34478-SHE - NGTS 3.1.1 - Substation Interlocking Schemes
34478-SHE - NGTS 3.1.1 - Substation Interlocking Schemes
34478-SHE - NGTS 3.1.1 - Substation Interlocking Schemes
NGTS 3.1.1
Issue 1
October 1993
CONTENTS Page
Foreword . . . . . . . . . . . . . . . . . . . . . . . 1
Scope . . . . . . . . . . . . . . . . . . . . . . . . . 1
References . . . . . . . . . . . . . . . . . . . . . 1
General Requirements . . . . . . . . . . . . 1
Performance Requirements . . . . . . . . 3
Test Requirements . . . . . . . . . . . . . . . 3
Technical Data Required for
Approval . . . . . . . . . . . . . . . . . . . . . . . 3
M B Humphries
General Manager
Technology and Science Division
© National Grid Company plc 1993
No part of this publication may be reproduced,
stored in a retrieval system, or transmitted in
any form or by any means electronic, mechanical,
photocopying, recording or otherwise, without
the written permission of the NGC obtained from
the issuing location.
Registered Office
National Grid House
Kirby Corner Road
Coventry
CV4 8JY
Registered in
England and Wales
No. 2366977
Published by:
FOREWORD
This document defines the requirements for interlocking schemes in National Grid Company
substations.
1 SCOPE
This functional Specification is applicable to interlocking for air (AIS) and gas (GIS) insulated
switchgear at substations connected to the National Grid Company system and with equipment
installed rated at 145, 300 or 420 kV.
2 REFERENCES
This document makes reference to or shall be read in conjunction with the documents listed
below:
3 GENERAL REQUIREMENTS
3.1.1 Substations shall be provided with a full interlocking scheme to ensure that all
disconnectors, fixed earthing switches (or other interlocked earthing devices) and, where required,
circuit-breakers are operated in the correct sequence so that personnel do not endanger
themselves and/or the integrity of the transmission system by incorrect or inadvertent operation
of equipment. Where necessary, such interlocking shall also be extended to cover limitation of
access to areas where there is a risk that normal safety clearances may be infringed.
(i) Interlocking between circuit-breakers and disconnectors to ensure disconnectors do not make
or break load currents.
(ii) Interlocking between disconnectors and earthing switches to ensure that earthing switches
cannot be closed on to a locally energised circuit and cannot be energised, when closed, by
operation of disconnectors.
(iii) Interlocking between disconnectors and adjacent earthing switches to permit operation of the
disconnector when earthing switches are closed on both sides of the disconnector. Such
interlocking is not required for equipment rated at 145 kV and below.
(iv) Ensuring correct sequence of on load busbar transfer switching operations at multiple busbar
substations.
NGTS 3.1.1
Page 2 Issue 1
October 1993
(v) Ensuring that a bus-coupler or bus-section circuit-breaker is only closed with its associated
disconnectors both open or both closed.
(vi) Ensuring access to areas of the substation where safety clearances may be infringed unless
appropriate safety measures, such as isolation and earthing, have been taken.
3.1.3 The interlocking of switching sequences involving only power operated switchgear shall be
by electrical means. The correct interlocking status shall be confirmed automatically on initiation
of an operation from any control position or from auto-switching or sequential-isolation equipment.
3.1.4 The interlocking of switching sequences involving manually operated switchgear may be
by electrical or mechanical means. The interlocking shall be designed such that the correct
interlocking status must be confirmed immediately before an operation.
3.1.5 Interlocking systems shall, where practicable, be fail-safe. They shall not be defeatable
without the use of tools, clip leads etc or a purpose designed override facility which shall be
lockable with safety locks to the approval of NGC.
3.1.7 Interlocking shall be effective for switching and operating sequences when they are being
followed in either direction (for example; if an earthing switch must be closed before an access
gate can be opened then the gate must be secured closed before the earthing switch can be
opened).
3.1.8 Interlocking schemes shall, where reasonably practicable, provide the maximum operational
flexibility and shall not unnecessarily impose fixed operating sequences.
3.1.9 Where an interlocking scheme is being supplied for an extension to an existing substation
at the same operating voltage then, unless otherwise agreed by NGC, the interlocking type and
philosophy shall match that existing.
In all cases, interlocking for a substation extension shall be fully interfaced with the existing
interlocking scheme to achieve the functional requirements specified in this document.
3.1.11 Proposed interlocking schemes shall be submitted to NGC for project approval.
3.2.1 Mechanical interlocking shall, unless otherwise agreed by NGC, be by key operated
systems.
3.2.2 Interlock keys shall be of a non-masterable design (i.e no master key can be supplied or
manufactured). Differs shall not be repeated on the same substation site.
Note: Differ is the term for the difference in a key which prevents it being interchangeable with
another.
3.2.3 Interlock keys shall be engraved with an identifying reference which shall be unique to that
substation site. The identifier shall, where appropriate, include the system number of the
switching device where the key is located during normal operation and shall be to the approval
of NGC. Key locations shall be marked with the identifier of the required key.
3.2.4 Where key exchange boxes are provided they shall be located in convenient positions with
regard to normal substation operating sequences.
NGTS 3.1.1
Page 3 Issue 1
October 1993
3.2.5 Where mechanical key interlocking is fitted to disconnector and earthing switch
mechanisms the requirements specified in Clause 3.4 of NGTS 3.2.2 shall apply.
3.3.1 A facility shall be provided to allow the interlock system of each disconnector or earthing
switch to be defeated. This may take the form of a self-resetting switch or push-button to bypass
electrical circuits or by another means agreed by NGC. The override facility shall meet the
requirements of Clause 3.1.5 above.
3.3.2 Disconnector and earthing switch mechanisms which form part of electrical interlocking
schemes shall meet the requirements of Clause 3.5 of NGTS 3.2.2.
In addition to the requirements of Clause 3.3 above the following shall apply:
3.4.1 The system shall operate in accordance with the agreed logic table for the application. Any
combination of inputs for which an output has not been specified shall give no output.
4 PERFORMANCE REQUIREMENTS
4.1 Mechanical and hard-wired electrical interlocking schemes shall operate satisfactorily under
the full range of environmental conditions specified for the associated primary equipment.
4.2 Microprocessor based interlocking systems shall comply with the relevant performance
requirements of NGTS 2.7 and 2.13.
5 TEST REQUIREMENTS
5.1.1 Microprocessor based interlocking systems shall be type tested in accordance with the
relevant requirements of NGTS 2.7 and NGTS 2.13.
5.1.1 Microprocessor based interlocking systems shall be routine tested in accordance with the
relevant requirements of NGTS 2.7 and NGTS 2.13.
5.3.1 Site pre-commissioning tests shall be carried out to demonstrate the correct and
satisfactory operation of the interlocking scheme. The detailed test programme shall be agreed
with NGC.
5.3.2 For microprocessor based interlocking schemes the Contractor shall test all combinations
of inputs to demonstrate the correct operation of the logic or shall carry out a test programme
agreed by NGC.
NGTS 3.1.1
Page 4 Issue 1
October 1993
6.1 Microprocessor based interlocking systems shall be subject to NGC's Type Approval
procedure as defined in NGTS 1.
To gain approval, the specified type tests shall be performed, or test reports submitted in lieu, to
demonstrate that the relevant performance requirements are satisfied. Any test reports offered
shall be of a standard acceptable to NGC.
Suppliers shall also demonstrate that the relevant general requirements of this document, NGTS
2.7 and NGTS 2.13 are met by the equipment offered.
6.2 Mechanical and hard-wired electrical interlocking schemes will not be subject to Type
Approval. However, the requirements for implementation of these schemes will be assessed
during Type Approval of disconnectors and earthing switches.