Lec 3-Economic Dispatch of A Power System
Lec 3-Economic Dispatch of A Power System
Converting the heat-rate curve from Btu/h to $/h results in the fuel cost curve
The fuel cost of generator i can be represented as a quadrature function of real power generation
The incremental fuel cost curve can be obtain by plotting the derivative of the fuel-cost curve
versus the real power.
Economic Dispatch Neglecting Losses and No Generator limits
the transmission lines losses are neglected, then the model dose not consider system configuration
and line impedances.
The first condition results in
Since
Where P1, P2, and P3 are in MW. The total load PD is 800 Mw. Neglecting line losses and generator limits, find the
optimal dispatch and the total cost in $/h.
Or:
Where Pi(min) and Pi(max) are the minimum and maximum generating limits respectively for
plant i.
Example 2: find the optimal dispatch and total cost in $/h for thermal plants of example 1 when the
total load is 975 MW, with the following generator limits (in MW).
For long transmission lines, losses are a major factor and effect the optimum dispatch of generation
The coefficient Bij are called loss coefficient or B- coefficient. These coefficient assumed constant.
Example 3:
The fuel cost in $/h of three thermal plants of a power system are
Where P1, P2, and P3 are in Mw. Plant outputs are subjected to the following limits
Where the loss coefficient are specified in per unit on a 100-MVa base. Determine the optimal dispatch
of generation when the total system load is 150 MW.