Evaluation of HFO-1234YF As A Replacement For R134A in Frigori Fic Air Conditioning Systems
Evaluation of HFO-1234YF As A Replacement For R134A in Frigori Fic Air Conditioning Systems
Evaluation of HFO-1234YF As A Replacement For R134A in Frigori Fic Air Conditioning Systems
Evaluation of HFO-1234YF
as a Replacement for R134A in Frigorific
Air Conditioning Systems
Abstract The aim of this study was to compare and evaluate the frigorific air
conditioning system using HFO-1234yf and R-134a as a refrigerant. For this aim,
an experimental frigorific air conditioning system using both refrigerants was
developed and refrigerated air was introduced into a refrigerated room. The per-
formance parameters determined were the change of the air temperature in the
condenser inlet and time. The performance of frigorific air conditioning system has
been evaluated by applying energy analysis. Experiments were conducted for a
standard frigorific air conditioning system using the R134a as a refrigerant. Airflow
has been introduced to the refrigerated room for 60 min for each performance test.
From the result for both refrigerant, the temperature gradient in time was compa-
rable. The HFO-1234yf refrigerant can use the standard frigorific air conditioning
system that is currently being used by the R134a refrigerant, without any changes
needing to be made.
Nomenclature
COP Coefficient of performance
h Enthalpy (kJ kg−1)
m_ Mass flow rate (g s−1)
Q_ Cooling capacity (W)
W_ Power (W)
Subscripts
comp Compressor
cond Condenser
evap Evaporator
in Inlet
out Exit
r Refrigerant
ref Refrigerated room
14.1 Introduction
mobile air conditioners with a mixture of R134a and HFO-1234yf. They found that
in the HFO-1234yf/R134a mixture when more R134a was added, the properties of
flammability decrease, while compositions with R134a above 10 %, the mixture
became non-flammable.
In this study, to evaluate the comparative experimental performances, a frigorific
air conditioning system using HFO-1234yf and R134a was developed and refrig-
erated air was introduced into a refrigerated room. The effects of using R134a and
HFO-1234yf, as a refrigerant in a frigorific air conditioning system, and their
respective performances were determined comparatively.
The experimental system is made from original components of a frigorific air con-
ditioning system, as schematically shown in Fig. 14.1. It employs a seven-cylinder
fixed-capacity swash-plate SANDEN SD 5750 W compressor at 2200 rpm, a
9500 W parallel-flow micro-channel condenser, a 5750 W laminated-type evapo-
rator and thermostatic expansion valves. An experimental system was connected to a
refrigerated room for the test. The room dimensions are 210 cm × 220 cm × 220 cm.
This refrigerated room was insulated by 8-cm-thin isolation panels.
All lines in the refrigeration circuit of the system were made from copper tubing
and insulated by elastomeric material. The condenser was inserted into separate air
ducts of 1.2 m length. In order to provide the required airstreams in the air ducts, an
axial fan was placed at the condenser ducts. These ducts also contained electric
heaters located upstream of the condenser. The condenser electric heaters could be
controlled between 0 and 2 kW. To provide the required air temperature at the inlets
of the condenser, the refrigeration circuit was charged with 1500 g R134a and
HFO-1234yf. In order to gather data for the performance evaluation of the exper-
imental frigorific system, some mechanical measurements were conducted on the
system. The instruments and their locations are depicted in Fig. 14.1. The features
of the instrumentation can be seen in Table 14.1.
The temperatures of the refrigerant and air at the inlet and exit of each com-
ponent were measured by K-type thermocouples. The refrigerant pressures at the
inlet and exit of the compressor were monitored by digital manifold. The values of
most of the measured variables were acquired through a data acquisition system and
recorded on a computer. The airstream discharged from the evaporator duct was
supplied to the refrigerated room for cooldown tests. In order to measure the
compartment temperatures, a thermocouple was located at the exit of the evapo-
rator, while another one was suspended in the air close to the left wall, and the last
one was suspended in the air close to the right wall.
The refrigerant flow path in the experimental system is illustrated in Fig. 14.1.
The refrigerant passing through the condenser rejects heat to the ambient airstream.
Then, the refrigerant condenses and leaves the condenser as sub-cooled liquid.
After that, the refrigerant flow reaches the receiver tank, which keeps the unrequired
refrigerant when the thermostatic expansion valve decreases the refrigerant flow
rate at low-cooling loads reaches TXV located at the inlet of the evaporator. It
enters the evaporator, where it rejects cool air taken from the refrigerated room, and
leaves the evaporator as low-pressure superheated vapour. After, the refrigerant is
directed to the compressor, which receives the low-pressure refrigerant vapour and
compresses it to a high pressure. The performance of HFO-1234yf was tested in a
standard R134a frigorific air conditioning without alterations being made.
The performance of the frigorific air conditioning system can be evaluated by using
the first law of thermodynamics. The evaporator, the cooling capacity of the
experimental frigorific air conditioning system, can be evaluated from
14 Evaluation of HFO-1234YF as a Replacement for R134A … 155
Assuming that the compressor is adiabatic, the power absorbed by the refrigerant
during the compression process can be expressed as follows:
Q_ evap
COP ¼ ð14:3Þ
W_ comp
The effect of the air temperature at the condenser inlet on certain of the steady-state
performance parameters of the frigorific air conditioning system using HFO-1234yf
and R-134a as a refrigerant is shown in Figs. 14.2 and 14.3. As is shown in
Fig. 14.2, the steady-state cooling capacity usually increases on decreasing the
temperatures of the airstreams entering the condenser. Higher cooling capacity has
been provided with HFO-1234yf compared to the air conditioning systems using
R134a. Figure 14.3 indicates that COP drops with air temperature entering into the
condenser. This is due to the increasing cooling capacity and decreasing com-
pressor power with decreasing Tcond,in. Consequently, COP for both refrigerants is
closely comparable.
3500
2500
25 30 35
Air temperature at the condenser inlet (°C)
156 M. Direk et al.
COP
3
1
25 30 35
Air temperature at the condenser inlet (°C)
10
-10
0 5 10 15 20 25 30 35 40 45 50 55 60
time (d)
Figure 14.4 indicates a slight alteration in the air temperatures in the first 30 min,
the HFO-1234yf refrigerant dropping slightly lower during this period. This change
is only temporary, and the graph reveals how these two temperatures reunite fol-
lowing the initial 30 min and maintain the same decline thereafter. The graph
reveals promising results.
14.5 Conclusions
The steady-state results demonstrated that the frigorific air conditioning system
cooling capacity usually gets higher on decreasing the temperatures of the air-
streams travelling through the condenser. The frigorific air conditioning system
using R134a provided a higher cooling capacity when compared with the air
14 Evaluation of HFO-1234YF as a Replacement for R134A … 157
Acknowledgments The authors would like to thank the University of Yalova for supporting this
study through a Research Project No: 2013/BAP/063.
References