REB670 - Product Guide
REB670 - Product Guide
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no
responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
© Copyright 2017 ABB. All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2 Issued: November 2018
Revision: G
F 2018-11 2.2.2 Technical data updated for PSM and EF4PTOC. Corrections/
enhancements made to OC4PTOC, TRPTTR, UV2PTUV and OV2PTOV.
Case dimensions updated.
ABB 3
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Ordering of VT inputs inside of the busbar protection All CT inputs are provided with a restraint feature. The
IED will allow integration of voltage related functionality operation is based on the well-proven RADSS percentage
like under-voltage release, residual over-voltage, power restraint stabilization principle, with an extra
functions, metering and voltage recording during the stabilization feature to stabilize for very heavy CT
faults. However attention shall be given to the fact that saturation. Stability for external faults is guaranteed if a
inclusion of VT inputs will reduce number of available CT CT is not saturated for at least two milliseconds during
inputs (in total 24 analogue inputs are the product each power system cycle.
limit). Consequently when VT inputs are ordered the
busbar protection IED will be applicable for buses with a The advanced open CT detection algorithm detects
fewer number of bays. Practically the number of instantly the open CT secondary circuits and prevents
available CT inputs will limit the size of the station differential protection operation without any need for
which can be protected. additional check zone.
The IED has very low requirements on the main current Differential protection zones in the IED include a
transformers (that is, CTs) and no interposing current sensitive operational level. This sensitive operational
transformers are necessary. For all applications, it is level is designed to be able to detect internal busbar
possible to include and mix main CTs with 1A and 5A earth faults in low impedance earthed power systems
rated secondary current within the same protection (that is, power systems where the earth-fault current is
zone. Typically, CTs with up to 10:1 ratio difference can limited to a certain level, typically between 300A and
be used within the same differential protection zone. 2000A primary by a neutral point reactor or resistor).
Adjustment for different main CT ratios is achieved Alternatively this sensitive level can be used when high
numerically by a parameter setting. sensitivity is required from busbar differential
protection (that is, energizing of the bus via long line).
The numerical, low-impedance differential protection
function is designed for fast and selective protection for Overall operating characteristic of the differential
faults within protected zone. All connected CT inputs are function in the IED is shown in figure 1.
4 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Sensitive
differential
protection
Id [Primary Amps]
Operate
region
Differential protection
operation characteristic
DiffOperLevel
SensOperLevel SensIinBlock
s=0.53
Integrated overall check zone feature, independent from • Correct marshaling of backup-trip commands from
any disconnector position, is available. It can be used in internally integrated or external circuit breaker failure
double or triple busbar stations to secure stability of protections to all surrounding circuit breakers
the busbar differential protection in case of entirely • Easy incorporation of bus-section and/or bus-coupler
wrong status indication of busbar disconnector in any bays (that is, tie-breakers) with one or two sets of CTs
of the feeder bays. into the protection scheme
• Disconnector and/or circuit breaker status
Flexible, software based dynamic Zone Selection supervision
enables easy and fast adaptation to the most common
substation arrangements such as single busbar with or Advanced Zone Selection logic accompanied by
without transfer bus, double busbar with or without optionally available end-fault and/or circuit breaker
transfer bus, triple busbar with or without transfer bus, failure protections ensure minimum possible tripping
one-and-a-half breaker stations, double busbar-double time and selectivity for faults within the blind spot or
breaker stations, ring busbars, and so on. The software the end zone between bay CT and bay circuit breaker.
based dynamic Zone Selections ensures: Therefore the IED offers best possible coverage for such
faults in feeder and bus-section/bus-coupler bays.
• Dynamic linking of measured CT currents to the
appropriate differential protection zone as required Optionally available circuit breaker failure protection,
by substation topology one for every CT input into the IED, offers secure local
• Efficient merging of the two or more differential back-up protection for the circuit breakers in the
zones when required by substation topology (that is station.
load-transfer)
• Easy zone merging initiated by closing of bus- Optionally available four-stage, non-directional
sectionalizing disconnectors overcurrent protections, one for every CT input into the
• Selective operation of busbar differential protection IED, provide remote backup functionality for connected
ensures tripping only of circuit breakers connected to feeders and remote-end stations.
the faulty zone
Optionally available voltage and frequency protection
functions enable to include voltage release criterion for
busbar protection or to integrate independent over-,
under-voltage protection for the bus in the busbar
protection IED.
ABB 5
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
capacitor bank protection functions open possibilities There are five pre-configured variants of REB670. They
to integrate protection of shunt reactors and shunt are describe in the following Table:
capacitor banks into the busbar protection IED.
Table 2. REB670 pre-configured packages
It is normal practice to have just one busbar protection
12 AI max 3*IO 24 AI max 11*IO
IED per busbar. Nevertheless some utilities do apply two Cards 1/2 of 19" Cards full 19" rack
independent busbar protection IEDs per zone of rack
protection. This IED fits both solutions.
3Ph, 4 bays, 2 zone Used for small, Not applicable
A simplified bus differential protection for multi-phase BFP & OC fixed zones like T
protection optional! protection, meshed
faults and earth faults can be obtained by using a single,
corner, H-scheme,
one-phase IED with external auxiliary summation current
ring bus etc.
transformers. REB670–A20
The IED can be used in applications with IEC/UCA 3Ph, 8 bays, 2 zone Not applicable Used for
61850-9-2LE process bus with up to eight merging units BFP & OC substations/zones
(MU) depending on the other functionality included in protection optional! with up to 8 CT
inputs.
the IED. Each MU has eight analog channels, four
REB670–A31
currents and four voltages. Conventional and Merging
Unit channels can be mixed freely in the application. 1Ph, 12 bays, 2 zone Used for substation Used for substation
(three IEDs with up to 12 CT with up to 12 CT
Forcing of binary inputs and outputs is a convenient way required) BFP & OC inputs. Only three inputs. Possible to
to test wiring in substations as well as testing protection optional! IO cards available extend up to 24 CT
configuration logic in the IEDs. Basically it means that all No extension inputs. Optional
possibilities to 24 LDCMs can be used
binary inputs and outputs on the IED I/O modules (BOM,
CT inputs! Good to share binary IO.
BIM, IOM & SOM) can be forced to arbitrary values.
solution for REB670–B21
stations with fixed
Central Account Management is an authentication
zones (i.e. one-and-
infrastructure that offers a secure solution for enforcing half breaker
access control to IEDs and other systems within a station).
substation. This incorporates management of user REB670–B20
accounts, roles and certificates and the distribution of
1Ph, 24 bays, 2 zone Not applicable Used for substation
such, a procedure completely transparent to the user.
(three IEDs with up to 24 CT
required) BFP & OC inputs. Optional
The Flexible Product Naming allows the customer to use
protection optional! LDCMs can be used
an IED-vendor independent IEC 61850 model of the IED. to share binary IO.
This customer model will be exposed in all IEC 61850 REB670–B31
communication, but all other aspects of the IED will
remain unchanged (e.g., names on the local HMI and Available ACT configurations for pre-configured
names in the tools). This offers significant flexibility to REB670 SEMOD129275-87 v6
adapt the IED to the customers' system and standard Three configurations have been made available for pre-
solution. configured REB670 IED with two zones. Product variant
M11788-3 v10 with six zone is available as customized product only. It
Optional apparatus control for up to 30 objects can
shall be noted that all three configurations include the
provide a facility to draw simplified single line diagram
following features:
(SLD) of the station on the local HMI.
• fully configured for the total available number of bays
Description of pre-configured packages in each REB670 variant
• facility to take any bay out of service via the local HMI
or externally via binary input
• facility to block any of the two zones via the local HMI
or externally via binary input
• facility to block all bay trips via the local HMI or
externally via binary input, but leaving all other
function in service (that is BBP Zones, BFP and OCP
where applicable)
6 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
• facility to externally initiate built-in disturbance protection and overcurrent protection PH4SPTOC can be
recorder ordered together with this configuration, but they will
• facility to connect external breaker failure backup trip not be pre-configured. Thus these optional functions
signal from every bay shall be configured by the end user.
• facility to connect external bay trip signal
Configuration X03 SEMOD129275-124 v5
This configuration includes BBP with breaker failure
Configuration X01 SEMOD129275-116 v6 protection CCRBRF, end fault protection and
This configuration includes only busbar protection for overcurrent protection PH4SPTOC for double busbar-
simple stations layouts (in other words, one-and-a-half single breaker stations, where Zone Selection is done by
breaker, double breaker or single breaker stations). using a and b auxiliary contacts from every
Additionally it can be used for double busbar-single disconnectors and/or circuit breakers. Thus full
breaker stations where disconnector replica is done by disconnector/breaker supervision is available. This
using only b auxiliary contact from every disconnector configuration is available for only three REB670 variants
and/or circuit breakers. As a consequence no (that is A31, B21 and B31).
disconnector/breaker supervision will be available. It is
as well possible to adapt this configuration by the signal In order to use X03 configuration, optional breaker
matrix tool to be used as direct replacement of RED521 failure and overcurrent functions must be ordered.
terminals. This configuration is available for all five
REB670 variants (that is A20, A31, B20, B21 & B31). It shall Application examples of REB670 SEMOD121024-4 v6
be noted that optional functions breaker failure Examples of typical station layouts, which can be
protection CCRBRF, end fault protection and protected with REB670 are given below:
overcurrent protection PH4SPTOC can be ordered
together with this configuration, but they will not be
pre-configured. Thus these optional functions shall be
configured by the end user.
configuration is available for only three REB670 variants Figure 2. Example of T-connection
Version of REB670 pre-configured IED Numbers of feeders per busbar Number of REB670 IEDs required for the
scheme
ABB 7
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
QB1
ZA ZB
IEC11000238-1-en.vsd
IEC11000238 V1 EN-US
Table 4. Typical solutions for stations with two busbar sections connected with bus-sectionalizing disconnector
Version of REB670 pre-configured IED Total Number of feeders in both busbar Number of REB670 IEDs required for the
sections scheme
ZA
ZB
QB1 QB7 QB1 QB7 QB1 QB7 QB1 QB7 QB1 QB7 QB1 QB7
xx06000013.vsd
IEC06000013 V1 EN-US
ZA
ZB
QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2
BI1
IEC11000239-1-en.vsd
IEC11000239 V1 EN-US
8 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Version of REB670 pre-configured IED Number of feeders in the station Number of REB670 IED required for the
(excluding bus-coupler bay) scheme
ZA
ZB
QB1 QB2 QB7 QB1 QB2 QB7 QB1 QB2 QB7 QB20 QB1 QB2 QB7 QB1 QB2 QB7
xx06000015.vsd
IEC06000015 V1 EN-US
QA1
BI1
ZA1 ZA2
ZB1 ZB2
QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2
BI1 BI1 QA1 BI1
QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1 QA1
xx06000016.vsd
IEC06000016 V1 EN-US
Figure 7. Example of double bus-single breaker station with two bus-section and two bus-coupler breakers (typical GIS station layout)
Version of REB670 pre-configured IED Number of feeders on each side of the Number of REB670 IEDs required for the
station (excluding bus-coupler & bus- scheme
section bays)
ABB 9
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
ZA
ZB
IEC11000240-1-en.vsd
IEC11000240 V1 EN-US
Table 7. Typical solutions for one-and-half circuit breaker stations when CBF for middle breaker is not required
Version of REB670 pre-configured IED Number of diameters in the station Number of REB670 IEDs required for the
scheme
ZA
ZB
QA1 QA2 QA1 QA2 QA1 QA2 QA1 QA2 QA1 QA2
BI1 BI2 BI1 BI2 BI1 BI2 BI1 BI2 BI1 BI2
xx06000018.vsd
IEC06000018 V1 EN-US
Version of REB670 pre-configured IED Numbers of feeders per station Number of REB670 IEDs required for the
scheme
10 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
BI8 BI5
Q 5
B8 QB11 BI1 QA1 QB12 B
Q
ZA1 ZA2
QB41 QB21
QA4 QA2
BI4 BI2
QB42 QB22
QB31 BI3 QA3 QB32
ZB1 B
7 Q
B
6
ZB2
Q
BI7 BI6
xx06000019.vsd
IEC06000019 V1 EN-US
Note that customized REB670 is delivered without any configuration. Thus the complete IED engineering shall be done
by the customer or its system integrator. In order to secure proper operation of the busbar protection, it is strictly
recommended to always start engineering work from the PCM600 project for the pre-configured REB670 which is the
closest to the actual application. Then, necessary modifications shall be applied in order to adopt the customized IED
configuration to suite the actual station layout. The PCM600 project for the pre-configured REB670 IEDs is available in
the Connectivity Package USB flash drive. For the product covering up to six busbar zones, configuration examples are
provided in the REB670 Application Manual 1MRK 505 370-UEN.
GUID-79B8BC84-4AAB-44E7-86CD-FF63098B009D v3
The basic delivery includes one binary input module and the customer, since these are specific to the system,
one binary output module, which is sufficient for the object or application. Optional functions and optional
default configured I/O to trip and close circuit breaker. I/O ordered will not be configured at delivery. It should
All IEDs can be reconfigured with the help of the be noted that the standard only includes one binary
application configuration tool in PCM600. The IED can input and one binary output module and only the key
be adapted to special applications and special logic can functions such as tripping are connected to the outputs
be developed, such as logic for automatic opening of in the signal matrix tool. The required total I/O must be
disconnectors and closing of ring bays, automatic load calculated and specified at ordering.
transfer from one busbar to the other, and so on.
The configurations are as far as found necessary
The basic IED configuration is provided with the signal provided with application comments to explain why the
matrix, single line diagram and the application signals have been connected in the special way. On
configuration prepared for the functions included in the request, ABB is available to support the re-configuration
product by default. All parameters should be verified by work, either directly or to do the design checking.
ABB 11
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
Differential protection
12 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
Current protection
PH4SPTOC 51 Four step single phase overcurrent 0-24 12- 12- 24-
protection C08 C08 C09
CCSRBRF 50BF Breaker failure protection, single 0-24 12-C12 12-C12 24-C13
phase version
Voltage protection
Frequency protection
Multipurpose protection
1) 67 requires voltage
2) 67N requires voltage
ABB 13
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
Control
DPGAPC Generic 32 32 32 32 32 32
communication
function for Double
Point indication
14 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
Secondary
system
supervision
Logic
AND, GATE, INV, Basic configurable 40-496 40-49 40-49 40-49 40-49 40-49
LLD, OR, logic blocks (see 6 6 6 6 6
PULSETIMER, Table 10)
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
ABB 15
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
16 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Table 10. Total number of instances for basic configurable logic blocks
AND 328
GATE 64
INV 492
LLD 40
OR 496
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 108
XOR 40
SCILO Interlocking 30
BB_ES 6
A1A2_BS 4
A1A2_DC 6
ABC_BC 2
BH_CONN 2
BH_LINE_A 2
BH_LINE_B 2
DB_BUS_A 3
DB_BUS_B 3
DB_LINE 3
ABC_LINE 6
AB_TRAFO 4
RESIN1 1
RESIN2 59
ABB 17
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Table 12. Total number of instances for configurable logic blocks Q/T
ANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40
AND 220
GATE 49
INV 220
LLD 49
OR 220
PULSETIMER 89
RSMEMORY 40
SLGAPC 74
SRMEMORY 130
TIMERSET 113
VSGAPC 120
XOR 89
18 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
Monitoring
CMMXU Current 10 10 10 10 10 10
measurement
VMMXU Voltage 6 6 6 6 6 6
measurement
phase-phase
VNMMXU Voltage 6 6 6 6 6 6
measurement
phase-earth
SPGAPC Generic 96 96 96 96 96 96
communication
function for Single
Point indication
SP16GAPC Generic 16 16 16 16 16 16
communication
function for Single
Point indication 16
inputs
MVGAPC Generic 24 24 24 24 24 24
communication
function for
measured values
SSIMG 63 Insulation 21 21 21 21 21 21
supervision for gas
medium
SSIML 71 Insulation 3 3 3 3 3 3
supervision for
liquid medium
ABB 19
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
CHMMHAI ITHD Current harmonic 0-3 0-3 0-3 0-3 0-3 0-3
monitoring, 3 phase
VHMMHAI VTHD Voltage harmonic 0-3 0-3 0-3 0-3 0-3 0-3
monitoring, 3 phase
Metering
20 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
Station communication
MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10 60/10 60/10
MULTICMDSND
IEC 61850-9-2 Process bus 0-1 1-P30 1-P30 1-P30 1-P30 1-P30
communication, 8 merging units
PRP IEC 62439-3 Parallel redundancy protocol 0-1 1-P23 1-P23 1-P23 1-P23 1-P23
ABB 21
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
REB670 (A20)
REB670 (B20)
REB670 (A31)
REB670 (B31)
REB670 (B21)
REB670
(Customized)
HSR IEC 62439-3 High-availability seamless 0-1 1-P24 1-P24 1-P24 1-P24 1-P24
redundancy
Remote communication
BinSignRec1_1 Binary signal transfer receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6
BinSignRec1_2
BinSignReceive2
22 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
ABB 23
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
24 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
external multi-phase faults, which can cause CT second monitoring feature operates immediately when
saturation. Operating characteristic of sensitive the busbar through-going current is bigger than the
differential characteristics is shown in figure 1. user settable level. Both of these monitoring features
are phase segregated and they give out binary signals,
Check zone SEMOD120957-5 v5 which can be either used to trigger disturbance recorder
For busbar protection in stations with double or triple or for alarming purposes.
busbars when dynamic zone selection is needed, it is
sometimes required to include the overall differential
zone (that is, check zone). Hence, the built-in, overall Id a
tIdAlarm
ALDIFF
a>b t
check zone is available in the IED. Because the built-in IdAlarmLev b
• Open or closed only when clearly indicated by aux the integrated differential protection zones behave
contact status (that is, as in INX schemes) when disconnector alarm appears is freely configurable
by the end user.
Table 16 gives quick overview about both schemes.
It is possible by a parameter setting to override the
Note that the first scheme only requires fast breaking primary object status as either permanently open or
normally closed auxiliary contact (that is, b contact) for permanently closed. This feature can be useful during
proper operation. The timing of normally open auxiliary testing, installation and commissioning of the busbar
contact is not critical because it is only used for protection scheme. At the same time, separate alarm is
supervision of the primary object status. The second given to indicate that the actual object status is
scheme in addition requires properly timed-adjusted, overwritten by a setting parameter.
early-making normally open auxiliary contact (that is,
early making a contact) for proper operation. It is to be noted that it is as well possible to use only
normally closed auxiliary contacts for Zone Selection
Regardless which scheme is used the time-delayed logic. In that case the Switch function blocks are not
disconnector/circuit breaker status supervision alarm is used.
available (that is, 00 or 11 auxiliary contact status). How
Normally Normally when when Alarm after Information visible on local HMI
Open auxiliary Closed “Scheme 1 “Scheme 2 settable
contact auxiliary RADSS” INX” time delay
status contact is selected is selected
(that is, status
“closed” or (that is,
“a” contact) “open” or “b”
contact)
auxiliary contacts from the busbar disconnector are Via two dedicated binary input signals it is possible to:
available to the Zone Selection logic
• Trip only the bay circuit breaker (used for integrated
At the same time, an additional feature for OC protection tripping)
instantaneous or time delayed disconnection or even • Trip the whole differential zone to which this bay is
inversion of the connected bay current via separate presently connected (used for backup-trip command
logical signals is also available. This feature is provided from either integrated or external bay circuit breaker
in order to facilitate for bus-section or bus-coupler CT failure protection)
disconnection for tie-breakers with a CT only on one
side of the circuit breaker. This ensures correct and fast Finally dedicated trip binary output from the Bay
fault clearance of faults between the CT and the circuit function block is available in order to provide common
breaker within these bays. The same feature can be trip signal to the bay circuit breaker from busbar
individually used in any feeder bay to optimize Busbar differential protection, breaker failure protection,
differential protection performance, when feeder circuit backup overcurrent protection and so on.
breaker is open. Thus, the end-fault protection for faults
In this way the interface to the user is kept as simple as
between circuit breaker and the CT is available.
possible and IED engineering work is quite straight
However, to use this feature circuit breaker auxiliary
forward.
contacts and closing command to the circuit breaker
shall be wired to the binary inputs of the IED. Therefore, Six-zone busbar differential protection
he IED offers best possible coverage for these special
GUID-F7EB2E33-55A8-4665-B950-644E34DC5C4B v1
The six-zone busbar differential protection can provide
faults between CT and circuit breaker in feeder and bus- protection and monitoring for up to six freely
section/bus-coupler bays. configurable low-impedance differential protection
zones and up to twenty-four freely configurable single-
Within the Bay function block it is decided by a
phase CT inputs, which requires two TRM modules. For
parameter setting how this bay should behave during
busbar IED configuration, six types of function blocks
zone interconnection (that is, load transfer). For each
are available:
bay individually one of the following three options can
• One busbar protection main function block,
be selected:
BDZSGAPC.
• Bay current is forced out from both zones during zone • Six differential zone function blocks, BZNPDIF_Zx, (1≤
interconnection (used for bus-coupler bays) x ≤6).
• Bay current is unconditionally forced into both zones Note that we refer to the six differential protection
during zone interconnection (used in special zones as Zx, (1≤x≤6). Also sometimes we refer to the
applications) differential protection zones as the main zones to
• Bay current is connected to both zones during zone distinguish them from the check zone.
interconnection if the bay was previously connected to • One check zone function block BCZPDIF.
one of the two zones (typically used for feeder bays) • Five bus-section or bus-coupler bay function blocks
BICPTRC_x, (1≤ x ≤5).
The third option ensures that the feeder, which is out of Note that we also call a bus-section or bus-coupler bay
service, is not connected to any of the two zones during as a bus interconnector, and refer to its two sets CTs
zone interconnection. as CT1 and CT2 respectively.
• Twenty four feeder bay function blocks BFPTRC_Fx,
Within the Bay function block it is decided by a (1≤ x ≤24).
parameter setting whether this bay should be connected • 128 switch status function blocks BDCGAPC.
to the check zone or not. In this way the end user has
simple control over the bays, which shall be connected
to the overall check zone. Zone interconnection (Load transfer) SEMOD120992-4 v4
When this feature is activated the two integrated
By appropriate configuration logic it is possible to take differential protection zones are merged into one
any bay (that is, CT input) out of service. This can be common, overall differential zone. This feature is
done from the local HMI or externally via binary signal. In required in double busbar stations when in any of the
that case all internal current measuring functions (that feeder bays both busbar disconnectors are closed at the
is, differential protection, sensitive differential same time (that is, load transfer). As explained in above
protection, check zone, breaker failure protection and section Bay each CT input will then behave in the pre-set
overcurrent protection) are disabled. At the same time, way in order to ensure proper current balancing during
any trip command to this bay circuit breaker can be this special condition. This feature can be started
inhibited. automatically (when Zone Selection logic determines
that both busbar disconnectors in one feeder bay are
ABB 27
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
sent to the remote line end. In order to utilize this Four step directional negative phase sequence
functionality the circuit breaker status and CB closing overcurrent protection (NS4PTOC) has an inverse or
command must be connected to the IED. One of the definite time delay independent for each step
overcurrent steps can be set and configured to act as separately.
end-fault protection in the IED.
All IEC and ANSI time delayed characteristics are
The function is normally used as end fault protection to available together with an optional user defined
clear faults between current transformer and circuit characteristic.
breaker.
The directional function is voltage polarized.
Four step single phase overcurrent protection
NS4PTOC can be set directional or non-directional
PH4SPTOC SEMOD127816-4 v8 independently for each of the steps.
Four step single phase, non-directional overcurrent
protection (PH4SPTOC) has an inverse or definite time NS4PTOC can be used as main protection for
delay independent for each step separately. unsymmetrical fault; phase-phase short circuits, phase-
phase-earth short circuits and single phase earth faults.
All IEC and ANSI time delayed characteristics are
available together with an optional user defined time
characteristic.
28 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
NS4PTOC can also be used to provide a system backup The CCRBRF function can be programmed to give a
for example, in the case of the primary protection being single- or three- phase retrip to its own breaker to avoid
out of service due to communication or voltage unnecessary tripping of surrounding breakers at an
transformer circuit failure. incorrect initiation due to mistakes during testing.
Thermal overload protection, two time constants Breaker failure protection, single phase CCSRBRF SEMOD127870-4 v7
TRPTTR M13243-3 v12
Breaker failure protection, single phase version
If a power transformer reaches very high temperatures (CCSRBRF) ensures a fast backup tripping of the
the equipment might be damaged. The insulation within surrounding breakers in case the own breaker fails to
the transformer will experience forced ageing. As a open. CCSRBRF measurement criterion can be current
consequence of this the risk of internal phase-to-phase based, CB position based or an adaptive combination of
or phase-to-earth faults will increase. these two conditions.
The thermal overload protection (TRPTTR) estimates the A current based check with extremely short reset time is
internal heat content of the transformer (temperature) used as check criterion to achieve high security against
continuously. This estimation is made by using a inadvertent operation.
thermal model of the transformer with two time
constants, which is based on current measurement. CB position check criteria can be used where the fault
current through the breaker is small.
Two warning levels are available. This enables actions in
the power system to be done before dangerous The CCSRBRF provides three different options to select
temperatures are reached. If the temperature continues how t1 and t2 timers are run:
to increase to the trip value, the protection initiates a 1. By external start signal which is internally latched
trip of the protected transformer. 2. Follow the external start signal only
3. Follow external start signal and selected
The estimated time to trip before operation is FunctionMode
presented.
Breaker failure protection CCRBRF The CCSRBRF function can be programmed to give a
Breaker failure protection (CCRBRF) ensures a fast
M11550-6 v18
retrip to its own breaker to avoid unnecessary tripping
backup tripping of the surrounding breakers in case the of surrounding breakers at an incorrect initiation due to
own breaker fails to open. CCRBRF measurement mistakes during testing.
criterion can be current based, CB position based or an
Directional over/underpower protection GOPPDOP/
adaptive combination of these two conditions.
GUPPDUP SEMOD175421-4 v7
A current based check with extremely short reset time is The directional over-/under-power protection
used as check criterion to achieve high security against (GOPPDOP/GUPPDUP) can be used wherever a high/low
inadvertent operation. active, reactive or apparent power protection or
alarming is required. The functions can alternatively be
CB position check criteria can be used where the fault used to check the direction of active or reactive power
current through the breaker is small. flow in the power system. There are a number of
applications where such functionality is needed. Some
CCRBRF provides three different options to select how of them are:
t1 and t2 timers are run:
1. By external start signals which is internally latched • detection of reversed active power flow
2. Follow external start signal only • detection of high reactive power flow
3. Follow external start signal and the selected
FunctionMode Each function has two steps with definite time delay.
ABB 29
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
SEMOD171457-5 v8
Loss of voltage check (LOVPTUV ) is suitable for use in
8. Voltage protection networks with an automatic system restoration
function. LOVPTUV issues a three-pole trip command to
Two-step undervoltage protection UV2PTUV M13789-3 v12 the circuit breaker, if all three phase voltages fall below
Undervoltages can occur in the power system during
the set value for a time longer than the set time and the
faults or abnormal conditions. The two-step
circuit breaker remains closed.
undervoltage protection function (UV2PTUV) can be
used to open circuit breakers to prepare for system The operation of LOVPTUV is supervised by the fuse
restoration at power outages or as a long-time delayed failure supervision FUFSPVC.
back-up to the primary protection.
OV2PTOV has two voltage steps, each of them with Overfrequency protection SAPTOF
inverse or definite time delayed.
M14953-3 v12
Overfrequency protection function (SAPTOF) is
applicable in all situations, where reliable detection of
OV2PTOV has a high reset ratio to allow settings close
high fundamental power system frequency is needed.
to system service voltage.
Overfrequency occurs because of sudden load drops or
Two step residual overvoltage protection ROV2PTOV M13808-3 v11 shunt faults in the power network. Close to the
Residual voltages may occur in the power system during
generating plant, generator governor problems can also
earth faults.
cause over frequency.
Two step residual overvoltage protection (ROV2PTOV)
SAPTOF measures frequency with high accuracy, and is
function calculates the residual voltage from the three-
used mainly for generation shedding and remedial
phase voltage input transformers or measures it from a
action schemes. It is also used as a frequency stage
single voltage input transformer fed from an open delta
initiating load restoring. A definite time delay is
or neutral point voltage transformer.
provided for operate.
ROV2PTOV has two voltage steps, each with inverse or
SAPTOF is provided with an undervoltage blocking.
definite time delay.
The operation is based on positive sequence voltage
A reset delay ensures operation for intermittent earth
measurement and requires two phase-phase or three
faults.
phase-neutral voltages to be connected.
Voltage differential protection VDCPTOV SEMOD153862-5 v7 Rate-of-change of frequency protection SAPFRC
A voltage differential monitoring function is available. It M14965-3 v14
The rate-of-change of frequency protection function
compares the voltages from two three phase sets of
(SAPFRC) gives an early indication of a main disturbance
voltage transformers and has one sensitive alarm step
in the system. SAPFRC measures frequency with high
and one trip step.
accuracy, and can be used for generation shedding, load
Loss of voltage check LOVPTUV shedding and remedial action schemes. SAPFRC can
30 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
operations that otherwise might occur. Delta supervision function is used to quickly detect
(sudden) changes in the network. This can, for example,
The fuse failure supervision function basically has three be used to detect disturbances in the power system
different detection methods, negative sequence and network. Current based delta supervision (DELISPVC)
zero sequence based detection and an additional delta provides selectivity between load change and the fault.
voltage and delta current detection.
Present power system has many power electronic
The negative sequence detection algorithm is devices or FACTS devices, which injects a large number
recommended for IEDs used in isolated or high- of harmonics into the system. The function has
impedance earthed networks. It is based on the additional features of 2nd harmonic blocking and 3 rd
negative-sequence quantities.
harmonic start level adaption. The 2 nd harmonic blocking
The zero sequence detection is recommended for IEDs secures the operation during the transformer charging,
used in directly or low impedance earthed networks. It is when high inrush currents are supplied into the system.
based on the zero sequence measuring quantities.
Delta supervision of real input DELSPVC
GUID-8FAD2CCF-091F-4CDB-8ABF-1BDC874A8403 v2
The selection of different operation modes is possible Delta supervision functions are used to quickly detect
by a setting parameter in order to take into account the (sudden) changes in the power system. Real input delta
particular earthing of the network. supervision (DELSPVC) function is a general delta
function. It is used to detect the change measured
A criterion based on delta current and delta voltage qualities over a settable time period, such as:
measurements can be added to the fuse failure • Power
supervision function in order to detect a three phase • Reactive power
fuse failure, which in practice is more associated with • Temperature
voltage transformer switching during station • Frequency
operations. • Power factor
ABB 31
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M13444-3 v15
The apparatus control functions are used for control and
12. Control supervision of circuit breakers, disconnectors and
earthing switches within a bay. Permission to operate is
Synchrocheck, energizing check, and synchronizing
given after evaluation of conditions from other
SESRSYN M12480-3 v16 functions such as interlocking, synchrocheck, operator
The Synchronizing function allows closing of
place selection and external or internal blockings.
asynchronous networks at the correct moment including
the breaker closing time, which improves the network Apparatus control features:
stability. • Select-Execute principle to give high reliability
• Selection function to prevent simultaneous operation
Synchrocheck, energizing check, and synchronizing
• Selection and supervision of operator place
(SESRSYN) function checks that the voltages on both
• Command supervision
sides of the circuit breaker are in synchronism, or with
• Block/deblock of operation
at least one side dead to ensure that closing can be
• Block/deblock of updating of position indications
done safely.
• Substitution of position and quality indications
SESRSYN function includes a built-in voltage selection • Overriding of interlocking functions
scheme for double bus and 1½ breaker or ring busbar • Overriding of synchrocheck
arrangements. • Operation counter
• Suppression of mid position
Manual closing as well as automatic reclosing can be
checked by the function and can have different settings.
Two types of command models can be used:
For systems, which can run asynchronously, a • Direct with normal security
synchronizing feature is also provided. The main • SBO (Select-Before-Operate) with enhanced security
purpose of the synchronizing feature is to provide
controlled closing of circuit breakers when two Normal security means that only the command is
asynchronous systems are in phase and can be evaluated and the resulting position is not supervised.
connected. The synchronizing feature evaluates voltage Enhanced security means that the command is
difference, phase angle difference, slip frequency and evaluated with an additional supervision of the status
frequency rate of change before issuing a controlled value of the control object. The command sequence with
closing of the circuit breaker. Breaker closing time is a enhanced security is always terminated by a
setting. CommandTermination service primitive and an
AddCause telling if the command was successful or if
Autorecloser SMBRREC M12390-3 v17 something went wrong.
The auto recloser (SMBRREC) function provides:
• high-speed and/or delayed auto reclosing Control operation can be performed from the local HMI
• single and/or three phase auto reclosing with authority control if so defined.
• support for single or multi-breaker applications.
Interlocking M13531-3 v4
The interlocking function blocks the possibility to
The auto recloser can be used for delayed busbar
operate primary switching devices, for instance when a
restoration.
disconnector is under load, in order to prevent material
Up to five reclosing shots can be performed. The first damage and/or accidental human injury.
shot can be single-, two-, and /or three-phase
Each apparatus control function has interlocking
depending on the type of the fault and the selected auto
modules included for different switchyard
reclosing mode.
arrangements, where each function handles interlocking
Several auto reclosing functions can be provided for of one bay. The interlocking function is distributed to
multi-breaker arrangements. A priority circuit allows one each IED and is not dependent on any central function.
circuit breaker to reclose first and the second will only For the station-wide interlocking, the IEDs communicate
close if the fault proved to be transient. via the system-wide interbay bus (IEC 61850-8-1) or by
using hard wired binary inputs/outputs. The
Each auto reclosing function can be configured to co- interlocking conditions depend on the circuit
operate with the synchrocheck function. configuration and apparatus position status at any
given time.
Apparatus control APC
32 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
for the interlocking conditions. The interlocking The GOOSE XLN Receive component is used to collect
conditions can be altered, to meet the customer’s information from another device’s XCBR/XSWI logical
specific requirements, by adding configurable logic by node sent over process bus via GOOSE. The GOOSE XLN
means of the graphical configuration tool. Receive component includes 12 different outputs (and
their respective channel valid bits) with defined names
Switch controller SCSWI M13486-3 v10
to ease the 61850 mapping of the GOOSE signals in the
The Switch controller (SCSWI) initializes and supervises configuration process.
all functions to properly select and operate switching
primary apparatuses. The Switch controller may handle Local remote LOCREM/Local remote control
and operate on one multi-phase device or up to three LOCREMCTRL M17086-3 v11
one-phase devices. The signals from the local HMI or from an external local/
remote switch are connected via the function blocks
Circuit breaker SXCBR M13489-3 v6
local remote (LOCREM) and local remote control
The purpose of Circuit breaker (SXCBR) is to provide the (LOCREMCTRL) to the Bay control (QCBAY) function
actual status of positions and to perform the control block. The parameter ControlMode in function block
operations, that is, pass all the commands to primary LOCREM is set to choose if the switch signals are
apparatuses in the form of circuit breakers via binary coming from the local HMI or from an external hardware
output boards and to supervise the switching operation switch connected via binary inputs.
and position.
Logic rotating switch for function selection and
Circuit switch SXSWI LHMI presentation SLGAPC SEMOD114908-4 v11
M16492-3 v6
The purpose of Circuit switch (SXSWI) function is to The logic rotating switch for function selection and
provide the actual status of positions and to perform LHMI presentation (SLGAPC) (or the selector switch
the control operations, that is, pass all the commands to function block) is used to get an enhanced selector
primary apparatuses in the form of disconnectors or switch functionality compared to the one provided by a
earthing switches via binary output boards and to hardware selector switch. Hardware selector switches
supervise the switching operation and position. are used extensively by utilities, in order to have
different functions operating on pre-set values.
Reservation function QCRSV M13506-3 v5
Hardware switches are however sources for
The purpose of the reservation (QCRSV) function is maintenance issues, lower system reliability and an
primarily to transfer interlocking information between extended purchase portfolio. The selector switch
IEDs in a safe way and to prevent double operation in a function eliminates all these problems.
bay, switchyard part, or complete substation.
Selector mini switch VSGAPC
Reservation input RESIN M16501-3 v5
The Selector mini switch (VSGAPC) function block is a
SEMOD158756-5 v10
The Reservation input (RESIN) function receives the multipurpose function used for a variety of applications,
reservation information from other bays. The number of as a general purpose switch.
instances is the same as the number of involved bays
(up to 60 instances are available). VSGAPC can be controlled from the menu, from a symbol
on the single line diagram (SLD) on the local HMI or from
Bay control QCBAY M13447-3 v8
Binary inputs.
The Bay control (QCBAY) function is used together with
Local remote and local remote control functions to Generic communication function for Double Point
handle the selection of the operator place per bay. indication DPGAPC SEMOD55850-5 v7
QCBAY also provides blocking functions that can be Generic communication function for Double Point
distributed to different apparatuses within the bay. indication (DPGAPC) function block is used to send
double point position indications to other systems,
Proxy for signals from switching device via GOOSE equipment or functions in the substation through IEC
XLNPROXY GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1
61850-8-1 or other communication protocols. It is
The proxy for signals from switching device via GOOSE especially intended to be used in the interlocking
(XLNPROXY) gives an internal representation of the station-wide logics.
position status and control response for a switch
modelled in a breaker IED. This representation is Single point generic control 8 signals SPC8GAPC SEMOD176462-4 v11
identical to that of an SXCBR or SXSWI function. The Single point generic control 8 signals (SPC8GAPC)
function block is a collection of 8 single point
ABB 33
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
commands that can be used for direct commands for user to adapt the configuration to the specific
example reset of LEDs or putting IED in "ChangeLock" application needs. The list below shows a summary of
state from remote. In this way, simple commands can be the function blocks and their features.
sent directly to the IED outputs, without confirmation.
Confirmation (status) of the result of the commands is These logic blocks are also available as part of an
supposed to be achieved by other means, such as binary extension logic package.
inputs and SPGAPC function blocks. The commands can
• AND function block. The AND function is used to form
be pulsed or steady with a settable pulse time.
general combinatory expressions with boolean
Automation bits, command function for DNP3.0 variables. The AND function block has up to four
AUTOBITS inputs and two outputs. One of the outputs is
Automation bits function for DNP3 (AUTOBITS) is used
SEMOD158591-5 v8
inverted.
within PCM600 to get into the configuration of the
• GATE function block is used for whether or not a
commands coming through the DNP3 protocol. The
signal should be able to pass from the input to the
AUTOBITS function plays the same role as functions
output.
GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for
LON). • INVERTER function block that inverts the input signal
to the output.
Single command, 16 signals M12446-6 v5
The IEDs can receive commands either from a • LLD function block. Loop delay used to delay the
substation automation system or from the local HMI. output signal one execution cycle.
The command function block has outputs that can be
used, for example, to control high voltage apparatuses • OR function block. The OR function is used to form
or for other user defined functionality. general combinatory expressions with boolean
variables. The OR function block has up to six inputs
and two outputs. One of the outputs is inverted.
• INDEXTSPQT extracts individual signals from a group Fixed signal function block FXDSIGN M15322-3 v15
signal input. The value part of single position input is The Fixed signals function (FXDSIGN) has nine pre-set
copied to SI_OUT output. The time part of single (fixed) signals that can be used in the configuration of
position input is copied to TIME output. The quality an IED, either for forcing the unused inputs in other
bits in the common part and the indication part of function blocks to a certain level/value, or for creating
inputs signal are copied to the corresponding quality certain logic. Boolean, integer, floating point, string
output. types of signals are available.
• INVALIDQT function which sets quality invalid of One FXDSIGN function block is included in all IEDs.
outputs according to a "valid" input. Inputs are copied
to outputs. If input VALID is 0, or if its quality invalid Elapsed time integrator with limit transgression and
bit is set, all outputs invalid quality bit will be set to overflow supervision TEIGAPC GUID-2D64874A-F266-4251-8EED-E813F40513D7 v3
invalid. The time stamp of an output will be set to the The Elapsed time integrator function (TEIGAPC) is a
latest time stamp of INPUT and VALID inputs. function that accumulates the elapsed time when a
given binary signal has been high.
• INVERTERQT function block that inverts the input
signal and propagates the time stamp and the quality The main features of TEIGAPC
of the input signal.
• Applicable to long time integration (≤999 999.9
• ORQT OR function block that also propagates the time seconds).
stamp and the quality of the input signals. Each block • Supervision of limit transgression conditions and
has six inputs and two outputs where one is inverted. overflow.
• Possibility to define a warning or alarm with the
• PULSETIMERQT Pulse timer function block can be resolution of 10 milliseconds.
used, for example, for pulse extensions or limiting of • Retaining of the integration value.
operation of outputs. The function also propagates • Possibilities for blocking and reset.
the time stamp and the quality of the input signal. • Reporting of the integrated time.
Each block has two outputs where one is inverted. The Boolean to integer conversion, 16 bit (B16I) is used to
memory setting controls if the block after a power transform a set of 16 boolean (logical) signals into an
interruption should return to the state before the integer.
interruption, or be reset. The function also propagates
Boolean to integer conversion with logical node
the time stamp and the quality of the input signal.
representation, 16 bit BTIGAPC SEMOD175781-4 v8
• SRMEMORYQT function block is a flip-flop that can set Boolean to integer conversion with logical node
or reset an output from two inputs respectively. Each representation, 16 bit (BTIGAPC) is used to transform a
ABB 35
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
set of 16 boolean (logical) signals into an integer. The • measured voltages, currents, frequency, active,
block input will freeze the output at the last value. reactive and apparent power and power factor
• measured analog values from merging units
Integer to Boolean 16 conversion IB16 SEMOD158373-5 v6 • measured currents
Integer to boolean 16 conversion function (IB16) is used • primary phasors
to transform an integer into a set of 16 boolean (logical) • positive, negative and zero sequence currents and
signals. voltages
• mA, input currents
Integer to Boolean conversion for six-zone busbar
• pulse counters
BCTZCONN GUID-6F3BBA7D-9C02-4B7C-B7AF-907CC49C4553 v2
Integer to Boolean conversion for six-zone busbar Voltage and power can be measured only when VT
(BCTZCONN) is used to transform the zone connection inputs into the REB670 are available.
integer signal of each CT from one bay function block
into 7 binary (logical) signals in the six-zone busbar Supervision of mA input signals M16054-3 v2
differential protection. It is intended to facilitate the The main purpose of the function is to measure and
recording of zone connection information from each bay process signals from different measuring transducers.
function block to the disturbance recorder. Many devices used in process control represent various
parameters such as frequency, temperature and DC
The BCTZCONN function does not have a logical node battery voltage as low current values, usually in the
mapping and is designed to receive only an integer input range 4-20 mA or 0-20 mA.
locally. If the BLOCK input is activated, it freezes the
logical outputs at the last values. Alarm limits can be set and used as triggers, e.g. to
generate trip or alarm signals.
Integer to Boolean 16 conversion with logic node
representation ITBGAPC SEMOD158421-5 v9
The function requires that the IED is equipped with the
Integer to boolean conversion with logic node mA input module.
representation function (ITBGAPC) is used to transform
an integer which is transmitted over IEC 61850 and Disturbance report DRPRDRE M12153-3 v14
received by the function to 16 boolean (logic) output Complete and reliable information about disturbances in
signals. the primary and/or in the secondary system together
with continuous event-logging is accomplished by the
Comparator for integer inputs INTCOMP
GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1
disturbance report functionality.
The function gives the possibility to monitor the level of
integer values in the system relative to each other or to Disturbance report (DRPRDRE), always included in the
a fixed value. It is a basic arithmetic function that can be IED, acquires sampled data of all selected analog input
used for monitoring, supervision, interlocking and other and binary signals connected to the function block with
logics. a maximum of 40 analog and 352 binary signals.
Comparator for real inputs REALCOMP The Disturbance report functionality is a common name
GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1
The function gives the possibility to monitor the level of for several functions:
real value signals in the system relative to each other or
• Event list
to a fixed value. It is a basic arithmetic function that can
• Indications
be used for monitoring, supervision, interlocking and
• Event recorder
other logics.
• Trip value recorder
• Disturbance recorder
• Settings information
36 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
the standard Comtrade format as a reader file HDR, a Information about the pre-fault and fault values for
configuration file CFG, and a data file DAT. The same currents and voltages are vital for the disturbance
applies to all events, which are continuously saved in a evaluation.
ring-buffer. The local HMI is used to get information
The Trip value recorder calculates the values of all
about the recordings. The disturbance report files can
selected analog input signals connected to the
be uploaded to PCM600 for further analysis using the
Disturbance recorder function. The result is magnitude
disturbance handling tool.
and phase angle before and during the fault for each
Event list DRPRDRE analog input signal.
M12412-6 v8
Continuous event-logging is useful for monitoring the
The trip value recorder information is available for the
system from an overview perspective and is a
disturbances locally in the IED.
complement to specific disturbance recorder functions.
The trip value recorder information is an integrated part
The event list logs all binary input signals connected to
of the disturbance record (Comtrade file).
the Disturbance recorder function. The list may contain
up to 1000 time-tagged events stored in a ring-buffer. Disturbance recorder DRPRDRE M12156-3 v12
The Disturbance recorder function supplies fast,
Indications DRPRDRE M12030-3 v7 complete and reliable information about disturbances in
To get fast, condensed and reliable information about
the power system. It facilitates understanding system
disturbances in the primary and/or in the secondary
behavior and related primary and secondary equipment
system it is important to know, for example binary
during and after a disturbance. Recorded information is
signals that have changed status during a disturbance.
used for different purposes in the short perspective (for
This information is used in the short perspective to get
example corrective actions) and long perspective (for
information via the local HMI in a straightforward way.
example functional analysis).
There are three LEDs on the local HMI (green, yellow and
The Disturbance recorder acquires sampled data from
red), which will display status information about the IED
selected analog and binary signals connected to the
and the Disturbance recorder function (triggered).
Disturbance recorder function (maximum 40 analog and
The Indication list function shows all selected binary 352 binary signals). The binary signals available are the
input signals connected to the Disturbance recorder same as for the event recorder function.
function that have changed status during a disturbance.
The function is characterized by great flexibility and is
Event recorder DRPRDRE not dependent on the operation of protection functions.
Quick, complete and reliable information about
M12033-3 v8
It can record disturbances not detected by protection
disturbances in the primary and/or in the secondary functions. Up to ten seconds of data before the trigger
system is vital, for example, time-tagged events logged instant can be saved in the disturbance file.
during disturbances. This information is used for
The disturbance recorder information for up to 100
different purposes in the short term (for example
disturbances are saved in the IED and the local HMI is
corrective actions) and in the long term (for example
used to view the list of recordings .
functional analysis).
Event function
The event recorder logs all selected binary input signals M12805-6 v11
When using a Substation Automation system with LON
connected to the Disturbance recorder function. Each
or SPA communication, time-tagged events can be sent
recording can contain up to 150 time-tagged events.
at change or cyclically from the IED to the station level.
The event recorder information is available for the These events are created from any available signal in the
disturbances locally in the IED. IED that is connected to the Event function (EVENT). The
EVENT function block is used for LON and SPA
The event recording information is an integrated part of communication.
the disturbance record (Comtrade file).
Analog, integer and double indication values are also
Trip value recorder DRPRDRE transferred through the EVENT function.
GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6
Generic communication function for measured The Limit counter (L4UFCNT) provides a settable
values MVGAPC SEMOD55872-5 v10
counter with four independent limits where the number
Generic communication function for measured values of positive and/or negative flanks on the input signal
(MVGAPC) function is used to send the instantaneous are counted against the setting values for limits. The
value of an analog signal to other systems or equipment output for each limit is activated when the counted
in the substation. It can also be used inside the same value reaches that limit.
IED, to attach a RANGE aspect to an analog value and to
permit measurement supervision on that value. Overflow indication is included for each up-counter.
38 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
with respect to the fundamental signal amplitude which and STOPACC) and EnaAcc setting and it can be reset to
indicates the voltage signal quality factor. initial values with RSTACC input.
Additionally, the function is used to calculate the The maximum demand for active and reactive powers
numerical multiple of rated frequency harmonics are calculated for the set time interval tEnergy and
amplitude and harmonic distortion upto the 5 th order. It these values are updated every minute through output
helps the user to know the predominant harmonic channels. The active and reactive maximum power
frequencies order and their amplitudes present in the demand values are calculated for both forward and
system. The function also calculates the crest factor to reverse direction and these values can be reset with
indicate the effectiveness of the signal. All calculations RSTDMD input.
in the harmonic monitoring function are based on IEEE
1459 and IEEE 519 standards.
15. Metering
demand power values are also calculated by the Figure 12. Local human-machine interface
function. This function includes zero point clamping to
remove noise from the input signal. As output of this
function: periodic energy calculations, integration of The LHMI of the IED contains the following elements
energy values, calculation of energy pulses, alarm • Graphical display capable of showing a user defined
signals for limit violation of energy values and maximum single line diagram and provide an interface for
power demand, can be found. controlling switchgear.
• Navigation buttons and five user defined command
The values of active and reactive energies are calculated buttons to shortcuts in the HMI tree or simple
from the input power values by integrating them over a commands.
selected time tEnergy. The integration of active and • 15 user defined three-color LEDs.
reactive energy values will happen in both forward and • Communication port for PCM600.
reverse directions. These energy values are available as
output signals and also as pulse outputs. Integration of
energy values can be controlled by inputs (STARTACC The LHMI is used for setting, monitoring and controlling.
ABB 39
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
common source of absolute time for the synchronization IEC 62439-3 redundant communication PRP
of the IED when it is a part of a protection system. This Redundant communication according to IEC 62439-3
makes it possible to compare events and disturbance PRP-0, IEC 62439-3 PRP-1 parallel redundancy protocol
data between all IEDs within a station automation (PRP) is available as an option when ordering IEDs. PRP
system and in between sub-stations. A common source according to IEC 62439-3 uses two optical Ethernet
shall be used for IED and merging unit when IEC/UCA ports.
61850-9-2LE process bus communication is used.
M11345-3 v11 IEC 62439-3 High-availability seamless redundancy HSR
Redundant station bus communication according to IEC
Precision time protocol PTP
62439-3 Edition 2 High-availability seamless redundancy
PTP according to IEEE 1588-2008 and specifically its
(HSR) is available as an option when ordering IEDs.
profile IEC/IEEE 61850-9-3 for power utility automation
Redundant station bus communication according to IEC
is a synchronization method that can be used to
62439-3 uses two optical Ethernet ports.
maintain a common time within a station. This time can
be synchronized to the global time using, for instance, a The HSR ring supports the connection of up to 30 relays.
GPS receiver. If PTP is enabled on the IEDs and the If more than 30 relays are to be connected, it is
switches that connect the station are compatible with recommended to split the network into several rings to
IEEE 1588, the station will become synchronized to one guarantee the performance for real-time applications.
common time with an accuracy of under 1us. Using an
IED as a boundary clock between several networks will Routes GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v1
keep 1us accuracy on three levels or when using an HSR, A route is a specified path for data to travel between the
15 IEDs can be connected in a ring without losing a source device in a subnetwork to the destination device
single microsecond in accuracy. in a different subnetwork. A route consists of a
destination address and the address of the gateway to
be used when sending data to the destination device,
see Figure 14.
18. Ethernet
Device 1 Device 1
Source Destination
IEC16000095-1-en.vsdx
IEC16000095 V1 EN-US
AP1 AP2 AP3 AP1 AP2 AP3 Figure 14. Route from source to destination through gateway
SFP_301 SFP_302 SFP_303 SFP_301 SFP_302 SFP_303
IEC16000092-1-en.vsdx
IEC16000092 V1 EN-US
40 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Available communication protocols are: automation systems but the main use is for Substation
Monitoring Systems SMS.
• IEC 61850-8-1 communication protocol
• IEC/UCA 61850-9-2LE communication protocol IEC 60870-5-103 communication protocol SEMOD120137-5 v4
• LON communication protocol A single glass or plastic port is provided for the IEC
• SPA communication protocol 60870-5-103 standard. This allows design of simple
• IEC 60870-5-103 communication protocol substation automation systems including equipment
from different vendors. Disturbance files uploading is
Several protocols can be combined in the same IED. provided.
IEC 61850-8-1 communication protocol M14787-3 v16 Measurands for IEC 60870-5-103 I103MEAS
IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in 103MEAS is a function block that reports all valid
PCM600. The IED is equipped with up to six (order measuring types depending on the connected signals.
dependent) optical Ethernet rear ports for IEC 61850-8-1 The set of connected inputs will control which ASDUs
station bus communication.The IEC 61850-8-1 (Application Service Data Units) are generated.
communication is also possible from the electrical
Ethernet front port. IEC 61850-8-1 protocol allows Measurands user-defined signals for IEC 60870-5-103
intelligent electrical devices (IEDs) from different I103MEASUSR
vendors to exchange information and simplifies system I103MEASUSR is a function block with user-defined input
engineering. IED-to-IED communication using GOOSE measurands in monitor direction. These function blocks
and client-server communication over MMS are include the FunctionType parameter for each block in
supported. Disturbance recording file (COMTRADE) the private range, and the Information number
uploading can be done over MMS or FTP. parameter for each block.
Status for user-defined signals for IEC 60870-5-103 DNP3.0 communication protocol SEMOD153688-5 v3
I103USRDEF An electrical RS485 serial port, optical serial ports on the
I103USRDEF comprises function blocks with user- serial communication module (SLM), optical Ethernet
defined input signals in monitor direction. These ports are available for DNP3.0 communication. DNP3.0
function blocks include the FunctionType parameter for Level 2 communication with unsolicited events, time
each block in the private range, and the information synchronization and disturbance reporting is provided
number parameter for each input signal. for communication to RTUs, Gateways or HMI systems.
Function commands for IEC 60870-5-103 I103CMD Multiple command and transmit M14791-3 v3
I103CMD is a command function block in control When IEDs are used in Substation Automation systems
direction with pre-defined output signals. The signals with LON, SPA or IEC 60870-5-103 communication
are in steady state, not pulsed, and stored in the IED in protocols, the Event and Multiple Command function
case of restart. blocks are used as the communication interface for
vertical communication to station HMI and gateway, and
IED commands for IEC 60870-5-103 I103IEDCMD as interface for horizontal peer-to-peer communication
I103IEDCMD is a command block in control direction (over LON only).
with defined IED functions. All outputs are pulsed and
they are NOT stored. Pulse-time is a hidden parameter.
42 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
and long range LDCM SEMOD168481-4 v10 relays and is used for trip output or any signaling
The line data communication module (LDCM) is used for purpose.
communication between the IEDs situated at a distance
<110 km/68 miles or from the IED to the optical-to- Static binary output module SOM
SEMOD174196-4 v4
electrical converter with G.703 or G.703E1 interface The static binary output module has six fast static
located at a distance < 3 km/1.9 miles away. The LDCM outputs and six change over output relays for use in
module sends and receives data to and from another applications with high speed requirements.
LDCM module. The IEEE/ANSI C37.94 standard format is
used. Binary input/output module IOM
M6939-3 v6
The binary input/output module is used when only a few
Galvanic X.21 line data communication module X.21- input and output channels are needed. The ten standard
LDCM GUID-3C6C7DAC-1DB1-4CB8-991F-3B1D86551F28 v3
output channels are used for trip output or any signaling
A module with built-in galvanic X.21 converter which e.g. purpose. The two high speed signal output channels are
can be connected to modems for pilot wires is also used for applications where short operating time is
available. essential. Eight optically isolated binary inputs cater for
required binary input information.
Galvanic interface G.703 resp G.703E1 M16035-3 v5
The external galvanic data communication converter G. mA input module MIM
M15020-3 v4
703/G.703E1 makes an optical-to-galvanic conversion The milli-ampere input module is used to interface
for connection to a multiplexer. These units are transducer signals in the –20 to +20 mA range from for
designed for 64 kbit/s resp 2Mbit/s operation. The example OLTC position, temperature or pressure
converter is delivered with 19” rack mounting transducers. The module has six independent,
accessories. galvanically separated channels.
Figure 16. Case with rear cover and 19” rack mounting kit
has twelve inputs in different combinations of currents
and voltage inputs.
IEC06000182-2-en.vsd
IEC06000182 V2 EN-US
M15243-12 v10
IEC08000163‐3‐en.vsdx
IEC08000163 V3 EN-US
44 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Case size A B C D E F G H I
(mm)/
(inches)
6U, 1/2 x 19” 265.9/ 223.7/ 247.5/ 255.0/ 205.8/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 8.81 9.74 10.04 8.10 7.50 18.36 9.15 19
6U, 3/4 x 19” 265.9/ 335.9/ 247.5/ 255.0/ 318.0/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 13.23 9.74 10.04 12.52 7.50 18.36 9.15 19
6U, 1/1 x 19” 265.9/ 448.0/ 247.5/ 255.0/ 430.1/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 17.65 9.74 10.04 16.86 7.50 18.36 9.15 19
The G and H dimensions are defined by the 19” rack mounting kit.
ABB 45
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
The latest versions of the connection diagrams can be Connection diagram, REB670 2.2, B21X02
downloaded from 1MRK002807-BC
http://www.abb.com/protection-control.
Connection diagram, REB670 2.2, B21X03
Connection diagrams for IEC Customized products 1MRK002807-BD
Connection diagram, 670 series 2.2 1MRK002801-AG Connection diagram, REB670 2.2, B31X01
1MRK002807-BE
Connection diagrams for Configured products
Connection diagram, REB670 2.2, B31X02
Connection diagram, REB670 2.2, A20X01
1MRK002807-BF
1MRK002807-BH
Connection diagram, REB670 2.2, B31X03
Connection diagram, REB670 2.2, A31X01
1MRK002807-BG
1MRK002807-BK
Connection diagrams for ANSI Customized products
Connection diagram, REB670 2.2, A31X02
1MRK002807-BL Connection diagram, 670 series 2.2 1MRK002802-AG
46 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets
the specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to
perform its intended functions according to the specified requirements
Presumptions for Technical Data 6. Parameter SBase used by the tested function is set
GUID-1E949E38-E04D-4374-A086-912C25E9F93C v2
The technical data stated in this document are only valid equal to:
under the following circumstances: – √3 × IBase × UBase
7. The rated secondary quantities have the following
1. Main current transformers with 1 A or 2 A secondary values:
rating are wired to the IED 1 A rated CT inputs. – Rated secondary phase current Ir is either 1 A or 5 A
2. Main current transformer with 5 A secondary rating
depending on selected TRM.
are wired to the IED 5 A rated CT inputs.
– Rated secondary phase-to-phase voltage Ur is
3. CT and VT ratios in the IED are set in accordance with
within the range from 100 V to 120 V.
the associated main instrument transformers. Note
– Rated secondary power for three-phase system S r =
that for functions which measure an analogue signal
√3 × U r × Ir
which do not have corresponding primary quantity
the 1:1 ratio shall be set for the used analogue inputs 8. For operate and reset time testing, the default
on the IED. Example of such functions are: HZPDIF, setting values of the function are used if not explicitly
ROTIPHIZ and STTIPHIZ. stated otherwise.
4. Parameter IBase used by the tested function is set 9. During testing, signals with rated frequency have
equal to the rated CT primary current. been injected if not explicitly stated otherwise.
5. Parameter UBase used by the tested function is set
equal to the rated primary phase-to-phase voltage.
ABB 47
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Table 17. TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Current inputs
Rated current Ir 1 or 5 A
Note! All current and voltage data are specified as RMS values at rated frequency
48 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Table 18. TRM - Energizing quantities, rated values and limits for measuring transformer
Description Value
Frequency
Current inputs
Rated current Ir 1A 5A
Voltage inputs *)
Note! All current and voltage data are specified as RMS values at rated frequency
M6389-1 v5
Power consumption -
each mA board £2W
each mA input £ 0.1 W
Auxiliary DC voltage
M12286-1 v9 IP15843-1 v3
ABB 49
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Binary inputs 16 -
Power consumption
24/30 V, 50 mA max. 0.05 W/input -
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M50609-2 v9
Table 22. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
50 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M12573-1 v11
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
ABB 51
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M12318-1 v9
Table 24. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
52 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Maximum 72 outputs may be activated The stated operate time for functions
simultaneously with influencing factors include the operating time for the
within nominal range. After 6 ms an binary inputs and outputs.
additional 24 outputs may be
activated. The activation time for the M12584-1 v9
Table 25. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
ABB 53
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Maximum 72 outputs may be activated The stated operate time for functions
simultaneously with influencing factors include the operating time for the
within nominal range. After 6 ms an binary inputs and outputs.
additional 24 outputs may be
activated. The activation time for the SEMOD175395-2 v8
Table 26. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
1.0 s 10 A 10 A
0.2 s 30 A 30 A
1.0 s 10 A 10 A
220 V/0.2 A
250 V/0.15 A
54 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Table 27. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0 s 10 A
0.2 s 30 A
1.0 s 10 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Table 28. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
ABB 55
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Influencing factors
M16705-1 v16 IP15846-1 v1
100-250 V DC ±20%
Interruption
interval
0–50 ms No restart
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ±2.0%
Harmonic frequency dependence for differential protection (10% 2nd, 3rd and 5th harmonic of fr ±6.0%
content)
56 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Level 4
Surge immunity test 2-4 kV, 1.2/50ms high energy IEC 60255-26, Zone A
1-2 kV, BOM and IRF outputs IEC 60255-26, Zone B
Conducted common mode immunity test 30-3 V, 15-150 Hz IEC 61000-4-16, Level 4
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Level 5
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Level 5
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Level 5
ABB 57
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40°C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle IEC 60068-2-30
= 24 hours)
Test According to
Vibration endurance test Class I: Rack, flush and wall mount IEC 60255-21-1
Shock response test Class I: Rack, flush and wall mount IEC 60255-21-2
Shock withstand test Class I: Rack, flush and wall mount IEC 60255-21-2
Bump test Class I: Rack, flush and wall mount IEC 60255-21-2
58 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
ABB 59
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
60 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
1-4
Minimum operate time for inverse curves , (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Inverse time characteristics, see table 147, 16 curve types See table 147, table 148 and table 149
table 148 and table 149
ABB 61
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
SEMOD127584-2 v8
Inverse time characteristics, 16 curve types See table 147, table 148, and table 149
see table 147, table 148, and
table 149
62 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M15223-1 v18
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Inverse time characteristics, see Table 147, 16 curve types See Table 147, Table 148 and Table 149
Table 148 and Table 149
*Note: Operate time and reset time are only valid if harmonic blocking is turned off for a step.
ABB 63
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6
Table 41. Four step directional negative phase sequence overcurrent protection NS4PTOC
Minimum operate time for inverse (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
curves, step 1 - 4
Inverse time characteristics, see table 16 curve types See table 147, table 148 and table 149
147, table 148 and table 149
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
64 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M13266-2 v9
Alarm level 1 and 2 (50–99)% of heat content ±2.0% of heat content trip
operate value
Reset level temperature (10–95)% of heat content trip ±2.0% of heat content trip
GUID-E2098AA8-A92F-4F85-98FA-A1BD9D40B3F5 v3
Phase current level for blocking of contact function (5-200)% of lBase ±1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir
Time delay for back-up trip at multi-phase start at 0 to 2 x Iset (0.000-60.000) s ± 0.2% or ± 35 ms whichever is
greater
Additional time delay for a second back-up trip at 0 to 2 x Iset (0.000-60.000) s ± 0.2% or ± 35 ms whichever is
greater
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ± 0.2% or ± 30 ms whichever is
greater
ABB 65
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
SEMOD127592-2 v8
Phase current level for blocking of contact function (5-200)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir
Additional time delay for a second back-up trip at 0 to 2 x Iset (0.000-60.000) s ± 0.2% or ± 35 ms whichever is
greater
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ± 0.2% or ± 30 ms whichever is
greater
S r = 1.732 × U r × I r
Independent time delay to operate for (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
Step 1 and Step 2 at 2 x Sr to 0.5 x Sr and
k=0.000
66 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
SEMOD175159-2 v9
Independent time delay to operate for (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
Step 1 and Step 2 at 0.5 x Sr to 2 x Sr and
k=0.000
ABB 67
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-6A7DA510-E145-4C5B-A7DC-97BC4258E621 v9
Inverse time characteristic According to IEC 60871-1 (2005) ±20% or ±200 ms whichever is greater
and IEEE/ANSI C37.99 (2000)
68 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Definite time delay, step 1 at 1.2 x Uset (0.00-6000.00) s ±0.2% or ±40ms whichever is greater
to 0
Definite time delay, step 2 at 1.2 x Uset (0.000-60.000) s ±0.2% or ±40ms whichever is greater
to 0
ABB 69
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M13304-1 v14
Definite time delay, low step (step 1) at (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is greater
0 to 1.2 x Uset
Definite time delay, high step (step 2) at (0.000-60.000) s ±0.2% or ±45 ms whichever is greater
0 to 1.2 x Uset
70 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M13317-2 v14
Definite time delay low step (step 1) at (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is greater
0 to 1.2 x Uset
Definite time delay high step (step 2) (0.000–60.000) s ± 0.2% or ± 45 ms whichever is greater
at 0 to 1.2 x Uset
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential alarm at 0.8 x UDAlarm to 1.2 x
UDAlarm
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential trip at 0.8 x UDTrip to 1.2 x
UDTrip
Independent time delay for voltage (0.000–60.000)s ±0.2% or ±40 ms whichever is greater
differential reset at 1.2 x UDTrip to 0.8 x
UDTrip
ABB 71
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
SEMOD175210-2 v6
Time delay for enabling the (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
functions after restoration
Time delay to block when all (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
three phase voltages are not
low
72 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Operate time, definite time function at fset (0.000-60.000)s ±0.2% or ±100 ms whichever is greater
+ 0.02 Hz to fset - 0.02 Hz
Reset time, definite time function at fset - 0.02 (0.000-60.000)s ±0.2% or ±120 ms whichever is greater
Hz to fset + 0.02 Hz
Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN-US (Equation 2)
U=Umeasured
M14964-1 v12
Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz ±2.0 mHz
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms
Operate time, definite time function at fset -0.02 Hz to fset +0.02 Hz (0.000-60.000)s ±0.2% ±100 ms
whichever is greater
Reset time, definite time function at fset +0.02 Hz to fset -0.02 Hz (0.000-60.000)s ±0.2% ±120 ms,
whichever is greater
ABB 73
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M14976-1 v10
Definite time delay for frequency gradient trip (0.000-60.000) s ±0.2% or ±120 ms whichever is
greater
74 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Independent time delay, overcurrent at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
0 to 2 x Iset, step 1 - 2
Independent time delay, undercurrent (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
at 2 x Iset to 0, step 1 - 2
Overcurrent (non-directional):
Undercurrent:
Overcurrent:
Inverse time characteristics, see table 16 curve types See table 147, 148 and table 149
147, 148 and table 149
Overcurrent:
Minimum operate time for inverse (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
curves, step 1 - 2
ABB 75
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
0.8 x Uset to 1.2 x Uset, step 1 - 2
Independent time delay, undervoltage (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater
at 1.2 x Uset to 0.8 x Uset, step 1 - 2
Overvoltage:
Undervoltage:
Overvoltage:
Inverse time characteristics, see table 4 curve types See table 153
153
Undervoltage:
Inverse time characteristics, see table 3 curve types See table 154
154
High and low voltage limit, voltage (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
dependent operation, step 1 - 2 ±1.0% of U at U > Ur
Overcurrent:
Undercurrent:
Overvoltage:
76 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Undervoltage:
ABB 77
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Max. = 30 ms
Operate value, alarm for pilot fuse failure (10.0-80.0)% of UBase ±0.5% of Ur
78 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-DAECF9F5-1D0B-43FC-AD29-8F96E05DD0DA v2
ABB 79
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ±2.5 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ±2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ±0.5% of Ur
synchrocheck
Time delay output for synchrocheck when angle difference between (0.000-60.000) s ±0.2% or ±35 ms whichever is
bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 greater
degrees
Maximum closing angle between bus and line for synchronizing (15-30) degrees ±2.0 degrees
tMaxSynch, which resets synchronizing function if no close has been (0.000-6000.00) s ±0.2% or ±35 ms whichever is
made before set time greater
Time delay for energizing check when voltage jumps from 0 to 90% (0.000-60.000) s ±0.2% or ±100 ms whichever is
of Urated greater
Operate time for energizing function when voltage jumps from 0 to Min. = 70 ms –
90% of Urated Max. = 90 ms
80 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M12379-1 v13
Dead time:
shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms
shot 1 “t1 2Ph” whichever is greater
shot 1 “t1 3Ph “
shot 1 “t1 3PhHS”
Extend three-phase dead time duration “tExtended t1” (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Minimum time that circuit breaker must be closed before new sequence is allowed (0.00-6000.00) s ±0.2% or ±35 ms
“tCBClosedMin” whichever is greater
Wait time for the slave to close when WAIT input has reset “tSlaveDeadTime” (0.100-60.000) s ±0.2% or ±35 ms
whichever is greater
Maximum wait time for release from master “tWaitForMaster” (0.00-6000.00) s ±0.2% or ±15 ms
whichever is greater
Wait time after close command before proceeding to next shot “tAutoContWait” (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater
Maximum wait time for fulfilled synchrocheck conditions “tSync” (0.00-6000.00) s ±0.2% or ±45 ms
whichever is greater
Delay time before indicating successful reclosing “tSuccessful” (0.000-60.000) s ±0.2% or ±50 ms
whichever is greater
Maximum wait time for circuit breaker closing before indicating unsuccessful (0.00-6000.00) s ±0.2% or ±45 ms
“tUnsucCl” whichever is greater
ABB 81
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Logic GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2
3 ms 8 ms 100 ms
ALMCALH - - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2
3 ms 8 ms 100 ms
WRNCALH - - 5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2
3 ms 8 ms 100 ms
INDCALH - 5 -
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
GATE 34 10 20
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v3
3 ms 8 ms 100 ms
82 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2
3 ms 8 ms 100 ms
LLD 10 10 20
GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
GUID-C6C98FE0-F559-45EE-B853-464516775417 v3
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XOR 10 10 20
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1
3 ms 8 ms 100 ms
ANDQT - 20 100
ABB 83
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
GUID-C1E61AE5-22CF-4198-97CF-8C8043EE96D2 v1
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10
GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2
3 ms 8 ms 100 ms
INVALIDQT 10 6 6
GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1
3 ms 8 ms 100 ms
INVERTERQT - 20 100
GUID-88B27B3C-26D2-47AF-9878-CC19018171B1 v1
3 ms 8 ms 100 ms
ORQT - 20 100
GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORYQT - 10 30
GUID-341562FB-6149-495B-8A63-200DF16A5590 v1
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1
84 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XORQT - 10 30
GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8
3 ms 8 ms 100 ms
SLGAPC 10 10 54
VSGAPC 10 10 100
AND 80 40 100
OR 80 40 100
PULSETIMER 20 20 49
GATE — — 49
TIMERSET 34 30 49
XOR 10 10 69
LLD — — 49
SRMEMORY 10 10 110
INV 80 40 100
RSMEMORY 10 10 20
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v3
3 ms 8 ms 100 ms
B16I 6 4 8
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2
3 ms 8 ms 100 ms
BTIGAPC 4 4 8
ABB 85
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v2
3 ms 8 ms 100 ms
IB16 6 4 8
GUID-7D6B459F-3050-41A6-A925-1F548AF0E29A v1 GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2
3ms
BCTZCONN 34
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4
Table 94. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v3
3 ms 8 ms 100 ms
INTCOMP 10 10 10
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v4
3 ms 8 ms 100 ms
REALCOMP 10 10 10
86 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
ABB 87
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
88 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M12760-1 v11
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) -
of channels, typical value) at 50 Hz, 280 seconds (80
recordings) at 60 Hz
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
ABB 89
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v9
Independent time delay for spring charging (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
time alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
lockout
Function Value
Resolution 1 ms
Function Value
Buffer capacity Maximum number of indications presented for single disturbance 352
90 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M12702-1 v4
Function Value
Resolution 1 ms
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum 340 seconds (100 recordings) at 50 Hz
number of channels, typical value) 280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value
Time limit for warning supervision, (0 - 99999.9) hours ±0.1% of set value
tWarning
ABB 91
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-09EC65AC-C60B-4256-A601-FE2CC90D26EC v1
Fundamental Harmonic
Frequency (0.95 - 1.05) X fr 2nd order to 5th order (0.1 - 0.5) X Ir ± 2 mHz
Fundamental Harmonic
Frequency (0.95 - 1.05) X fr 2nd order to 5th order (0.1 - 0.5) X V ± 2 mHz
Total Harmonic (10 to 150) V 2nd order to 5th order (0.1 - 0.5) X V ± 4%
Distortion
(VTHD)
92 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Metering M13404-2 v5
Table 119. Function for energy calculation and demand handling ETPMMTR
Energy metering kWh Export/Import, kvarh Input from MMXU. No extra error at steady load
Export/Import
ABB 93
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Function Value
Protocol DNP3.0
Protocol LON
Protocol SPA
Function Value
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
94 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M12589-1 v4
Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
ABB 95
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
Function Value
96 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
M12756-1 v11
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Multi-mode fiber
glass 50/125 µm
Transmission rate / Data rate 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s 2 Mbit/s / 64 kbit/s
Insulation 1 kV
ABB 97
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Hardware
IED
M11778-1 v7 SEMOD53385-1 v1
Table 134. Water and dust protection level according to IEC 60529
Electrical safety
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v2 GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
Connection system
SEMOD53376-2 v6 SEMOD53371-1 v1
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
M12583-1 v8
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
98 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3
ABB 99
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2
Supported types of clock Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock (TC)
Function Value
Accuracy +/-1μs
100 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
SEMOD141136-2 v9
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
ABB 101
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Reset characteristic:
tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
102 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US
I = Imeasured/Iset
ABB 103
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US
I = Imeasured/Iset
GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v4
Table 150. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection
Reset characteristic:
tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
104 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Table 151. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US
I = Imeasured/Iset
Table 152. RI and RD type inverse time characteristics for Sensitive directional residual overcurrent and power protection
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US
I = Imeasured/Iset
ABB 105
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
SEMOD116978-2 v10
U> = Uset
U = Umeasured
k 480
t 2.0
0.035
U Un
32 0.5
Un
IECEQUATION2423 V2 EN-US
k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U> ø
IECEQUATION2421 V1 EN-US
106 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
U< = Uset
U = Umeasured
k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN-US
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
ABB 107
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
U> = Uset
U = Umeasured
108 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0.
Example of a complete code: REB670*2.2-F00X00 - A1000000000000000 - B00000000000000000000000000 - C0824088000282400440200000 -
D22202020 - E66600 - F6 - S0 - G022 - H03020010000 - K00000000 - L1134 - M2400 - P11100000000000000 - B1X0 - AC - CA - B - A3X0 -
CD1D1ARGN1N1XXXXXXX - KKKXXHKKLAGXSY
Impedance protection -
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -
Current protection -
C 0 0 0 0 0 0 0 0 0 0 0 0 0 -
Product REB670*
Product version 2.2
Configuration alternative
Busbar protection REB670 F00
ACT configuration
No ACT configuration downloaded X00
Ordering number
Busbar protection REB670 1MRK002820-AG
ABB 109
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A 0 0 0 0 0 0 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
C 0 0 0 0 0 0 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8
D 0 0 0
Position 1 2 3 4
E 00
110 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Position 1
F
Position 1
S 0
Position 1 2 3
G 0
Position 1 2 3 4 5 6 7 8 9 10 11
H 0 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8
K 0 0 0 0 0 0 0 0
Position 1 2 3
L
ABB 111
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Position 1 2 3 4 5 6
M 0 0 0
Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
P 0 0 0 0 0 0 0 0 0 0 0 0 0 0
112 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Mounting details with IP40 of protection from the front Ordering no Selection Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A
19" rack mounting kit for 3/4 x 19" case or 3xRHGS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D Wall mounting not
recommended with
communication modules with
fiber connection
Flush mounting kit 1MRK002420-PA E
Flush mounting kit + IP54 mounting seal 1MRK002420-NA F
Selected
Human machine hardware interface Case size Ordering no Selection Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B
3/4 x 19”, IEC 1MRK000028-CA
1/1 x 19”, IEC 1MRK000028-BA
Medium size - graphic display, ANSI keypad symbols 1/2 x 19", ANSI 1MRK000028-AB C
3/4 x 19”, ANSI 1MRK000028-CB
1/1 x 19”, ANSI 1MRK000028-BB
Selected
P41/X411
ABB 113
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
When ordering I/O modules, observe the maximum quantities according to the tables below.
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but
can also be freely placed.
Note: The maximum quantity of I/O modules depends on the type of connection terminals.
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19” rack casing, 14 6 4 4 14 *)
one (1) TRM
1/1 x 19” rack casing, 11 6 4 4 11 *)
two (2) TRM
3/4 x 19” rack casing, 8 6 4 4 8 *)
one (1) TRM
3/4 x 19” rack casing, 5 5 4 4 5 *)
two (2) TRM
1/2 x 19” rack casing, 3 3 3 1 3
one (1) TRM
*) including a combination of maximum four modules of type BOM, SOM and MIM
114 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
P14/X141
P15/X151
P16/X161
(front view/rear
view)
ABB 115
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
116 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Table 192. Station communication, remote end serial communication and time synchronization selection
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
view) and type of LDCM
modules supported
depend on the total
amount of I/O and
communication
modules in the IED.
Available slots in 1/2, 3/4 and 1/1 █ █ █ █ █ █ █ █ █ █ █ █ Max 2 LDCM in 1/2
case with 1 TRM case
Available slots in 3/4 and 1/1 case █ █ █ █ █ █ █ █ █ █ █ █ █ █
with 2 TRM K X X X X X X X F
ABB 117
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REB670 *2.2-A31X02- C07H05-B1A12-AC-CA-B-A1A1-CDAB1RGN1N1XXXXXXX-KKKKXHKKLAGFSX. Using the code of each position #1-11
specified as REB70*1-2 2-3 3 3 3 3 3 3-4 4-5 6-7 7- 8-9 9 9 9-10 10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11 11 11 11 11 11 11 11 11
Product version Configuration alternatives Software options Language
# 1 - 2 - 3 - 4 -
REB670* 2.2 - - - -
Binary input/output modules Station communication, remote end serial communication and time
synchronization
10 - 11
-
Position
Product version #1 Notes and rules
Version no. 2.2
Selection for position #1 2.2
118 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Mounting details with IP40 of protection from the front Ordering no #6 Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A Only for A20/B20
19" rack mounting kit for 3/4 x 19" case or 3xRHGS6 1MRK002420-BA B
19" rack mounting kit for 1/1 x 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-DA D Wall mounting not
recommended with
communication modules with
fiber connection
Flush mounting kit 1MRK002420-PA E
Flush mounting kit + IP54 mounting seal 1MRK002420-NA F
Selection for
position #6
ABB 119
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Human machine hardware interface Case size Ordering no #8 Notes and rules
Medium size - graphic display, IEC keypad symbols 1/2 x 19", IEC 1MRK000028-AA B Only for A20/B20
3/4 x 19”, IEC 1MRK000028-CA
1/1 x 19”, IEC 1MRK000028-BA Only for A31/B21/B31
Medium size - graphic display, ANSI keypad symbols 1/2 x 19", ANSI 1MRK000028-AB C Only for A20/B20
3/4 x 19”, ANSI 1MRK000028-CB
1/1 x 19”, ANSI 1MRK000028-BB Only for A31/B21/B31
Selection for
position #8
P40/X401
P41/X411
slot P41/X411 is optional for
B21 and not valid for A20 and
B20. A31/B31 require two TRMs.
No Transformer input module included X0 X0 Only valid if IEC 61850-9-2
Process bus communication is
selected.
TRM 12I 1A, 50/60 Hz, compression terminals 1MRK002247-CG A1 A1
TRM 12I 5A, 50/60 Hz, compression terminals 1MRK002247-CH A2 A2
TRM 12I 1A, 50/60 Hz, ring lug terminals 1MRK002247-CC B1 B1
TRM 12I 5A, 50/60 Hz, ring lug terminals 1MRK002247-CD B2 B2
Selection for
position #9
120 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
view) rack, 8 in 3/4 rack with
1 TRM, 5 in 3/4 rack
with 2 TRM and 11 in
1/1 rack with 2 TRM
1/2 case with 1 TRM █ █ █ Only for A20/B20
3/4 case with 1 TRM █ █ █ █ █ █ █ █ Only for A20/B20
3/4 case with 2 TRM █ █ █ █ █ Only for A31/B21/B31
1/1 case with 2 TRM █ █ █ █ █ █ █ █ █ █ █ Only for A31/B21/B31
Compression terminals C
No board in slot X X X X X X X X X
Binary output module 24 output 1MRK000614-AB A A A A A A A A A A Maximum 4 BOM+SOM
relays (BOM) boards. P5 not in B21/
B31.
One BOM required in
postion P4.
BIM 16 inputs, RL24, 24-30VDC, 50 1MRK000508-DD B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 1 BIM required in
mA position P3. 2 BIMs
required in position P3
and P5 for B21 and B31.
BIM 16 inputs, RL48, 48-60VDC, 1MRK000508-AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
50mA
BIM 16 inputs, RL110, 110-125VDC, 1MRK000508-BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
50mA
BIM 16 inputs, RL220, 220-250VDC, 1MRK000508-CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
50mA
BIM 16 inputs, RL220, 220-250VDC, 1MRK000508-CE E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
120mA
BIM 16 inputs, RL24, 24-30VDC, 1MRK000508-HA F F F F F F F F F P5 not in B21/B31
50mA, enhanced pulse counting
BIM 16 inputs, RL48, 48-60VDC, 1MRK000508-EA G G G G G G G G G
50mA, enhanced pulse counting
BIM 16 inputs, RL110, 110-125VDC, 1MRK000508-FA H H H H H H H H H
50mA, enhanced pulse counting
BIM 16 inputs, RL220, 220-250VDC, 1MRK000508-GA K K K K K K K K K
50mA, enhanced pulse counting
IOM 8 inputs, 10+2 outputs, RL24, 1MRK000173-GD L1 L1 L1 L1 L1 L1 L1 L1 L1
24-30VDC, 50mA
IOM 8 inputs, 10+2 outputs, RL48, 1MRK000173-AE M1 M1 M1 M1 M1 M1 M1 M1 M1
48-60VDC, 50mA
IOM 8 inputs, 10+2 outputs, RL110, 1MRK000173-BE N1 N1 N1 N1 N1 N1 N1 N1 N1
110-125VDC, 50mA
IOM 8 inputs, 10+2 outputs, RL220, 1MRK000173-CE P1 P1 P1 P1 P1 P1 P1 P1 P1
220-250VDC, 50mA
IOM 8 inputs 10+2 outputs, RL220, 1MRK000173-CF P2 P2 P2 P2 P2 P2 P2 P2 P2
220-250VDC, 110mA
IOM with MOV 8 inputs, 10+2 1MRK000173-GC U U U U U U U U U
outputs, RL24, 24-30VDC, 50mA
IOM with MOV 8 inputs, 10+2 1MRK000173-AD V V V V V V V V V
outputs, RL48, 48-60VDC, 50mA
IOM with MOV 8 inputs, 10+2 1MRK000173-BD W W W W W W W W W
outputs, RL110, 110-125VDC, 50mA
IOM with MOV 8 inputs, 10+2 1MRK000173-CD Y Y Y Y Y Y Y Y Y
outputs, RL220, 220-250VDC,
50mA
SOM Static output module, 12 1MRK002614-BA T1 T1 T1 T1 T1 T1 T1 T1 SOM must not to be
outputs; 6 standard relays + 6 placed in the position
static outputs, 48-60VDC nearest to NUM: 1/2
case slot P5, 3/4 case 1
SOM Static output module, 12 1MRK002614-CA T2 T2 T2 T2 T2 T2 T2 T2
TRM slot P10, 3/4 case
outputs; 6 standard relays + 6
2 TRM slot P7, 1/1 case
static outputs, 110-250VDC
2 TRM slot P13.
P5 not in B21/B31.
Selection for C
position #10
ABB 121
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
P31:1/X311
P31:2/X312
P31:3/X313
P32:2/X322
P32:3/X323
LDCM mode
view) and type of LDCM
modules supported
depend on the total
amount of I/O and
communication
modules in the IED.
Available slots in 1/2 and 3/4 case █ █ █ █ █ █ █ █ █ █ █ █
with 1 TRM
Available slots in 3/4 and 1/1 case █ █ █ █ █ █ █ █ █ █ █ █ █ █
with 2 TRM
No communication board X X X X X X X X X X X X
included
Ethernet SFP, optical LC 1MRK005500-AA K K K K K K Ethernet SFP is basic
connector in P30:1. P30:6:1 and
P30:6:2 require the
Ethernet SFP, RJ45 connector 1MRK005500-BA P P P P P P
Optical Ethernet
module in P30:6.
Optical Ethernet module 1MRK002266-EA H
Serial SPA/LON/DNP/IEC 1MRK001608-AB L
60870-5-103 plastic interface
Serial SPA/LON/DNP/IEC 1MRK001608-BB M
60870-5-103 plastic/glass
interface
Serial SPA/LON/DNP/IEC 1MRK001608-CB N
60870-5-103 glass interface
Galvanic RS485 communication 1MRK002309-AA G G G
module
Optical short range LDCM 1MRK002122-AB A A A A A A Max 2 LDCMs can be
ordered. Always place
LDCM modules on the
same board to support
redundant
communication: in
P30:5 and P30:6, P31:2
and P31:3 or P32:2 and
P32:3.
Line data communication, default — X Default if no LDCM is
64kbps mode selected
Allow line data communication in 1MRK007002-AA Y
2Mbps mode
GPS time module 1MRK002282-AB S S S S
IRIG-B time synchronization 1MRK002305-AA F F F F
module
Selection for
position #11
122 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Accessories IP15151-1 v1
External current transformer unit
SEMOD123520-4 v5
3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 5/1 A Quantity: 1MRK 000 643-FA
3 pcs SLCE 8–1 summation transformers on apparatus plate (2U high), 2/1 A Quantity: 1MRK 000 643-GA
Cable for antenna, 40 m (Appx. 131 ft) Quantity: 1MRK 001 665-BA
ABB 123
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
Protection cover
M15040-3 v7
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-TA
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-SA
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-RA
Combiflex
IP15161-1 v1
Key switch for lock-out of settings via LHMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
SEMOD130267-5 v8
Mounting kit
Side-by-side mounting kit Quantity: 1MRK 002 420-Z
Front connection cable between LHMI and PC Quantity: 1MRK 001 665-CA
SEMOD131414-4 v4
Note: One (1) IED Connect USB flash drive containing user documentation (Operation manual,
Technical manual, Installation manual, Commissioning manual, Application manual and Getting
started guide), Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect USB flash drive requested. Quantity: 1MRK 002 290-AE
124 ABB
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity: 1MRK 505 370-UEN
Communication protocol manual, IEC 61850 Edition 1 IEC Quantity: 1MRK 511 392-UEN
Communication protocol manual, IEC 61850 Edition 2 IEC Quantity: 1MRK 511 393-UEN
Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 394-UEN
ABB 125
Busbar protection REB670 1MRK 505 373-BEN G
Version 2.2
For our reference and statistics we would be pleased to be provided with the following application data:
Documents related to REB670 Document numbers Operation manual IEC:1MRK 500 127-UEN
ANSI:1MRK 500 127-UUS
Application manual IEC:1MRK 505 370-UEN
ANSI:1MRK 505 370-UUS Engineering manual IEC:1MRK 511 398-UEN
ANSI:1MRK 511 398-UUS
Commissioning manual IEC:1MRK 505 372-UEN
ANSI:1MRK 505 372-UUS Installation manual IEC:1MRK 514 026-UEN
ANSI:1MRK 514 026-UUS
Product guide 1MRK 505 373-BEN
Communication protocol 1MRK 511 391-UUS
Technical manual IEC:1MRK 505 371-UEN manual, DNP3
ANSI:1MRK 505 371-UUS
Communication protocol 1MRK 511 394-UEN
Type test certificate IEC:1MRK 505 373-TEN manual, IEC 60870-5-103
ANSI:1MRK 505 373-TUS
Communication protocol 1MRK 511 392-UEN
manual, IEC 61850 Edition 1
126 ABB
127
ABB AB
Grid Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Scan this QR code to visit our website
www.abb.com/protection-control
1MRK 505 373-BEN