Erq 125-250 0a7w1b Service
Erq 125-250 0a7w1b Service
Erq 125-250 0a7w1b Service
Service Manual
ERQ Condensing Unit Three Phase
ERQ 125/200/250 A7W1B
EKEQD/F/MCBV3 (control box)
EKEXV 50/63/80/100/125/140/200/250
www.daikin.eu
ESiEN09-06
Service Manual
ERQ Condensing Unit Three Phase
ERQ 125/200/250 A7W1B
EKEQD/F/MCBV3 (control box)
EKEXV 50/63/80/100/125/140/200/250
www.daikin.eu
ESiEN09-06
1. Introduction .............................................................................................v
1.1 Safety Cautions ........................................................................................v
Part 4 Function............................................................................ 21
1. Function general ...................................................................................22
1.1 Symbol ...................................................................................................22
1.2 Operation Mode......................................................................................23
2. Basic Control.........................................................................................24
2.1 Normal Operation ...................................................................................24
2.2 Compressor PI Control...........................................................................25
2.3 Step Control of Outdoor Unit Fans .........................................................27
2.4 Outdoor Unit Fan Control in Cooling Operation .....................................28
3. Special Control......................................................................................29
3.1 Startup Control .......................................................................................29
3.2 Oil Return Operation ..............................................................................30
3.3 Defrosting Operation ..............................................................................32
3.4 Pump-down Residual Operation ............................................................33
3.5 Standby ..................................................................................................34
3.6 Stopping Operation ................................................................................35
4. Protection Control .................................................................................36
4.1 High Pressure Protection Control...........................................................36
4.2 Low Pressure Protection Control............................................................37
4.3 Discharge Pipe Protection Control .........................................................38
4.4 Inverter Protection Control .....................................................................39
4.5 STD Compressor Overload Protection...................................................40
4.6 Injection Control (only for ERQ 125 A7W1B) .........................................40
5. Other Control.........................................................................................41
5.1 Emergency Operation (only for ERQ 250 A7W1B) ................................41
Table of Contents i
ESiEN09-06
ii Table of Contents
ESiEN09-06
Index ............................................................................................. i
iv Table of Contents
ESiEN09-06 Introduction
1. Introduction
1.1 Safety Cautions
Cautions and Be sure to read the following safety cautions before conducting repair work.
Warnings The caution items are classified into “ Warning” and “ Caution”. The “ Warning”
items are especially important since they can lead to death or serious injury if they are not
followed closely. The “ Caution” items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for a repair.
Working on the equipment that is connected to a power supply can cause an
electrical shook.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas discharges during the repair work, do not touch the
discharging refrigerant gas.
The refrigerant gas can cause frostbite.
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.
v
Introduction ESiEN09-06
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
vi
ESiEN09-06 Introduction
Warning
Be sure to use the specified cable to connect between the AHU and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the AHU and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump-down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the remote control, be sure to disposed of
the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly. For integral units
If the packing and seal are not installed properly, water can enter the room and only
wet the furniture and floor.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.
vii
Introduction ESiEN09-06
Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the AHU after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture
and floor.
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get
Caution an unexpected result or has to restart (part of) a procedure.
Warning
viii
ESiEN09-06
Part 1
General Information
1. Model Names of Outdoor Unit, Control Box and Expansion Valve Kit....2
1.1 Outdoor Units ...........................................................................................2
1.2 Control Box...............................................................................................3
1.3 Expansion Valve Kit .................................................................................4
2. Combination Table ..................................................................................5
General Information 1
Model Names of Outdoor Unit, Control Box and Expansion Valve Kit ESiEN09-06
Model name
Series Model Name Power Supply
Inverter Heat Pump ERQ 125A 200A 250A W1B
2 General Information
ESiEN09-06 Model Names of Outdoor Unit, Control Box and Expansion Valve Kit
Control type X
Control of air temperature (Td, Ts or Tr) by means of external device (DDC controller).
Control type Y
Control of evaporating and condensing temperature (Te, Tc) by Daikin control (no DDC needed).
Control type Z
Control of air temperature (Ts or Tr) by Daikin control (no DDC needed).
Legend:
Td Discharge air control
Ts Suction air control
Tr Room air control
Te Evaporating temperature control
Tc Condensing temperature control
AHU Air handling unit
DDC Digital controller
General Information 3
Model Names of Outdoor Unit, Control Box and Expansion Valve Kit ESiEN09-06
Depending on the heat exchanger, a connectable EKEXV (expansion valve kit) must be
selected to these limitations.
Allowed heat exchanger volume (dm3) Allowed heat exchanger capacity (kW)
EKEXV class Minimum Maximum Minimum Maximum
63 1.66 2.08 6.3 7.8
80 2.09 2.64 7.9 9.9
100 2.65 3.30 10.0 12.3
125 3.31 4.12 12.4 15.4
140 4.13 4.62 15.5 17.6
200 4.63 6.60 17.7 24.6
250 6.61 8.25 24.7 30.8
4 General Information
ESiEN09-06 Combination Table
2. Combination Table
Heat pump
P: Pair: Combination depending on AHU heat exchanger volume and capacity.
Allowed heat exchanger volume (dm3) Allowed heat exchanger capacity (kW)
EKEXV class Minimum Maximum Minimum Maximum
63 1.66 2.08 6.3 7.8
80 2.09 2.64 7.9 9.9
100 2.65 3.3 10 12.3
125 3.31 4.12 12.4 15.4
140 4.13 4.62 15.5 17.6
200 4.63 6.6 17.7 24.6
250 6.61 8.25 24.7 30.8
Note: If conflicting result occurs, capacity selection has priority over volume.
General Information 5
Combination Table ESiEN09-06
6 General Information
ESiEN09-06
Part 2
Specifications
1. Specifications ..........................................................................................8
1.1 Outdoor Units ...........................................................................................8
Specifications 7
Specifications ESiEN09-06
1. Specifications
1.1 Outdoor Units
Heat Pump 50Hz Standard Series ERQ 125/200/250 A7W1B
TECHNICAL SPECIFICATIONS ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B
Nominal Cooling kW 14,0 22,4 28,0
capacity
Heating kW 16,0 25,0 31,5
COP Cooling 3,98 4,29 3,77
Heating 4,00 4,50 4,09
Capacity range HP 5 8 10
Nominal input Cooling kW 3,52 5,22 7,42
Heating kW 4,00 5,56 7,70
PED category 2
Casing Colour Daikin white
Material Painted galvanised steel
Dimensions Unit Height mm 1680
Width mm 635 930
Depth mm 765
Packing Height mm 1855
Width mm 796 1055
Depth mm 860
Weight Unit kg 159 187 240
Packed unit kg 182 217 273
Packing Carton kg 3,8 4,02
information
Wood kg 19,15 20,85
Plastic kg 0,215 0,265
Heat Specifications Length mm 1483 1778
exchanger
Nr of rows 54
Fin pitch 2
Nr of passes 8 18
Face area m² 1,762 2,112
Nr of stages 2
Empty tubeplate
0
hole
Tube type HI-XSS (8)
Fin Type Non-symmetric waffle louvre
Treatment Hydrophylic and anti corrosion resistant
Fan Type Propeller
Quantity 1
Air flow rate Cooling m³/min 95 171 185
(nominal at
230V) Heating m³/min 95 171 185
External static pressure Pa 78 Pa in high static pressure
Discharge direction Vertical
Motor Quantity 1
Model Brushless DC
Speed rpm
Output W 350 750
Speed
(nominal) rpm
Cooling
Speed rpm
(nominal)
Heating
Compressor Quantity 1 2
Motor Quantity 1
Model Inverter
Speed rpm 6300 7980 6300
Motor kW
2,8 3,8 1,2
output
Type Hermetically sealed scroll compressor
Crankcase W
33
heater
Quantity 0 1
Model ON - OFF
Speed rpm 2900
Motor kW
4,5
output
Type Hermetically sealed scroll compressor
Crankcase W 33
heater
8 Specifications
ESiEN09-06 Specifications
Specifications 9
Specifications ESiEN09-06
Notes (1) European/international technical standard setting the limits for voltage changers, voltage fluctuations and flicker in public low-voltage supply systems for
equipment with rated ≤ 75A.
(2) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with
input current > 16A and ≤ 75A per phase.
Notes:
- MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth
leakage circuit breaker).
- MSC means the maximum current during start up of the compressor.
- Maximum allowable voltage range variation between phases is 2%.
- RLA is based on following conditions: indoor temperature: 27°CDB/19°CWB, outdoor
temperature: 35°CDB.
- Select wire size based on the value of MCA or TOCA.
- TOCA means the total value of each OC set.
- Voltage range: units are suitable for use on electrical systems where voltage supplied
to unit terminal is not below or above listed range limits.
- FLA means the full load amps of the fan motor.
- In accordance with EN/IEC 61000-3-11 (1), respectively EN/IEC 61000-3-12 (2), it may
be necessary to consult the distribution network operator to ensure that the equipment
is connected only to a supply with Zsys (4) ≤ Zmax, respectively Ssc (3) ≥ minimum Ssc
value.
10 Specifications
ESiEN09-06
Part 3
Refrigerant Circuit
Refrigerant Circuit 11
Refrigerant Circuit ESiEN09-06
1. Refrigerant Circuit
1.1 ERQ 125 A7W1B
No. in
refrigerant
system Symbol Name Major Function
diagram
Inverter compressor is operated on frequencies between 52Hz and 188Hz by using
the inverter. The number of operating steps is as follows when Inverter compressor is
A M1C Inverter compressor (INV)
operated.
RXYQ5P: 18 steps
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
D M1F Inverter fan
speed by using the inverter.
Electronic expansion valve While in heating operation, PI control is applied to keep the outlet superheated degree
E Y1E (Main: EV1) of air heat exchanger constant.
G Y1S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
J Y2S Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.
Used to cool the compressor by injecting refrigerant when the compressor discharge
K Y4S Solenoid valve (Injection) SVT
temperature is high.
M Y3S 4-way valve Used to switch the operation mode between cooling and heating.
N S1NPH High pressure sensor Used to detect high pressure.
O S1NPL Low pressure sensor Used to detect low pressure.
In order to prevent the increase of high pressure when a malfunction occurs, this
P S1PH HP pressure switch (For INV switch is activated at high pressure of 4.0 MPa or more to stop the compressor
compressor)
operation.
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
T — Pressure regulating valve 1 resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Used to return the refrigerating oil separated through the oil separator to the
W — Capillary tube compressor.
1 R1T Thermistor (Outdoor air: Ta) Used to detect outdoor temperature, correct discharge pipe temperature, and others.
2 R2T Thermistor (Suction pipe: Ts) Used to detect suction pipe temperature.
Thermistor (INV discharge Used to detect discharge pipe temperature, make the temperature protection control of
3 R3T
pipe: Tdi) compressor, and others.
Thermistor (Heat exchanger Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
4 R4T deicer: Tb) operation, and others.
5 R6T Thermistor (Liquid pipe Tl) Used to detect liquid pipe temperature.
Thermistor (Accumulator inlet Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
6 R7T Ts1) superheated degree constant in heating operation, and others.
12 Refrigerant Circuit
ESiEN09-06 Refrigerant Circuit
T
PRESSURE FILTER
REGULATING VALVE
5 (CHECK VALVE TYPE)
4
ELECTRONIC
SOLENOID EXPANSION VALVE
VALVE K E
SV
HIGH PRESSURE
SENPH
SENSOR
CHECK VALVE
N
1
FILTER
FILTER
SEPARATOR
CAPILLARY FILTER
TUBE
OIL
HIGH PRESSURE
SOLENOID SWITCH
SV
HPS
VALVE FILTER P
FILTER J 3
COMPRESSOR
INV
A
CAPILLARY W
G TUBE
SOLENOID
SV
VALVE
LOW PRESSURE SENPL
2 SENSOR
O
3D050782
Refrigerant Circuit 13
Refrigerant Circuit ESiEN09-06
F Y2E Electronic expansion valve PI control is applied to keep the outlet superheated degree of subcooling heat
(Subcool: EV2) exchanger constant.
G Y1S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
J Y2S Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.
M Y3S 4-way valve Used to switch the operation mode between cooling and heating.
N S1NPH High pressure sensor Used to detect high pressure.
O S1NPL Low pressure sensor Used to detect low pressure.
In order to prevent the increase of high pressure when a malfunction occurs, this
P S1PH HP pressure switch (For INV switch is activated at high pressure of 4.0 MPa or more to stop the compressor
compressor)
operation.
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
T — Pressure regulating valve resulting in no damage of functional parts due to the increase of pressure in
(Liquid pipe)
transportation or storage.
Used to subcool liquid refrigerant from the electronic expansion valve (cooling) or
V — Subcooling heat exchanger AHUs (heating).
W — Capillary tube Used to return the refrigerating oil separated through the oil separator to the INV
compressor.
1 R1T Thermistor (Outdoor air: Ta) Used to detect outdoor temperature, correct discharge pipe temperature, and others.
2 R2T Thermistor (Suction pipe: Ts) Used to detect suction pipe temperature.
Thermistor (INV discharge Used to detect discharge pipe temperature, make the temperature protection control of
3 R3T pipe: Tdi) compressor, and others.
4 R4T Thermistor (Heat exchanger Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
deicer: Tb) operation, and others.
Used to detect gas pipe temperature on the evaporation side of subcooling heat
Thermistor (Subcooling heat
5 R5T exchanger gas pipe: Tsh) exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
constant, and others.
Thermistor (Receiver outlet
6 R6T Used to detect receiver outlet liquid pipe temperature.
liquid pipe: Tl)
Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
7 R7T Thermistor (Accumulator inlet) superheated degree constant in heating operation, and others.
14 Refrigerant Circuit
ESiEN09-06 Refrigerant Circuit
CHECK VALVE
SEPARATOR
HIGH PRESSURE
SWITCH
OIL
HPS
CAPILLARY P
3
TUBE
FILTER
W
A
COMPRESSOR CAPILLARY TUBE
INV
FILTER
FILTER
O
SOLENOID
LOW PRESSURE
SV
VALVE SENPL
SENSOR
J
2
3D050783
Refrigerant Circuit 15
Refrigerant Circuit ESiEN09-06
F Y2E Electronic expansion valve PI control is applied to keep the outlet superheated degree of subcooling heat
(Subcool: EV3) exchanger constant.
G Y1S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
J Y2S Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.
M Y3S 4-way valve Used to switch the operation mode between cooling and heating.
N S1NPH High pressure sensor Used to detect high pressure.
O S1NPL Low pressure sensor Used to detect low pressure.
HP pressure switch (For INV
P S1PH compressor) In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the compressor
Q S2PH HP pressure switch (For STD operation.
compressor 1)
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
Pressure regulating valve
U — (Liquid pipe) resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Used to subcool liquid refrigerant from the electronic expansion valve (cooling) or
V — Subcooling heat exchanger
AHUs (heating).
Used to return the refrigerating oil separated through the oil separator to the INV
W — Capillary tube compressor.
X — Capillary tube Used to return the refrigerating oil separated through the oil separator to the STD1
compressor.
1 R1T Thermistor (Outdoor air: Ta) Used to detect outdoor temperature, correct discharge pipe temperature, and others.
2 R2T Thermistor (Suction pipe: Ts) Used to detect suction pipe temperature.
Thermistor (INV discharge
3 R31T pipe: Tdi) Used to detect discharge pipe temperature, make the temperature protection control of
Thermistor (STD1 discharge compressor, and others.
4 R32T
pipe: Tds1)
Thermistor (Heat exchanger Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
5 R4T
deicer: Tb) operation, and others.
Used to detect gas pipe temperature on the evaporation side of subcooling heat
6 R5T Thermistor (Subcooling heat exchanger, keep the superheated degree at the outlet of subcooling heat exchanger
exchanger gas pipe: Tsh)
constant, and others.
7 R6T Thermistor (Liquid pipe: Tl) Used to detect liquid pipe temperature.
8 R7T Thermistor (Accumulator inlet) Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
superheated degree constant in heating operation, and others.
16 Refrigerant Circuit
ESiEN09-06 Refrigerant Circuit
CHECK VALVE
FILTER
V F
PRESSURE REGULATING VALVE
ELECTRONIC U
6 EXPANSION VALVE 5
ACCUMULATOR 8
FILTER
D
M
FOUR WAY VALVE
7 SENPH HIGH PRESSURE SENSOR
N
SOLENOID 1
SV
VALVE
CHECK VALVE CHECK VALVE
G
FILTER FILTER
SEPARATOR
SEPARATOR
HIGH PRESSURE Q
HPS HPS
HIGH PRESSURE
SWITCH SENSOR
OIL
OIL
CAPILLARY P FILTER
TUBE 3 4
FILTER
COMPRESSOR
FILTER
A INV CAPILLARY TUBE CAPILLARY X
COMPRESSOR
B
STD1
FILTER W TUBE
SOLENOID VALVE
SV
3D050784
Refrigerant Circuit 17
Functional Parts Layout ESiEN09-06
Heat exchanger
Solenoid valve
(accumulatorACCUMULATOR
oil return)
(Y2S)
Solenoid valve (injection)
(Y4S)
4-Way valve
(Y3S)
Solenoid valve
Pressure switch (High
(Hot gas bypass)
pressure protection)
(Y1S)
(S1PH)
Pressure sensor
(Low pressure) Thermistor (M1C,
(S1NPL) Discharge pipe)
THERMISTOR
(R3T)
Front View
Fan motor
(M1F)
Thermistor (Accumulator)
Pressure switch (High pressure protection)
(R7T)
Pressure sensor (S1PH)
(High pressure)
(S1NPH)
4 way valve
Thermistor (Air)
(Y3S)
(R1T)
Thermistor (Coil)
(R4T) Solenoid valve (Accumulator oil return)
(Y2S)
Compressor (Inverter)
(M1C)
18 Refrigerant Circuit
ESiEN09-06 Functional Parts Layout
Heat exchanger
Accumulator
Front View
Fan motor
(M1F)
4-Way valve
(Y3S)
Thermistor (Air)
(R1T)
Pressure sensor
(Low pressure) Compressor (Inverter)
(S1NPL) Solenoid valve (M1C)
(Accumulator oil return) Conp. lead wire (Inverter)
(Y2S) (M1C)
Refrigerant Circuit 19
Functional Parts Layout ESiEN09-06
Front View
Fan motor
(M1F)
4-Way valve
(Y3S)
Thermistor (Air)
(R1T)
20 Refrigerant Circuit
ESiEN09-06
Part 4
Function
Function 21
Function general ESiEN09-06
1. Function general
1.1 Symbol
Symbol Electric symbol Description or function
20S1 Y3S Four way valve (Energize during heating)
DSH – Discharge pipe superheated degree
DSHi – Discharge pipe superheat of inverter compressor
DSHs – Discharge pipe superheat of standard compressor
EV – Opening of electronic expansion valve
EV1 Y1E Electronic expansion valve for main heat exchanger
EV2 Y2E Electronic expansion valve for sub-coolig heat exchanger
Value of INV compressor discharge pipe temperature (R31T) compensated with
HTDi – outdoor air temperature
Value of STD compressor discharge pipe temperature (R32T, R33T) compensated
HTDs – with outdoor air temperature
Pc S1NPH Value detected by high pressure sensor
Pe S1NPL Value detected by low pressure sensor
SH – Evaporator outlet superheat
SHS – Target evaporator outlet superheat
SVO Y2S Solenoid valve for oil return
SVP Y1S Solenoid valve for hot gas bypass
SVT Y4S Solenoid valve for injection
Ta R1T (A1P) Outdoor air temperature
Tb R4T Heat exchanger outlet temperature at cooling
Ts2 R2T Suction pipe temperature detected with the suction pipe thermistor (R2T)
Tsh R5T (–) Temperature detected with the subcooling heat exchanger outlet thermistor (R5T)
Tc – High pressure equivalent saturation temperature
TcS – Target temperature of Tc
Te – Low pressure equivalent saturation temperature
TeS – Target temperature of Te
Tfin R1T Inverter fin temperature
Tl R6T Liquid pipe temperature detected with the liquid pipe thermistor (R6T)
Tp – Calculated value of compressor port temperature
Ts1 R7T Suction pipe temperature detected with the accumulator inlet thermistor
22 Function
ESiEN09-06 Function general
Malfunction/
Standby
(Retry)
AHU stop or
Startup control thermostat OFF Pump-down
Operation mode • Cooling startup control residual
changeover AHU thermostat ON operation
(After completion of • Heating startup control
startup control)
Malfunction/Standby
Operation After completion of (Retry) AHU stop or
mode startup control thermostat off (After
changeover completion of oil return
AHU stop or or defrost control)
Normal operation thermostat OFF
• Compressor PI control
• Motorized valve PI control Heating
• Protection control Large capacity
startup
Cooling
in operation
Malfunction/Standby
(Retry)
Oil
return IN Yes
conditions are met. Oil return operation
No
Outdoor unit
rotation
Defrost IN Yes
conditions are met. Defrosting operation
No
Operation mode changeover
(after completion of oil return
or defrost control)
*)
In the event AHU stops or the
thermostat turns OFF while in oil
return operation or defrosting
operation, pump-down residual
operation is performed on
completion of the oil return
operation or defrosting operation.
Function 23
Basic Control ESiEN09-06
2. Basic Control
2.1 Normal Operation
2.1.1 List of Functions in Normal Operation
(Electric Function of Functional Part
Part Name Symbol Symbol) Normal Cooling Normal Heating
PI control, High pressure PI control, High pressure
(M1C, M2C) protection, Low pressure protection, Low pressure
Compressor ⎯ protection, Td protection, protection, Td protection,
INV protection, INV protection,
Outdoor unit fan (M1F) Cooling fan control Step 7 or 8
Four way valve 20S1 (Y1R) OFF ON
Main motorized valve EV1 (Y1E) 480 pls PI control
Subcool heat exchanger EV2 (Y2E) PI control PI control
electronic expansion valve
Energized when the system is set
Hot gas bypass valve SVP (Y1S) OFF to low pressure control mode
Accumulator oil return valve SV0 (Y2S) ON ON
24 Function
ESiEN09-06 Basic Control
[Cooling operation]
Controls compressor capacity to adjust Te to Te : Low pressure equivalent saturation
achieve target value (TeS). temperature (°C)
Te set value (Make this setting while in Setting TeS : Target Te value
mode 2.) (Varies depending on Te setting, operating
frequency, etc.)
Te setting
L M (Normal) H
(factory
setting)
3 6 9
[Heating operation]
Controls compressor capacity to adjust Tc to Tc : High pressure equivalent saturation
achieve target value (TcS). temperature (°C)
Te set value (Make this setting while in Setting TcS : Target Tc value
mode 2.) (Varies depending on Tc setting, operating
frequency, etc.)
Tc setting
L M (Normal) H
(factory
setting)
43 46 49
Function 25
Basic Control ESiEN09-06
Notes:
1. INV : Inverter compressor
STD1 : Standard compressor 1
2. Depending on the operating conditions of compressors, the compressors may run in patterns
other than those aforementioned.
26 Function
ESiEN09-06 Basic Control
* Figures listed above are all those controlled while in standard mode, which vary when the
system is set to high static pressure or capacity precedence mode.
Function 27
Basic Control ESiEN09-06
Pc<2.75MPa Pc>3.24MPa
*For fan revolutions in each step,
Upper limit of outdoor unit refer to information on page 107.
fan revolutions
Step 7
PI control
Lapse of 20 sec.
PI control
-1 step on Hold the +1 step on
outdoor unit fan current step on outdoor unit fan
outdoor unit fan
PI control Lapse of 20 sec.
28 Function
ESiEN09-06 Special Control
3. Special Control
3.1 Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
3.1.1 Startup Control in Cooling Operation
Thermostat ON
Ending conditions A lapse of one minute A lapse of 10 sec. • A lapse of 130 sec.
OR • Pc - Pe>0.39MPa
Function 29
Special Control ESiEN09-06
• 3 min. • 3 min.
Ending conditions 20 sec. or • Ts - Te<5°C or • Pe<0.6MPa
• HTdi>110°C
30 Function
ESiEN09-06 Special Control
• 4 min. • 10 sec.
Ending conditions 170 sec. or or
• Ts - Te<5°C • Pc - Pe>0.4MPa
Function 31
Special Control ESiEN09-06
• 10 min. • 10 sec.
Ending conditions 170 sec. or • Tb>11°C or • Pc - Pe>0.4MPa
32 Function
ESiEN09-06 Special Control
Function 33
Special Control ESiEN09-06
3.5 Standby
3.5.1 Restart Standby
Used to forcedly stop the compressor for a period of 3 minutes, in order to prevent the frequent ON/OFF of the
compressor and equalize the pressure within the refrigerant system.
Actuator Operation
Compressor OFF
Ta>30°C: STEP4
Outdoor unit fan Ta≤ 30°C: OFF
Four way valve Holds
Main motorized valve (EV1) 0 pls
Subcooling motorized (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Accumulator oil return valve (SVO) OFF
Injection (SVT) (ERQ 125 A7W1B model) OFF
Ending conditions 3 min.
34 Function
ESiEN09-06 Special Control
Function 35
Protection Control ESiEN09-06
4. Protection Control
4.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
After 10 sec.
Pc>3.43MPa
INV upper limit frequency:
Pc<3.24MPa
Current step maintained 1-step up from current
Pc>3.55MPa compressor frequency
After 15 sec.
After 10 sec.
STD compressor Pc>3.64MPa
standby
Pc>3.10MPa
Pc<2.9MPa
System load down 1 step
After 10 sec.
Pc>3.10MPa
Pc<3.0MPa
Current step maintained INV upper limit rps:
Pc>3.49MPa 1-step up
After 60 sec.
Pc<2.52MPa
36 Function
ESiEN09-06 Protection Control
Pe<0.34MPa Pe>0.39MPa
Pe<0.07MPa
After 10 sec.
Function 37
Protection Control ESiEN09-06
[INV compressor]
[STD compressor]
After 10 min.
38 Function
ESiEN09-06 Protection Control
Nomal operation
Nomal operation
Tfin>84°C
Tfin<81°C
INV upper limit frequency: 1-step / & INV upper limit rps = max
1 min down from current
compressor rps
Tfin>93°C
Function 39
Protection Control ESiEN09-06
STD compressor ON
SVT = OFF
SVT = ON
40 Function
ESiEN09-06 Other Control
5. Other Control
5.1 Emergency Operation (only for ERQ 250 A7W1B)
If the compressor cannot operate, this control inhibits any applicable compressor or outdoor unit
from operating to perform emergency operation only with the operative compressor or outdoor
unit.
Caution
In order to disable the compressor operation due to a failure or else, be sure to do so
in emergency operation mode.
NEVER attempt to disconnect power supply wires from magnetic contactors or else.
(Doing so will operate compressors in combination that disables oil equalization
between the compressors, thus resulting in malfunctions of other normal
compressors.)
Function 41
Other Control ESiEN09-06
5.1.2 Principle
[Set the system to operation prohibition mode by compressor]
• In order to set an INV compressor to operation
prohibition mode, set No. 42 of Setting mode 2 to LED display (7:ON 7:OFF 9:Blink)
"EMERGENCY OPERATION". H1P----H7P
(Procedure)
(1) Press and hold the MODE button (BS1) for a 7777777
777777
period of 5 seconds or more.
(2) Press the SET button (BS2) 42 times. 777
777
777
7 (Factory set)
(3) Press the RETURN button (BS3) once. 7777779
77777
(4) Press the SET button (BS2) once. 7777797
7777
(5) Press the RETURN button (BS3) twice. 7777777
777777
(6) Press the MODE button (BS1) once. 7777777
77 7777
• In order to set STD1 compressor to operation
prohibition mode, set No. 19 of Setting mode 2 to LED display (7:ON 7:OFF 9:Blink)
"STD1 OPERATION PROHIBITION". (ERQ 250 H1P----H7P
A7W1B)
(Procedure) 7777777
777777
(1) Press and hold the MODE button (BS1) for a
period of 5 seconds or more. 77
7777
7777
(2) Press the SET button (BS2) 19 times. 777777 (Factory set)
7777777
(3) Press the RETURN button (BS3) once. 777797
77777
(4) Press the SET button (BS2) once. 777777
7777777
(5) Press the RETURN button (BS3) twice.
7777777
77 7777
(6) Press the MODE button (BS1) once.
42 Function
ESiEN09-06 Other Control
Function 43
Outline of Control ESiEN09-06
6. Outline of Control
6.1 Thermostat Sensor in Remote Control (only for Z-
control)
Temperature is controlled by both the thermostat sensor in remote control and air suction
thermostat in the AHU. (This is however limited to when the field setting for the thermostat
sensor in remote control is set to “Use.”)
Cooling If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
remote control near the position of the user when the suction temperature is near the preset
temperature.
°C
Preset temperature
(Ts)
°C
And, assuming suction temperature has changed from 30°C to 18°C (F → A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F → D).
Remote control thermostat sensor is used for temperatures from 25°C to 21°C (D → B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B → A).
44 Function
ESiEN09-06 Outline of Control
Heating When heating, the hot air rises to the top of the room, resulting in the temperature being lower
near the floor where the occupants are. When controlling by body thermostat sensor only, the
unit may therefore be turned off by the thermostat before the lower part of the room reaches the
preset temperature. The temperature can be controlled so the lower part of the room where the
occupants are doesn’t become cold by widening the range in which thermostat sensor in remote
control can be used so that suction temperature is higher than the preset temperature.
°C
Preset temperature
(Ts)
°C
(V2769)
Ex: When heating Assuming the preset temperature in the figure above is 24°C, and
the suction temperature has changed from 18°C to 28°C (A → D):
Body thermostat sensor is used for temperatures from 18°C to 25°C (A → C).
Remote control thermostat sensor is used for temperatures from 25°C to 28°C (C → D).
And, assuming suction temperature has changed from 28°C to 18°C (D → A):
Remote control thermostat sensor is used for temperatures from 28°C to 23°C (D → B).
Body thermostat sensor is used for temperatures from 23°C to 18°C (B → A).
Function 45
Outline of Control ESiEN09-06
Conditions for starting freeze prevention: Temperature is -1°C or less for total of 40 min., or
temperature is -5°C or less for total of 10 min.
Conditions for stopping freeze prevention: Temperature is +7°C or more for 10 min.
continuously
10 min.
46 Function
ESiEN09-06 Outline of Control
Objective In cooling (or fan operation) or heating, if outdoor air is low in temperature, stop the fan forcibly.
[Heating]
Turn OFF the fan for a period of 60 minutes at a suction temperature of –5°C or lower.
In order to monitor the outdoor air temperature, however, turn ON the fan for a period of one
minute and turn OFF the fan again at a temperature of –5°C or lower after the said timer
completes the operative period.
Reset the 60-minute timer when the fan stops running.
* The thermostat will not turn ON in one minute due to the temperature while the fan stops.
This control shall be disabled at test run both in cooling and heating. (The test run shall be
conducted first.)
Function 47
Outline of Control ESiEN09-06
48 Function
ESiEN09-06
Part 5
Control Box EKEQ - CBV3
power supply
(depend on AHU)
Attention:
Need software block to prevent
EKEQFCB / EKEQDCB Air Thermistor AHU
VRV AHUs to be connected on
(Pair application only) (only needed for (Third party Air handling unit)
control type Z)
ERX condensing unit.
* 2 types depending on Can be both on air or water control
control type H/E thermistor 1
Communication
2 lines (F1,F2) H/E thermistor 2
Remocon connection
EKEQFCB => BRC1D = service tool
EKEQDCB => BRC1D = required option
control
cool/heat
ON/OFF
remarks:
0-10V DC
selection Control
Fan status
Capacity step
Defrost status
51
Different Systems with their Control Boxes
Different Systems with their Control Boxes ESiEN09-06
DDC
Allowable height:
AHU
≤ 5m
Total system: ≤ 30 m
EXV-kit (outdoor unit can be above
or below the AHU)
outdoor
Piping Communication
A B C D E F
125
ERQ depend on
3 phase 200 length: 5 < A ≤ 50 m length: ≤ 5 m ≤ 100 m ≤ 20 m ≤ 20 m DDC
250
EKEXV-KIT
Field supply
EKEQMCB AHU
EKEXV-KIT
Qty of
EKEXV - kits
VRV indoor 1 is limited by
connection
ratio.
VRV indoor n
Multi application with VRV means the ability to combine 1 outdoor unit + several AHU, as well
as VRV indoors (minimum 1 is required). The required control box for this application is
EKEQM.
Gas pipe
Gas pipe
Liquid pipe Liquid pipe
EXV - kit 1
AHU
(Third party Air handling
unit)
Communication
2 lines (F1,F2)
Remocon connection
(required option) distances:
A,B,C,D,E : see below
53
Different Systems with their Control Boxes
Different Systems with their Control Boxes ESiEN09-06
KIT n
Indoor 1
Indoor n
Allowable height:
AHU1
≤ 5m
Total system: ≤ 40 m
EXV-kit 1
≤ 15 m (outdoor unit can be above
AHU n or below the AHU)
≤ 5m
EXV-kit n
outdoor
Piping Communication
A+B B C D E
follow std.
consider same as 1
VRV indoor unit length: ≤ 5 m VRV wiring ≤ 50 m ≤ 50 m
length policy
Connection ratio: 50-110%
2. X, Y, Z Control
The D, F, M boxes have different types of control, giving the ability to control different
temperatures (Td, Ts, Tr, Te or Tc).
Schematic:
AHU
Te
Ts
Td
Tr
DDC ROOM
Legend:
Td Discharge air control
Ts Suction air control
Tr Room air control
Te Evaporating temperature control
Tc Condensing temperature control
AHU Air handling unit
DDC Digital controller
EKEQD: Z-control
EKEQF: X, Y-control
EKEQM: Z-control
2.1 X-Control
Control of air temperature (Td, Ts or Tr) by means of an external device (DDC controller, 0-10V
control).
output
10V Tmeasured 0~10 V
5V DDC
0V
-∆T Tset +∆ ∆T Tset
∆T = Tset - Tmeasured
Tmeasured = Td, Ts or Tr
In case of X-control, a DDC-controller is needed to operate the unit. This DDC-controller is field
supply but in order to connect it to our ERQ-system, it is required that it emits a 0-10 VDC signal
towards the control box.
Inside the control box, this 0-10 VDC signal is converted into a voltage level.
The output voltage increase gives the voltage at which the level increases.
The output voltage decrease gives the voltage at which the level decreases.
Example:
Room temperature = 20°C, set temperature = 25°C. Heating operation: DDC controller,
calculates the difference and sends a 3 VDC signal (fictive value) to the control box. This is
between 1,8 and 3,8 so in level 2. When the room temperature rises to 23°C, the DDC controller
detects a smaller temperature difference and will send out a higher signal, ex. 5 VDC. The
output voltage has increased so you have to use the highest line, indicating that you are now in
level 3. When the window is opened, the room temperature drops and the difference with the set
temperature is higher. The DDC sends a 1 V signal. According to the “output voltage
decreasing” line, we are now in level 1.
Example, continued:
3 VDC = level 2, thus meaning an increase of the refrigerant target temperature. In heating
mode, this means Tc + 1°C. Logically, the room temperature will rise so at the next signal, we
are in level 3, where Tc is kept even.
Cooling Heating
T < 0 level 1 + level 2 DDC asks less capacity DDC asks more capacity
T = 0 level 3 no change no change
T > 0 level 4 + level 5 DDC asks more capacity DDC asks less capacity
T = room temp. - set temp.
2.2 Y-Control
Control of evaporating and condensing temperature (Te and Tc) by Daikin control (no DDC
needed).
Fixed Te or Tc
Te = user setting: -3 ~ 10°C
Tc = user setting: 43 ~ 49°C
++ Low cost
No BRC needed
-- No air temperature control
With Y-control, there is no external input to change Te/Tc value. Their values can only be
changed by local setup with a Daikin remote control (during installation). We refer to the chapter
“Field Setting” for further information.
2.3 Z-Control
Control of air temperature (Ts or Tr) by Daikin control (no DDC needed).
++ Low cost
-- BRC needed
No possibility for Td control
~50Hz
230V
A1P : Printed circuit board
Wiring Diagram of Control Box
: Live
: Neutral
3. Wiring Diagram of Control Box
: Connector
Outdoor
: Wire clamp
: Protective earth (Screw)
: Seperate component
: Optional accessory
: Field wiring
F-box
: Live
: Neutral Outdoor
: Connector
: Wire clamp
: Protective earth (Screw)
: Seperate component
: Optional accessory
: Field wiring
59
Wiring Diagram of Control Box
Attention Points ESiEN09-06
4. Attention Points
Do not forget to place the capacity setting adapter. Otherwise, you’ll get UA or PJ error.
All capacity setting adapters are delivered with the control box.
Polarity of the C5/C6-contact (F-box, X-control) C5 = ”-”, C6 = ”+”
3 6 5 1 3 6 5 1
2 2
4
7 7
11 10 9 8 13 12 9 8 13
1 EKEQFCBV3 2 EKEQDCBV3
2 4 11 8 9 10 5 7 3 5 1 X24A 6
FAN expansion valve gas liquid defrost remocon outdoor ON/OFF error operation 0-10 V
L N C7 C8 Y1 Y2 Y3 Y4 Y5 Y6 R3 R4 R1 R2 C9 C10 P1 P2 F1 F2 T1 T2 C1 C2 C3 C4 C5 C6
F1 F2
R3T
R2T
L N Y1 Y2 Y3 Y4 Y5 Y6 0 +10
H1 H3 H2 H4 H4 H7 H7 H5 H6
H1 H2 H4 H5 H6
H3 H7
3 EKEQFCBV3 4 EKEQFCBV3
2 4 10 5 3 1 X24A 12
F1 F2
R3T
R2T
R1T
L N Y1 Y2 Y3 Y4 Y5 Y6
H5
H1 H2 H3 H4 H4 H8 H6
H7 H1 H2 H4 H6 H7 H8
H3 H5
5 EKEQDCBV3 6 EKEQDCBV3
EKEQFCBV3 Option kit for combination of Daikin condensing units Installation and
EKEQDCBV3 with field supplied air handling units operation manual
Installation of thermistors .......................................... 71 control". It can be used to control the room temperature or
air discharge temperature.
Refrigerant piping work ............................................. 72 ■ Operation with fixed Te/Tc temperature control
Test operation............................................................ 72 This system operates on a fixed evaporating temperature.
■ EKEQDCB control box
The system will operate as a standard indoor unit to control the
Operation and maintenance ................................... 72 room temperature. This system does not require a specific
external controller.
What to do before operation...................................... 72
■ Do NOT connect the system to DIII-net devices:
Operation and display signals ................................... 74
Troubleshooting......................................................... 74
Maintenance.............................................................. 75
Disposal requirements............................................... 75
READ THESE INSTRUCTIONS CAREFULLY BEFORE This could result in malfunction or breakdown of the total
INSTALLATION AND OPERATION. system.
■ This equipment is not designed for year-round cooling
IMPROPER INSTALLATION OR ATTACHMENT OF
applications with low indoor humidity conditions, such as
EQUIPMENT OR ACCESSORIES COULD RESULT IN
Electronic Data Processing rooms.
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY ■ This appliance is not intended for use by persons, including
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE children, with reduced physical, sensory or mental capabilities,
SPECIFICALLY DESIGNED FOR USE WITH THE or lack of experience and knowledge, unless they have been
EQUIPMENT AND HAVE THEM INSTALLED BY A given supervision or instruction concerning use of the appliance
PROFESSIONAL. by a person responsible for their safety.
Children should be supervised to ensure that they do not play
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
with the appliance.
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
EKEQFCBV3 + EKEQDCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
64 with field supplied air handling units
4PW52446-1
INSTALLATION NAME AND FUNCTION OF PARTS (See figure 1 and
figure 2)
■ For installation of the air handling unit, refer to the air handling
unit installation manual. Parts and components
■ Never operate the air conditioner with the discharge pipe 1 Outdoor unit
thermistor (R3T), suction pipe thermistor (R2T) and pressure 2 Control box (EKEQFCB / EKEQDCB)
sensors (S1NPH, S1NPL) removed. Such operation may burn 3 Air handling unit (field supply)
out the compressor.
4 Controller (field supply)
■ The equipment is not intended for use in a potentially explosive
5 Field piping (field supply)
atmosphere.
6 Expansion valve kit
Wiring connections
ACCESSORIES 7 Outdoor unit power supply
8 Control box wiring
EKEQFCB EKEQDCB (Power supply and communication between control box and
outdoor unit)
Thermistor (R1T) — 1
9 Air handling unit thermistors
Thermistor (R3T/R2T) 10 Communication between controller and control box
2
(2.5 m cable)
11 Power supply and control wiring for air handling unit and controller
Insulation sheet 2 (power supply is separate from the outdoor unit)
12 Air thermistor control for air handling unit
Rubber sheet 2
13 Remote control ( = for service only)
Wire to wire splice 4 6
BEFORE INSTALLATION
Installation and
1
operation manual
EKEQFCBV3 + EKEQDCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 65
4PW52446-1
2 Selecting the expansion valve SELECTING THE INSTALLATION SITE
The corresponding expansion valve needs to be selected for
your air handling unit. Select the expansion valve according to This is a class A product. In a domestic environment this product may
the above limitations. cause radio interference in which case the user may be required to
take adequate measures.
NOTE ■ If conflicting result, capacity selection has Select an installation site where the following conditions are fulfilled
priority over volume. and that meets your customer’s approval.
■ The expansion valve is an electronic type, it is ■ The option boxes (expansion valve and electrical control box)
controlled by the thermistors that are added in can be installed inside and outside).
the circuit. Each expansion valve can control a
range of air handling units sizes. ■ Do not install the option boxes in or on the outdoor unit.
■ Do not put the option boxes in direct sunlight. Direct sunlight will
■ The selected air handling unit must be
increase the temperature inside the option boxes and may
designed for R410A.
reduce its lifetime and influence its operation.
■ Extraneous substances (including mineral oils
■ Choose a flat and strong mounting surface.
or moisture) must be prevented from getting
mixed into the system. ■ Operating temperature of the control box is between –10°C and
■ SST: saturated suction temperature at exit of 40°C.
air handling unit. ■ Keep the space in front of the boxes free for future maintenance.
■ Keep air handling unit, power supply wiring and transmission
3 Selecting the capacity setting adapter (see accessories) wiring at least 1 m away from televisions and radios. This is to
■ The corresponding capacity setting adapter needs to be prevent image interference and noise in those electrical
selected depending on the expansion valve. appliances. (Noise may be generated depending on the
conditions under which the electric wave is generated, even if
■ Connect the correct selected capacity setting adapter to
1 m is kept.)
X24A (A1P). (See figure 4 and figure 6)
■ Make sure the control box is installed horizontally. Screw nuts
Capacity Capacity position must be downwards.
setting adapter setting adapter
label label
EKEXV kit (indication) EKEXV kit (indication)
Precautions
63 J71 140 J160
80 J90 200 J224 Do not install or operate the unit in rooms mentioned below.
100 J112 250 J280 ■ Where mineral oil, like cutting oil is present.
125 J140 ■ Where the air contains high levels of salt such as air near the
ocean.
For the following items, take special care during construction ■ Where sulphurous gas is present such as that in areas of hot
and check after installation is finished spring.
■ In vehicles or vessels.
Tick ✓ ■ Where voltage fluctuates a lot such as that in factories.
when
checked ■ Where high concentration of vapor or spray are present.
■ Are the thermistors fixed firmly? ■ Where machines generating electromagnetic waves are
Thermistor may come loose. present.
■ Is the freeze-up setting done correctly? ■ Where acidic or alkaline vapor is present.
The air handling unit may freeze up.
■ The option boxes must be installed with entrances downward.
■ Is the control box fixed firmly?
The unit may drop, vibrate or make noise.
■ Do electrical connections comply with specifications?
The unit may malfunction or components may burn out.
■ Are wiring and piping correct?
The unit may malfunction or components may burn out.
■ Is the unit safely grounded?
Dangerous at electric leakage.
EKEQFCBV3 + EKEQDCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
66 with field supplied air handling units
4PW52446-1
VALVE KIT INSTALLATION Cautions for brazing
Brazing work
6 6
For details, see manual of the outdoor unit.
1 Refrigerant piping
3 Prepare the inlet/outlet field piping just in front of the connection
2 Part to be brazed
(do not braze yet).
3 Taping
192.5 mm 4 Hands valve
5 Pressure-reducing valve
6 Nitrogen
Electrical work
2 Push out ONLY the second lower wire intake hole (B) from
inside to outside. Do not damage the membrane.
3 Pass valve cable (with wires Y1 ... Y6) from the control box
C through that membrane wire intake hole and connect the cable
wires into the terminal connector (C) following instructions as
described in step 4. Route the cable out of the valve kit box
according to figure below and fix with the tie wrap (D). See
"Electric wiring work" on page 68 for more details.
B A AC
B
A Inlet coming from the outdoor unit
B Outlet to air handling unit
C Pipe fixing clamp
7 After brazing, put the lower pipe insulation back in place and
close it with the upper insulation cover (after pealing off the
liner).
8 Secure the pipe fixing clamp (C) in place again (2x M5).
EKEQFCBV3 + EKEQDCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 67
4PW52446-1
4 Use a small screwdriver and follow indicated instructions for ELECTRIC WIRING WORK
connecting cable wires into the terminal connector according to
the wiring diagram. ■ All field supplied parts and materials and electric works must be
conform to local codes.
■ Use copper wire only.
3 ■ All wiring must be performed by an authorized electrician.
■ A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
■ Refer to the installation manual attached to the outdoor unit for
the size of power supply electric wire connected to the outdoor
unit, the capacity of the circuit breaker and switch, wiring and
1 wiring instructions.
■ Attach the earth leakage circuit breaker and fuse to the power
4
supply line.
2
5 Make sure that field wiring and insulation is not squeezed when 1 For connection to outdoor unit and to controller (field supply):
closing the valve kit box cover. Pull the wires inside through the screw nut and close the nut
6 Close the valve kit box cover (4x M5). firmly in order to ensure a good pull relieve and water protection.
6 Close the lid securely after installation to ensure that the control
box is watertight.
EKEQFCBV3 + EKEQDCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
68 with field supplied air handling units
4PW52446-1
Connecting the wiring: EKEQFCBV3
■ Connect the wires to the terminal board according to the wiring ■ Connect cables according to specifications of the next table.
diagram in figure 3. See figure 4 for wiring intake in the
control box. The wiring intake hole indication H1 refers to the H1 Take special precaution for connection to the controller
cable of the corresponding wiring diagram. (field supply). Do not miswire the output signals nor the
input signal (ON/OFF). This mistake could damage the
entire system.
Wiring diagram
A1P.....................Printed circuit board X2M-C3/C4 ........ Output: operation / compressor ON/OFF
A2P.....................Printed circuit board (for voltage conversion) X2M-C5/C6 ........ Input: 0-10 V DC capacity control
A3P.....................Printed circuit board (power supply) X2M-F1/F2......... Communication outdoor unit
F1U.....................Fuse (250 V, F5A)(A1P) X2M-P1/P2 ........ Communication remote control
F2U.....................Fuse (250 V, T1A)(A3P) X2M-T1/T2......... Input: ON/OFF
F3U.....................Field fuse ........... Field wiring
HAP ....................Light emitting diode (service monitor-green) L......................... Live
K2R.....................Magnetic relay (error status) N ........................ Neutral
K3R.....................Magnetic relay (operation / compressor ON/OFF) , ......... Connector
K4R.....................Magnetic relay (fan) ......................... Wire clamp
K5R.....................Magnetic relay (defrost signal)
..................... Protective earth (screw)
K1R,KAR,KPR....Magnetic relay
............... Separate component
Q1DI ...................Earth leakage breaker
............... Optional accessory
R2T.....................Thermistor (liquid)
BLK.................... Black
R3T.....................Thermistor (gas)
BLU.................... Blue
R5 .......................Resistance (120 )
BRN ................... Brown
R6 .......................Capacity adapter
GRN................... Green
T1R.....................Transformer (220 V/21.8 V)
GRY ................... Gray
X1M,X2M,X3M ...Terminal block
ORG .................. Orange
Y1E.....................Electronic expansion valve
PNK ................... Pink
X1M-C7/C8.........Output: fan ON/OFF
RED ................... Red
X1M-C9/C10.......Output: defrost signal
WHT .................. White
X1M-R1/R2.........Thermistor liquid
YLW ................... Yellow
X1M-R3/R4.........Thermistor gas
X1M-Y1~6 ..........Expansion valve
X2M-C1/C2.........Output: error status
EKEQFCBV3 + EKEQDCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 69
4PW52446-1
Connecting the wiring: EKEQDCBV3
■ Connect the wires to the terminal board according to the wiring
diagram in figure 5. See figure 6 for wiring intake in the control
box. The wiring intake hole indication H1 refers to the H1 cable
of the corresponding wiring diagram.
■ Connect cables according to specifications of the next table.
Wiring diagram
A1P .................... Printed circuit board ............Field wiring
A2P .................... Printed circuit board (option KRP4) L .........................Live
F1U .................... Fuse (250 V, F5A)(A1P) N.........................Neutral
F3U .................... Field fuse , ..........Connector
HAP.................... Light emitting diode (service monitor-green) .........................Wire clamp
K1R .................... Magnetic relay
......................Protective earth (screw)
K4R .................... Magnetic relay (fan)
...............Separate component
Q1DI................... Earth leakage breaker
...............Optional accessory
R1T..................... Thermistor (air)
BLK.....................Black
R2T .................... Thermistor (liquid)
BLU ....................Blue
R3T .................... Thermistor (gas)
BRN....................Brown
R7....................... Capacity adapter
GRN ...................Green
T1R .................... Transformer (220 V/21.8 V)
GRY....................Gray
X1M,X3M ...........Terminal block
ORG ...................Orange
Y1E .................... Electronic expansion valve
PNK ....................Pink
X1M-C1/C2 ........Output: fan ON/OFF
RED....................Red
X1M-F1/F2 .........Communication outdoor unit
WHT ...................White
X1M-P1/P2.........Communication remote control
YLW....................Yellow
X1M-R1/R2 ........Thermistor liquid
X1M-R3/R4 ........Thermistor gas
X1M-R5/R6 ........Thermistor air
X1M-T1/T2 .........Input: ON/OFF
X1M-Y1~6 ..........Expansion valve
EKEQFCBV3 + EKEQDCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
70 with field supplied air handling units
4PW52446-1
INSTALLATION OF THERMISTORS Fixation of the thermistor
1
2 2 Put the supplied piece of rubber around the thermistor
(R2T/R3T) in order to avoid loosening of the thermistor
after some years.
1 Liquid R2T
2 Gas R3T
1 2
4 Insulate the thermistor with the supplied insulation sheet.
45
°
EKEQFCBV3 + EKEQDCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 71
4PW52446-1
Installation of longer thermistor cable (R1T/R2T/R3T)
■ In case of poor distribution in the air handling unit, 1 or
The thermistor is supplied with a standard cable of 2.5 m. This cable more passes of the air handling unit may freeze-up
can be made longer to up to 20 m. (collect ice) ➞ put the thermistor (R2T) on this
position.
Install the longer thermistor cable with the delivered wire to wire
splices ■ Depending on operation conditions (e.g.: outdoor
ambient temperature) it is possible that the settings
1 Cut the wire or bundle the remainder of the thermistor cable. must be changed after commissioning.
Keep at least 1 m of the original thermistor cable.
Do not bundle the cable inside the control box.
2 Strip the wire ±7 mm at both ends and insert these ends into the OPERATION AND MAINTENANCE
wire to wire splice.
If T1/T2 is applicable:
3 Pinch the splice with the correct crimp tool (pliers).
■ Closing the T1/T2 signal starts operation of the air handling unit.
4 After connection, heat up the shrink-insulation of the wire to wire ■ Opening the T1/T2 signal stops operation of the air handling
splice with a shrink-heater to make a water tight connection. unit.
5 Wrap electrical insulation tape around the connection.
6 Put a pull-relief in front of and behind the connection. WHAT TO DO BEFORE OPERATION
■ The connection must be made on an accessible
■ Before initiating operation, contact your dealer to get
location.
the operation manual that corresponds to your
■ To make the connection waterproof, the connection system.
can also be made in a switch box or connector box.
■ Refer to the dedicated manual of the controller (field
■ The thermistor cable should be located at least supply) and air handling unit (field supply).
50 mm away from power supply wire. Not following
this guideline may result in malfunction due to ■ Make sure that the air handling unit fan is ON when
electrical noise. the outdoor unit is in normal operation.
EKEQFCBV3 + EKEQDCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
72 with field supplied air handling units
4PW52446-1
Operation with 0–10 V capacity control Operation with fixed Te/Tc temperature control
The 0–10 V input is only used for this system of operation and is the The evaporating temperature (Te)/condensing temperature (Tc) at
base of the capacity control. which the application has to operate can be set by code numbers as
This system needs a field supplied controller with a temperature listed below.
sensor. The temperature sensor can be used to control any
Mode No. Code No. Description of setting(*)
temperature:
01 Te = 3°C
■ Suction air of the air handling unit
02 Te = 4°C
■ Room air
03 Te = 5°C
■ Discharge air of the air handling unit
04 Te = 6°C (factory setting)
Program the field supplied controller to generate a 0–10 V signal 13(23)–1
within conditions as listed. Also refer to the graphic and further data 05 Te = 7°C
in this paragraph for more details. 06 Te = 8°C
■ When target temperature is reached: 5 V 07 Te = 9°C
■ When lower refrigerant temperature is needed: 5–10 V 08 Te = 10°C
■ When higher refrigerant temperature is needed: 0–5 V Tc = 43°C
01
C 02 Tc = 44°C
03 Tc = 45°C
+ΔTmax
13(23)–2 04 Tc = 46°C (factory setting)
05 Tc = 47°C
ΔT=0 06 Tc = 48°C
07 Tc = 49°C
(*) Depending on the operating temperature condition or on selection of the air
handling unit, operation or safety activation of the outdoor unit may take priority
and actual Te/Tc will be different from the set Te/Tc .
–ΔTmax
0 5 10 V A Operation setting in case of power failure
A Controller voltage output to EKEQFCB Measures must be taken to ensure that after power failure,
Capacity increase area T1/T2 is according to the setting of your preference.
Neglecting this caution will result in improper operation.
Capacity decrease area
Voltage output = linear function with T
Mode No. Code No. Description of setting
T = [actual measured temperature] – [target temperature]
When T=0, the target temperature is reached. T1/T2 must be open at power
01
restore.(*)
Tmax = maximum temperature variation as defined by installation
Recommended value for Tmax=[1°C~5°C]. 12(22)–5 After power failure, the status of
T1/T2 must remain identical to the
02
initial T1/T2 status prior to the power
ǻT (°C) –ǻTmax 0 +ǻTmax failure.
Voltage output from controller (*) After power failure, T1/T2 must be changed to open (no cooling/heating
0V 5V 10 V requested).
(field supply)
EKEQFCBV3 + EKEQDCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 73
4PW52446-1
OPERATION AND DISPLAY SIGNALS Trouble shooting
If one of the following malfunctions occurs, take the measures shown
For EKEQF only below and contact your dealer.
Abnormal operation on
condenser or control system The system must be repaired by a qualified service person.
Error: open
Power failure ■ If a safety device such as a fuse, a breaker, or an earth leakage
C1/C2 error
signal breaker frequently actuates, or ON/OFF switch does not
Normal operation
No error: closed properly work.
(relay activated) T1/T2 is open: no error Turn off the main power switch.
detection anymore
Output C3/C4 Open Compressor not operating ■ If the display , the unit number and the operation lamp
operation flash and the malfunction code appears;
signal Closed Compressor operating
Notify your dealer and report the malfunction code.
C7/C8 fan Open Fan off
If the system does not operate properly, and none of the above
output Closed Fan on
mentioned malfunctions is evident, investigate the system according
C9/C10 defrost Open No defrost operation to the following procedures.
output Closed Defrost operation
If the system does not operate at all
Only necessary for field
C5/C6:
0–10 V setting 13(23)–0 = 01
■ Check if there is a power failure.
capacity step Wait until power is restored. If power failure occurs during
0–10 V capacity control(*)
Input operation, the system automatically restarts immediately after
No cooling/heating
Open the power supply recovers.
T1/T2(†) requested
Closed Cooling/heating requested ■ Check if the fuse has blown or breaker has been tripped.
(*) Refer to paragraph "Operation with 0–10 V capacity control" on page 73.
Change the fuse or set the breaker.
(†) See field setting 12(22)–5.
If the system stops operating after operation is complete
■ Check if the air inlet or outlet of outdoor or air handling unit is
For EKEQD only
blocked by obstacles.
C1/C2 fan Open Fan off Remove the obstacle and make it well-ventilated.
Output
output Closed Fan on ■ Check if the air filter is clogged.
No cooling/heating Ask a qualified service person to clean the air filter.
Open
T1/T2(*) requested
Input ■ The error signal is given and the system stops.
Closed Cooling/heating requested If the error resets after 5-10 minutes, the unit safety device was
(*) See field setting 12(22)–5. activated but the unit restarted after evaluation time.
If the error persists, contact your dealer.
■ The fan of the air handling unit must operate before If the system operates but it does not sufficiently cool/heat
cooling operation is required to the outdoor unit. ■ Check if the air inlet or outlet of the air handling unit or the
■ When the operation signal is activated, the air outdoor unit is blocked with obstacles.
handling unit and fan must operate. Failure to this will Remove the obstacle and make it well-ventilated.
cause a safety to operate or freezing up of the air ■ Check if the air filter is clogged.
handling unit. Ask a qualified service person to clean the air filter.
■ Check if the doors or the windows are open.
TROUBLESHOOTING Shut doors or windows to prevent wind from coming in.
■ Check if direct sunlight enters the room.
To set up the system and make trouble shooting possible, it is Use curtains or blinds.
required to connect the remote control to the option kit.
■ Check if there are too many inhabitants in the room.
Cooling effect decreases if heat gain of the room is too large.
Not a malfunction of the air conditioner ■ Check if the heat source of the room is excessive.
Cooling effect decreases if heat gain of the room is too large.
The system does not operate
The air handling unit is freezing up
■ The system does not restart immediately after the cooling/
heating is requested. ■ The liquid thermistor (R2T) is not put on the coldest position and
If the operation lamp lights, the system is in normal operating part of the air handling unit is freezing up.
condition. Thermistor must be put on the coldest position.
It does not restart immediately because one of its safety devices ■ The thermistor has come loose.
actuates to prevent the system from being overloaded. The The thermistor must be fixed.
system will turn on again automatically after 3 minutes. ■ The air handling unit fan is not operating continuously.
■ The system does not restart immediately after the power supply When the outdoor unit stops operating, the air handling unit fan
is turned on. must continue operation to melt the ice that was accumulated
Wait 1 minute until the micro computer is prepared for operation. during outdoor unit operation.
Ensure that the air handling unit fan keeps operating.
In these cases, contact your dealer.
EKEQFCBV3 + EKEQDCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
74 with field supplied air handling units
4PW52446-1
MAINTENANCE NOTES
DISPOSAL REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
EKEQFCBV3 + EKEQDCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 75
4PW52446-1
System B: EKEQM-box: Installation and Operation Manual ESiEN09-06
2 11
9 8 10 7 6
F1 F2
R3T
R2T
R1T
L N Y1 Y2 Y3 Y4 Y5 Y6
H5
H1 H2 H3 H4 H4 H8 H6
H7
2 4 10 5 3 1 X24A 6
H1 H2 H4 H6 H7 H8
H3 H5 H5
3
Option kit for combination of Daikin condensing units Installation and
EKEQMCBV3
with field supplied air handling units operation manual
EKEQMCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 79
4PW52447-1
INSTALLATION BEFORE INSTALLATION
■ For installation of the air handling unit, refer to the air handling ■ Refer to the installation manual of the outdoor unit for details on
refrigerant piping, additional refrigerant charging, and inter-unit
unit installation manual.
wiring.
■ Never operate the air conditioner with the discharge pipe
thermistor (R3T), suction pipe thermistor (R2T) and pressure
sensors (S1NPH, S1NPL) removed. Such operation may burn Since design pressure is 4 MPa or 40 bar, pipes of larger
out the compressor. wall thickness may be required. Refer to paragraph
"Selection of piping material" on page 82.
■ The equipment is not intended for use in a potentially explosive
atmosphere.
■ Precautions for R410A
■ The refrigerant requires strict cautions for keeping the
ACCESSORIES system clean, dry and tight.
- Clean and dry
Foreign materials (including mineral oils or moisture)
Quantity
should be prevented from getting mixed into the system.
Thermistor (R1T) 1 - Tight
Read "Piping installation" on page 81 carefully and follow
Thermistor (R3T/R2T)
(2.5 m cable)
2 these procedures correctly.
■ Since R410A is a mixed refrigerant, the required additional
Insulation sheet 2
refrigerant must be charged in its liquid state. (If the
Rubber sheet 2 refrigerant is in state of gas, its composition changes and the
system will not work properly).
Wire to wire splice 6
■ The connected air handling units must have heat exchangers
designed exclusively for R410A.
Installation and operation
1
manual
Capacity setting adapter 8 Lifetime of the outdoor unit, operation range or operation reliability
may be influenced if you neglect these limitations.
Stopper (closing cup) 1
This control box can only be used in heat pump applications.
Obligatory accessory NOTE ■ For maximum number of indoor units, see the
outdoor unit specifications.
EKEQMCB ■ If the total capacity of the connected indoor units
exceeds the capacity of the outdoor unit, cooling
Expansion valve kit EKEXV
and heating performance may drop when running
Refer to chapter "Valve kit installation" for installation instructions. the indoor units.
Refer to the section on performance charac-
teristics in the Engineering Data Book for details.
Optional accessories ■ The capacity class of the air handling unit is
determined by the selection of the expansion
EKEQMCB valve kit according to Table 1.
EKEQMCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
80 with field supplied air handling units
4PW52447-1
1 The air handling unit can be connected as a standard indoor unit SELECTING THE INSTALLATION SITE
to the outdoor unit. The limitations of connection are determined
by the outdoor unit. This is a class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to
Additional limits exist when connecting the EKEQMCB take adequate measures.
control box. These can be found in the technical data
Select an installation site where the following conditions are fulfilled
book of the EKEQMCB and in this manual.
and that meets your customer’s approval.
2 Selecting the expansion valve ■ The option boxes (expansion valve and electrical control box)
can be installed inside and outside.
The corresponding expansion valve needs to be selected for
your air handling unit. Select the expansion valve according to ■ Do not install the option boxes in or on the outdoor unit.
the above limitations. ■ Do not put the option boxes in direct sunlight. Direct sunlight will
increase the temperature inside the option boxes and may
NOTE ■ If conflicting result, capacity selection has reduce its lifetime and influence its operation.
priority over volume.
■ Choose a flat and strong mounting surface.
■ The expansion valve is an electronic type, it is
■ Operating temperature of the control box is between –10°C and
controlled by the thermistors that are added in
40°C.
the circuit. Each expansion valve can control a
range of air handling units sizes. ■ Keep the space in front of the boxes free for future maintenance.
■ The selected air handling unit must be ■ Keep air handling unit, power supply wiring and transmission
designed for R410A. wiring at least 1 m away from televisions and radios. This is to
prevent image interference and noise in those electrical
■ Extraneous substances (including mineral oils
appliances. (Noise may be generated depending on the
or moisture) must be prevented from getting
conditions under which the electric wave is generated, even if
mixed into the system.
1 m is kept.)
■ SST: saturated suction temperature at exit of
■ Make sure the control box is installed horizontally. Screw nuts
air handling unit.
position must be downwards.
3 Selecting the capacity setting adapter (see accessories)
■ The corresponding capacity setting adapter needs to be Precautions
selected depending on the expansion valve.
Do not install or operate the unit in rooms mentioned below.
■ Connect the correct selected capacity setting adapter to
X24A (A1P). (See figure 3) ■ Where mineral oil, like cutting oil is present.
■ Where the air contains high levels of salt such as air near the
Capacity Capacity
setting adapter setting adapter
ocean.
label label ■ Where sulphurous gas is present such as that in areas of hot
EKEXV kit (indication) EKEXV kit (indication)
spring.
50 J56 125 J140
■ In vehicles or vessels.
63 J71 140 J160
■ Where voltage fluctuates a lot such as that in factories.
80 J90 200 J224
■ Where high concentration of vapor or spray are present.
100 J112 250 J280
■ Where machines generating electromagnetic waves are
present.
For the following items, take special care during
■ Where acidic or alkaline vapor is present.
construction and check after installation is finished
■ The option boxes must be installed with entrances downward.
Tick ✓
when
checked PIPING INSTALLATION
■ Are the thermistors fixed firmly?
Thermistor may come loose. Piping limits
■ Is the freeze-up setting done correctly?
The air handling unit may freeze up. 1
■ Is the control box fixed firmly? 2
A
The unit may drop, vibrate or make noise. 3 L
■ Do electrical connections comply with specifications?
4
The unit may malfunction or components may burn out.
5
■ Are wiring and piping correct?
The unit may malfunction or components may burn out.
1 Air handling unit
■ Is the unit safely grounded?
Dangerous at electric leakage. 2 Connection pipe from expansion valve kit to air handling unit
3 Valve kit
4 Liquid pipe
5 Gas pipe
Max (m)
A –5/+5(*)
L 5
(*) Below or above the valve kit.
EKEQMCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 81
4PW52447-1
Piping connections Cautions for brazing
Make sure to install gas and liquid pipe diameters in function of the ■ Be sure to carry out a nitrogen blow when brazing.
air handling unit capacity class. Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
Connection pipe film on the inside of the pipes, adversely affecting valves and
Air handling unit capacity class Gas pipe Liquid pipe
compressors in the refrigerating system and preventing normal
50 Ø12.7 Ø6.4 operation.
63 ■ When brazing while inserting nitrogen into the piping, nitrogen
80 must be set to 0.02 MPa with a pressure-reducing valve (=just
100 Ø15.9 enough so that it can be felt on the skin).
125 Ø9.52 1 2 3 4 5
140
200 Ø19.1
250 Ø22.2
6 6
Selection of piping material
1 Refrigerant piping
1. Foreign materials inside pipes (including oils for fabrication) 2 Part to be brazed
must be 30 mg/10 m or less.
3 Taping
2. Use the following material specification for refrigerant piping:
4 Hands valve
■ Construction material: phosphoric acid deoxidized seamless 5 Pressure-reducing valve
copper for refrigerant.
6 Nitrogen
■ Temper grade: use piping with temper grade in function of the
pipe diameter as listed in the table below. ■ For details, see manual of the outdoor unit.
Pipe Ø Temper grade of piping material
≤ 15.9 O
≥ 19.1 1/2H
O = Annealed
1/2H = Half hard
3. In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the
following into account:
■ select the pipe size nearest to the required size.
■ use the suitable adapters for the change-over from inch to
mm pipes (field supply).
EKEQMCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
82 with field supplied air handling units
4PW52447-1
VALVE KIT INSTALLATION Electrical work
1 Remove the valve kit box cover by unscrewing 4x M5. 2 Push out ONLY the second lower wire intake hole (B) from
inside to outside. Do not damage the membrane.
2 Drill 4 holes on correct position (measurements as indicated in
3 Pass valve cable (with wires Y1 ... Y6) from the control box
figure below) and fix the valve kit box securely with 4 screws
through the provided holes Ø9 mm. through that membrane wire intake hole and connect the cable
wires into the terminal connector (C) following instructions as
described in step 4. Route the cable out of the valve kit box
NOTE ■ Make sure that the expansion valve is installed
according to figure below and fix with the tie wrap (D). See
vertically. "Electric wiring work" on page 84 for more details.
■ Make sure there is enough free space for future
maintenance. AC
Brazing work
B
For details, see manual of the outdoor unit.
192.5 mm
D
340 mm
3
B A
6 Braze the field piping. 5 Make sure that field wiring and insulation is not squeezed when
closing the valve kit box cover.
■ Make sure to cool the filters and valve body with
a wet cloth and make sure the body temperature 6 Close the valve kit box cover (4x M5).
does not exceed 120°C during brazing.
■ Make sure that the other parts such as electrical
box, tie wraps and wires are protected from direct
brazing flames during brazing.
7 After brazing, put the lower pipe insulation back in place and
close it with the upper insulation cover (after pealing off the
liner).
8 Secure the pipe fixing clamp (C) in place again (2x M5).
EKEQMCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 83
4PW52447-1
INSTALLATION OF THE ELECTRICAL CONTROL Precautions
BOX (See figure 3) ■ Thermistor cable and remote control wire should be located at
least 50 mm away from power supply wires and from wires to
1 Control box
the controller. Not following this guideline may result in
2 Hanger brackets malfunction due to electrical noise.
3 Main PCB ■ Use only specified wires, and tightly connect wires to the
4 Transformer terminals. Keep wiring in neat order so that it does not obstruct
5 Terminal other equipment. Incomplete connections could result in
overheating, and in worse case electric shock or fire.
6 Optional PCB (KRP4)
Mechanical installation
1 Fix the control box with its hanger brackets to the mounting
surface.
Use 4 screws (for holes of Ø6 mm).
6 Close the lid securely after installation to ensure that the control
box is watertight.
EKEQMCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
84 with field supplied air handling units
4PW52447-1
Connecting the wiring: EKEQMCBV3
■ Connect the wires to the terminal board according to the wiring
diagram in figure 2. See figure 3 for wiring intake in the control
box. The wiring intake hole indication H1 refers to the H1 cable
of the corresponding wiring diagram. There are 2 wiring intake
holes to allow for branching of the communication wire.
■ Connect cables according to specifications of the next table.
Wiring diagram
A1P.....................Printed circuit board ........... Field wiring
A2P.....................Printed circuit board (option KRP4) L......................... Live
F1U.....................Fuse (250 V, F5A)(A1P) N ........................ Neutral
F3U.....................Field fuse , .......... Connector
HAP ....................Light emitting diode (service monitor-green) ......................... Wire clamp
K1R.....................Magnetic relay
...................... Protective earth (screw)
K4R.....................Magnetic relay (fan)
............... Separate component
Q1DI ...................Earth leakage breaker
............... Optional accessory
R1T .....................Thermistor (air)
BLK.................... Black
R2T.....................Thermistor (liquid)
BLU.................... Blue
R3T.....................Thermistor (gas)
BRN ................... Brown
R7 .......................Capacity adapter
GRN................... Green
T1R.....................Transformer (220 V/21.8 V)
GRY ................... Gray
X1M,X3M............Terminal block
ORG .................. Orange
Y1E.....................Electronic expansion valve
PNK ................... Pink
X1M-C1/C2.........Output: fan ON/OFF
RED ................... Red
X1M-F1/F2..........Communication outdoor unit
WHT .................. White
X1M-P1/P2 .........Communication remote control
YLW ................... Yellow
X1M-R1/R2.........Thermistor liquid
X1M-R3/R4.........Thermistor gas
X1M-R5/R6.........Thermistor air
X1M-T1/T2..........Input: ON/OFF
X1M-Y1~6 ..........Expansion valve
EKEQMCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 85
4PW52447-1
INSTALLATION OF THERMISTORS Fixation of the thermistor
1
2 2 Put the supplied piece of rubber around the thermistor
(R2T/R3T) in order to avoid loosening of the thermistor after
some years.
1 Liquid R2T
2 Gas R3T
1 2
4 Insulate the thermistor with the supplied insulation sheet.
45
°
Air thermistor
The air thermistor (R1T) can be installed either in the room that needs
temperature control or in the suction area of the air handling unit.
EKEQMCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
86 with field supplied air handling units
4PW52447-1
Installation of longer thermistor cable (R1T/R2T/R3T)
■ In case of poor distribution in the air handling unit, 1 or
The thermistor is supplied with a standard cable of 2.5 m. This cable more passes of the air handling unit may freeze-up
can be made longer to up to 20 m. (collect ice) ➞ put the thermistor (R2T) on this
position.
Install the longer thermistor cable with the delivered wire to wire
splices ■ Depending on operation conditions (e.g.: outdoor
ambient temperature) it is possible that the settings
1 Cut the wire or bundle the remainder of the thermistor cable. must be changed after commissioning.
Keep at least 1 m of the original thermistor cable.
Do not bundle the cable inside the control box.
2 Strip the wire ±7 mm at both ends and insert these ends into the OPERATION AND MAINTENANCE
wire to wire splice.
If T1/T2 is applicable:
3 Pinch the splice with the correct crimp tool (pliers).
■ Closing the T1/T2 signal starts operation of the air handling unit.
4 After connection, heat up the shrink-insulation of the wire to wire ■ Opening the T1/T2 signal stops operation of the air handling
splice with a shrink-heater to make a water tight connection. unit.
5 Wrap electrical insulation tape around the connection.
6 Put a pull-relief in front of and behind the connection. WHAT TO DO BEFORE OPERATION
■ The connection must be made on an accessible
■ Before initiating operation, contact your dealer to get
location.
the operation manual that corresponds to your
■ To make the connection waterproof, the connection system.
can also be made in a switch box or connector box.
■ Refer to the dedicated manual of the controller (field
■ The thermistor cable should be located at least supply) and air handling unit (field supply).
50 mm away from power supply wire. Not following ■ Make sure that the air handling unit fan is ON when
this guideline may result in malfunction due to
the outdoor unit is in normal operation.
electrical noise.
■ For refrigerant piping of outdoor unit, refer to the installation Measures must be taken to ensure that after power failure,
manual supplied with the outdoor unit. T1/T2 is according to the setting of your preference.
Neglecting this caution will result in improper operation.
■ Follow the outdoor unit specifications for additional charging,
piping diameter and installation.
Mode No. Code No. Description of setting
■ The maximum allowed piping length depends on the connected
outdoor model. T1/T2 must be open at power
01
restore.(*)
EKEQMCBV3
Option kit for combination of Daikin condensing units Installation and operation manual
with field supplied air handling units 87
4PW52447-1
TROUBLESHOOTING The air handling unit is freezing up
■ The liquid thermistor (R2T) is not put on the coldest position and
To set up the system and make trouble shooting possible, it is part of the air handling unit is freezing up.
required to connect the remote control to the option kit. Thermistor must be put on the coldest position.
■ The thermistor has come loose.
Not a malfunction of the air conditioner The thermistor must be fixed.
■ The air handling unit fan is not operating continuously.
The system does not operate When the outdoor unit stops operating, the air handling unit fan
■ The system does not restart immediately after the must continue operation to melt the ice that was accumulated
cooling/heating is requested. during outdoor unit operation.
If the operation lamp lights, the system is in normal operating Ensure that the air handling unit fan keeps operating.
condition.
In these cases, contact your dealer.
It does not restart immediately because one of its safety devices
actuates to prevent the system from being overloaded. The
system will turn on again automatically after 3 minutes.
MAINTENANCE
■ The system does not restart immediately after the power supply
is turned on.
Wait 1 minute until the micro computer is prepared for operation. ■ Only a qualified service person is allowed to perform
maintenance.
■ Before obtaining access to terminal devices, all power
Trouble shooting supply circuits must be interrupted.
If one of the following malfunctions occurs, take the measures shown ■ Water or detergent may deteriorate the insulation of
below and contact your dealer. electronic components and result in burn-out of these
components.
The system must be repaired by a qualified service person.
■ If a safety device such as a fuse, a breaker, or an earth leakage
breaker frequently actuates, or ON/OFF switch does not DISPOSAL REQUIREMENTS
properly work.
Dismantling of the unit, treatment of the refrigerant, of oil and of other
Turn off the main power switch.
parts must be done in accordance with relevant local and national
■ If the display , the unit number and the operation lamp legislation.
flash and the malfunction code appears;
Notify your dealer and report the malfunction code.
If the system does not operate properly, and none of the above
mentioned malfunctions is evident, investigate the system according
to the following procedures.
If the system does not operate at all
■ Check if there is a power failure.
Wait until power is restored. If power failure occurs during
operation, the system automatically restarts immediately after
the power supply recovers.
■ Check if the fuse has blown or breaker has been tripped.
Change the fuse or set the breaker.
If the system stops operating after operation is complete
■ Check if the air inlet or outlet of outdoor or air handling unit is
blocked by obstacles.
Remove the obstacle and make it well-ventilated.
■ Check if the air filter is clogged.
Ask a qualified service person to clean the air filter.
■ The error signal is given and the system stops.
If the error resets after 5-10 minutes, the unit safety device was
activated but the unit restarted after evaluation time.
If the error persists, contact your dealer.
If the system operates but it does not sufficiently cool/heat
■ Check if the air inlet or outlet of the air handling unit or the
outdoor unit is blocked with obstacles.
Remove the obstacle and make it well-ventilated.
■ Check if the air filter is clogged.
Ask a qualified service person to clean the air filter.
■ Check if the doors or the windows are open.
Shut doors or windows to prevent wind from coming in.
■ Check if direct sunlight enters the room.
Use curtains or blinds.
■ Check if there are too many inhabitants in the room.
Cooling effect decreases if heat gain of the room is too large.
■ Check if the heat source of the room is excessive.
Cooling effect decreases if heat gain of the room is too large.
EKEQMCBV3
Installation and operation manual Option kit for combination of Daikin condensing units
88 with field supplied air handling units
4PW52447-1
ESiEN09-06
Part 6
Test Operation
Test Operation 89
Test Operation ESiEN09-06
1. Test Operation
1.1 Installation Process
Below Figure shows the installation process. Install in the order of the steps shown.
1. Selection of Location
7. Pipe Insulation
90 Test Operation
ESiEN09-06 Test Operation
Have the airtight test and the vacuum drying been conducted
Check airtight test and vacuum according to the procedure in the Installation Manual?
drying.
Test Operation 91
Test Operation ESiEN09-06
Check the LED display of the Check to be sure the transmission is normal.
outdoor unit PC board. The transmission is normal if the LEDs display conditions as shown in
table below.
LED display ON OFF Blinking
COOL / HEAT select
Micro-
LED display computer MODE TEST Low
Demand Multi
(Default status before operation noise
monitor IND MASTER SLAVE
delivery)
HAP H1P H2P H3P H4P H5P H6P H7P H8P
One outdoor unit installed
92 Test Operation
ESiEN09-06 Test Operation
1.2.3.1 Preparations
<Needed tools>
• To prevent entry of any impurities and insure sufficient
pressure resistance, always use the special tools
Gauge manifold dedicated for R-410A.
Charge hose valve • Use charge hose that have pushing stick for connecting
to service port of shutoff valves or refrigerant charge
port.
• The vacuum pump for vacuum drying should be able to
lower the pressure to –100.7kPa
Vacuum pump (5 Torr –755mm Hg).
• Take care the pump oil never flow backward into the
refrigerant pipe during the pump stops.
<The system for air tight test and vacuum drying>
• Referring to figure 28, connect an nitrogen tank, refrigerant tank, and a vacuum pump to the
outdoor unit.
• The shutoff valve and valve A~C in figure 28 should be open or closed as shown in the table
below.
Liquid side
shutoff valve
Refrigerant charge port
Gas side
shutoff valve Outdoor
Charge Shutoff valve unit
hose service port
Measuring device
Gouge manifold
Valve B
Nitrogen
Valve C
To indoor unit
R-410A cylinder Vacuum pump Valve A
(with siphon) Interunit pipings
Gas flow
fig. 28
Note:
The airtightness test and vacuum drying should be done using the liquid side and gas side
shutoff valve service ports.
See the [R-410A] Label attached to the front plate of the outdoor unit for details on the
location of the service port (see figure at right).
See [Shutoff valve operation procedure] for details on handling the shutoff valve.
The refrigerant charge port is connected to unit pipe.
When shipped, the unit contains refrigerant, so use caution when attaching the charge hose.
Test Operation 93
Test Operation ESiEN09-06
Note:
If moisture might enter the piping, follow belows.
(I.e., if doing work during the rainy season, if the actual work takes long enough that
condensation may form on the inside of the pipes, if rain might enter the pipes during
work, etc.)
1. After performing the vacuum drying for two hours, pressurize to 0.05 MPa (i.e., vacuum
breakdown) with nitrogen gas, then depressurize down to –100.7 kPa for an hour using the
vacuum pump (vacuum drying).
2. If the pressure does not reach –100.7 kPa even after depressurizing for at least two hours,
repeat the vacuum breakdown - vacuum drying process.
After vacuum drying, maintain the vacuum for an hour and make sure the pressure does not rise
by monitoring with a vacuum gauge.
Caution Always use the proper refrigerant (R-410A). If charged with the refrigerant containing an
improper material, it may cause an explosion or accident.
R-410A is a mixed refrigerant, so charging it as a gas will cause the refrigerant composition
to change, which may prevent normal operation.
94 Test Operation
ESiEN09-06 Test Operation
Note:
Do not open the shutoff valve until “1.2.1 Check work prior to turn power supply on” in page
91 are completed. If the shutoff valve is left open without turning on the power, it may cause
refrigerant to buildup in the compressor, leading insulation degradation.
Be sure to use the correct tools.
The shutoff valve is not a back-seat type. If forced it to open, it might break the valve body.
When using a service port, use the charge hose.
After tightening the cap, make sure no refrigerant gas is leaking.
[Tightening torque]
The sizes of the shutoff valves on each model and the tightening torque for each size are listed
in the table below.
<Size of Shutoff Valve>
5HP type 8HP type 10HP type 12HP type 14HP type 16HP type 18HP type
φ 12.7
φ 9.5
Liquid side The 12HP type corresponds The 18HP type corresponds to the
to the 12.7-diameter 15.9-diameter onsite
shutoff valve onsite piping using the included piping using the
piping. accessory pipe.
φ 25.4
The 10HP type corresponds to the
Gas side φ 15.9 φ 19.1 22.2-diameter onsite piping using the accessory pipe.
shutoff valve The 12 ~ 18HP type corresponds to the 28.6-diameter onsite
piping using the accessory pipe.
<Tightening torque>
Tightening torque N·m (Turn clockwise to close)
Shutoff valve size Cap
Shaft (valve body) Service port
(valve lid)
φ 9.5 5.4 - 6.6 13.5 - 16.5
Hexagonal wrench
4 mm
φ 12.7 8.1 - 9.9 18.0 - 22.0
Hexagonal wrench 11.5 - 13.9
φ 15.9 13.5 - 16.5 6 mm
φ 19.1 22.5 - 27.5
Hexagonal wrench
27.0 - 33.0
φ 25.4 8 mm
Service port
Cap
fig 34
[To open]
1. Remove the cap and turn the shaft counterclockwise with the hexagon wrench (JISB4648).
2. Turn it until the shaft stops.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
[To close]
1. Remove the cap and turn the shaft clockwise with the hexagon wrench (JISB4648).
2. Securely tighten the valve until the shaft contacts the main body seal.
3. Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)
Test Operation 95
Test Operation ESiEN09-06
Caution Make sure to use the protect tool (protective groves and goggles) when charging the
refrigerant.
Due to a danger of liquid hammer, the refrigerant must not be charged over the allowable
maximum amount when charging the refrigerant.
Do not perform the refrigerant charging operation under working for the AHU.
When opening the front panel, make sure to take caution to the fan rotation during the
working.
After the outdoor unit stops operating, the fan may keep rotation for a while.
Note:
If operation is performed within 12 minutes after the AHU and outdoor units are turned on,
H2P will be lit on and the compressor will not operate.
In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the
compressor to start up after the unit starting operating. This is not a malfunction.
<About refrigerant charging>
The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the unit’s internal piping is already charged with
refrigerant, so be careful when connecting the charge hose.
After adding the refrigerant, make sure to close the lid of the refrigerant charging port.
The tightening torque for the lid is 11.5 to 13.9 Nm.
See [Shutoff valve operation procedure] in 1.2.4.1 for details on how to handle shutoff
valves.
When done or when pausing the refrigerant charging operation, close the valve of the
refrigerant tank immediately. If the tank is left with the valve open, the amount of refrigerant
which is properly charged may be off the point. More refrigerant may be charged by any
remaining pressure after the machine is stopped.
<About check operation>
Make sure to perform the check operation after installation. Otherwise, the malfunction code
“U3” will be displayed and normal operation cannot be performed.
And the failure of “Check of miswiring” may also cause abnormal operation. Performance
may drop due to the failure of “Judgment of piping length”.
The check operation cannot be performed in recovery or other service modes.
1. Make sure the following works are complete in accordance with the installation manual.
Piping work
Wiring work
Air tight test
Vacuum drying
Installation work for AHU
2. Calculate the “additional charging amount” using the installation manual.
96 Test Operation
ESiEN09-06 Test Operation
3. Open the valve C (See the figure 31. The valve A, B and the liquid and gas side shutout
valve must be left closed), and charge the refrigerant of the “additional charging amount”
from the liquid side shutout valve service port.
If the “additional charging amount” was charged fully, close the valve C and go to step 5.
If the “additional charging amount” was not charged fully, go to step 4.
fig 31
Note:
The refrigerant will be charged about 22kg in one hour at outdoor temp. 30°C DB (6kg at 0°C
DB).
Pipe intake
fig 32
Test Operation 97
Test Operation ESiEN09-06
STEP2 If necessary, set the field setting by using the dip switch on the outdoor unit PC-
board(A1P).
STEP3 • Close the EL. COMPO. BOX lid and all front panel except on the side of the EL.
COMPO. BOX (*1) and turn the power to the outdoor unit and all connected AHU. (*2)
• After H2P stop blinking (about 12 minutes after turning on the power), check LED
displays as shown in the table [Display of normal system] and the system is normal
state.
If H2P is blinking, check the malfunction code in the remote control, and correct the
malfunction in accordance with [Remote control display malfunction code] in page
100.
(*1) Lead the refrigerant charge hose etc from the pipe intake. All front panels must be
closed at the procedure (9).
(*2) • If you perform the refrigerant charging operation within the refrigerant system that
have
the power off unit, the operation cannot finish properly.
For confirming the number of the outdoor and AHUs with the power on, see
[How to check how many units are connected] in chapter 1.2.4.1. In case of a multi
system,
turn on the power to all outdoor units in the refrigerant system.
• To energize the crankcase heater, make sure to turn on for 6 hours before starting
operation.
STEP4 Start the additional refrigerant charge operation.
(About the system settings for additional refrigerant charge operation, refer to the
[Service Precaution] label attached on the EL. COMPO. BOX lid in the outdoor unit.)
Open valve A immediately after starting the compressor.
STEP5 Close the valve A if the “additional charging amount” of refrigerant was charged, and
push the RETURN button (BS3) once.
STEP6 Record the charging amount on the accessory “REQUEST FOR THE INDICATION”
label and attach it to the back side of the front panel.
5. After completing the additional refrigerant charging perform the check operation following
below
98 Test Operation
ESiEN09-06 Test Operation
NOTE:
• For check operation, the following work will be performed.
Check of shutoff valve opening
Check of miswiring
Judgment of piping length
Check of refrigerant overcharge
• It takes about 40 minutes to complete the check operation.
STEP4 Make the onsite settings as needed using the push button (BS1-BS5) on the outdoor
unit PC-board (A1P) with the power on.
STEP5 Perform the check operation following the Check Operation Method of the [Service
Precautions] label on the EL. COMPO. BOX lid. The system operation for about 40
minutes and automatically stops the check operation.
If the malfunction code is not displayed in the remote control after the system stop,
check operation is completed. Normal operation will be possible after 5 minutes. If the
malfunction code is displayed in the remote control, correct the malfunction following
[Remote control displays malfunction code] and perform the check operation again.
Test Operation 99
Test Operation ESiEN09-06
Use an insulated rod to operate the push buttons via the inspection door of EL. COMPO. BOX
lid.
There is a risk of electric shock if you touch any live parts, since this operation must be
performed with the power on.
NOTE:
• Heating is not possible if the outdoor temperature is 24°C or higher. Refer to the Operation
manual.
• If a knocking sound can be heard in the liquid compression of the compressor, stop the unit
immediately and then energize the crank case heater for a sufficient length of time before
restarting the operation.
• Once stopping, the compressor will not restart in about 5 minutes even if the On/Off button of
the remote control is pushed.
• When the system operation is stopped by the remote control, the outdoor units may continue
operating for further 5 minutes at maximum.
• The outdoor unit fan may rotate at low speeds if the Night-time low noise setting or the
External low noise level setting is made, but this is not a malfunction.
NOTE:
After the test run, when handing the unit over to the customer, make sure the EL.COMPO.BOX
lid, the inspection door, and the unit casing are all attached.
AHU If ON button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. (Returns to normal when
automatic setting is complete.)
1.3.3 When an AHU or Outdoor unit Has Been Added, or AHU or Outdoor
Unit PC Board Has Been Changed
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address.
Status
Outdoor unit Test lamp H2P .... ON
Can also be set during operation described above.
AHU If ON button is pushed during operation described above, the "UH" or "U4"
malfunction indicator blinks. (Returns to normal when automatic setting is
complete.)
LED (H1~8P)
Push button
switch (BS1~5)
Caution When the 400 volt power supply is applyed to "N" phase by mistake,
replace Inverter P.C.B (A2P) and control transformer (T1R, T2R) in
switch box together.
(V0847)
HAP
(3) Mode setting switch H1P H2P H3P H4P H5P H6P H7P H8P
BS1 BS2 BS3 BS4 BS5 1 2 3 4 1 2 3 4
DS1 DS2
MODE SET RETURN TEST RESET
F1 F2 F1 F2 Q1 Q2
Indoor – Outdoor −
Outdoor Outdoor Multi outdoor
(V3054)
(1) Microcomputer normal monitor
This monitor blinks while in normal operation, and turns on or off when a malfunction occurs.
3. Field Setting
3.1 Field Setting from Remote Control
Individual function of AHU can be changed from the remote control. At the time of installation or
after service inspection / repair, make the local setting in accordance with the following
description.
Wrong setting may cause malfunction.
SECOND GROUP
SETTING
FIELD
CODE NO. SET
3 MODE
1
6
5 4 2
1. When in the normal mode, press the “ ” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “ ” button.
3. Push the “ ” upper button and select FIRST CODE NO.
4. Push the “ ” lower button and select the SECOND CODE NO.
5. Push the “ ” button once and the present settings are SET.
6. Push the “ ” button to return to the NORMAL MODE.
MODE NO.
FIRST
CODE NO.
UNIT NO.
SECOND
CODE NO.
Fan off during thermo off and fan on during defrost/oil return will result in fan on during thermo
off.
Thermo off
When the DDC controller maintains level A for more than B minutes, and the thermostat is on,
thermo off is carried out for at least C minutes. After C minutes, thermostat on-conditions are
checked.
Mode n° setting Setting switch n° Setting position n° Setting
51 8 00 level A = 1 (cooling)
01 level A = 1 or 2 (cooling)
6 00 B = 3 min, C = 3 min
01 B = 5 min, C = 3 min
02 B = 7 min, C = 3 min
03 --
04 B = 3 min, C = 5 min
05 B = 5 min, C = 5 min
06 B = 7 min, C = 5 min
07 --
08 B = 3 min, C = 10 min
09 B = 5 min, C = 10 min
10 B = 7 min, C = 10 min
9 00 level A = 5 (heating)
04 level A = 4 or 5 (heating)
Thermo on
When the DDC controller reaches level D or higher (lower for heating) and the thermostat is off
for at least C minutes (refer to thermo off conditions), thermostat on is carried out for at least E
minutes.
Mode n° setting Setting switch n° Setting position n° Setting
51 7 00 D = level 1 (cooling)
02 D = level 2 (cooling)
04 D = level 3 (cooling)
06 D = level 4 (cooling)
08 D = level 5 (cooling)
5 00 E = 3 min
01 E = 5 min
02 E = 10 min
b 00 D = level 1 (heating)
01 D = level 2 (heating)
02 D = level 3 (heating)
03 D = level 4 (heating)
04 D = level 5 (heating)
(5.2) Y-control
(5.3) Z-control
(6.2) Y-control
Since there is no external input to change the Te/Tc value, their values can only be changed by
local setup by means of the Daikin remote control (during installation).
Cooling: Te setting
Heating: Tc setting
prohibit the operation of compressor(s) Make this setting while in "Setting mode 2".
Emergency concerned or outdoor unit(s) concerned
7 For system with a single outdoor unit: Set
operation (*1) and to conduct emergency operation of the with No. 19 or 42.
system only with operable compressor(s)
or outdoor unit(s).
If a necessary amount of refrigerant cannot
Additional be charged due to the stop of outdoor unit, Set No. 20 of "Setting mode 2" to ON and
8 refrigerant operate the outdoor unit and then refill then charge refrigerant.
charging (*1) refrigerant.
Used to recover refrigerant on site.
Refrigerant With operations of AHU and outdoor units
9 Set No. 21 of "Setting mode 2" to ON.
recovery mode (*1) prohibited, fully open the expansion valve
of the AHU and outdoor units.
Used to conduct vacuuming on site.
Fully open the expansion valves of the
Vacuuming mode
10 AHU and outdoor units, and energize part Set No. 21 of "Setting mode 2" to ON.
(*1) of solenoid valves. Use a vacuum pump to
conduct vacuuming.
Used for the troubleshooting of DC
compressors.
Power transistor
12 Inverter waveform output makes it possible Set No. 28 of "Setting mode 2" to ON.
check mode to judge whether a malfunction results from
the compressor or the PC board.
Setting of model In order to replace the PC board by a spare For this setting, set the DS2-2, -3, and-4
13 with spare PC switches on the PC board to the model
board one, be sure to make model setting. concerned.
For setting items of (*1), refer to detailed information provided on previous page.
DS1-2 ON
Not used Do not change the factory settings.
~DS1-4 OFF (Factory set)
DS2-1 ON
Not used Do not change the factory settings.
~4 OFF (Factory set)
Caution DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
After the replacement by the spare PC board, be sure to make settings shown below.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
ON ON
Initial conditions of dip switches OFF OFF
1 2 3 4 1 2 3 4
DS1 DS2
DS2-2 Model setting Make the following settings according to models of outdoor units.
(All models are set to OFF at factory.)
ERQ 125 ERQ 200 ERQ 250
DS2-3
DS2-2 OFF OFF ON
DS2-3 OFF ON ON
DS2-4 DS2-4 OFF OFF OFF
∗ If the DS1-1~1-4, DS2-2~2-4 setting has not been carried out, error code “UA” are displayed
and unit can not be operated.
DS1 DS2
HEAT PUMP(5HP) ON
Set DS2-1 to ON.
ERQ 125 OFF
1 2 3 4 1 2 3 4
DS1 DS2
HEAT PUMP(8HP) ON
Set DS2-1 and DS2-3 to ON.
ERQ 200 OFF
1 2 3 4 1 2 3 4
DS1 DS2
HEAT PUMP(10HP) ON Set DS2-1, DS2-2 and DS2-3
ERQ 250 OFF to ON.
1 2 3 4 1 2 3 4
Push and hold the BS1 (Normal) Push the BS1(MODE button)
(MODE button) for 5 seconds. one time.
Setting mode 2 Setting mode 1 Monitor mode
On Off Blinking
Press BS1 (MODE button) for more than 5 sec. Setting mode 1 Press BS1(MODE button).
(Initial condition)
Setting condition
(Contents) display
Press BS3
(RETURN button). Press BS1
(MODE button).
Press BS1
(MODE button).
(V2762)
a. “Setting mode 1”
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ·····················Used to select COOL or HEAT by individual outdoor
unit (factory set).
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
w ON
x OFF
c Blink
Pushing the RETURN (BS3) button will return the system to the initial condition of "Setting
Push the RETURN (BS3) button to
determine the setting. mode 1".
15 wxxwwww
Address 0 wxxxxxx ∗
1
Cool / Heat
w x x x x x w
Binary number 1 wxxxxxw
Unified address (6 digits) ~
31 wxwwwww
Address 0 wxxxxxx ∗
2
Low noise/demand
w x x x x w x
Binary number 1 wxxxxxw
address (6 digits) ~
31 wxwwwww
3
Test operation
(Refer to the description w x x x x w w
Test operation: ON wxxxxxw
on page 180) Test operation: OFF wxxxxwx ∗
5 AHU forced fan w x x x w x w
Normal operation wxxxxxw ∗
Indoor forced fan H wxxxxwx
6
AHU forced
w x x x w w x
Normal operation wxxxxxw ∗
operation Indoor forced operation wxxxxwx
Quick defrost wxxxwxx
10 Defrost
setting
changeover
w x x w x w x Normal (factory setting) wxxxxwx ∗
Slow defrost wxxxxxw
External low noise/demand:
NO wxxxxxw ∗
12 External low noise/ w x x w w x x
wxxxxwx
demand setting External low noise/demand:
YES
High static pressure setting:
OFF wxxxxxw ∗
18 High
static pressure
w x w x x w x
setting High static pressure setting:
ON
wxxxxwx
Emergency OFF wxxxxxx ∗
19 operation
(STD compressor is w x w x x w w STD 1, 2 operation: Inhibited wxxxxxw
inhibited to operate.) STD 2 operation: Inhibited wxxxxwx
Additional refrigerant
20 charging operation w x w x w x x
Refrigerant charging: OFF wxxxxxw ∗
setting Refrigerant charging: ON wxxxxwx
Refrigerant
21 recovery/vacuuming w x w x w x w
Refrigerant recovery / vacuuming: OFF wxxxxxw ∗
mode setting Refrigerant recovery / vacuuming: ON wxxxxwx
OFF wxxxxxx ∗
22 Night-time low noise w x w x w w x
Level 1 (outdoor fan with 6 step or lower) wxxxxxw
setting Level 2 (outdoor fan with 5 step or lower) wxxxxwx
Level 3 (outdoor fan with 4 step or lower) wxxxxww
14
Contents of malfunction (the
latest) c x x w w w x Malfunction
code table
15
Contents of malfunction
(1 cycle before) c x x w w w w Refer page
181.
16
Contents of malfunction
(2 cycle before) c x w x x x x
20 Contents of retry (the latest) c x w x w x x
Push the RETURN (BS3) button and
switches to the initial status of 21 Contents of retry (1 cycle before) c x w x w x w
“Monitor mode”. 22 Contents of retry (2 cycle before) c x w x w w x
25 Number of multi connection
outdoor units c x w w x x w Lower 6 digits
∗ Push the MODE (BS1) button and The numbers in the "No." column represent the number of times to press the
returns to “Setting mode 1”. SET (BS2) button.
(V2765)
Setting item 0 Display contents of “Number of units for various settings”
EMG operation / ON c x x w x x x
backup operation
setting OFF c x x x x x x
Defrost select setting Short c x x x w x x
Medium c x x x c x x
Long c x x x x x x
Te setting H c x x x x w x
M c x x x x c x
L c x x x x x x
Tc setting H c x x x x x w
M c x x x x x c
L c x x x x x x
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and
confirm the data for each setting.
H Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
977 7979
The number of terminal blocks for No. 12 and 13 is expressed as
64 16
No.12 128 32 an 8-digit binary number, which is the combination of four upper,
and four lower digits for No. 12 and 13 respectively. (0 - 128)
977 7997 In d the address for No. 12 is 0101, the address for No. 13 is
4 1 0110, and the combination of the two is 01010110 (binary
No.13 8 2 number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.
H See the preceding page for a list of data, etc. for No. 0 - 25.
c Set Cool / Heat for Outdoor Unit System by AHU Remote Control
Set outdoor unit PC board DS1-1 to IN (factory set).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
Dip SW.
DS1-1
IN I
A B C F1 F2
control box
remote control
d Set Cool / Heat for Outdoor Unit System by Cool / Heat Selector
Set outdoor unit PC board DS1-1 to OUT (factory set).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
TEST
C/H SELECT
MODE L.N.O.P. DEMAND
MALFNC. IND MASTER SLAVE
Dip SW.
DS1-1 IN I
A B C F1 F2
control box
remote control
Cool/Heat
selector
A. When the low noise operation is carried out by external instructions (with the use
of the external control adapter for outdoor unit)
1. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2",
or "Mode 3") for set item No. 25 (Setting of external low noise level).
3. If necessary, while in "Setting mode 2", set the setting condition for the set item No. 29
(Setting of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the low
noise operation command will be ignored to put the system into normal operation mode.)
B. When the low noise operation is carried out automatically at night (The external
control adapter for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2", or "Mode 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)
Rated operation
sound Operation sound during
Night time night-time low noise mode is
Operation sound instructed can be set with
of mode 1 “Night-time low noise level
setting”. (Factory setting is
Operation sound “OFF”.)
of mode 2
Operation sound
of mode 3 Operation sound level set with
“Night-time low noise setting”
Set with “Night-time low noise start setting”. Set with “Night-time low noise end setting”.
(Factory setting is “PM 10:00”.) (Factory setting is “AM 8:00”.)
A. When the demand operation is carried out by external instructions (with the use of the
external control adapter for outdoor unit).
1. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
2. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the normal demand operation is carried out. (Use of the external control
adapter for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
(V3082)
{: ON z: OFF c: Blink
c d e
Setting Setting Setting No. indication Setting No. indication Setting Setting contents indication (Initial setting)
No. contents contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12 External NO
low noise / { z z z z z z { z z { { z z (Factory { z z z z z c
Demand setting)
setting
YES { z z z z c z
22 Night-time OFF
low noise { z { z { { z (Factory { z z z z z z
setting setting)
Mode 1 { z z z z z c
Mode 2 { z z z z c z
Mode 3 { z z z z c c
25 External { z { { z z { Mode 1 { z z z z z c
low noise
setting Mode 2
(Factory { z z z z c z
setting)
Mode 3 { z z z c z z
26 Night-time { z { { z { z PM 8:00 { z z z z z c
low noise
start setting PM 10:00
(Factory { z z z z c z
setting)
PM 0:00 { z z z c z z
27 Night-time { z { { z { { AM 6:00 { z z z z z c
low noise
end setting AM 7:00 { z z z z c z
AM 8:00
(Factory { z z z c z z
setting)
29 Capacity Low noise
precedence precedence
setting
{ z { { { z { (Factory
{ z z z z z c
setting)
Capacity
precedence
{ z z z z c z
30 Demand 60 % of
setting 1 { z { { { { z rated power { z z z z z c
consumption
70 % of
rated power
consumption { z z z z c z
(Factory
setting)
80 % of
rated power { z z z c z z
consumption
32 Normal OFF
demand { z z z z z z (Factory { z z z z z c
setting setting)
ON { z z z z c z
Setting mode indication section Setting No. indication section Set contents indication section
[Operation procedure]
c In setting mode 2 with units in stop mode, set “Refrigerant Recovery / Vacuuming mode” to
ON. The respective expansion valve of the units are fully opened. (H2P turns to display
“TEST OPERATION” (blinks), “TEST OPERATION” is displayed on the remote control, and
the all outdoor unit operation is prohibited.
After setting, do not cancel “Setting Mode 2” until completion of refrigerant recovery
operation.
d Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detal.)
e Press Mode button “BS1” once and reset “Setting Mode 2”.
[Operating procedure]
c With Setting Mode 2 while the unit stops, set “Refrigerant recovery / Vacuuming mode” to
ON. The expansion valves of the units fully open and some of solenoid valves open.
(H2P blinks to indicate the test operation, and the remote control displays "Test Operation",
thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
d Use the vacuum pump to perform vacuuming operation.
e Press Mode button “BS1” once and reset “Setting Mode 2”.
Completion
Part 7
Installation and Operation
Manual
Installation manual
English
Inverter condensing unit
Installationsanleitung
Deutsch
Invertierer Verflüssiger
Manuel d'installation
Français
Groupe condenseur à inverter
Montagehandleiding
Nederlands
Condensorunit met inverter
Manual de instalación
Español
Unidad condensadora Inverter
Manuale d'installazione
Italiano
Unità di condensazione a inverter
Manual de instalação
Portugues
Unidade de condensação com inversor
\ \
d d f
D D
d
D
A+B+C+D A+B
1+2 1 2 1 a ≥10 mm a ≥50 mm a ≥200 mm 4
b ≥300 mm b ≥100 mm b ≥300 mm
1 c ≥10 mm c ≥50 mm B
d ≥500 mm d ≥500 mm b
3
8 2 a ≥10 mm
b ≥300 mm
a ≥50 mm
b ≥100 mm
a ≥200 mm
b ≥300 mm
Aa e c C
5 7 3 c ≥10 mm c ≥50 mm
2 d ≥500 mm d ≥500 mm d
e ≥20 mm e ≥100 mm e ≥400 mm
2 a ≥10 mm a ≥50 mm
3 4 3
00
b ≥300 mm b ≥100 mm
≥10 1000
b
0
c ≥10 mm c ≥50 mm
≥1
h2
d ≥500 mm d ≥500 mm D
≥1000
6
00
≥1500
e ≥20 mm e ≥100 mm
00
f ≥600 mm f ≥500 mm
0
≥1
1500
a ≥10 mm a ≥50 mm
≥1500 4
b ≥300 mm b ≥100 mm
h1
≥1500
1 c ≥10 mm c ≥50 mm
500
d ≥500 mm d ≥500 mm
e ≥20 mm e ≥100 mm
(mm)
3 2
4
5
3 3 3 ERQ125 ERQ200+250
5 5 5
5 3
1 5 1 1
2 2 4
4 5
6 7
A
B
1 2 4 5 6
≥67 ≥67
722-737
67
765
≥100 ≥100
67
3 7
6 7 8
10
A B
9
2 3
3 2 11
1 3 1
2
2
8
4 8 8 7
4 8 8
1 4 6 5
11
1 10
5 9 1
8
B
A
8 9
A
2
9 10
1
10
A
12
D
9 8
C
7
3
90
14
1 15
25
16 11
150
4 4
2 3 5 6 12 13
12 11
13 14 15
1 9
1 7 8 1
4 8
L1 L2 L3 N
5 2 2
2 6 7
A1P TO IN-D
3 7 F1 F2
L N F1 F2 P1 P2
8 3 6 3
L1 L2
4
9
2
10 6 3
11 5 5 4
13 14 15
17 18
1 3 2 5 4
3 18
19
1 O
U
16 TO IN/D T
2 UNIT ON DS1
4
F1 F2 OFF
A1P
1 2 3 4
A B C F1 F2 A B C F1 F2 I
ABC N
C/H SELECTOR TO IN/D UNIT
1 3 6 4 2 2
F1 F2
4 F1 F2 P1 P2 P1 P2
5 1
16 17 19
23
1 2
20
O
U
T 22
ON DS1
1 2
OFF 3
ABC 1 2 3 4
I 4 4
N
5 5
ABC 6
1 6 5 4 3
20 22 23
21
1 10 2 3 5
10
24
5 4
11
6 6
7
8
9 12
2
9 4 13
11 1 3 6 14
6
24
25
10
7 7 5 4
8 11
9 2
12 7
8
9 12
2
13
1 3 6 14
14 13 15 16
21 25
ERQ125A7W1B
ERQ200A7W1B Inverter condensing unit Installation manual
ERQ250A7W1B
CONTENTS Page
The refrigerant R410A requires strict cautions for keeping
1. Introduction........................................................................................... 142 the system clean, dry and tight.
1.1. Combination ............................................................................. 142 ■ Clean and dry
1.2. Standard supplied accessories ................................................ 142
1.3. Technical and Electrical specifications ..................................... 142 Foreign materials (including mineral oils such as
2. Main components ................................................................................. 142 SUNISO oil or moisture) should be prevented from
getting mixed into the system.
3. Selection of location ............................................................................. 142
■ Tight
4. Inspecting and handling the unit........................................................... 143
R410A does not contain any chlorine, does not
5. Unpacking and placing the unit ............................................................ 143
destroy the ozone layer, and does not reduce the
6. Refrigerant piping ................................................................................. 144 earth’s protection against harmful ultraviolet radiation.
6.1. Installation tools ....................................................................... 144 R410A can contribute slightly to the greenhouse effect
6.2. Selection of piping material ...................................................... 144
6.3. Pipe connection ....................................................................... 144
if it is released. Therefore we should take special
6.4. Connecting the refrigerant piping ............................................. 144 attention to check the tightness of the installation.
6.5. Protection against contamination when installing pipes........... 146
Read "6. Refrigerant piping" on page 144 carefully and
7. Leak test and vacuum drying ............................................................... 147
follow these procedures correctly.
8. Field wiring ........................................................................................... 147
8.1. Internal wiring – Parts table...................................................... 148
8.2. Optional parts cool/heat selector.............................................. 148 Since design pressure is 4.0 MPa or 40 bar, pipes of larger
8.3. Power circuit and cable requirements ...................................... 149
8.4. General cautions ...................................................................... 149
wall thickness may be required. The wall thickness of
8.5. System examples..................................................................... 150 piping must be carefully selected, refer to paragraph
8.6. Leading power line and transmission line ................................ 150 "6.2. Selection of piping material" on page 144 for more
8.7. Field line connection: cool/heat selection................................. 150 details.
8.8. Field line connection: power wiring .......................................... 151
8.9. Wiring example for wiring inside unit........................................ 152
Do NOT connect the system to DIII-net devices:
9. Pipe insulation ...................................................................................... 152
10. Checking of unit and installation conditions.......................................... 152
11. Charging refrigerant ............................................................................. 152
11.1. Important information regarding the refrigerant used............... 152
11.2. Precautions when adding R410A............................................. 153
11.3. Stop valve operation procedure ............................................... 153
11.4. Additional refrigerant charge .................................................... 154
11.5. Checks after adding refrigerant................................................ 154
12. Before operation ................................................................................... 155
12.1. Service precautions ................................................................. 155 This could result in malfunction or breakdown of the total system.
12.2. Checks before initial start-up.................................................... 155
12.3. Field setting.............................................................................. 155
12.4. Test operation .......................................................................... 157
13. Service mode operation ....................................................................... 158
14. Caution for refrigerant leaks ................................................................. 159
15. Disposal requirements.......................................................................... 159
2 Fuse 3 Bring the unit as close as possible to its final installation position
in its original package to prevent damage during transport. (See
3 Earth leakage breaker
figure 4)
4 Remote control
5 Cool/heat selector 1 Packaging material
6 Air handling unit 2 Opening (large)
7 Control box 3 Belt sling
8 Expansion valve kit 4 Opening (small) (40x45)
5 Protector
In places with weak reception, keep distances of 3 m
or more to avoid electromagnetic disturbance of other 4 Lift the unit preferably with a crane and 2 belts of at least 8 m
equipment and use conduit tubes for power and long. (See figure 4)
transmission lines.
Always use protectors to prevent belt damage and pay attention
■ In heavy snowfall areas, select an installation site to the position of the unit’s centre of gravity.
where snow will not affect the operation of the unit.
■ The refrigerant R410A itself is nontoxic, nonflammable NOTE Use a belt sling of ≤ 20 mm wide that adequately
and is safe. If the refrigerant should leak however, its bears the weight of the unit.
concentration may exceed the allowable limit
depending on room size. Due to this, it could be 5 If a forklift is to be used, preferably transport the unit with pallet
necessary to take measures against leakage. Refer to first, then pass the forklift arms through the large rectangular
the chapter "Caution for refrigerant leaks". openings on the bottom of the unit. (See figure 5)
■ Do not install in the following locations. 5.1 From the moment you use a forklift to move the unit to its final
• Locations where sulfurous acids and other position, lift the unit under the pallet.
corrosive gases may be present in the
atmosphere. 5.2 Once at final position, unpack the unit and pass the forklift arms
Copper piping and soldered joints may corrode, through the large rectangular openings on the bottom of the unit.
causing refrigerant to leak.
• Locations where a mineral oil mist, spray or vapour
NOTE Use filler cloth on the forklift arms to prevent
may be present in the atmosphere. damaging the unit. If the paint on the bottom
frame peels off, the anti corrosion effect may
Plastic parts may deteriorate and fall off or causing
decrease.
water leakage.
• Locations where equipment that produces electro-
magnetic waves is found.
The electromagnetic waves may cause the control 5. UNPACKING AND PLACING THE UNIT
system to malfunction, preventing normal
operation. ■ Remove the four screws fixing the unit to the pallet.
• Locations where flammable gases may leak, where ■ Make sure the unit is installed level on a sufficiently strong base
thinner, gasoline, and other volatile substances are to prevent vibration and noise.
handled, or where carbon dust and other
incendiary substances are found in the Do not use stands to only support the corners. (See figure 6)
atmosphere.
Leaked gas may accumulate around the unit, X Not allowed (except for ERQ125)
causing an explosion. O Allowed (units: mm)
■ When installing, take strong winds, typhoons or
earthquakes into account. ■ Make sure the base under the unit is larger than the 765 mm of
Improper installation may result in fall over of the unit. the unit depth. (See figure 7)
■ The height of the foundation must at least be 150 mm from the
floor.
■ The unit must be installed on a solid longitudinal foundation
(steelbeam frame or concrete) as indicated in figure 7.
Model A B
ERQ125 635 497
ERQ200+250 930 792
20 mm
foundation bolts M12. It is best to screw in
the foundation bolts until their length 2. Use the following material specification for refrigerant piping:
remains 20 mm above the foundation ■ Construction material: phosphoric acid deoxidized seamless
surface. copper for refrigerant.
■ Prepare a water drainage channel around the ■ Temper grade: use piping with temper grade in function of
foundation to drain waste water from around the unit. the pipe diameter as listed in the table below.
■ If the unit is to be installed on a roof, check the Pipe Ø Temper grade of piping material
strength of the roof and its drainage facilities first. ≤ 15.9 O
■ If the unit is to be installed on a frame, install the ≥ 19.1 1/2H
waterproofing board within a distance of 150 mm O = Annealed
under the unit in order to prevent infiltration of water 1/2H = Half hard
coming from under the unit.
■ The pipe thickness of the refrigerant piping should comply
■ When installed in a corrosive with relevant local and national regulations. The minimal pipe
environment, use a nut with thickness for R410A piping must be in accordance with the
plastic washer (1) to protect the table below.
nut tightening part from rust.
Minimal thickness
1 Pipe Ø t (mm)
9.5 0.80
15.9 0.99
6. REFRIGERANT PIPING 19.1 0.80
22.2 0.80
Do not insert fingers, rods or other objects into the air 3. In case the required pipe sizes (inch sizes) are not available, it is
inlet or outlet. When the fan is rotating at high speed, it also allowed to use other diameters (mm sizes), taken the
will cause injury. following into account:
■ select the pipe size nearest to the required size.
Use R410A to add refrigerant. ■ use the suitable adapters for the change-over from inch to
All field piping must be installed by a licensed refrigeration mm pipes (field supply).
technician and must comply with relevant local and
national regulations.
6.3. Pipe connection
Caution to be taken when brazing refrigerant piping
Be sure to perform a nitrogen blow when brazing and to read the
Do not use flux when brazing copper-to-copper refrigerant
paragraph " Caution to be taken when brazing refrigerant piping" on
piping. (Particularly for the HFC refrigerant piping)
page 144 first.
Therefore, use the phosphor copper brazing filler metal
(BCuP) which does not require flux. NOTE The pressure regulator for the nitrogen released when
Flux has extremely harmful influence on refrigerant piping doing the brazing should be set to 0.02 MPa or less.
systems. For instance, if the chlorine based flux is used, it (See figure 8)
will cause pipe corrosion or, in particular, if the flux contains
fluorine, it will damage the refrigerant oil. 1 Refrigerant piping
Be sure to perform a nitrogen blow when brazing. Brazing 2 Location to be brazed
without performing nitrogen replacement or releasing 3 Nitrogen
nitrogen into the piping will create large quantities of 4 Taping
oxidized film on the inside of the pipes, adversely affecting
5 Manual valve
valves and compressors in the refrigerating system and
preventing normal operation. 6 Regulator
Ventilate the area immediately in the event of a leak. Residue can clog pipes and break equipment.
NOTE Make sure the pump oil does not flow oppositely into
the system while the pump is not working.
See figure 9.
1 Pinched piping
2 Stop valve
3 Service port
4 Point of melting the brazing metal
5 Small lower piece of pipe
3
2 A
L2
1
L1 B
1 Outdoor unit
2 Expansion valve kit
3 Air handling unit
B (*) —
–30 / +30
(*) Below or above the outdoor unit.
R4T ..................... Thermistor (coil-deicer) ■ For connection wiring to the central remote
control, refer to the installation manual of the
R5T ..................... Thermistor (coil-outlet) central remote control.
R6T ..................... Thermistor (liquid-pipe receiver) ■ Use insulated wire for the power cord.
R7T ..................... Thermistor (accumulator)
R10...................... Resistor (current sensor) (A4P) (A8P)
R31T~R33T......... Thermistor (discharge) (M1C~M3C)
R50,R59 .............. Resistor
R95...................... Resistor (current limiting)
S1NPH ................ Pressure sensor (high)
S1NPL................. Pressure sensor (low)
S1PH,S3PH ........ Pressure switch (high)
SD1 ..................... Safety devices input
T1A...................... Current sensor (A6P,A7P)
V1R ..................... Power module (A4P,A8P)
V1R,V2R ............. Power module (A3P)
X1A,X4A.............. Connector (M1F,M2F)
X1M..................... Terminal strip (power supply)
X1M..................... Terminal strip (control) (A1P)
X1M..................... Terminal strip (A5P)
Y1E,Y2E.............. Expansion valve (electronic type) (main, subcool)
Y1S ..................... Solenoid valve (hotgas bypass)
Y2S ..................... Solenoid valve (oil return)
Y3S ..................... Solenoid valve (4 way valve)
Y4S ..................... Solenoid valve (injection)
Z1C~Z7C............. Noise filter (ferrite core)
Z1F...................... Noise filter (with surge absorber)
(1) European/International Technical Standard setting the limits for voltage changes,
voltage fluctuations and flicker in public low-voltage supply systems for equipment
with rated current ≤ 75 A.
(2) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems with
input current >16 A and ≤ 75 A per phase.
For the above wiring, always use vinyl cords with 0.75
to 1.25 mm2 sheath or cables (2-core wires). (3-core
wire cables are allowable for the cooler/heater
changeover remote control only.)
1 Cool/heat selector
Shaft
■ Be sure to use tools exclusively for R410A to ensure required Hexagonal
pressure resistance and to prevent foreign materials from mixing Stop valve size Valve body wrench Cap (valve lid) Service port
Refrigerant containers must be opened slowly. Closing stop valve (See figure 23)
1. Remove the cap and turn the valve clockwise with the hexagon
wrench.
2. Securely tighten the valve until the shaft contacts the main body
seal.
3. Make sure to tighten the cap securely.
For the tightening torque, refer to the table above.
The refrigerant leak detection function can not be used. LED display Cooling/Heating
Micro-
(Default changeover
computer
status
operation Ready Indi- Bulk Bulk Low
before
monitor Mode /Error vidual (master) (slave) noise Demand Multi
Follow the procedures below. delivery)
HAP H1P H2P H3P H4P H5P H6P H7P H8P
Single
When charging a system, charging over
permissible quantity can cause liquid hammer.
the
outdoor unit c x x w x x x x x
system
Always use protective gloves and protect your eyes
when charging refrigerant. 3 Remote control malfunction code display
When the refrigerant charging procedure is done or
when pausing, close the valve of the refrigerant tank Remote control heating mode malfunction codes
immediately. If the tank is left with the valve open, the
Error
amount of refrigerant which is properly charged may code
get off point. More refrigerant may be charged by any
P8 Close valve A immediately and press the TEST OPERATION
remaining pressure after the unit has stopped. recharge button once.
operation The operation will restart from the charging mode judgement
Electric shock warning onwards.
P2 Close valve A immediately. Check
Close the electric box lid before turning on the main
charge following items:
power. After correcting the
hold - Check if the gas side stop valve is
abnormality, restart
Perform the settings on the circuit board (A1P) of the opened correctly
the automatic
- Check if the valve of the refrigerant
outdoor unit and check the LED display after the cylinder is opened
charging procedure
power is on via the service lid which is in the lid of the again.
- Check if the air inlet and outlet of the
electric box. air handling unit are not obstructed
Operate switches with an insulated
stick (such as a ball-point pen) to Remote control cooling mode malfunction codes
avoid touching the life parts. Error code
Make sure to re-attach the
Close valve A and replace the empty cylinder. When renewed,
inspection cover into the switch box cover after the job open valve A (the outdoor unit will not stop operating).
is finished. The code on the display shows the unit where a cylinder is to be
PA, PH, PC
renewed:
replace
PA = master unit, PH = slave unit 1, PC = slave unit 2, flashing PA,
Make sure to turn ON the power 6 hours before cylinder
PH and PC = all units
starting the operation. This is necessary to warm the After recplacing the cylinder, open valve A again and continue the
crankcase by the electric heater. work.
If operation is performed within 12 minutes after the air P8 Close valve A immediately.
handling unit and outdoor units are turned on, the recharge Restart the automatic charging procedure again.
operation
H2P-LED will be lit and the compressor will not
operate. Close valve A immediately. Check
following items:
- Check if the gas side stop valve is
NOTE See "11.3. Stop valve operation procedure" on P2
opened correctly
page 153 for details on how to handle stop valves. - Check if the valve of the refrigerant
charge
cylinder is opened After correcting the
The refrigerant charging port is connected to the hold
- Check if the air inlet and outlet of the abnormality, restart
piping inside the unit. air handling unit are not obstructed the automatic
The unit’s internal piping is already factory - Check if the indoor temperature is not charging procedure
lower than 20°C DB again.
charged with refrigerant, so be careful when
connecting the charge hose. Close valve A immediately. Confirm the
* malfunction code by the remote control
After adding the refrigerant, do not forget to close abnormal and correct the abnormality by following
the lid of the refrigerant charging port. stop the "Correcting after abnormal completion
of the test operation".
The tightening torque for the lid is 11.5 to
13.9 N•m.
In order to ensure uniform refrigerant distribution, 11.5. Checks after adding refrigerant
it may take the compressor ±10 minutes to start
Are the stop valves for both liquid and gas open?
up after the unit has started operation. This is not
a malfunction. Is the amount of refrigerant, that has been added, recorded?
NOTE Remark that during the first running period of the unit,
12.1. Service precautions required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.
WARNING: ELECTRIC SHOCK
Caution when performing service to inverter Make sure that the circuit breaker on the power supply
equipment panel of the installation is switched off.
Attach the power wire securely.
1 Do not open the electric box cover for 10 minutes after
the power supply is turned off. Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.
2 Measure the voltage between terminals on the
terminal block for power supply with a tester and After the installation, check the following before switching on the
confirm that the power supply is shut off. circuit breaker:
In addition, measure the points, as shown in the figure
1 The position of the switches that require an initial setting
below, with a tester and confirm that the voltage of the
capacitor in the main circuit is less than 50 V DC. Make sure that switches are set according to your application
needs before turning the power supply on.
A2P 2 Power supply wiring and transmission wiring
A1P
TP1 TP2 Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
A3P instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.
3 Pipe sizes and pipe insulation
Make sure that correct pipe sizes are installed and that the
3 To prevent damaging the PC-board, touch a insulation work is properly executed.
noncoated metal part to eliminate static electricity
4 Air tight test and vacuum drying
before pulling out or plugging in connectors.
Make sure the air tight test and vacuum drying were completed.
4 The performing of the service to the inverter
equipment must be started after the junction 5 Additional refrigerant charge
connectors X1A and X2A for the fan motors in the The amount of refrigerant to be added to the unit should be
outdoor unit are been pulled out. Be carefull not to written on the included "Added Refrigerant" plate and attached
touch the live parts. to the rear side of the front cover.
(If a fan rotates due to strong wind, it may store 6 Insulation test of the main power circuit
electricity in the capacitor or in the main circuit and
Using a megatester for 500 V, check that the insulation
cause electric shock.)
resistance of 2 M or more is attained by applying a voltage of
5 After the service is finished, plug the junction 500 V DC between power terminals and earth. Never use the
connecter back in. Otherwise the error code E7 will be megatester for the transmission wiring.
displayed on the remote control and normal operation
7 Installation date and field setting
will not be performed.
Be sure to keep record of the installation date on the sticker on
For details refer to the wiring diagram labeled on the back the rear of the upper front panel according to EN60335-2-40.
of the electric box cover. and keep record of the contents of the field setting.
Pay attention to the fan. It is dangerous to inspect the unit while the
fan is running. Be sure to turn off the main switch and to remove the 12.3. Field setting
fuses from the control circuit located in the outdoor unit.
If required, carry out field settings according to the following
NOTE Play it safe! instructions. Refer to the service manual for more details.
For protection of the PCB, touch the switch box casing
by hand in order to eliminate static electricity from your Opening the switch box and handling the switches
body before performing service.
When carrying out field settings, remove
the inspection cover (1).
1
Operate the switches with an insulated
stick (such as a ball-point pen) to avoid 2
touching live parts.
Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.
NOTE Make sure that all outside panels, except for the panel
on the electric box, are closed while working.
Close the lid of the electric box firmly before turning on
the power.
1 LED H1~8P 1 Turn the power on for the outdoor unit, the control box and air
2 Push button switches handling unit.
BS1~BS5
Be sure to turn the power on at least 6 hours before operation
3 Dip switch 1 (DS1: 1~4) inorder to have power running to the crank case heater.
4 Dip switch 2 (DS2: 1~4) 1 2 Make sure that transmission is normal by checking the LED
5 Dip switch 3 (DS3: 1~2) 2
display on the outdoor unit circuit board (A1P). (If transmission is
4 normal, each LED will be displayed as shown below.)
3
5 LED display Micro- Cooling/Heating
(Default computer changeover
status
operation Ready Indivi- Bulk Bulk Low
before
LED state delivery)
monitor Mode /Error dual (master) (slave) noise Demand Multi
HAP H1P H2P H3P H4P H5P H6P H7P H8P
Throughout the manual the state of the LEDs is indicated as follows: Single
outdoor unit c x x w x x x x x
x OFF system
w ON
Setting the mode
c Blinking
The set mode can be changed with the BS1 MODE button according
to the following procedure:
Setting the dip switches (only in case of a heat pump unit) For setting mode 1: Press the BS1 MODE button once, the
What to set with dip switch DS1 H1P LED is off x.
1 COOL/HEAT selector (refer to "8.7. Field line connection: cool/ For setting mode 2: Press the BS1 MODE button for
heat selection" on page 150) 5 seconds, the H1P LED is on w.
( OFF = not installed = factory setting)
If the H1P LED is blinking c and the BS1 MODE button is pushed
2~4 NOT USED once, the setting mode will change to setting mode 1.
DO NOT CHANGE THE FACTORY SETTING.
What to set with dip switch DS2 NOTE If you get confused in the middle of the setting
1~4 NOT USED process, push the BS1 MODE button. Then it returns
DO NOT CHANGE THE FACTORY SETTING. to setting mode 1 (H1P LED is off).
What to set with dip switch DS3
1+2 NOT USED
Setting mode 1
DO NOT CHANGE THE FACTORY SETTING.
(not in case of cooling only unit)
Setting the push button switch (BS1~5) The H1P LED is off (COOL/HEAT selection setting).
Setting procedure
Function of the push button switch which is located on the outdoor
unit PCB (A1P): 1 Push the BS2 SET button and adjust the LED indication to
either one of the possible settings as shown below in the field
TEST: C/H SELECT marked :
MODE L.N.O.P DEMAND MULTI
HWL: IND MASTER SLAVE
1 In case of COOL/HEAT setting by each individual outdoor unit
circuit.
H1P H2P H3P H4P H5P H6P H7P H8P
H1P H2P H3P H4P H5P H6P H7P
BS1 BS2 BS3 BS4 BS5
1 x x c x x x x
MODE SET RETURN TEST RESET
The figure shows state of the LED indications when the unit is
shipped from the factory.
Setting procedure Refer to the service manual for more details and for other settings.
1 Push the BS2 SET button according to the required function Confirmation of the set mode
(A~H). The LED indication that matches the required function is
shown below in the field marked : The following items can be confirmed by setting mode 1 (H1P
LED is off)
Possible functions
A additional refrigerant charging operation (not applicable). Check the LED indication in the field marked .
B refrigerant recovery operation/vacuuming operation. 1 Indication of the present operation state
C setting of high static pressure.
- x, normal
D automatic low noise operation setting at nighttime.
E low noise operation level setting ( L.N.O.P ) via the external
- w, abnormal
control adapter. - c, under preparation or under test operation
F power consumption limitation setting ( DEMAND ) via the external
control adapter. H1P H2P H3P H4P H5P H6P H7P
B w x w x w x w 1(*) x x w x x x x
C w x w x x w x (*) This setting = factory setting.
H1P H2P H3P H4P H5P H6P H7P 12.4. Test operation
ON w x x x x c x
w x x x x x c
(*)
Do not insert fingers, rods or other objects into the air
OFF
inlet or outlet. When the fan is rotating at high speed, it
(*) This setting = factory setting
will cause injury.
3.2 Possible settings for function D
The noise of level 3 < level 2 < level 1 ( 1 ). Do not perform the test operation while working on the
air handling units.
H1P H2P H3P H4P H5P H6P H7P
OFF (*)
w x x x x x x When performing the test operation, not only the outdoor
unit, but the connected air handling unit will operate as
1 w x x x x x c well. Working on a air handling unit while performing a test
2 w x x x x c x operation is dangerous.
3 w x x x x c c In the check operation, the following checks and judgement will
(*) This setting = factory setting be performed:
3.3 Possible settings for function E and F Check of the stop valve opening
For function E ( L.N.O.P ) only: the noise of level 3 < level 2 Check for wrong wiring
< level 1 ( 1 ).
For function F ( DEMAND ) only: the power consumption of Judgement of piping length
level 1< level 2 < level 3 ( 3 ). It takes ±30 minutes to complete the check operation.
H1P H2P H3P H4P H5P H6P H7P
1 w x x x x x c
2 (*)
w x x x x c x
3 w x x x c x x
(*) This setting = factory setting
1 Close the electric box lid and all front panels except the one on The test operation is only completed if there is no malfunction code
the side of the electric box. displayed on the remote control. In case of a displayed malfunction
code, perform the following actions to correct the abnormality:
2 Turn on the power to the outdoor unit, control box and air
handling units. Be sure to turn the power ON at least 6 hours Confirm the malfunction code on the remote control
before operation in order to have power running to the crank Installation error Error code Remedial action
case heater.
The stop valve of an E3 Check referring to the table in
3 Make the field setting as needed using the push buttons on the outdoor unit is left E4 "11.4. Additional refrigerant charge"
closed. F3 on page 152
PCB (A1P) of the outdoor unit. Refer to "12.3. Field setting" on
UF
page 155.
The phases of the U1 Exchange two of the three phases
4 Set the check operation (without initial refrigerant decision) power to the outdoor (L1, L2, L3) to make a positive
following setting mode 2 in the field setting and perform the units are reversed. phase connection.
check operation. No power is supplied U1 Check if the power wiring for the
to an outdoor unit, U4 outdoor units are connected
The system operates for ±30 minutes and automatically stops control box or air correctly.
the check operation. handling unit (If the power wire is not connected
(including phase to L2 phase, no malfunction display
If no malfunction code is displayed on the remote control interruption). will appear and the compressor will
after the system has stopped, check if the operation is not work.)
completed. Normal operation will be possible after 5 minutes. Incorrect UF Check if the refrigerant line piping
interconnections and the unit wiring are consistent
If a malfunction code is displayed on the remote control, between units with each other.
correct the malfunction and perform the check operation
Refrigerant E3 Recalculate the required amount of
again as decribed in "Correcting after abnormal completion of overcharge F6 refrigerant from the piping length
the test operation" on page 156 UF and correct the refrigerant charge
level by recovering any excessive
Test operation procedure refrigerant with a refrigerant
recovery machine.
1 Close all front panels except the front panel of the electric box.
Insufficient refrigerant E4 Check if the additional refrigerant
2 Turn ON the power to all outdoor units and the connected air F3 charge has been finished correctly.
handling units. Recalculate the required amount of
refrigerant from the piping length
Be sure to turn on the power 6 hours before operation in order to and add an adequate amount of
have power running to the crank case heater and to protect the refrigerant.
compressor.
After correcting the abnormality, press the BS3 RETURN button
3 Make the field setting as described in the paragraph "12.3. Field and reset the malfunction code.
setting" on page 155.
Carry out the test operation again and confirm that the
4 Press the BS1 MODE button once, and set to the SETTING abnormality is properly corrected.
MODE (H1P LED = OFF).
5 Press and hold the BS4 TEST button down for 5 seconds or
more. The unit will start the test operation.
13. SERVICE MODE OPERATION
The test operation is automatically carried out in cooling
mode, the H2P LED will light up and the messages "Test Vacuuming method
operation" and "Under centralized control" will display on the
At the first installation, this vacuuming is not required. It is required
remote control.
only for repair purposes.
It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts. 1 When the unit is at standstill and under the setting mode 2, set
the required function B (refrigerant recovery operation/
During the test operation, the refrigerant running sound or the
vacuuming operation) to ON (ON).
magnetic sound of a solenoid valve may become loud and
- After this is set, do not reset the setting mode 2 until the
the LED display may change, but these are not malfunctions.
vacuuming is finished.
During the test operation, it is not possible to stop the unit - The H1P LED is on and the remote control indicates
operation from a remote control. To abort the operation, (test operation) and (external control) and the
press the BS3 RETURN button. The unit will stop after operation will be prohibited.
±30 seconds.
2 Evacuate the system with a vacuum pump.
6 Close the front panel in order to let it not be the cause of
misjudgement. 3 Press the BS1 MODE button and reset the setting mode 2.
7 Check the test operation results by the LED display on the Refrigerant recovery operation method
outdoor unit. by a refrigerant reclaimer
H1P H2P H3P H4P H5P H6P H7P 1 When the unit is at standstill and under the setting mode 2, set
Normal completion x x w x x x x the required function B (refrigerant recovery operation/
vacuuming operation) to ON (ON).
Abnormal completion x w w x x x x - The air handling unit and the outdoor unit expansion valves
8 When the test operation is fully completed, normal operation will will fully open and some solenoid valves will be turned on.
be possible after 5 minutes. - The H1P LED is on and the remote control indicates
(test operation) and (external control) and the
Otherwise, refer to " Correcting after abnormal completion of the
operation will be prohibited.
test operation" on page 158 to take actions for correcting the
abnormality.
≤
refrigerant system
According to the appropriate European Standard, the maximum maximum concentration level
size (m3) of smallest (kg/m3)
allowed concentration level of refrigerant to a humanly space for
room in which there is
R410A is limited to 0.44 kg/m3. an air handling unit
installed
Operation manual
English
Inverter condensing unit
Bedienungsanleitung
Deutsch
Invertierer Verflüssiger
Manuel d'utilisation
Français
Groupe condenseur à inverter
Gebruiksaanwijzing
Nederlands
Condensorunit met inverter
Manual de operación
Español
Unidad condensadora Inverter
Manuale d'uso
Italiano
Unità di condensazione a inverter
ERQ100A7V1B
Manual de operações
ERQ125A7V1B Unidade de condensação com inversor
Portugues
ERQ140A7V1B
\ \
ERQ125A7W1B
ERQ200A7W1B Instrukcja obs³ugi
polski
ERQ250A7W1B Skraplacz typu Inverter
1 2
3 6 5 1 3 6 5 1
2 2
13
7 7
12 9 8 4 11 10 9 8 14
1 2
1 4 2 3
3 4
1
2
UNIT NO.
3 4 5
6 7 8
1 1
6 7 8
NOTES
ERQ100A7V1B ERQ125A7W1B
ERQ125A7V1B
ERQ140A7V1B
ERQ200A7W1B
ERQ250A7W1B
Inverter condensing unit Operation manual
CONTENTS Page
Warnings
1. Safety cautions..................................................................................... 162
■ It is not good for your health to expose your body to the air flow
2. Important information regarding the refrigerant used ........................... 163 for a long time.
3. What to do before operation................................................................. 163 ■ In order to avoid electric shock, fire or injury, or if you detect any
4. Remote control..................................................................................... 164 abnormality such as smell of fire, turn off the power supply and
5. Changeover switch: Name and function of each switch....................... 164 call your dealer for instructions.
6. Operation range ................................................................................... 164 ■ Ask your dealer for installation of the air conditioner.
7. Operation procedure ............................................................................ 164 Incomplete installation performed by yourself may result in a
7.1. Cooling, heating, and fan only operation ................................. 164 water leakage, electric shock, and fire.
8. Energy saving and optimum operation................................................. 165 ■ Do not place objects in direct proximity of the outdoor unit and
9. Maintenance......................................................................................... 165 do not let leaves and other debris accumulate around the unit.
9.1. Maintenance after a long stop period....................................... 165 Leaves are a hotbed for small animals which can enter the unit.
9.2. Maintenance before a long stop period ................................... 165 Once in the unit, such animals can cause malfunctions, smoke
10. Following symptoms are not air conditioner troubles ........................... 165 or fire when making contact with electrical parts.
11. Troubleshooting.................................................................................... 166 ■ Ask your dealer for improvement, repair, and maintenance.
12. After-sales service and warranty .......................................................... 167 Incomplete improvement, repair, and maintenance may result in
12.1. After-sales service ................................................................... 167
a water leakage, electric shock and fire.
12.2. Shortening of "maintenance cycle" and "replacement cycle" ■ Do not insert fingers, rods or other objects into the air inlet or
needs to be considered in following situations ........................ 167 outlet. When the fan is rotating at high speed, it will cause injury.
■ Never let the air handling unit or the remote control get wet.
Thank you for purchasing this Daikin air conditioner. It may cause an electric shock or a fire.
Carefully read this operation manual before using the air ■ Never use a flammable spray such as hair spray, lacquer or
conditioner. It will tell you how to use the unit properly and paint near the unit.
help you if any trouble occurs. After reading the manual, It may cause a fire.
file it away for future reference. ■ Never replace a fuse with that of wrong ampere ratings or other
wires when a fuse blows out.
The English text is the original instruction. Other languages are
Use of wire or copper wire may cause the unit to break down or
translations of the original instructions.
cause a fire.
■ Never put any objects into the air inlet or outlet.
Objects touching the fan at high operating speed can be
1. SAFETY CAUTIONS dangerous.
■ Never press the button of the remote control with a hard, pointed
Read the following cautions carefully and use your equipment object.
properly. The remote control may be damaged.
WARNING ■ Never pull or twist the electric wire of the remote control.
It may cause the unit to malfunction.
Improper handling can lead to such serious consequences
as death, severe injury or damage to the equipment. ■ Never inspect or service the unit by yourself.
Ask a qualified service person to perform this work.
■ To prevent refrigerant leak, contact your dealer.
NOTE These instructions will ensure proper use of the When the system is installed and runs in a small room, it is
equipment. required to keep the concentration of the refrigerant, if by any
Be sure to follow these important safety cautions. chance coming out, below the limit. Otherwise, oxygen in the
room may be affected, resulting in a serious accident.
Keep these warning sheets handy so that you can refer to them ■ The refrigerant in the air conditioner is safe and normally does
if needed. not leak. If the refrigerant leaks in the room, contact with a fire of
Also, if this equipment is transferred to a new user, make sure to a burner, a heater or a cooker may result in a harmful gas.
hand over this user’s manual to the new user. Turn off any combustible heating devices, ventilate the room
and contact the dealer where you purchased the unit.
Do not use the air conditioner until a service person confirms
that the portion where the refrigerant leaks is repaired.
■ Improper installation or attachment of equipment or accessories
could result in electric shock, short-circuit, leaks, fire or other
damage to the equipment. Be sure to use only accessories
made by Daikin which are specifically designed for use with the
equipment and have them installed by a professional.
■ Ask your dealer to move and reinstall the air conditioner.
Incomplete installation may result in a water leakage, electric
shock, and fire.
■ Do not let children play on and around the outdoor unit. 2 Control box
If they touch the unit carelessly, it may result in injury. 3 Air handling unit (field supply)
■ Do not place a flower vase or anything containing water on the 4 Remote control (standard)
unit. 5 Field piping (field supply)
Water may enter the unit, causing an electric shock or fire.
6 Expansion valve kit
■ Do not place the controller exposed to direct sunlight.
Wiring connections
The LCD display may get discolored, failing to display the data.
7 Outdoor unit power supply
■ Do not wipe the controller operation panel with benzine, thinner,
chemical dustcloth, etc. 8 Control box wiring
(Power supply and communication between control box and
The panel may get discolored or the coating peeled off. If it is outdoor unit)
heavily dirty, soak a cloth in water-diluted neutral detergent,
9 Air handling unit thermistors
squeeze it well and wipe the panel clean. Wipe it with another
dry cloth. 10 Communication between controller and control box
■ Never touch the internal parts of the controller. 11 Power supply and control wiring for air handling unit and controller
(power supply is separate from the outdoor unit)
Do not remove the front panel. Some parts inside are dangerous
to touch and a machine trouble may happen. For checking and 12 Air thermistor control for air handling unit
adjusting the internal parts, contact your dealer. 13 Controller (field supply)
■ Avoid placing the controller in a spot splashed with water. 14 Remote control (optional, for service only)
Water coming inside the machine may cause an electric leak or
may damage the internal electronic parts. For more details, refer to the manual of the control box.
Operation range 1 Select operation mode with the field supplied controller.
2 Close T1/T2.
Use the system in the following temperature and humidity ranges for
safe and effective operation. The operation lamp lights up and the system starts operation.
It may take longer to reach the set temperature for general heating
7. OPERATION PROCEDURE operation than for cooling operation.
The following operation is performed in order to prevent the heating
■ Operation procedure varies according to the combination of
capacity from dropping or cold air from blowing.
outdoor unit and remote control. Read "3. What to do before
operation" on page 163. Defrost operation
■ To protect the unit, turn on the main power switch 6 hours before ■ In heating operation, freezing of the outdoor unit coil increases.
operation. Heating capability decreases and the system goes into defrost
■ If the main power supply is turned off during operation, operation operation.
will restart automatically after the power turns back on again. ■ The air handling unit fan stops and the remote control displays
■ Refer to the manual supplied with the control box for operation .
and functionality. ■ In case no remote control is installed, a defrost signal is
■ Refer to the manual supplied with the remote control for outputted from the control box.
operation and functionality. ■ After maximum 10 minutes of defrost operation, the system
returns to heating operation again.
7.1. Cooling, heating, and fan only operation (See figure 4 Hot start
and figure 6) In order to prevent cold air from blowing out of an air handling unit at
The fan may keep on running for a while after the heating operation the start of heating operation, the air handling unit fan can be
stops. stopped, depending on the control of the air handling unit.
In case a remote control is installed, the remote control displays
For systems with Daikin remote control and without cool/heat . It may take some time before the fan starts. This is not a
changeover remote control switch (See figure 4) malfunction.
Cooling operation
Heating operation
Symptom 4.2: Air handling unit, outdoor unit The system must be repaired by a qualified service person.
■ When the system is changed over to heating operation after ■ If a safety device such as a fuse, a breaker or an earth leakage
defrost operation breaker frequently actuates or the ON/OFF switch does not
Moisture generated by defrost becomes steam and is properly work.
exhausted. Measure: Turn off the main power switch.
■ If water leaks from the unit
Symptom 5: The remote control display reads "U4" or "U5" and stops, but
then restarts after a few minutes Measure: Stop the operation.
■ This is because the remote control is intercepting noise from ■ The operation switch does not work well.
electric appliances other than the air conditioner. This prevents Measure: Turn off the power.
communication between the units, causing them to stop.
■ If the display TEST , the unit number and the operation lamp
Operation automatically restarts when the noise ceases.
flash and the malfunction code appears. (Only when a remote
control is connected) (See figure 5)
Symptom 6: Noise of air conditioners
■ A continuous low hissing sound is heard when the system is in 2 Air handling unit number in which a malfunction occurs
cooling or defrost operation. 3 Operation lamp
This is the sound of refrigerant gas flowing through both indoor 4 Malfunction code
and outdoor units.
■ A hissing sound which is heard at the start or immediately after Measure: Notify your dealer and report the malfunction code.
stopping operation or defrost operation. If the system does not properly operate except for the above
This is the noise of refrigerant caused by flow stop or flow mentioned cases and none of the above mentioned malfunctions is
change. evident, investigate the system according to the following
Symptom 6.2: Outdoor unit procedures.
■ When the tone of operating noise changes. 1 If the system does not operate at all
This noise is caused by the change of frequency.
■ Check if there is no power failure.
Wait until power is restored. If power failure occurs during
Symptom 7: Dust comes out of the unit
operation, the system automatically restarts immediately after
■ When the unit is used for the first time in a long time. the power supply is recovered.
This is because dust has gotten into the unit.
■ Check if no fuse has blown or breaker has worked. Change the
fuse or reset the breaker if necessary.
Symptom 8: The units can give off odours
■ The unit can absorb the smell of rooms, furniture, cigarettes, 2 If the system goes into fan only operation, but as soon as it
etc., and then emit it again. goes into heating or cooling operation, the system stops
■ Check if air inlet or outlet of outdoor or air handling unit is not
Symptom 9: The outdoor unit fan does not spin. blocked by obstacles. Remove any obstacle and make it well-
■ During operation. ventilated.
The speed of the fan is controlled in order to optimize product
operation.
Symptom 10: The display shows " " . (Only when a remote control is
connected)
■ This is the case immediately after the main power supply switch
is turned on and means that the remote control is in normal
condition. This continues for one minute.
Symptom 11: The compressor in the outdoor unit does not stop after a
short heating operation
■ This is to prevent oil and refrigerant from remaining in the
compressor. The unit will stop after 5 to 10 minutes.
■ Check the fan speed setting on your remote control. Electric motor 20,000 hours
■ Check for open doors or windows. Shut doors and windows to PCB 25,000 hours
prevent wind from coming in. Heat exchanger 5 years
■ Check if there are too many occupants in the room during Sensor (thermistor, etc.) 5 years
1 year
cooling operation Remote control and switches 25,000 hours
■ Check if the heat source of the room is excessive. Drain pan 8 years
■ Check if direct sunlight enters the room. Use curtains or blinds. Expansion valve 20,000 hours
■ Check if the air flow angle is proper. Electromagnetic valve 20,000 hours
If after checking all above items, it is impossible to fix the problem Table 1 assumes the following conditions of use:
yourself, contact your dealer and state the symptoms, the complete
model name of the air conditioner (with manufacturing number if 1. Normal use without frequent starting and stopping of the unit.
possible) and the installation date (possibly listed on the warranty card). Depending on the model, we recommend not starting and
stopping the machine more than 6 times/hour.
2. Operation of the unit is assumed to be 10 hours/day and 2,500
hours/year.
12. AFTER-SALES SERVICE AND WARRANTY
NOTE 1. Table 1 indicates main components.
Warranty period Refer to your maintenance and inspection contract
■ This product includes a warranty card that was filled out by the for more details.
dealer at the time of installation. The completed card was 2. Table 1 indicates recommended intervals of
checked by the customer and stored carefully. maintenance cycles. However, in order to keep
■ If repairs to the air conditioner are necessary within the warranty the unit operational as long as possible,
period, contact your dealer and keep the warranty card at hand. maintenance work may be required sooner.
Recommended intervals can be used for
appropriate maintenance design in terms of
12.1. After-sales service budgetting maintenance and inspection fees.
Depending on the content of the maintenance and
■ Recommendations for maintenance and inspection inspection contract, inspection and maintenance
Since dust collects when using the unit for several years, cycles may in reality be shorter than listed.
performance of the unit will deteriorate to some extent.
As taking apart and cleaning interiors of units requires technical
expertise and in order to ensure the best possible maintenance 12.2. Shortening of "maintenance cycle" and "replacement
of your units, we recommend to enter into a maintenance and cycle" needs to be considered in following situations
inspection contract on top of normal maintenance activities.
Our network of dealers has access to a permanent stock of ■ The unit is used in locations where:
essential components in order to keep your air conditioner in 1. heat and humidity fluctuate out of the ordinary
operation as long as possible. 2. power fluctuation is high (voltage, frequency, wave distortion,
Contact your dealer for more information. etc.)
■ When asking your dealer for an intervention, always state: (The unit cannot be used if power fluctuation is outside the
• the complete model name of the air conditioner allowable range.)
• the manufacturing number (stated on the nameplate of the 3. bumps and vibrations are frequent
unit) 4. dust, salt, harmful gas or oil mist such as sulfurous acid and
• the installation date hydrogen sulfide may be present in the air
• the symptoms or malfunction, and details of the defect.
5. the machine is started and stopped frequently or operation time
is long (sites with 24 hour air-conditioning).
WARNING
■ Do not modify, disassemble, remove, reinstall or
repair the unit yourself as incorrect dismantling or
installation may cause an electric shock or fire.
Contact your dealer.
■ In case of accidental refrigerant leaks, make sure
there are no naked flames. The refrigerant itself is
entirely safe, non-toxic and non-combustible, but it will
generate toxic gas when it accidentally leaks into a
room where combustible air from fan heaters, gas
cookers, etc. ... is present.
Always have qualified service personnel confirm that
the point of leakage has been repaired or corrected
before resuming operation.
Maintenance cycle
(replacements and/
Component Inspection cycle or repairs)
Air filter 5 years
High efficiency filter (Optional) 1 year
1 year
Fuse 10 years
Crankcase heater 8 years
Part 8
Troubleshooting
Troubleshooting 169
ESIE09-06
170 Troubleshooting
ESiEN09-06 Symptom-based Troubleshooting
1. Symptom-based Troubleshooting
Symptom Supposed Cause Countermeasure
1 The system does not start operation at all. Blowout of fuse(s) Turn Off the power supply and
then replace the fuse(s).
Cutout of breaker(s) • If the knob of any breaker is in
its OFF position, turn ON the
power supply.
• If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
ON
Knob
Tripped
OFF
Circuit breaker
Troubleshooting 171
Symptom-based Troubleshooting ESiEN09-06
172 Troubleshooting
ESiEN09-06 Symptom-based Troubleshooting
Troubleshooting 173
Troubleshooting by Remote Control ESiEN09-06
Normal
mode
Press Inspection/Test Operation button once.
Press Inspection/Test Operation
Or after 30 minutes
button once.
After 10 seconds
174 Troubleshooting
ESiEN09-06 Troubleshooting by Remote Control
ON/OFF button
Inspection display
Malfunction code
Inspection/Test button
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or
more will clear the failure history indication shown above. In this case, on the codes display,
the malfunction code will blink twice and then change to “00” (=Normal), the Unit No. will
change to “0”, and the operation mode will automatically switch from check mode to normal
mode (displaying the set temperature).
Troubleshooting 175
Troubleshooting by Remote Control ESiEN09-06
Push the button for 4 seconds or longer. Push the button for 4 seconds or longer.
176 Troubleshooting
ESiEN09-06 Troubleshooting by Remote Control
Mode Function Contents and operation method Remote control display example
No
40 Malfunction history
display
Display malfunction history.
The history No. can be changed with the Unit 1
button.
Malfunction code 40
2-U4
Malfunction code
Hystory No: 1 - 9
1: Latest
(VE007)
41 Display of sensor
and address data
Display various types of data.
Select the data to be displayed with the Sensor data display
button. Sensor data
0: Thermostat sensor in remote control. Unit No. Sensor type
1: Suction or level (if DDC-control: 0 = level 1
etc.)
41
2: Liquid pipe 1 1
3: Gas pipe 27
Temperature °C
Address display
Unit No. Address type
41
1 8
1
Address
(VE008)
Troubleshooting 177
Troubleshooting by Remote Control ESiEN09-06
Operation lamp
ON/OFF button
(VL050)
178 Troubleshooting
ESiEN09-06 Troubleshooting by Remote Control
w: ON x: OFF c: Blink
Malfunction Operation Inspection Unit No. Malfunction contents Page
code lamp display Referred
AHU A0 c c c Error of external protection device 185
A1 c c c PC board defect, E2 PROM defect 186
A3 c c c Malfunction of drain level control system (S1L) 187
A6 c c c Fan motor (M1F) lock, overload 189
A9 c c c Malfunction of moving part of electronic expansion 190
valve (20E)
AF w x c Drain level about limit 192
AH w x c Malfunction of air filter maintenance —
AJ c c c Malfunction of capacity setting 193
C4 c c c Malfunction of thermistor (R2T) for heat exchange 194
(loose connection, disconnection, short circuit, failure)
C5 c c c Malfunction of thermistor (R3T) for gas pipes (loose 195
connection, disconnection, short circuit, failure)
C9 c c c Malfunction of thermistor (R1T) for air inlet (loose 196
connection, disconnection, short circuit, failure)
CJ w w w Malfunction of thermostat sensor in remote control 197
Outdoor Unit E1 c c c PC board defect 198
E3 c c c Actuation of high pressure switch 199
E4 c c c Actuation of low pressure sensor 201
E5 c c c Compressor motor lock 203
E6 c c c Standard compressor lock or over current 205
E7 c c c Malfunction of outdoor unit fan motor 206
E9 c c c Malfunction of moving part of electronic expansion 209
valve (Y1E, Y2E)
F3 c c c Abnormal discharge pipe temperature 211
F6 c c c Refrigerant overcharged 212
H7 c c c Abnormal outdoor fan motor signal 213
H9 c c c Malfunction of thermistor (R1T) for outdoor air (loose 214
connection, disconnection, short circuit, failure)
J2 c c c Current sensor malfunction 215
J3 c c c Malfunction of discharge pipe thermistor (R31~33T) 216
(loose connection, disconnection, short circuit,
failure)
J5 c c c Malfunction of thermistor (R2T) for suction pipe 217
(loose connection, disconnection, short circuit,
failure)
J6 c c c Malfunction of thermistor (R4T) for heat exchanger 218
(loose connection, disconnection, short circuit,
failure)
J7 c c c Malfunction of receiver outlet liquid pipe thermistor (R6T) 219
J9 c c c Malfunction of subcooling heat exchanger gas pipe 220
thermistor (R5T)
JA c c c Malfunction of discharge pipe pressure sensor 221
JC c c c Malfunction of suction pipe pressure sensor 222
L0 c c c Inverter system error —
L4 c c c Malfunction of inverter radiating fin temperature rise 223
L5 c c c DC output overcurrent of inverter compressor 225
L8 c c c Inverter current abnormal 227
L9 c c c Inverter start up error 229
Troubleshooting 179
Troubleshooting by Remote Control ESiEN09-06
w: ON x: OFF c: Blink
Malfunction Operation Inspection Unit No. Malfunction contents Page
code lamp display Referred
Outdoor Unit LA c c c Malfunction of power unit —
LC c c c Malfunction of transmission between inverter and 231
control PC board
P1 c c c Inverter over-ripple protection 234
P4 c c c Malfunction of inverter radiating fin temperature rise 235
sensor
PJ c c c Faulty field setting after replacing main PC board or 237
faulty combination of PC board
System U0 w x c Low pressure drop due to refrigerant shortage or 238
electronic expansion valve failure
U1 c c c Reverse phase / open phase 239
U2 c c c Power supply insufficient or instantaneous failure 240
U3 c c c Check operation is not completed. 243
U3 w x c Check operation is not completed. 243
U4 c c c Malfunction of transmission between AHU and 244
outdoor units
U5 c c c Malfunction of transmission between remote control 246
and AHU
U5 x w x Failure of remote control PC board or setting during 246
control by remote control
U9 c c c Malfunction of transmission between AHU and 247
outdoor unit in the same system
UA c c c Improper combination of AHU and outdoor units, 248
AHUs and remote control
UE c c c Malfunction of transmission between central remote —
control and AHU
UF c c c Refrigerant system not set, incompatible wiring / 250
piping
UH c c c Malfunction of system, refrigerant system address 251
undefined
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
180 Troubleshooting
ESiEN09-06 Troubleshooting by Remote Control
Troubleshooting 181
Troubleshooting by Remote Control ESiEN09-06
w: ON x: OFF c:Blink
Malfunction Confirmation of malfunction 1 Confirmation of malfunction 2 Confirmation of malfunction 3 Confirmation of malfunction 4
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
E3 c x x c c c x x c c c x x x x c x x
E4 c x c x x c x x x x c x x
E5 c x c x c c x x x x c x x
E6 c x c c x c x x x x c x x
c x x x x c x c
E7 c x c c c c x x x x c x x
∗1
c x x x x c x c
c x x x c c x x
c x x x c c x c
E9 c c x x c c x x x x c x x
c x x x x c x c
c x x x x c c x
H7 c x c x x c x c c c c x x x x c x x
c x x x c c x x
∗1
H9 c c x x c c x x x x c x x
c x x x c c x x
F3 c x c x c c x x c c c x x x x c x x ∗1
F6 c x c c x c x x x x c x x c c
J2 c x c c x c x x c x c x x x x c x x
c x x x x c x c
J3 c x x c c c x x x x c x x
c x x x x c x c
c x x x x c c x
c x x x c c x x
c x x x c c x c
c x x x c c c x
J5 c x c x c c x x x x c x x
c x x x c c x x
c x x x x c x c
∗1
c x x x c c x c
J6 c x c c x c x x x x c x x
c x x x c c x x
J7 c x c c c c x x x x c x x
c x x x c c x x
J9 c c x x c c x x x x c x x
c x x x c c x x
JA c c x c x c x x x x c x x
c x x x c c x x
JC c c c x x c x x x x c x x
c x x x c c x x
(L2) c x c c c c x x c x c x x x x c x x
L4 c x c x x c x x x x c x x
L5 c x c x c c x x x x c x x
L5 c x x x x c x c
L8 c c x x x c x x x x c x x
c x x x x c x c
c x x x x c
∗1
c x x x x c c x
c x x x c c x x
L9 c c x x c c x x x x c x x
c x x x x c x x
c x x x x c x c
c x x x x c c x
LC c c c x x c x x x x c x c
182 Troubleshooting
ESiEN09-06 Troubleshooting by Remote Control
Push the RETURN (BS3) button Transmission error between AHU and I/O transmission error U4
once to display "First digit" of outdoor unit
I/O transmission error
malfunction code.
Transmission error between outdoor Sequential startup ADP alarm U7
units, transmission error between
thermal storage units, duplication of IC Sequential startup ADP malfunction U7
address Malfunction of transmission between
multi units (Multi 1)
Malfunction of transmission between
multi units (Multi 2)
<Confirmation of malfunction 2>
Abnormal multi horsepower setting
Push the SET (BS2) button once to Detail Abnormal multi address setting
display "Second digit" of malfunction description Excessive multi connections
code. on next Multi system malfunction
page.
Transmission error of other system AHU system abnormal in other system U9
or other AHU system abnormal in own
system
Erroneous field setting System transmission malfunction UA
Overconnection malfunction of AHUs
<Confirmation of malfunction 3>
Malfunction of field setting
Push the SET (BS2) button once to Refrigerant abnormal
display "malfunction location".
Multi-ID abnormal
Alarm of TSS field setting UA
Alarm of CT address setting
Faulty system malfunction Wiring error (Auto-address error) UH
Transmission error in accessory Malfunction of multi-level connection UJ
devices
Alarm of multi-level connection UJ
<Confirmation of malfunction 4>
Conflict in wiring and piping, no setting Conflict in wiring and piping UF
for system
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Troubleshooting 183
Troubleshooting by Remote Control ESiEN09-06
w: ON x: OFF c:Blink
Malfunction Confirmation of malfunction 1 Confirmation of malfunction 2 Confirmation of malfunction 3 Confirmation of malfunction 4
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
P1 c c x x x c x x x c c x x x x c x x
P3 c x x c c c x x x x c x x
P4 c x c x x c x x x x c x x ∗1
PJ c c c x c c x x x x c x x
c x x x x c x c
c x x x x c c x
U0 c c x x c c x x x x c x x x x c x x c c
U1 c x x x c c x x x x c x x
U2 c x x c x c x x x x c x x
c x x x x c x c
U3 c x x c c c x x x x c x x c c
c x x x x c x c c c
U4 c x c x x c x x x x c x x c c
c x x x x c x c c c
U7 c x c c c c x x x x c x c c c
U7 c x x x x c x x c c
c x x x x c c x c c
c x x x x c c c c c
c x x x c c x x c c
c x x x c c x c c c
c x x x c c c x c c
c x x x c c c c c c
U9 c c x x c c x x x x c x x c c
UA c c x c x c x x x x c x x c c
c x x x x c x c c c
c x x x x c c x c c
c x x x c c x x c c
c x x x c c x c c c
UA c x x x c c c x c c
c x x x c c c c c c
UH c c x c c c x x x x c x x c c
UJ c c c x c c x x x x c x x
∗1
UJ c x x x x c x c
UF c c c c c c x x x x c x x c c
184 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Detect open or short circuit between external input terminals in AHU.
Malfunction
Detection
Malfunction When an open circuit occurs between external input terminals with the remote control set to
Decision "external ON/OFF terminal".
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
External
protection device is YES
connected to terminals T1 and
T2 of the AHU terminal Actuation of external protection
block. device.
NO
ON/OFF
input from
outside (mode No.
12, first code No. 1) has YES
been set to external Change the second code No. to
protection device input "01" or "02" .
(second code No. 03)
by remote
control.
NO
AHU PC board replacement.
(V2776)
Troubleshooting 185
Troubleshooting by Indication on the Remote Control ESiEN09-06
Malfunction When data could not be correctly received from the E²PROM
Decision E²PROM: Type of nonvolatile memory. Maintains memory contents even when the power
Conditions supply is turned off.
Troubleshooting
186 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Applicable AHU
Models
Malfunction When rise of water level is not a condition and the float switch goes OFF.
Decision
Conditions
Troubleshooting 187
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
NO YES
Loose connection of connector.
YES YES
Modify the float switch’s
connection and turn on again.
The
drain pump is
connected to X25A or NO
terminals Y1 and Y2 of Connect the drain pump and
the AHU PC turn on again.
board.
YES
The drain
pump works when YES
the power supply is reset Check the drain piping for
for the AHU. clogging or upward slope, etc.
NO
The
voltage of
terminals Y1 and
Y2 or X25A is 220~240 V NO
(within 5 minutes of Replace AHU PC board.
resetting the power
supply).
YES
Replace the drain pump or
check for dirt, etc.
(V2778)
188 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Detection
Malfunction When number of turns can’t be detected even when output voltage to the fan is maximum
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
wiring from the
fan motor securely NO
connected to connectors on Connect the wiring and turn on
the AHU PC again.
board?
YES
Wiring
between the AHU YES
PC board and fan motor is Fix the wiring and turn on again.
disconnected.
NO
NO
Replace the fan motor.
(V2779)
Troubleshooting 189
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Use a microcomputer to check the electronic expansion valve for coil conditions.
Malfunction
Detection
Malfunction When the pin input of the electronic expansion valve is not normal while in the initialization of
Decision the microcomputer.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
electronic
expansion valve is NO
connected to X7A of the After connecting, turn the power
AHU PC board. supply off and then back on.
YES
Normal
when coil
check (∗1) of the NO
moving part of the electronic Replace the moving part of the
expansion valve is electronic expansion valve.
checked.
YES
The
connecting cable is YES
short-circuited or Replace the connecting cable.
disconnected.
NO
If you turn the power supply off
and turn on again, and it still does
not help, replace the AHU PC
board.
(V2781)
190 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
∗1: Coil check method for the moving part of the electronic expansion valve
Disconnect the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × { × { ×
Approx. Approx.
300Ω 150Ω
2. Yellow × { × {
Approx. Approx.
300Ω 150Ω
3. Orange × { ×
Approx.
150Ω
4. Blue × {
Approx.
150Ω
5. Red ×
6. Brown
{: Continuity
×: No continuity
Troubleshooting 191
Troubleshooting by Indication on the Remote Control ESiEN09-06
Applicable AHU
Models
Method of Water leakage is detected based on float switch ON/OFF operation while the compressor is in
Malfunction non-operation.
Detection
Malfunction When the float switch changes from ON to OFF while the compressor is in non-operation.
Decision
Conditions
Troubleshooting
Field drain
piping has a defect YES
such as upward Modify the drain piping.
sloping.
NO
A
humidifier unit YES
(optional accessory) is Check if the humidifier unit is
installed on the leaking.
AHU.
NO
Defect of AHU PC board.
(V2782)
192 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Capacity is determined according to resistance of the capacity setting adapter and the memory
Malfunction inside the IC memory on the AHU PC board, and whether the value is normal or abnormal is
Detection determined.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The AHU PC NO
board was replaced with a
replacement PC Replace the AHU PC board.
board.
YES
Was the
capacity setting
adapter mounted when YES
replacing the PC board? Replace the AHU PC board.
NO
Install a capacity setting adapter.
(V2783)
Troubleshooting 193
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Malfunction detection is carried out by temperature detected by heat exchanger thermistor.
Malfunction
Detection
Malfunction When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the YES
thermistor normal? Normal (The malfunction is
caused by faulty contact.)
NO
Remove the thermistor from
the AHU PC board, and then
make resistance measurement
of the thermistor using a
multiple meter.
* NO
5 kΩ to 90 kΩ Replace the thermistor (R2T).
YES
Replace the AHU PC board.
194 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Detection
Malfunction When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the YES
thermistor normal? Normal (The malfunction is
caused by faulty contact.)
NO
Remove the thermistor from
the AHU PC board, and then
make resistance measurement
of the thermistor using a
multiple meter.
* NO
5 kΩ to 90 kΩ Replace the thermistor (R3T).
YES
Replace the AHU PC board.
Troubleshooting 195
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Malfunction detection is carried out by temperature detected by suction air temperature
Malfunction thermistor.
Detection
Malfunction When the suction air temperature thermistor becomes disconnected or shorted while the unit is
Decision running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the YES
thermistor normal? Normal (The malfunction is
caused by faulty contact.)
NO
Remove the thermistor from
the AHU PC board, and then
make resistance measurement
of the thermistor using a
multiple meter.
* NO
5 kΩ to 90 kΩ Replace the thermistor (R1T).
YES
Replace the AHU PC board.
196 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Malfunction detection is carried out by temperature detected by remote control air temperature
Malfunction thermistor. (Note:)
Detection
Malfunction When the remote control air temperature thermistor becomes disconnected or shorted while the
Decision unit is running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is "CJ" YES
displayed on the remote Replace remote control.
control?
NO
External factor other than
equipment malfunction.
(for example, noise etc.)
(V2787)
Note: In case of remote control thermistor malfunction, unit is still operable by suction air thermistor on
AHU.
Troubleshooting 197
Troubleshooting by Indication on the Remote Control ESiEN09-06
Malfunction When data could not be correctly received from the E²PROM
Decision E²PROM: Type of nonvolatile memory. Maintains memory contents even when the power
Conditions supply is turned off.
Troubleshooting
Return to YES
normal? External factor other than
malfunction (for example,
NO noise etc.).
Replace the outdoor unit
main PC Board (A1P).
(V3064)
198 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Detection
Malfunction Error is generated when the HPS activation count reaches the number specific to the operation
Decision mode.
Conditions (Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure: 2.85MPa
Troubleshooting 199
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
· Mount a pressure gauge on the high-pressure service port.
· Connect the Service Checker.
· Reset the operation using the remote control,
and then restart the operation.
NO YES
Are the
characteristics of the high NO
Replace the high pressure sensor.
pressure sensor normal?
(See *1.)
YES
Is the pressure
NO
detected with the PCB Replace the main PCB.
normal? (See *2.)
YES
· The high pressure sensor is normal, and the pressure detected with the PCB is also normal.
· The high pressure has really become high.
*1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on “Pressure Sensor”.)
*2: Make a comparison between the high pressure value checked with the Service Checker
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
+5V
Connector for high
pressure sensor (Red)
(4) Red
(3) High
Black
pressure
(2) sensor
Micro controller
A/D input (1) White
Make measurement of DC
voltage between these wires.
200 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Detection
Malfunction Error is generated when the low pressure is dropped under specific pressure.
Decision Operating pressure:0.07MPa
Conditions
Troubleshooting 201
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the stop
NO
valve open? Open the stop valve.
YES
Are the
characteristics of the
low pressure sensor NO
Replace the low pressure sensor.
normal? (See *1.)
YES
Is the
pressure detected NO
with the PCB normal? Replace the main PCB.
(See *2.)
YES
· The low pressure sensor is normal, and the pressure
detected with the PCB is also normal.
· The low pressure has really become low.
*1: Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on “Pressure Sensor”.)
*2: Make a comparison between the low pressure value checked with the Service Checker
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
+5V
Connector for low pressure sensor
(Blue)
(4) Red
202 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Inverter PC board takes the position signal from UVW line connected between the inverter and
Malfunction compressor, and the malfunction is detected when any abnormality is observed in the phase-
Detection current waveform.
Malfunction This malfunction will be output when the inverter compressor motor does not start up even in
Decision forced startup mode.
Conditions
Troubleshooting 203
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the stop NO
valve open? On-site causes.
Open the stop valve.
Power OFF YES
Check the compressor cable
for disconnection and flaws.
The
compressor cable has a YES
Replace the cable, and
defect. then securely connect
the connectors.
NO
Are wire
connections made
to phases U, V, and W in NO
Make wire connections
the proper order and without a mistake.
manner? W
NO
U
Are wire
connections NO V
properly made (according Make wire connections
to the Wiring Are the wire connections without a mistake.
Diagram)? mixed up with those for
non-inverter compressor?
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
NO
The
insulation resistance YES
is low (i.e., not more than Replace the
100kW.) compressor.
NO
Check the compressor motor
coil for any broken wire.
NO
Some phase YES
has a broken wire.
NO
Restart
the compressor,
and then check whether or NO
End of work
not the malfunction Faulty pressure
recurs. equalization or else
may have occurred.
Power ON YES Check the refrigerant
system.
Has the
compressor
started up at high YES
differential pressure (not Faulty pressure
less than equalization:
0.5MPa)? Check the refrigerant
system.
NO
Replace the
compressor.
· Conduct checks and
diagnosis of the
compressor.
204 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Malfunction Malfunction is decided when the detected current value exceeds the below mentioned value for
Decision 2 seconds.
Conditions 400 V unit: 15.0 A
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the stop NO
valve open? Open the stop valve.
YES
NO
Is the power NO
supply voltage normal? Correct the power voltage.
YES
Is the
magnetic switch (K2M, NO
Replace the magnetic
K3M) normal? switch.
YES
Check the wiring from power supply ~ current sensor (A6P, A7P) ~
MgS (K2M, K3M) ~ compressor
Is above wiring NO
Correct wiring.
correct?
YES
Is current NO
sensor correct? ∗1 Replace the corresponding
current sensor (A6P or
A7P).
YES
Replace compressor.
(V3051)
Troubleshooting 205
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Malfunction of fan motor system is detected according to the fan speed detected by hall IC
Malfunction when the fan motor runs.
Detection
Malfunction When the fan runs with speed less than a specified one for 6 seconds or more when the fan
Decision motor running conditions are met
Conditions When connector detecting fan speed is disconnected
When malfunction is generated 4 times, the system shuts down.
206 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
Different
power supply
cable connector and
signal cable connector have
been connected to the relay YES
harness. (Power supply and signal Use connectors of the same
cable connectors of different color in combination for the
colors are connected for power supply and signal
one and the same cables for the relay harness
motor.) (e.g. natural color to natural
color, or red to red).
NO
Connectors of
harness between the
compressor inverter PCB YES
Insert the connectors in the
and the fan inverter PCB harness.
(A4P and A8P) are
disconnected.
NO
The fuse
(white tubular fuse) YES
on the fan inverter PCB has a Replace the fan inverter
broken wire (has no PCB.
continuity).
NO
With the
connector
disconnected from the YES
fan motor, the fan cannot Replace the outdoor unit fan
be rotated by motor.
hand.
NO
Resistance
between the fan motor YES
power supply cable terminal and Replace the outdoor unit fan
the motor frame (metal motor.
part) is not more
than 1MΩ.
NO
A
(V3076)
Troubleshooting 207
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Check 1
Check for the fan motor
connector (Power supply cable)
Resistance of
the U, V and W phases
of the fan motor has got YES
imbalanced or short circuits have Replace the outdoor unit fan
been established among the motor.
U, V and W phases.
NO
Check 2
Check for the fan motor
connector (Signal cable)
Has a
short circuit
been established
between the fan motor signal YES
Replace the outdoor unit fan
cables Vcc and GND, and UVW motor.
and GND,
respectively?
NO
Turn ON the power supply.
The
LED (HAP) on
the compressor
inverter PCB is blinking, but YES
Replace the fan inverter
the LED (HAP) on the fan PCB.
inverter PCB is not
blinking.
NO
Replace the outdoor unit fan
motor.
(V3077)
208 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Malfunction Error is generated under no common power supply when the power is on.
Decision
Conditions
Troubleshooting 209
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Return to normal? External factor other than
malfunction (for example, noise
NO etc.).
Electronic
expansion valve is NO
connected to X21A and X23A of After connecting, turn the power
outdoor unit PC board off and then back on again.
(A1P). * X26A only for RXYQ5M
YES
Normal
when coil
check (∗1) of the NO
moving part of the electronic Replace the moving part of the
expansion valve is electronic expansion valve.
checked.
YES
The
connecting cable is YES
short-circuited or Replace the connecting cable.
disconnected.
NO
Replace outdoor unit PC board
(A1P).
(V3067)
(Orange) 1
(Red) 2
Measuring points
(Yellow) 3 1-6
2-6
(Black) 4
3-6
4-6
5
(Gray) 6
(V3067)
210 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Abnormality is detected according to the temperature detected by the discharge pipe
Malfunction temperature sensor.
Detection
Malfunction When the discharge pipe temperature rises to an abnormally high level
Decision When the discharge pipe temperature rises suddenly
Conditions
Troubleshooting
Discharge
pipetemperature is YES
115°C or higher when the unit Refrigerant shortage, compression
stop by malfunction. defect, etc. Defect of the
refrigerant system.
NO
Pull out the discharge pipe
thermistor from the outdoor
PCB, and then make
measurement of resistance
using a multiple meter.
Are the
characteristics of
the discharge pipe NO
thermistor normal? Replace the discharge pipe
(3.5~400KΩ) ∗ thermistor.
YES
Replace outdoor unit PC board
(A1P).
(V3068)
Troubleshooting 211
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Excessive charging of refrigerant is detected by using the outside air temperature, heat
Malfunction exchanging deicer temperature and liquid pipe temperature during a check run.
Detection
Malfunction When the amount of refrigerant, which is calculated by using the outside air temperature, heat
Decision exchanging deicer temperature and liquid pipe temperature during a check run, exceeds the
Conditions standard.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the
above thermistor NO
installed on pipes correctly? Install thermistor correctly.
YES
Remove the outside air
thermistor, heat exchanging
deicer thermister and the liquid
pipe thermistor from the outdoor PCB
and measure resistance with a tester.
Is the
characteristic of the NO
above thermistor normal? Replace thermistor.
YES
Refrigerant overcharged.
(V2797)
212 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the fan
motor connector NO
X2A connected to PC Connect correctly.
board for Fan inverter
correctly?
YES
Check of fan motor connector.
(H1)
The
resistance of fan
motor read wire NO
connector pins between Replace fan motor.
Vcc-UVW and GND-UVW
balanced?
YES
Replace fan inverter PC Board.
(A3P)
(V3069)
5 Gray GND
4 Pink Vcc
Measure the
resistance
between
3 Orange W Vcc-UVW and
GND-UVW.
2 Blue V
1 Yellow U
(V2799)
Troubleshooting 213
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Detection
Malfunction When the outside air temperature thermistor has short circuit or open circuit.
Decision
Conditions
Troubleshooting
Connector is NO
connected to X18A of Connect the connector and turn on
outdoor PC board again.
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
(R1T) from the outdoor Replace the thermistor (R1T)
unit PC board.
(1.8kΩ to
800kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3070)
214 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Malfunction is detected according to the current value detected by current sensor.
Malfunction
Detection
Malfunction When the current value detected by current sensor becomes 5A or lower, or 40A or more during
Decision standard compressor operation.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
connector for
current sensor NO
connected to X25A, X26A Connect the connector, and
on outdoor unit PC operate unit again.
board (A1P)?
YES
Are the current
sensors inversely connected to YES
two STD compressors? Correct the connections between
the current sensors and the STD
compressors.
NO
Is the
current sensor NO
mounted on the T-phase Mount the current sensor
(A6P) and R-phase correctly, and operate unit again.
(A7P) wire?
YES
Replace current sensor and
outdoor unit PC board.
(V3071)
Troubleshooting 215
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Malfunction is detected from the temperature detected by discharge pipe temperature
Malfunction thermistor.
Detection
Malfunction When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Decision
Conditions
Supposed Defect of thermistor (R31T, R32T or R33T) for outdoor unit discharge pipe
Causes Defect of outdoor unit PC board (A1P)
Defect of thermistor connection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector is
connected to X29A of NO
outdoor unit PC board Connect the connector and turn on
(A1P). again.
YES
Resistance
is normal when
measured after
disconnecting the NO
thermistor R31, 32T or R33T Replace the thermistor (R31, 32T
from the outdoor unit or R33T)
PC board. (2.5kΩ
to 1.3kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3072)
The alarm indicator is displayed when the fan is being used also.
216 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Malfunction is detected from the temperature detected by the suction pipe temperature
Malfunction thermistor.
Detection
Malfunction When a short circuit or an open circuit in the suction pipe temperature thermistor is detected.
Decision
Conditions
Supposed Defect of thermistor (R2T), (R7T) for outdoor unit suction pipe
Causes Defect of outdoor unit PC board (A1P)
Defect of thermistor connection
Troubleshooting
Connector
is connected to NO
X30A, of outdoor unit PC Connect the connector and turn on
board. (A1P) again.
YES
Resistance is
normal when
measured after NO
disconnecting the thermistor Replace the thermistor R2T.
(R2T), (R7T) from the
outdoor unit PC board.
(1.8kΩ to
800kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3073)
Troubleshooting 217
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Detection
Malfunction When a short circuit or an open circuit in the heat exchange thermistor is detected.
Decision
Conditions
Troubleshooting
Connector
is connected to NO
X30A of outdoor unit PC Connect the connector and turn on
board (A1P). again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
Replace the thermistor R4T.
R4T from the indoor unit
PC board. (1.8kΩ
to 800kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3074)
218 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Malfunction is detected according to the temperature detected by liquid pipe thermistor.
Malfunction
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
connector for
liquid pipe
thermistor connected to NO
Connect the connector and
X30A on outdoor unit PC operate unit again.
board (A1P)?
YES
Is the
resistance
measured after
removing the thermistor NO
(R6T) from outdoor unit PC Replace thermistor (R6T).
board normal? (1.8kΩ
to 800kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3075)
Troubleshooting 219
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Malfunction is detected according to the temperature detected by subcooling heat exchanger
Malfunction gas pipe thermistor.
Detection
Malfunction When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
connector
for subcooling
heat exchanger gas pipe NO
thermistor connected to Connect the connector and
X30A on outdoor unit operate unit again.
PC board
(A1P)?
YES
Is the
resistance
measured after
removing the thermistor NO
(R5T) from outdoor unit PC Replace thermistor (R5T).
board normal? (1.8kΩ
to 800kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3075)
220 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Detection
Malfunction When the high pressure sensor is short circuit or open circuit.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The high
pressure sensor is NO
connected to X32A of Connect the high pressure sensor
outdoor unit PC and turn on again.
board (A1P).
YES
The
relationship
between the ∗1 VH
and high pressure is
normal (see ∗2) when voltage is YES
measured between X32A pins Replace outdoor unit PC board
(1) and (3) of outdoor unit (A1P).
PC board (A1P)
(see ∗1).
NO
Replace the high pressure sensor.
(V2806)
∗1: Voltage measurement point
Outdoor unit PC board (A2P)
+5V
X32A
Red
High pressure sensor
GND Black
Microcomputer White
A/D input
Troubleshooting 221
Troubleshooting by Indication on the Remote Control ESiEN09-06
Malfunction When the low pressure sensor is short circuit or open circuit.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The low
pressure sensor is NO
connected to X31A of outdoor Connect low pressure sensor
unit PC board (A1P). properly and restart system.
YES
The
relationship
between the ∗1
VL and low pressure is
normal (see ∗2) when YES
voltage is measured between Replace outdoor unit PC board
X31A pins (2) and (3) of (A1P).
outdoor unit PC
board (A1P)
(see ∗1).
NO
Replace the low pressure sensor.
(V2808)
X31A
Red
Low pressure sensor
GND Black
Microcomputer White
A/D input
222 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Malfunction When the temperature of the inverter radiation fin increases above 93°C.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Fin
temperature of the YES
compressor inverter is Faulty radiation from the
high. If the fin reaches a switch box:
Power OFF temperature of 93°C, the Conduct the checks
NO malfunction will occur. shown below.
• Radiation fin for stains
Remove and insert the fin
• Airflow for interference
thermistor connector "X111A".
• Fan propeller for damage
• Whether or not outdoor
Troubleshooting 223
Troubleshooting by Indication on the Remote Control ESiEN09-06
224 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting
Compressor inspection
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The YES
compressor cable has a Replace the cable, and
defect. then securely connect the
connectors.
NO
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
Troubleshooting 225
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
NO
Check the compressor motor
coil for any broken wire.
NO
Restart the
compressor, and then NO
check whether or not the Normal
Power ON · On-site causes such as
malfunction
recurs. instantaneous power
failure or open phase
YES · Conduct checks and
diagnosis of the
Replace the inverter PCB. compressor.
Power OFF
Restart the
compressor, and then NO
Power ON End of work
check whether or not the
malfunction
recurs.
YES Replace the compressor.
· Conduct checks and
diagnosis of the
compressor.
226 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Malfunction When overload in the compressor is detected. (Inverter secondary current 16.1A)
Decision
Conditions
Power ON A current of
not less than 15A flows YES
through the compressor. Overcurrent:
Check the compressor
and refrigerant system
NO (in the same manner as
that for E3).
NO
Is the stop valve Open the stop valve.
open?
YES
Are wire
connections properly NO
made (according to the Wiring Rectify the wire
Diagram)? Check the compressor cable for connections.
any disconnection or flaws.
YES
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
Power OFF
NO
The
insulation resistance is YES
low, i.e., not more Replace the
than 100kΩ.) compressor.
NO
Check the power transistor on
the inverter PC board using a
multiple tester.
NO
Does the power YES
transistor have any Replace the inverter
abnormalities? PCB.
The inverter is likely
NO to have got faulty due
Connect the compressor cable, to the malfunction of
and then restart the operation. the compressor. After
the completion of
replacement, be sure
A to check the
compresssor.
Troubleshooting 227
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
A
Is a
difference NO
between high pressure
and low pressure prior Faulty pressure
to startup equalization:
0.2MPa? Check the refrigerant
system.
YES
Check of compressor:
Check the compressor
for abnormal sounds,
vibration, operating
conditions, and others
according to the
Compressor Diagnosis
Procedure.
228 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of This malfunction code will be output if overcurrent occurs at the time of startup.
Malfunction
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
insulation resistance YES
is low (i.e., not more Replace the
than 100kΩ.) compressor.
NO
Check the power transistor on
the inverter PC board using a
multiple tester.
NO
Does the power YES
transistor have any Replace the inverter
abnormalities? PCB.
The inverter is likely
NO to have got faulty due
to the malfunction of
Connect the compressor cable, the compressor. After
and then restart the operation. the completion of
replacement, be sure
A to check the
compresssor.
Troubleshooting 229
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
A
Is a
difference between NO
high pressure and low pressure Faulty pressure
prior to startup equalization:
0.2MPa? Check the refrigerant
system.
YES
Check of compressor:
Check the compressor
for abnormal sounds,
vibration, operating
conditions, and others
according to the
Compressor Diagnosis
Procedure.
230 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Check the communication state between inverter PC board and control PC board by micro-
Malfunction computer.
Detection
Supposed Malfunction of connection between the inverter PC board and outdoor control PC board
Causes Defect of outdoor control PC board (transmission section)
Defect of inverter PC board
Defect of noise filter
Faulty fan inverter
Incorrect type of fan inverter
Faulty compressor
Faulty fan motor
Troubleshooting 231
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the
fan transmission
wire connectors (X3A: Black, NO
X4A: Yellow) wrongly Connect the connectors
connected? to the corresponding
color (black or yellow).
YES
Power ON
Check
whether or not
the power supply voltage NO
between L2 and N falls in the On-site cause.
range of 220 to Correct the wiring.
240VAC?
YES
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
NO
The
insulation resistance YES
is low (i.e., not more Replace the fan motor.
than 1MΩ.) Replace the fan driver
PC board.
NO
Check for connector connections: Remove and insert the
connectors shown below.
[Fan 1] [Fan 2]
• A1P X28A ⇔ X6A A3P • A4P X51A ⇔ X5A A8P
• A1P X20A ⇔ X4A A3P • A4P X4A ⇔ X3A A8P
• A3P X61A ⇔ X402A A2P • A8P X4A Short connector
• A3P X1A ⇔ X403A A2P
• A3P X5A ⇔ X5A A4P Note) X3A: black
• A3P X41A ⇔ X3A A4P X4A: yellow
• A4P X4A Short connector
NO
F400U
A
232 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting
Is the micro
controller normal NO
monitor (green) of the A1P This is not LC.
blinking? Recheck for the
malfunction code.
YES
Check 10 or more seconds after
the power supply is turned ON.
Power ON The A3P, YES
A4P, and A8P do not A3P: Replace the
blink. inverter PCB.
∗If the PCB replaced is
badly damaged, the
NO compressor is likely to
get faulty. To make
sure, recheck the
compressor.
The LC YES
malfunction recurs. Replace the control
PC board.
NO
End of measures:
The malfunction may
temporarily result from
on-site causes.
Causes: Instantaneous
power failure (open
phase), noises, or
else.
Troubleshooting 233
Troubleshooting by Indication on the Remote Control ESiEN09-06
Malfunction When the resistance value of thermistor becomes a value equivalent to open or short circuited
Decision status.
Conditions H Malfunction is not decided while the unit operation is continued.
"P1" will be displayed by pressing the inspection button.
When the amplitude of the ripple exceeding a certain value is detected for consecutive 4
minutes.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Imbalance
in supplied voltage is YES Open YES
in excess of 14 V (Y1). phase? Open phase
∗1 Normalize field cause.
NO NO
Fix power supply voltage
imbalance.
Part or wiring defect
Is the After turning the power supply
voltage OFF, check and repair the
imbalance applied to the YES
main circuit wiring or parts.
inverter in excess of 14 (1) Loose or disconnected
V (Y1)? ∗2 wiring between power
supply and inverter
NO <When voltage monitoring is possible:> (2) K2 contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
Using a device capable of noise filter
constant recording of power
supply voltage record
power supply voltage ∗1. Measure voltage at the X1M power supply
between 3 phases (L1 ~ L2, terminal block.
L2 ~ L3, L3~L1) for about ∗2. Measure voltage at terminals L1, L2 and L3 of
one continuous week. the diode module inside the inverter while the
compressor is running.
No abnormalities are
observed in the power Power supply voltage imbalance
supply, but the imbalance
in voltage recurs. measure
Replace the inverter PC board.
Explanation for users ∗In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results"and leave Be sure to explain to the user that
it up to him to improve the imbalance. there is a "power supply imbalance"
for which DAIKIN is not responsible.
(V2816)
234 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Detection
Malfunction When the resistance value of thermistor becomes a value equivalent to open or short circuited
Decision status.
Conditions H Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
End
Troubleshooting 235
Troubleshooting by Indication on the Remote Control ESiEN09-06
236 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of The faulty (or no) field setting after replacing PC board or faulty PC board combination is
Malfunction detected through communications with the inverter.
Detection
Malfunction Whether or not the field setting or the type of the PC board is correct through the communication
Decision date is judged.
Conditions
Supposed Faulty (or no) field setting after replacing main PC board
Causes Mismatching of type of PC board
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has the PC NO
board been replaced?
YES
When
replacing the main PC NO
board, were field settings Correct the field
properly made? settings.
YES
Is the type of PC NO
board correct? ∗ Replace with a correct
PC board.
YES
Reset, and then restart.
Troubleshooting 237
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Resistance
is normal when
measured with the
suction pipe thermistor NO
(R7T) and coil thermistor (R4T) Replace the thermistor.
disconnected from the
outdoor unit PC
board. ∗1
YES
Replace the outdoor unit PC
board (A1P).
(V2819)
238 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of The phase of each phase is detected by reverse phase detection circuit and right phase or
Malfunction reverse phase are judged.
Detection
Troubleshooting
There is
an open phase
at the power supply YES
terminal section (X1M) of Fix the open phase. Requires
the outdoor unit. inspection of field power supply
section.
NO
Operation is YES
normal if one place of power Reverse phase
supply line phase is Counter measure of the problem is
replaced. completed by phase replacement.
NO
Replace outdoor unit PC board
(A1P).
(V2820)
Troubleshooting 239
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction When the voltage aforementioned is not less than 780V or not more than 320V, or when the
Decision current-limiting voltage does not reach 200V or more or exceeds 740V.
Conditions
240 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Check
for power supply
voltage. Voltage NO
between phases: 380 to 415V On-site causes.
Phase voltage: 220 Make proper wire connections
to 240V without open phase, erroneous
connections, or erroneous order of
phases.
Power ON YES
Unbalanced power NO
supply? (Not more than 2%:
Phase voltage of not more On-site causes
than approx. Correct the unbalanced loads to
5V) eliminate the unbalanced state.
YES Unbalanced voltage will cause
extremely unbalanced current,
Disconnect the cable from the thus impairing the service life of or
compressor, and then check resulting in the malfunction of the
Power OFF the compressor for the equipment.
insulation resistance.
NO
The insulation YES
resistance is low (i.e., not more Replace the compressor.
than 100kΩ.)
NO
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
NO
The insulation YES
resistance is low (i.e., not more Replace the fan motor.
than 1MΩ.) Replace the fan driver.
NO
Check the inverter power
transistor.
Troubleshooting 241
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
A
242 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Malfunction Malfunction is decided when the unit starts operation without check operation.
Decision
Conditions
Troubleshooting
Has the
check operation NO
performed on Outdoor unit Press and hold BS4 on the
PC board? outdoor master PCB for 5
seconds or more, or turn ON the
YES local setting mode 2-3 to conduct
a check operation.
Performs the chech operation
again and completes the check
operation.
Troubleshooting 243
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of Microcomputer checks if transmission between AHU and outdoor units is normal.
Malfunction
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
Causes or wrong wiring
Outdoor unit power supply is OFF
System address doesn’t match
Defect of AHU PC board
Defect of outdoor unit PC board
244 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has
the AHU or
outdoor unit PC
board been replaced,
or has the AHU - outdoor or YES
Push and hold the RESET
outdoor - outdoor unit button on the master outdoor
transmission wiring unit PC Board for 5 seconds.
been modified? * The unit will not operate for
up to 12 minutes.
NO
All AHU Is AHU -
remote controls outdoor and YES
of the same refrigerant NO
outdoor - outdoor unit Replace the AHU PC Board
system display "U4." transmission wiring indicated by the malfunction
normal? code U4.
NO
YES Fix the AHU/outdoor or
outdoor/outdoor unit
Reset the power supply. transmission wiring.
The
Outdoor voltage between
unit PC board NO terminals L1 and N of the NO
microcomputer monitor outdoor unit PC board is Supply 220~240 V.
(HAP) blinks. 220~240 V ±10%.
YES
YES
The fuse on YES
the outdoor unit’s PC Replace the fuse.
board is burnt.
Operation
NO ready lamp (H2P) is
blinking.
YES
Lamp does YES
not go off for 12 minutes Push and hold the RESET
or more. button on the outdoor unit PC
board for 5 seconds.
NO
Is AHU -
outdoor and outdoor - NO
outdoor unit transmission Fix the AHU/outdoor or
wiring normal? outdoor/outdoor unit
transmission wiring.
YES
Disconnect
the outdoor -
outdoor unit transmission NO
wiring, and then check with a Replace the outdoor unit PC
single system whether Board (A1P).
or not it is normal.
YES
Mount the DIII NET extended
adapter.
(V2822)
Troubleshooting 245
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of In case of controlling with 2-remote control, check the system using microcomputer is signal
Malfunction transmission between AHU and remote control (main and sub) is normal.
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Operation
All indoor PC returns to normal
board microcomputer NO NO
when the power is turned Replace AHU PC board.
monitors blink. off momentarily.
YES YES
There is possibility of
Replace the remote control malfunction caused by noise.
Check the surrounding area
and turn on again.
YES
Normal Normal
NO
YES
Normal Normal
NO
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
(V2823)
246 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Method of Detect the malfunction signal of any other AHU within the system concerned.
Malfunction
Detection
Malfunction When the malfunction decision is made on any other AHU within the system concerned.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
"U9" has
been displayed for 2 NO
Re-diagnose by display after
minutes or more. passage of 2 minutes or more.
YES
The outdoor unit PC board
indicated by the malfunction code
U9 is normal.
Check for the AHU of other
system, and then conduct
troubleshooting by diagnosis
according to the Malfunction
Code Flowchart.
Troubleshooting 247
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of A difference occurs in data by the type of refrigerant between AHU and outdoor units.
Malfunction The number of AHUs is out of the allowable range.
Detection
Malfunction The malfunction decision is made as soon as either of the abnormalities aforementioned is
Decision detected.
Conditions
248 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the NO
malfunction code "UA" Normal
displayed? (It is assumed that the code is
displayed due to temporary
YES external cause (e.g. noises).
Is the
malfunction
code "UA" displayed YES
for all AHUs connected to
one and the same
system?
Is the
NO outdoor PC board YES
replaced to spare parts PC The setting after replacing spare
board? PC board has not been set yet.
Is the Please set as per page 109, 110.
type of
refrigerant for the NO
AHUs with "UA" displayed NO
Correct the combination of indoor
corresponding to that units with "UA" displayed.
for the outdoor
units? The
total of
AHUs displaying
YES "UA" and AHUs NO
connected to the same The number of AHUs that can be
refrigerant system is connected to a single outdoor unit
within connectable system is excess of allowable
number of range.
unit*
YES
Replace the AHU PC board.
Does the
refrigerant type of NO
AHU and outdoor unit Matches the refrigerant type of
match? AHU and outdoor unit.
YES
Is it a
multi outdoor unit NO
Replace the outdoor unit main PC
connection system? board.
YES
Is the
combination of master NO
Change to a correct combination.
unit and slave unit
correct?
YES
Replace the outdoor unit main PC
board.
(V2827)
∗ The number of AHUs that can be connected to a single outdoor unit system depends on the
model of outdoor unit.
Troubleshooting 249
Troubleshooting by Indication on the Remote Control ESiEN09-06
Method of On check operation, the number of AHUs in terms of transmission is not corresponding to that
Malfunction of AHUs that have made changes in temperature.
Detection
Malfunction The malfunction is determined as soon as the abnormality aforementioned is detected through
Decision checking the system for any erroneous connection of units on the check operation.
Conditions
Supposed Improper connection of transmission wiring between AHU-outdoor units and outdoor-
Causes outdoor units
Failure to execute check operation
Defect of AHU PC board
Stop valve is left in closed
Troubleshooting
YES
Is
Is the AHU-outdoor and
check operation NO YES
outdoor-outdoor unit Replace AHU PC board.
carried out? transmission wiring
normal?
YES
NO
Is AHU -
outdoor and NO
outdoor - outdoor unit After fixing incorrect wiring,
transmission wiring push and hold the RESET
normal? button on the master outdoor
unit PC board for 5 seconds.
YES * The unit will not run for up to
12 minutes.
Note: Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected AHUs in the fan
mode for at least an hour.
250 Troubleshooting
ESiEN09-06 Troubleshooting by Indication on the Remote Control
Malfunction The malfunction decision is made as soon as the abnormality aforementioned is detected.
Decision
Conditions
Supposed Improper connection of transmission wiring between AHU-outdoor units and outdoor-
Causes outdoor units
Defect of AHU PC board
Defect of outdoor unit PC board (A1P)
Troubleshooting 251
Troubleshooting by Indication on the Remote Control ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Does
Is a
electricity malfunction
being introduced occur even after 12
for the first time after YES NO
minutes elapses from the Normal
installation or after an AHU time when electricity is
or outdoor unit PC introduced to AHU
board has been and outdoor
replaced? units?
NO YES
Is AHU -
outdoor and NO
outdoor - outdoor unit After fixing incorrect wiring,
transmission wiring push and hold the RESET
normal? button on the master outdoor
unit PC board for 5 seconds.
YES * The unit will not run for up to
12 minutes.
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds
Does a
malfunction occur? NO
Normal
YES
Disconnect the
outdoor-outdoor
unit transmission wiring YES
to create the one-system Mount the DIII NET extension
status, and then check adapter.
whether or not
the system is
normal.
NO
Does a
"UH" malfunction NO
occur for all AHUs in the Replace AHU PC board.
system?
YES
Replace outdoor unit PC
board (A1P).
(V2831)
252 Troubleshooting
ESiEN09-06 Troubleshooting (OP: Unified ON/OFF Controller)
Malfunction
Decision
Conditions
Troubleshooting 253
Troubleshooting (OP: Unified ON/OFF Controller) ESiEN09-06
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is a
malfunction code YES
displayed on the remote Diagnose the cause with the
control? air conditioner’s failure
diagnosis manual.
NO
Has a
once connected YES
AHU been removed or its Reset power supply for all
address changed? optional controllers for
centralized control
simultaneously.
NO
Is the
power supply for
the AHU displaying a NO
malfunction turned Turn the power supply of the
on? AHU on.
YES
Is
transmission wiring YES
disconnected or wired Fix the wiring correctly.
incorrectly?
NO
Is Is the
transmission with all NO group No. of NO
AHUs malfunctioning? malfunctioning AHUs Set the group No.
set? correctly.
YES YES
YES
Is the
master controller’s YES
connector for setting master Connect the connector
controller disconnected. correctly.
NO
Replace the central PC board.
(V2841)
254 Troubleshooting
ESiEN09-06 Troubleshooting (OP: Unified ON/OFF Controller)
Red U
Black W
5 Gray GND
4 Pink Vcc
Measure the resistance
3 Orange W values between Vcc
and U,V,W, and GND
and U,V,W.
2 Blue V
1 Yellow U
Troubleshooting 255
Troubleshooting (OP: Unified ON/OFF Controller) ESiEN09-06
[In cooling] Is the suction air temperature not more than 43°C?
Short circuit
High suction air
temperature of Is the outdoor temperature not more than 43°C?
High suction
air outdoor unit High ambient temperature
temperature
of the High suction Short circuit Is the suction air temperature not more than 27°C?
condenser air temperature
of AHU High ambient temperature Is the indoor temperature not more than 27°C?
Is the connector properly connected?
Faulty suction air thermistor of AHU Are the thermistor resistance characteristics normal?
[In heating]
High suction air temperature of outdoor unit Is the outdoor temperature not more than 16°CWB?
Faulty outdoor temperature thermistor of outdoor unit Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation Dirty condenser Is the heat exchanger clogged? (In cooling)
in condensing
capacity
Mixing of non-condensable gas Is air or else mixed in the refrigerant system?
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EV1) is fully open.
*2: In heating, the AHU electronic expansion valve is used for “subcooled degree control”.
SDK04009
256 Troubleshooting
ESiEN09-06 Troubleshooting (OP: Unified ON/OFF Controller)
*1: For details of the compressor capacity control while in cooling, refer to “Compressor PI Control”.
*2: The “low pressure protection control” includes low pressure protection control and hot gas bypass control. For details, refer to “Low Pressure Protection Control”.
*3: In cooling, the AHU electronic expansion valve is used for “superheated degree control”.
*4: In heating, the outdoor unit electronic expansion valve (EV1) is used for “superheated degree control of outdoor unit heat exchanger”.
SDK04009
Troubleshooting 257
Troubleshooting (OP: Unified ON/OFF Controller) ESiEN09-06
258 Troubleshooting
ESiEN09-06
Part 9
Appendix
1. Piping Diagrams..................................................................................260
1.1 Outdoor Unit .........................................................................................260
2. Wiring Diagrams for Reference...........................................................263
2.1 Outdoor Unit .........................................................................................263
2.2 Field Wiring ..........................................................................................266
3. List of Electrical and Functional Parts .................................................267
3.1 Outdoor Unit .........................................................................................267
4. Option List ...........................................................................................269
5. Thermistor Resistance / Temperature Characteristics........................270
6. Pressure Sensor .................................................................................272
7. Method of Checking The Inverter’s Power Transistors and Diode
Modules...............................................................................................273
Appendix 259
Piping Diagrams ESiEN09-06
1. Piping Diagrams
1.1 Outdoor Unit
ERQ 125 A7W1B
Pressure Filter
regulating valve
(check valve type)
Electronic
expansion valve
Solenoid
SV
valve
Accumulator Capillary tube
Four way
valve
SENPH
High pressure
sensor
Check valve
Filter
Filter
separator
Capillary tube Filter
Oil
Solenoid High pressure
SV
HPS
valve Filter switch
Filter
COMPRESSOR
INV
Capillary tube
Solenoid
SV
valve
Low pressure SENPL
sensor
3D050782
260 Appendix
ESiEN09-06 Piping Diagrams
Check valve
Electronic Filter
expansion valve
Pressure
regulating valve
(check valve type)
Accumulator
Filter
SENPH
High pressure
sensor
Solenoid
SV
separator
High pressure
Oil
HPS
switch
Capillary tube
Filter
COMPRESSOR
Capillary tube
INV
Filter
Filter
valve sensor
SENPL
3D050783
Appendix 261
Piping Diagrams ESiEN09-06
Check valve
Filter
Accumulator
Filter
Solenoid
SV
valve
Check valve Check valve
Filter Filter
separator
separator
High pressure HPS HPS
High pressure
switch sensor
Oil
Oil
Capillary tube Filter
Filter
COMPRESSOR COMPRESSOR
Filter
Solenoid
SV
3D050784
262 Appendix
2.1
Appendix
ESiEN09-06
263
264
ERQ 200 A7W1B
Appendix
ESiEN09-06
Appendix
ESiEN09-06
265
266
2.2
POWER SUPPLY
L N
OUTDOOR UNIT
MAIN SWITCH
ERQ 125/200/250 A7W1B
Wiring Diagrams for Reference
Field Wiring
L N
F1F2
SWITCH
LN
FUSE
NOTES:
9. INSTALL THE MAIN SWITCH THAT CAN INTERRUPT ALL THE POWER SOURCES
L IN AN INTEGRATED MANNER BECAUSE THIS SYSTEM CONSISTS OF THE
N F2F1 EQUIPMENT UTILIZING THE MULTIPLE POWER SOURCES.
10. FOR DETAILED CONTROL BOX SIDE CONNECTION, SEE CONTROL BOX
MANUAL AND WIRING DIAGRAM.
CONTROL BOX
Appendix
ESiEN09-06
ESiEN09-06 List of Electrical and Functional Parts
Appendix 267
List of Electrical and Functional Parts ESiEN09-06
268 Appendix
ESiEN09-06 Option List
4. Option List
No Item
COOL/HEAT SELECTOR
FIXING BOX
CENTRAL DRAIN PAN KIT
Notes:
Appendix 269
Thermistor Resistance / Temperature Characteristics ESiEN09-06
Outdoor unit for fin thermistor R1T Outdoor unit For outdoor air R1T
For coil R2T
For suction pipe R4T
For Receiver gas pipe R5T
For Receiver outlet liquid pipe R6T
(kΩ)
TºC 0.0 T°C 0.0 0.5 T°C 0.0 0.5
-10 - -20 197.81 192.08 30 16.10 15.76
-8 - -19 186.53 181.16 31 15.43 15.10
-6 88.0 -18 175.97 170.94 32 14.79 14.48
-4 79.1 -17 166.07 161.36 33 14.18 13.88
-2 71.1 -16 156.80 152.38 34 13.59 13.31
0 64.1 -15 148.10 143.96 35 13.04 12.77
2 57.8
-14 139.94 136.05 36 12.51 12.25
4 52.3
6 47.3 -13 132.28 128.63 37 12.01 11.76
8 42.9 -12 125.09 121.66 38 11.52 11.29
10 38.9 -11 118.34 115.12 39 11.06 10.84
12 35.3 -10 111.99 108.96 40 10.63 10.41
14 32.1 -9 106.03 103.18 41 10.21 10.00
16 29.2 -8 100.41 97.73 42 9.81 9.61
18 26.6 -7 95.14 92.61 43 9.42 9.24
20 24.3 -6 90.17 87.79 44 9.06 8.88
22 22.2 -5 85.49 83.25 45 8.71 8.54
24 20.3 -4 81.08 78.97 46 8.37 8.21
26 18.5
-3 76.93 74.94 47 8.05 7.90
28 17.0
-2 73.01 71.14 48 7.75 7.60
30 15.6
-1 69.32 67.56 49 7.46 7.31
32 14.2
34 13.1 0 65.84 64.17 50 7.18 7.04
36 12.0 1 62.54 60.96 51 6.91 6.78
38 11.1 2 59.43 57.94 52 6.65 6.53
40 10.3 3 56.49 55.08 53 6.41 6.53
42 9.5 4 53.71 52.38 54 6.65 6.53
44 8.8 5 51.09 49.83 55 6.41 6.53
46 8.2 6 48.61 47.42 56 6.18 6.06
48 7.6 7 46.26 45.14 57 5.95 5.84
50 7.0 8 44.05 42.98 58 5.74 5.43
52 6.7 9 41.95 40.94 59 5.14 5.05
54 6.0
10 39.96 39.01 60 4.96 4.87
56 5.5
58 5.2 11 38.08 37.18 61 4.79 4.70
60 4.79 12 36.30 35.45 62 4.62 4.54
62 4.46 13 34.62 33.81 63 4.46 4.38
64 4.15 14 33.02 32.25 64 4.30 4.23
66 3.87 15 31.50 30.77 65 4.16 4.08
68 3.61 16 30.06 29.37 66 4.01 3.94
70 3.37 17 28.70 28.05 67 3.88 3.81
72 3.15 18 27.41 26.78 68 3.75 3.68
74 2.94 19 26.18 25.59 69 3.62 3.56
76 2.75 20 25.01 24.45 70 3.50 3.44
78 2.51
21 23.91 23.37 71 3.38 3.32
80 2.41
22 22.85 22.35 72 3.27 3.21
82 2.26
23 21.85 21.37 73 3.16 3.11
84 2.12
86 1.99 24 20.90 20.45 74 3.06 3.01
88 1.87 25 20.00 19.56 75 2.96 2.91
90 1.76 26 19.14 18.73 76 2.86 2.82
92 1.65 27 18.32 17.93 77 2.77 2.72
94 1.55 28 17.54 17.17 78 2.68 2.64
96 1.46 29 16.80 16.45 79 2.60 2.55
98 1.38 30 16.10 15.76 80 2.51 2.47
270 Appendix
ESiEN09-06 Thermistor Resistance / Temperature Characteristics
Outdoor Unit
Thermistors for
Discharge Pipe
(R3T, R31∼ 33T)
(kΩ)
T°C 0.0 0.5 T°C 0.0 0.5 T°C 0.0 0.5
0 640.44 624.65 50 72.32 70.96 100 13.35 13.15
1 609.31 594.43 51 69.64 68.34 101 12.95 12.76
2 579.96 565.78 52 67.06 65.82 102 12.57 12.38
3 552.00 538.63 53 64.60 63.41 103 12.20 12.01
4 525.63 512.97 54 62.24 61.09 104 11.84 11.66
5 500.66 488.67 55 59.97 58.87 105 11.49 11.32
6 477.01 465.65 56 57.80 56.75 106 11.15 10.99
7 454.60 443.84 57 55.72 54.70 107 10.83 10.67
8 433.37 423.17 58 53.72 52.84 108 10.52 10.36
9 413.24 403.57 59 51.98 50.96 109 10.21 10.06
10 394.16 384.98 60 49.96 49.06 110 9.92 9.78
11 376.05 367.35 61 48.19 47.33 111 9.64 9.50
12 358.88 350.62 62 46.49 45.67 112 9.36 9.23
13 342.58 334.74 63 44.86 44.07 113 9.10 8.97
14 327.10 319.66 64 43.30 42.54 114 8.84 8.71
15 312.41 305.33 65 41.79 41.06 115 8.59 8.47
16 298.45 291.73 66 40.35 39.65 116 8.35 8.23
17 285.18 278.80 67 38.96 38.29 117 8.12 8.01
18 272.58 266.51 68 37.63 36.98 118 7.89 7.78
19 260.60 254.72 69 36.34 35.72 119 7.68 7.57
20 249.00 243.61 70 35.11 34.51 120 7.47 7.36
21 238.36 233.14 71 33.92 33.35 121 7.26 7.16
22 228.05 223.08 72 32.78 32.23 122 7.06 6.97
23 218.24 213.51 73 31.69 31.15 123 6.87 6.78
24 208.90 204.39 74 30.63 30.12 124 6.69 6.59
25 200.00 195.71 75 29.61 29.12 125 6.51 6.42
26 191.53 187.44 76 28.64 28.16 126 6.33 6.25
27 183.46 179.57 77 27.69 27.24 127 6.16 6.08
28 175.77 172.06 78 26.79 26.35 128 6.00 5.92
29 168.44 164.90 79 25.91 25.49 129 5.84 5.76
30 161.45 158.08 80 25.07 24.66 130 5.69 5.61
31 154.79 151.57 81 24.26 23.87 131 5.54 5.46
32 148.43 145.37 82 23.48 23.10 132 5.39 5.32
33 142.37 139.44 83 22.73 22.36 133 5.25 5.18
34 136.59 133.79 84 22.01 21.65 134 5.12 5.05
35 131.06 128.39 85 21.31 20.97 135 4.98 4.92
36 125.79 123.24 86 20.63 20.31 136 4.86 4.79
37 120.76 118.32 87 19.98 19.67 137 4.73 4.67
38 115.95 113.62 88 19.36 19.05 138 4.61 4.55
39 111.35 109.13 89 18.75 18.46 139 4.49 4.44
40 106.96 104.84 90 18.17 17.89 140 4.38 4.32
41 102.76 100.73 91 17.61 17.34 141 4.27 4.22
42 98.75 96.81 92 17.07 16.80 142 4.16 4.11
43 94.92 93.06 93 16.54 16.29 143 4.06 4.01
44 91.25 89.47 94 16.04 15.79 144 3.96 3.91
45 87.74 86.04 95 15.55 15.31 145 3.86 3.81
46 84.38 82.75 96 15.08 14.85 146 3.76 3.72
47 81.16 79.61 97 14.62 14.40 147 3.67 3.62
48 78.09 76.60 98 14.18 13.97 148 3.58 3.54
49 75.14 73.71 99 13.76 13.55 149 3.49 3.45
50 72.32 70.96 100 13.35 13.15 150 3.41 3.37
Appendix 271
Pressure Sensor ESiEN09-06
6. Pressure Sensor
PH = 1.38V-0.69 PH : Detected Pressure [High Side] MP
PL = 0.57V-0.28 PL : Detected Pressure [Low Side] MPa
Detected Pressure PH : High pressure (MPa) VH : Output Voltage [High Side] VDC
VL : Low pressure (MPa) VL : Output Voltage [Low Side] VDC
V : Voltage (V)
272 Appendix
ESiEN09-06 Method of Checking The Inverter’s Power Transistors and Diode Modules
Inverter PC board
J1
J2
J3
P1 P3 N3 U V W
Electronic circuit
DM P1 P2 P3 IGBT
X10A K2
J1
L1
J2
L2
L3 J3
N3
U V W
X11A
(V2895)
According to the checking aforementioned, it is probed that the malfunction results from the
faulty inverter.The following section describes supposed causes of the faulty inverter.
• Faulty compressor (ground leakage)
• Faulty fan motor (ground leakage)
• Entry of conductive foreign particles
• Abnormal voltage (e.g. overvoltage, surge (thunder), or unbalanced voltage)
In order to replace the faulty inverter, be sure to check for the points aforementioned.
Appendix 273
Method of Checking The Inverter’s Power Transistors and Diode Modules ESiEN09-06
274 Appendix
ESiEN09-06
Part 10
Precautions for New
Refrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A) .........................................276
1.1 Outline ..................................................................................................276
1.2 Refrigerant Cylinders............................................................................278
1.3 Service Tools........................................................................................279
Temperature Steam pressure Density Specific heat at constant Specific enthalpy Specific entropy
(°C) (kPa) (kg/m3 ) pressure (kJ/kgK) (kJ/kg) (kJ/KgK)
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
Cylinder
Siphon tube
Refrigerant can be charged in liquid state with cylinder in
upright position.
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be sure to follow the regulations.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool and dark place
in the same way as any other high-pressure gases.
It should also be noted that high-pressure vessels are equipped with safety devices that
releases gas when the ambient temperature reaches more than a certain level (fusible plug
melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
Tool compatibility
Compatibility
Tool HFC HCFC Reasons for change
R-410A R-407C R-22
•Do not use the same tools for R-22 and
Gauge manifold R-410A.
5
Charge hose •Thread specification differs for
R-410A and R-407C.
Charging cylinder 5 { •Weighting instrument used for HFCs.
Gas detector { 5 •The same tool can be used for HFCs.
Vacuum pump •To use existing pump for HFCs,
(pump with reverse flow { vacuum pump adapter must be
preventive function) installed.
Weighting instrument {
•Seal material is different between
Charge mouthpiece 5 R-22 and HFCs.
•Thread specification is different
between R-410A and others.
Flaring tool (Clutch type) { •For R-410A, flare gauge is necessary.
Torque wrench { •Torque-up for 1/2 and 5/8
Pipe cutter {
Pipe expander {
Pipe bender {
Refrigerant piping See the chart below. •Only φ19.1 is changed to 1/2H material
while the previous material is "O".
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
* O: Soft (Annealed)
H: Hard (Drawn)
1. Flaring tool
Flare gauge
Specifications
• Dimension A
Unit:mm
Nominal size
Tube O.D. A +0
-0.4
Differences
• Change of dimension A
Dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
2. Torque wrench
Specifications
• Dimension B Unit:mm
Nominal size Class-1 Class-2 Previous
1/2 24 26 24
5/8 27 29 27
No change in tightening torque
No change in pipes of other sizes
Differences
• Change of dimension B
Only 1/2", 5/8" are extended
Dimension B
Specifications
• Discharge speed z Maximum degree of vacuum
50 l/min (50Hz) Select a vacuum pump which is able to keep
60 l/min (60Hz) the vacuum degree of the system in excess of
• Suction port UNF7/16-20(1/4 Flare) –100.7 kPa (5 torr – 755 mmHg).
UNF1/2-20(5/16 Flare) with adapter
Differences
• Equipped with function to prevent reverse oil flow
• Previous vacuum pump can be used by installing adapter.
4. Leak tester
Specifications
• Hydrogen detecting type, etc.
• Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
• Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
Specifications
• Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
• Offers high rust resistance and stability over long period of time.
Differences
• Can be used for R-410A and R-22 units.
Specifications
• High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
• Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
• 1/4" → 5/16" (2min → 2.5min)
• No oil is used in pressure test of gauges.
→ For prevention of contamination
• Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
• Change in pressure
• Change in service port diameter
Specifications
• Working pressure 5.08 MPa (51.8 kg/cm2)
• Rupture pressure 25.4 MPa (259 kg/cm2)
• Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
• Pressure proof hose
• Change in service port diameter
• Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
• Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
• The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
Specifications
• High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
• Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
• A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
• Measurement is based on weight to prevent change of mixing ratio during charging.
Specifications
• For R-410A, 1/4"→ 5/16" (2min → 2.5min)
• Material is changed from CR to H-NBR.
Differences
• Change of thread specification on hose connection side (For the R-410A use)
• Change of sealer material for the HFCs use.
Index
A Setting by pushbutton switches .................... 118
A0 .........................................................................185 Field Setting from Remote Controller .................. 106
A1 .........................................................................186 Freeze Prevention ................................................. 46
A3 .........................................................................187 Functional Parts Layout ........................................ 18
A6 .........................................................................189 RXYQ10P, 12P ............................................... 20
A9 .........................................................................190 RXYQ5P ......................................................... 18
Abnormal Discharge Pipe Temperature ...............211 RXYQ8P ......................................................... 19
Abnormal Outdoor Fan Motor Signal ...................213
About Refrigerant R-410A ....................................276 H
Actuation of High Pressure Switch .......................199 H7 ........................................................................ 213
Actuation of Low Pressure Sensor .......................201 H9 ........................................................................ 214
AF .........................................................................192 Heating Operation Prohibition ............................... 43
AJ .........................................................................193 High Pressure Protection Control .......................... 36
B I
Basic Control ..........................................................24 Improper Combination of AHU and Outdoor Units,
AHUs and Remote Controller ....................... 248
C Injection Control (only for RXYQ5P) ...................... 40
C4 .........................................................................194 Inverter Compressor Abnormal ........................... 225
C5 .........................................................................195 Inverter Compressor Motor Lock ......................... 203
C9 .........................................................................196 Inverter Current Abnormal ................................... 227
Check No. 2 .........................................................255 Inverter Over-Ripple Protection ........................... 234
Check Operation not Executed ............................243 Inverter Protection Control .................................... 39
CJ .........................................................................197 Inverter Start up Error ......................................... 229
Compressor Motor Overcurrent/Lock ...................205
Compressor PI Control ...........................................25 J
Contents of Control Modes ..................................113 J2 ........................................................................ 215
Cool / Heat Mode Switching .................................126 J3 ........................................................................ 216
Current Sensor Malfunction .................................215 J5 ........................................................................ 217
J6 ........................................................................ 218
D J7 ........................................................................ 219
Defrosting Operation ..............................................32 J9 ........................................................................ 220
Demand Operation .................................................43 JA ........................................................................ 221
Discharge Pipe Protection Control .........................38 JC ........................................................................ 222
Display “Under Centralized Control” Blinks (Repeats
Single Blink) ..................................................255 L
Drain Level above Limit ........................................192 L4 ........................................................................ 223
L5 ........................................................................ 225
E L8 ........................................................................ 227
E1 .........................................................................198 L9 ........................................................................ 229
E3 .........................................................................199 LC ........................................................................ 231
E4 .........................................................................201 List of Electrical and Functional Parts ................. 267
E5 .........................................................................203 Outdoor Unit ................................................. 267
E6 .........................................................................205 Low Pressure Drop Due to Refrigerant Shortage or
E7 .........................................................................206 Electronic Expansion Valve Failure .............. 238
E9 .........................................................................209 Low Pressure Protection Control .......................... 37
Emergency Operation ............................................41
Error of External Protection Device ......................185 M
Malfunction code indication by outdoor unit PC board
F ...................................................................... 181
F3 .........................................................................211 Malfunction of Capacity Determination Device .... 193
F6 .........................................................................212 Malfunction of Discharge Pipe Thermistor (R3,
Fan Motor (M1F) Lock, Overload .........................189 R31~33T) ..................................................... 216
Faulty Field Setting after Replacing Main PC Board or Malfunction of Drain Level Control System (S1L) 187
Faulty Combination of PC Board ..................237 Malfunction of High Pressure Sensor .................. 221
Field Setting .........................................................106 Malfunction of Inverter Radiating Fin Temperature
Field Setting from Outdoor Unit ............................114 Rise .............................................................. 223
List of Field Setting Items ..............................114 Malfunction of Inverter Radiating Fin Temperature
Index i
ESiEN09-06
P
P1 .........................................................................234
P4 .........................................................................235
PC Board Defect ..........................................186, 198
PJ .........................................................................237
Power Supply Insufficient or Instantaneous Failure ...
240
Precautions for New Refrigerant (R-410A) ..........276
Pressure Sensor ..................................................272
Procedure and Outline ...........................................91
Protection Control ..................................................36
Pump-down Residual Operation ............................33
R
Refrigerant Circuit ..................................................12
RXYQ10P, 12P ................................................16
RXYQ5P ..........................................................12
RXYQ8P ..........................................................14
ii Index
ESiEN09-06
L R
Low Pressure Drop Due to Refrigerant Shortage or Refrigerant Overcharged ..................................... 212
Electronic Expansion Valve Failure ..............238 Remote Controller Self-Diagnosis Function ........ 178
Remote Controller Service Mode ........................ 176
M Reverse Phase, Open Phase .............................. 239
Malfunction of Capacity Determination Device ....193 RXYQ10P, 12P ..................................................... 20
Malfunction of Discharge Pipe Thermistor (R3, RXYQ5P ................................................................ 18
R31~33T) ......................................................216 RXYQ8P ................................................................ 19
Malfunction of Drain Level Control System (S1L) 187
Malfunction of High Pressure Sensor ...................221 S
Malfunction of Inverter Radiating Fin Temperature Self-diagnosis by Wired Remote Controller ........ 175
Rise ...............................................................223 Setting of Low Noise Operation and Demand
Malfunction of Inverter Radiating Fin Temperature Operation ..................................................... 128
Rise Sensor ..................................................235 Image of operation in the case of A ...... 129, 131
Malfunction of Liquid Pipe Thermistor (R6T) ........219 Image of operation in the case of A and B ... 129,
131
Image of operation in the case of B .......129, 131
Simplified Remote Controller ...............................107
BRC2A51, BRC2C51 ....................................107
System is not Set yet ...........................................250
T
Test Operation .......................................................90
Thermostat Sensor in Remote Controller ...............44
Cooling ............................................................44
Heating ............................................................45
Torque wrench .....................................................281
Troubleshooting (OP: Unified ON/OFF Controller) ....
253
Troubleshooting by Remote Controller ................174
W
Weigher for refrigerant charge .............................284
Wired Remote Controller ......................................106
Wiring Diagrams for Reference ............................263
Field Wiring ....................................................266
Outdoor Unit ..................................................263
Naamloze Vennootschap
Zandvoordestraat 300 Daikin Europe N.V. is participating in the EUROVENT
Certification Programme. Products are as listed in the
B-8400 Oostende - Belgium EUROVENT Directory of Certified Products.
www.daikin.eu
BE 0412 120 336
RPR Oostende
ÉESiEN09-06BËÍ