:00 330 11 I 54.5 to performed in on-line condition to know is there any
10 10:00 570 19 4 52.5 problems or not in transformer..
11 9:00 930 31 14 59.59
12 10:00 990 33 14 56.65
13 10:00 1350 45 19 61.72
14 9:00 1320 44 24 61.74
15 9:00 1260 42 20 62.65
16 8:00 1290 43 16 60.74
17 10:00 1050 35 16 60.7
18 8:00 1230 41 20 62.67
19 9:00 1020 34 21 54.57
20 9:00 1290 43 18 60.77
21 9:00 1230 41 16 61.77
22 8:00 1170 39 20 60.75
23 9:00 1230 41 15 57.69
24 8:00 1380 46 19 60.74
25 9:00 990 33 11 55.61
26 10:00 450 15 8 55.55
27 9:00 1290 43 18 59.62
28 10:00 1290 43 18 60.75 Fig 8. Abnormal on Radiator
1057
Authorized licensed use limited to: Universidad de chile. Downloaded on November 09,2020 at 11:37:24 UTC from IEEE Xplore. Restrictions apply.
Second case is a transformer 1 in Cikupa high voltage
substation. [5] IEC 60422."Mineral Insulating Oil in Electrical
Equipment Supervision and Maintenance Guidance".
ThirdEdition 2005 .
Breakdown Voltaie
58.9
REFERENCES
[l] CIGRE TF Dl.Ol.lO, "Ageing of Cellulose in
Mineral-Oil Insulated Transformers," -, -, -, Technical
Brochure TB 323, Oct.2007.
1058
Authorized licensed use limited to: Universidad de chile. Downloaded on November 09,2020 at 11:37:24 UTC from IEEE Xplore. Restrictions apply.