DIGITAL
No Description Check Status
1 TAC-1 Running ON Status for Bed & Fly Ash
2 TAC-2 Running ON Status for Bed & Fly Ash
3 TAD-1 Running ON Status for Bed & Fly Ash
4 TAD-2 Running ON Status for Bed & Fly Ash
5 TAC-1 Trip Status for Bed & Fly Ash Doubt
6 TAC-2 Trip Status for Bed & Fly Ash Doubt
7 BED ASH SILO Level High Remaining
8 FLY ASH SILO Level High Remaining
9 BED ASH SILO ROTARY FEEDER-1 Running ON Status
10 BED ASH SILO ROTARY FEEDER-2 Running ON Status
11 FLY ASH SILO ROTARY FEEDER-1 Running ON Status
12 FLY ASH SILO ROTARY FEEDER-2 Running ON Status
13 Drain Pit Lime Stone Bunker High Level
14 Drain Pit Lime Stone Bunker Low Level
15 Instrument Air Pressure Normal at Fly Ash Silo Remaining
16 TAC-1 for Lime Stone & Bed Material Running ON Status
17 TAC-2 for Lime Stone & Bed Material Running ON Status
18 TAC Drier 1 for Lime Stone & Bed Material, Running ON Status
19 TAC Drier 2 for Lime Stone & Bed Material, Running ON Status
20 TAC-1 for Lime Stone & Bed Material, TRIP Status
21 TAC-2 for Lime Stone & Bed Material, TRIP Status
22 Lime Stone Bunker-1 Level High Remaining
23 Lime Stone Bunker-2 Level High Remaining
24 Lime Stone Surge Hopper Level High
25 Bed Material Surge Hopper Level High
26 Bed Material Bunker-1 Level High
27 Bed Material Bunker-2 Level High
28 TAC Pressure for Fly Ash & Bed Ash
ANALOG
Modbus Point Type : Input Register
No Description
1 Dry Fly Ash Silo Level
2 Dry Bed Ash Silo Level
3 Bed Material Bunker 1 Level
4 Bed Material Bunker 2 Level
5 Lime Stone Bunker 1 Level
6 Lime Stone Bunker 2 Level
Note :
DI Motor DO Motor
XB01 : Run/ ON YB01 : On Command
XB02 : Stop / OFF YB02 : Off Command
XB03 : RTS/RFS
XB12 : Trip
XB22 : L/R
DI Valve DO Valve
XG01 : Open F/B YG01 : Open Cmnd Valve
XG02 : Close F/B YG02 : Close Cmnd Valve
Signal Modbus List from AHS to DCS