Modbus List Signal From AHS To DCS Rev.2

The document describes a Modbus TCP/IP configuration with an IP address of 192.168.1.22 on port 502 to connect to slave ID 1. It then lists digital and analog input signals for monitoring equipment status including status descriptions, KKS tagging information, and data ranges.

Uploaded by

Jhon Manurung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views7 pages

Modbus List Signal From AHS To DCS Rev.2

The document describes a Modbus TCP/IP configuration with an IP address of 192.168.1.22 on port 502 to connect to slave ID 1. It then lists digital and analog input signals for monitoring equipment status including status descriptions, KKS tagging information, and data ranges.

Uploaded by

Jhon Manurung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 7

Protocol : Modbus TCP/IP

IP Address : 192.168.1.22
Port : 502
Slave ID : 1

DIGITAL
No Description Check Status
1 TAC-1 Running ON Status for Bed & Fly Ash
2 TAC-2 Running ON Status for Bed & Fly Ash
3 TAD-1 Running ON Status for Bed & Fly Ash
4 TAD-2 Running ON Status for Bed & Fly Ash
5 TAC-1 Trip Status for Bed & Fly Ash Doubt
6 TAC-2 Trip Status for Bed & Fly Ash Doubt
7 BED ASH SILO Level High Remaining
8 FLY ASH SILO Level High Remaining
9 BED ASH SILO ROTARY FEEDER-1 Running ON Status
10 BED ASH SILO ROTARY FEEDER-2 Running ON Status
11 FLY ASH SILO ROTARY FEEDER-1 Running ON Status
12 FLY ASH SILO ROTARY FEEDER-2 Running ON Status
13 Drain Pit Lime Stone Bunker High Level
14 Drain Pit Lime Stone Bunker Low Level
15 Instrument Air Pressure Normal at Fly Ash Silo Remaining
16 TAC-1 for Lime Stone & Bed Material Running ON Status
17 TAC-2 for Lime Stone & Bed Material Running ON Status
18 TAC Drier 1 for Lime Stone & Bed Material, Running ON Status
19 TAC Drier 2 for Lime Stone & Bed Material, Running ON Status
20 TAC-1 for Lime Stone & Bed Material, TRIP Status
21 TAC-2 for Lime Stone & Bed Material, TRIP Status
22 Lime Stone Bunker-1 Level High Remaining
23 Lime Stone Bunker-2 Level High Remaining
24 Lime Stone Surge Hopper Level High
25 Bed Material Surge Hopper Level High
26 Bed Material Bunker-1 Level High
27 Bed Material Bunker-2 Level High
28 TAC Pressure for Fly Ash & Bed Ash

ANALOG
Modbus Point Type : Input Register
No Description
1 Dry Fly Ash Silo Level
2 Dry Bed Ash Silo Level
3 Bed Material Bunker 1 Level
4 Bed Material Bunker 2 Level
5 Lime Stone Bunker 1 Level
6 Lime Stone Bunker 2 Level

Note :
DI Motor DO Motor
XB01 : Run/ ON YB01 : On Command
XB02 : Stop / OFF YB02 : Off Command
XB03 : RTS/RFS
XB12 : Trip
XB22 : L/R

DI Valve DO Valve
XG01 : Open F/B YG01 : Open Cmnd Valve
XG02 : Close F/B YG02 : Close Cmnd Valve
Signal Modbus List from AHS to DCS

KKS Tagging KKS Mapping at PLC Signal Type Range


00ETP01AN001.XB01 00ETP01AN001.XB01 Digital Event 0 1
00ETP02AN002.XB01 00ETP02AN001.XB01 Digital Event 0 1
00ETD01AN001.XB01 00ETP01AH001.XB01 Digital Event 0 1
00ETD02AN002.XB01 00ETP02AH001.XB01 Digital Event 0 1
00ETP01AN001.XB03 00ETP01AN001.XB03 Digital Alarm 0 1
00ETP02AN002.XB03 00ETP02AN001.XB03 Digital Alarm 0 1
00ETH00CL001.XC01 00ETH00CL001 Digital Alarm 0 1
00ETH00CL002.XC01 00ETH00CL002 Digital Alarm 0 1
00ETL04AM001.XB01 00ETL04AM001.XB01 Digital Alarm 0 1
00ETL05AM002.XB01 00ETL05AM002.XB01 Digital Event 0 1
00ETL02AM001.XB01 00ETL02AM001.XB01 Digital Event 0 1
00ETL03AM002.XB01 00ETL03AM002.XB01 Digital Event 0 1
00ETR00CL101 00ETR00CL101 Digital Alarm 0 1
00ETR00CL102 00ETR00CL102 Digital Alarm 0 1
01ETQ01CP102.XG01 01ETQ01CP102.XG01 Digital Event 0 1
00ETP03AN001.XB01 00ETP03AN001.XB01 Digital Event 0 1
00ETP04AN002.XB01 00ETP04AN002.XB01 Digital Event 0 1
00ETP03AH001.XB01 00ETP03AH001.XB01 Digital Event 0 1
00ETP04AH001.XB01 00ETP04AH001.XB01 Digital Event 0 1
00ETP03AN001.XB12 00ETP03AN001.XB12 Digital Alarm 0 1
00ETP04AN002.XB12 00ETP04AN002.XB12 Digital Alarm 0 1
00ETE00CL001.XC01 00ETE00CL001 Digital Alarm 0 1
00ETE00CL002.XC01 00ETE00CL002 Digital Alarm 0 1
00ETE00CL101.XG01 00ETE00CL101 Digital Alarm 0 1
00ETE00CL102.XG01 00ETE00CL102 Digital Alarm 0 1
00ETE00CL003.XC01 00ETE00CL003.XC01 Digital Alarm 0 1
00ETE00CL004.XC01 00ETE00CL004.XC01 Digital Alarm 0 1
00ETP03CP001.XC01 00ETP03CP001.XC01 Digital Event 0 1

KKS Tagging Signal Data Type Range


00ETH00CL002_XC01 Analog DINT 0 25
00ETH00CL001_XC01 Analog DINT 0 25
00ETE00CL003_XC01 Analog DINT 0 25
00ETE00CL004_XC01 Analog DINT 0 25
00ETE00CL001_XC01 Analog DINT 0 25
00ETE00CL002_XC01 Analog DINT 0 25
Unit Status Value Addrress
Status[0].0 1
Status[0].1 0
Status[0].2 0
Status[0].3 0
Status[0].4 0 RTS signal coming, because of inside logic PLC XB03 it must be for trip sign
Status[0].5 0 RTS signal coming, because of inside logic PLC XB03 it must be for trip sign
Status[0].6 0
Status[0].7 0
Status[0].8 0
Status[0].9 0
Status[0].10 0
Status[0].11 0
Status[0].12 0
Status[0].13 0
Status[0].14 0
Status[1].0 1
Status[1].1 0
Status[1].2 1
Status[1].3 1
Status[1].4 0
Status[1].5 0
Status[1].6 0
Status[1].7 0
Status[1].8 0
Status[1].9 0
Status[1].10 1
Status[1].11 1
Status[1].12 0

Unit Status Value Address


Meter Status[2] 2559 30005
Meter Status[3] 1 30007
Meter Status[4] 108 30009
Meter Status[5] -25 30011
Meter Status[6] 9 30013
Meter Status[7] -25 30015
PLC XB03 it must be for trip signal, but here using for RTS signal status
PLC XB03 it must be for trip signal, but here using for RTS signal status