Model 483C41 Eight-Channel ICP®/Voltage/Charge Sensor Signal Conditioner Installation and Operating Manual
Model 483C41 Eight-Channel ICP®/Voltage/Charge Sensor Signal Conditioner Installation and Operating Manual
Toll-free: 800-828-8840
24-hour SensorLine: 716-684-0001
Fax: 716-684-0987
E-mail: [email protected]
Web: www.pcb.com
Service, Repair, and Return
Policies and Instructions
The information contained in this document supersedes all similar information that
may be found elsewhere in this manual.
GENERAL OPERATION
MANUAL
For powering ICP®, and charge sensors, this signal conditioner provides an effective method for
managing large numbers of sensor channels. A simple command set, entered through industry
standard interface, allows the user to generate powerful application-specific programs to automate
system testing.
PCB PIEZOTRONICS, INC. 3425 WALDEN AVENUE DEPEW, NY 14043-2495 PHONE 716-684-0001 FAX 716-684-0987
®
ICP is a registered trademark of PCB Group, Inc.
Table of Contents
Table of Contents i
Table of Figures iii
1-0. INTRODUCTION AND SPECIFICATIONS 1
1-1. Introduction: Safety Considerations 1
1-2. System Description 2
®
1-2.1 ICP Input/Output Mode 2
1-3. Block Diagram 2
1-4. Installation 2
1-4.1 Grounding Techniques 3
1-5. Operation: Standard AC Line 3
1-6. Maintenance and Repair 3
2-0. THEORY OF OPERATION 3
2-1. Sensor Excitation 3
2-2. Input Protection 4
2-3. ICP® Input Fault Detection 4
2-4. Input Interface 4
2-5. Gain 4
2-6. Normalized Output Sensitivity 5
2.7. Low Pass Input Filter 5
2.8. Overload Detection 5
2-9. Connector Configuration 6
2-10 Non-Volatile Memory 6
2-11 Transducer Electronic Data Sheet (TEDS) Interface: 6
3-0. FRONT PANEL MODULE CONTROL 6
3-1. Introduction 6
3-2. Unit Initialization 6
3-3. Main Menu Format 7
3-4. Submenu Format and Command Selections 7
1) Gain Functionality 7
2) Sensor Input Mode 9
3) Input Filter 9
4) Output Filter 9
5) ICP Current Adjustment 10
6) Voltage Excitation 10
7) Input Coupling 11
8) Auto zero/ Auto balance 11
i
MODEL 483C41 GENERAL OPERATION MANUAL ii
9) Auto Range 11
10) Switched Output 12
11) Clamp 12
12) Bias Measurement 12
13) Channel Output Measurement 13
14) Calibration 13
15) LED Test 14
16) Firmware Version 14
17) Unit ID 14
18) Reset to Factory Default Settings 15
19) Display Content Options 15
20) Save Current Settings 16
21) Reserved 16
4-0. COMPUTER INTERFACE PROGRAMMING GUIDE 16
4-1. Introduction 16
4-2. Ethernet Communication 16
4-3. Communication Guidelines 20
4-4. Unit Initialization Procedure 20
4-5. Command Summary 21
4-6. Command Format 21
4-7. Multiple Board Models 22
4-8. Commands 22
GAIN 22
SENS 22
FSCI 23
FSCO 23
INPT 24
IEXC 24
FLTR 24
OFLT 25
CALB 25
RTED 26
ALLC 26
RBIA 26
STUS 27
UNIT 27
UNID 28
LPCR 28
LEDS 28
RSET 29
SAVS 29
Communication Responses 29
MODEL 483C41 GENERAL OPERATION MANUAL iii
Table of Figures
The following symbols and terms may be found on the equipment described in this manual.
This symbol on the unit indicates that the user should refer to the operating instructions located in the manual.
This symbol on the unit indicates that high voltage may be present. Use standard safety precautions to avoid personal
contact with this voltage.
This symbol indicates that the test fixture, Model 483C41, must be connected to earth ground via the power cord.
The WARNING heading used in this manual explains dangers that might result in personal injury or death. Always read
the associated information very carefully before performing the indicated procedure.
The Caution heading used in this manual explains hazards that could damage the instrument.
WARNING 1: The power supply/signal conditioner should not be opened by anyone other than qualified service
personnel. This product is intended for service by qualified personnel who recognize shock hazards and are familiar with
the safety precautions required to avoid injury.
WARNING 2: This equipment is designed with user safety in mind; however, the protection provided by the equipment
may be impaired if the equipment is used in a manner not specified by PCB Piezotronics, Inc.
Caution 1: Cables can kill your equipment. High voltage ElectroStatic Discharge (ESD) can damage electrical devices.
Similar to a capacitor, a cable can hold a charge caused by triboelectric transfer, such as that which occurs in the
following:
The solution for product safety: 1) Connect the cables only with the AC power off. 2) Temporarily “short” the end of the
cable before attaching it to any signal input or output.
Caution 2: ESD considerations should be made prior to performing any internal adjustments on the equipment. Any
piece of electronic equipment is vulnerable to ESD when opened for adjustments. Internal adjustments should therefore
be done ONLY at an ESD-safe work area. Many products have ESD protection, but the level of protection may be
exceeded by extremely high voltage that is typically present in normal situations.
EQUIPMENT RATINGS
For complete specifications, please refer to the enclosed Specification Sheet. This equipment operates optimally at +32 to
+120°F (0 to +50°C), in an environment having <85% relative humidity.
This model requires 100 to 240 VAC / 47 to 63 Hz to operate. In turn, it supplies up to 20 mA of constant current
excitation at 24 VDC to any connected ICP sensors or ICP in-line charge converters.
MODEL 483C41 GENERAL OPERATION MANUAL 2
1-4. Installation
This signal conditioner model comes in a standard 19-inch rack mount enclosure with a 1U (1.75”) height. The enclosure
should be located in such a way as to allow convenient access to the power outlet for disconnect purposes. Since these
models have low power consumption, they can be located in confined environments.
MODEL 483C41 GENERAL OPERATION MANUAL 3
1. Make sure the signal ground lines of all equipment are tied together. The signal grounds of the channels are typically
tied together via the case of the input and output BNC connectors. The individual channels of these models have their
signal ground line tied together internally at the power supply.
2. Insure that the sensor does not pick up line noise from the body under test. The case of the sensor should be isolated
from the body under (ground) using an isolation pad. The isolation pad breaks the loop formed by the signal path of the
sensor to the signal conditioner and the return (ground) from the signal conditioner back to the sensor.
3. Make sure that all equipment signal grounds of the test system are tied to the Earth ground at a single point and the
connections linking the equipment ground are made using a wire that can provide a very low impedance connection.
CAUTION: Refer to the rear panel for proper input voltage and currents.
Sensor excitation occurs as the constant current of all channels are set. 483C41 allows the constant current to be adjusted
up to 20 mA to provide the required excitation for most applications. Special situations, such as driving extra-long cables
(more than 1000 ft) with high frequency or fast rise time pulses, may require increasing the drive current to 12 mA or
higher.
Two voltage comparators consist of a window comparator that has two reference voltages (V ref) representing thresholds
for “short” and “open.” When the sensor’s bias voltage (Vbias) exceeds the comparator range, the front panel input fault
LED lights.
Voltage mode is similar to ICP® mode, except the excitation current is 0 mA. In charge mode, the signal from the charge
sensor is routed into a charge amplifier with a gain of 0.1, 1.0, or 10 mV/pC, followed by incremental voltage gain.
2-5. Gain
The Programmable Gain Amplification (PGA) block consists of a decimal gain amplifier. See Figure 5.
1 Volt
Gain = / Sensitivity (mV/unit)
Additionally, a feature to improve flexibility allows changing the output level to a value of 5 Volts/ unit instead of
normalized 1 Volt/ unit. Some users request the ability calculate the gain using a known input signal along with the sensor
sensitivity, and desired output level. The result of the request impacts the formula:
1 Volt/
Gain = / [Sensitivity (mV/unit) * Full Scale Input (units)]
Adding some simple error checking to insure the limits of the sensor and gain limits of the signal conditioner are not
exceeded completes the normalization process.
The error checking should provide a flag if the desired normalized output level is not feasible due to gain limitations. The
gain required may be too large given the sensor sensitivity defined, or too small which implies the sensor will not be
capable measure the expected value. The typical sensor will output a signal up to 5 Volts. The maximum swing may be
used in the error checking.
The 483C41 has the capability to provide signal conditioning for charge mode sensors in addition to the standard ICP
type. The sensitivity (mV/ pC) of the charge conversion will allow charge mode sensors (pC/ unit) to be normalized.
The current TEDS function will perform a read of the “raw” TEDS data and return the 32 bytes of TEDS sensor
EEPROM data and the 8 byte Application register contents, if it was programmed, and returns the data in an ASCII Hex
representation.
PCB 483C41
FW Ver n.n
The unit is initialized with the factory default settings.
The factory defaults are:
Gain = 1.0
Sensitivity = 10.0
Full Scale input = 1000.0
Full Scale output = 10.0
Input Mode = ICP®
Input Filter = Disabled
MODEL 483C41 GENERAL OPERATION MANUAL 7
Gain Type (GType on front panel): Allows the user to choose how the gain of each channel can be set. The selections
in the submenu are Gain and Normalize (Gain is the factory default setting). Pressing ENTER brings up the submenu
shown below. The up and down arrow key can be used toggle between the two options.
If the user attempts to use a menu selection (SENS, FSOT, FSIN, GAIN) that conflicts with the GType setting the
message ‘Invalid Item for Gain Entry Type’ will be displayed.
Gain (GAIN on front panel): Directly sets the gain value of each channel. For ICP®/voltage input modes: .1 to 200.0.
For charge mode: .01 to 2000.0. GType must be set to the Gain selection. See section 1-4.2c for instructions on setting
the gain directly. The gain step is .1.
NOTE: A microprocessor inside the conditioner transparently sets the charge and voltage gains when in charge mode.
This is done so sub-optimum values cannot be selected (ie – setting a low charge gain with a high voltage gain). Highest
resolution is achieved if the charge gain is set as high as possible.
Sensitivity (SENS on front panel): The sensor sensitivity is entered here using the and arrow keys and then
hitting Enter. GType must be set to the Normalize selection.
Full Scale Input (FSIN on front panel): The estimated full scale mechanical input (ex – engineering units, g’s, psi, bar,
etc.) is entered here using the and arrow keys and then hitting Enter. GType must be set to the Normalize
selection.
Full Scale Output (FSOT on front panel): The desired full scale output voltage is entered here using the and
arrow keys and then hitting Enter. GType must be set to the Normalize selection.
The submenus for SENS, FSIN and FSOT appear like this:
Normalized Output Example: A full scale output of 5 volts is desired and a full scale input of 380 engineering units is
expected. The sensor sensitivity is 9.96 mV/g. These values should be entered into FSOT, FSIN and SENS respectively.
The gain will be automatically set to 1.3 to give a 5 volt full scale output based on the expected input and sensor
sensitivity.
Normalization is useful when standardizing the output of channels with sensors of different sensitivities. Consider the
following example where 1V/unit standardization on each channel is desired:
NOTE: The GAIN menu selection will not show what the gain is set at when in the Normalize GType setting.
MODEL 483C41 GENERAL OPERATION MANUAL 9
Each channel’s Output filter setting can be set independently of the other channels. To change the Output Filter setting
from the main menu, use the left / right arrow key until the cursor is over the FLTo option, and then press the Enter
button.
MODEL 483C41 GENERAL OPERATION MANUAL 10
NOTE: The ON setting also indicates the filter corner, in kHz, implemented by the filter for the channel.
This Option is
Not Installed
7) Input Coupling (ACDC on front panel):
The input coupling option is not applicable to the 483C41 units. 483C41 is AC coupled only.
This Option is
Not Installed
8) Auto zero/ Auto balance (ZERO on front panel):
The Auto Zero/Auto Balance option is not applicable to the 483C41 units.
This Option is
Not Installed
9) Auto Range (ARNG on front panel):
The auto-range option is not applicable to the 483C41 units.
MODEL 483C41 GENERAL OPERATION MANUAL 12
This Option is
Not Installed
10) Switched Output (SWOT on front panel):
The Switched Output option is not applicable to the 483C41 units.
This Option is
Not Installed
11) Clamp (CLMP on front panel):
The Clamp option is not applicable to the 483C41 units.
This Option is
Not Installed
Chan Bias
2 0023.7
If unit had a short circuit, the bias voltage would be <2.0V. Proper bias voltage is between 2.0V and 22V. Anything over
22V would indicate an open circuit.
This Option is
Not Installed
14) Calibration (CAL on front panel):
The user may select the Internal Calibration setting by pressing the ENTER key on the front panel when the cursor is
located on the CAL option. When either the 100 or 1k Hz setting is selected the channel is forced into a charge mode, if it
isn’t set that way already, and an internal 100pC signal is generated. This signal is then converted to a voltage based on
the selected charge sensitivity (1mV/pC if the ICP setting was selected) after which the channels gain is applied to
provide an internal cal signal.
LED Test
CANCEL
Use the up or down arrow keys to select ‘Execute’ or ‘Cancel’. Both options return control to the main menu. If ‘Execute’
is selected then the LED’s will blink 3 times if ‘Cancel’ is selected then no action is taken.
PCB 483C41
FW Ver 1.6
17) Unit ID (Unit on front panel):
The user may change the Unit ID setting by pressing the ENTER key on the front panel when the cursor is located on the
Unit option.
The following submenu will appear. Use the up or down arrow key to change the Unit Id setting to a new value. Once
you have the desired setting selected hit ENTER to apply it.
Current Unit #
1
NOTE: Changing the Unit ID is only necessary if you have the Ethernet or RS-232 communication option installed and
you are communicating with more than one unit. If this is the case then all units in the network MUST have a unique ID.
Factory Defaults
Execute
19) Display Content Options (Disp on front panel):
The Display option allows the user to Lock or Unlock the display. To enter this mode, select the ‘DISP’ option from the
menu by placing the cursor over the display option and hitting enter.
Display Opts
Lock
If Lock is selected the any attempt to change another setting will cause the message “Unlock Display to Proceed” to be
displayed. The user must then reset the display option to UNLOCK to change any other setting.
MODEL 483C41 GENERAL OPERATION MANUAL 16
Save Settings
Execute
21) Reserved (Res on front panel):
No operation. These menu items are reserved for future use.
Selecting an item from the list, shown below, highlights the item in the list and enables more icons.
Select Assign IP and the following screen will appear. Select whether you want to assign a static IP address that
is appropriate for your network or have it assigned from a network server. Subsequent steps are self-explanatory.
Now you can use the assigned IP address to address the unit.
MODEL 483C41 GENERAL OPERATION MANUAL 18
Important Note: The communication protocol requires a unit id as part of the command header. The unit id is
not the IP address. To send commands to the unit Via Ethernet you must address the TCP-IP packets with the
proper IP address and ensure the packet payload contains the correct Unit Id in the command header.
The XPort device should be configured properly for communication with the signal conditioner. If problems
occur please check the communication parameters of the device as shown below.
Navigate to the actual device as shown in the left panel above and then click on the ‘Web Configuration’ tab and clock on
the ‘Go’ button. This will cause the following screen to appear, just select ‘OK’. There are no login parameters defined.
Following this screen the right panel will appear as shown below. Click on the ‘Connection’ item and check to see that
the parameters are shown as below and pay particular attention to the ‘Active Connection’ and ‘Endpoint’ Port items.
They should be set as shown below.
Next, check the Serial Settings. They should be 19200 baud, 8 data bits, no parity, 1 stop bit. And no flow control.
If any setting is changed click ‘Ok’ on the page and then activate the ‘Apply Settings’ item on the left side of the right
panel.
MODEL 483C41 GENERAL OPERATION MANUAL 19
MODEL 483C41 GENERAL OPERATION MANUAL 20
2) The number of characters for any command string, from the first character to the <CR>, may not exceed 255.
3) Status request commands, i.e., commands ending with a “?”, may only be sent within one transmission.
Example: 7:0:GAIN?<CR> <LF>
-Reads the gain setting of all channels.
“1:0:LEDS=0” <CR><LF>
R/W – the setting can be read from or written to the unit or channel.
R – The information can only be read from the unit or channel.
FCN – The command invokes a function in the unit.
Command Format:
'Unit#:Ch#:Cmd[=|?]{<value1 >{,< value2 >}}{;Ch#:Cmd[=|?]{<value1>{,< value2>}}}\n\r
Each message must be preceded by a Unit# & Channel# (both of which could be 0)
Messages may contain multiple commands separated by a semicolon ‘;’.
The second and subsequent commands in a message shall not contain a unit number but shall contain a channel
number.
Each command in a message will evoke a response message if one is warranted (not global)
Query’s ('?') can only be directed to one unit but if the channel=0 then each channel's setting will be returned in
the order 0-MAXCHANNELS separated by a ':'
MODEL 483C41 GENERAL OPERATION MANUAL 22
Command examples:
1:0:GAIN=100.2\r\n unit 1,all channels gain set to 100.2
1:1:GAIN=100.2;2:GAIN=120.3\r\n unit 1, channel 1 gain = 100.2; channel 2 gain = 120.3
1:3:GAIN=100.2;0:FLTR=1\r\n unit 1, channel 3 gain = 100.2; all channel’s filter = ON
Responses to a query with a channel number=0 will return the setting of each channel in a list separated by
semicolons ‘;’.
If the target of the query is a unit setting (ex. current excitation) then the channel number returned is the 1 st
channel of the board that processed the command.
Likewise, a global Query command will be responded to by the channel 1-4 board but will be ignored by the channel 5-8
board. However, in order to facilitate efficient communications with the second board, a second unit address was is used
to query the second board. A user’s control application can direct global channel setting queries to the second board of a
unit by addressing the query to the secondary unit address of the unit. The secondary unit address is defined to be the
normal unit address plus 128 (ex. If a unit’s address is 1 then the 2nd board’s address would be 129)
4-8. Commands
GAIN
SET GAIN: This command sets the programmable gain of a channel.
Setting:
The amplifier gain can be set directly by sending a Gain command:
When a channels gain is set directly the unit will adjust the FSI parameter of the gain equation using the
following equation; FSI = (((FSO*1000)/Gain)/Sens) to ensure it remains valid.
Query:
The Gain query returns all of the parameters used to determine it in a single response
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:=Gain:SENS:FSO:FSI;
Query: 1:5:GAIN?
Response: 1:GAIN:5= 5.0: 10.0: 10.0: 200.0;
SENS
The SENS command provides a mechanism to have the transducer Sensitivity influence the Gain setting of the
channel. Channel Gain is calculated using the equation;
MODEL 483C41 GENERAL OPERATION MANUAL 23
Gain = FSO*1000/(FSI*SENS). If a Sensitivity is entered that caused the gain to exceed the amplifiers
capability the FSI component will be adjusted to keep the equation valid.
Setting:
1:0:SENS=20.2\r\n (unit 1,all channels transducer sensitivity set to 20.2)
Setting Response: 1:SENS:ok
Query:
The SENS query returns the channels transducer sensitivity
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:= SENS;
Query: 1:1:SENS?
Response: 1:SENS:1= 6.0;
FSCI
The FSCI command provides a scaling mechanism to automatically set the gain based on a known input level (in
EU) and what output level (in Volts) you would like that Full Scale input level to be represented by. For instance
1000g’s = 10Volts. These 2 values along with the transducer sensitivity set the gain. Channel Gain is calculated
using the equation: Gain = FSO*1000/(FSI*SENS).
Setting:
1:1:FSCI=1000.000\r\n (unit 1, channel 1 FSI set to 1000.0)
Setting Response: 1:FSCI:ok
Query:
The FSCI query returns the channels Full Scale Input value in engineering units
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:= <fsci>;
Query: 1:1: FSCI?
Response: 1:FSCI:1=1000.0;
FSCO
The FSCO command provides a scaling mechanism to automatically set the gain based on a known input level
(in EU) and what output level (in Volts) you would like that Full Scale input level to be represented by. For
instance 1000g’s = 10Volts. These 2 values along with the transducer sensitivity set the gain. Channel Gain is
calculated using the equation:
Gain = FSO*1000/(FSI*SENS).
Setting:
1:1:FSCO=10.000\r\n (unit 1, channel 1 FSI set to 10.0)
Setting Response: 1:FSCO:ok
Query:
The FSCO query returns the channels Full Scale Output Value in volts
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:= <fsci>;
Query: 1:1: FSCO?
Response: 1:FSCO:1=10.0;
MODEL 483C41 GENERAL OPERATION MANUAL 24
INPT
The INPT command sets the input mode for a given channel. The mode selection is sent as an integer value. The
possible input modes and their associated values are:
CHARGE 0
VOLTAGE 1
ICP® 2
Setting:
1:1:INPT= 2\r\n (unit 1, channel 1 input mode set to ICP)
Setting Response: 1:INPT:ok
Query:
The INPT query returns the channels input mode selection
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:= <INPT>;
Query: 1:1:INPT?
Response: 1:INPT:1= 2;
IEXC
The IEXC command sets the current excitation level for a channel in ICP mode. The current excitation value is
sent as an integer value from 0 (off) to 20mA. If a channel’s input mode changes to Voltage mode then this
value will be forced to 0 automatically.
Setting:
1:1:IEXC= 2\r\n (unit 1, channel 1 is set to 2mA)
Setting Response: 1:IEXC:ok
Query:
The IEXC query returns the units excitation value.
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:= <IEXC>;
Query: 1:1:IEXC?
Response: 1:IEXC:1=2;\r\n
FLTR
The FLTR command selects the Input Filter corner (1-6) or Disables the Filter (0).
The standard factory installed corner selections are:
0= OFF
1=30 kHz
2=10 kHz
3=3 kHz
4=1 kHz
5=300 Hz
MODEL 483C41 GENERAL OPERATION MANUAL 25
6=100 Hz
Setting:
1:1:FLTR= 1\r\n ( unit 1, channel 1, Input Filter Enabled; Corner=30 kHz)
Setting Response: 2: FLTR:ok
Query:
The FLTR query returns the channels Output Filter.
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:= <0-6>;
Query 1:1:FLTR?;
Response:: 1:FLTR:1=1;\r\n
OFLT
The OFLT command enables or disables the Output Filter.
The Output Filter value is sent as an integer value of either 0 -Disable or 1-Enable.
Setting:
2:1:OFLT= 1\r\n ( unit 2, channel 1, Output Filter Enabled )
Setting Response: 2: OFLT:ok
Query:
The FLTR query returns the channels Output Filter.
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Ch#:= <0|1>;
Query: 2:1: OFLT?
Response: 2: OFLT:1=1;
CALB
The CALB command selects the Internal Calibration Reference Oscillator setting. When either the 100 or 1k Hz
setting is selected the channel is forced into a charge mode, if necessary, and an internal 100pC signal is
generated. This signal is then converted to a voltage after which the channels gain is applied to provide an
internal cal signal.
The CALB value is sent as an integer value of either 0 –Disable, 1-1000 Hz Enable, 2-100 Hz Enable
Setting:
1:1: CALB= 1\r\n (unit 1, channel 1, Oscillator=1 kHz )
Setting Response: 1:CALB:ok
Query:
The CALB query returns the channels Internal Reference Oscillator setting.
Query Format: Unit#:Ch#:CMD?
Response format:
Unit#:Cmd:Ch#:= <0|1>;
Query: 1:1: CALB?
Response: 1:CALB:1=1;\r\n
RTED
The RTED query returns the TEDS information that is stored in the sensor or other, TEDS capable, in-line
module attached to a specific channel. The signal conditioners are IEEE 1451.4 compliant in that they will read
the DS2430A Application Register Status to see if it indicates the 64 bit Application Register has data in it. If so
it will read the Application register contents and return it followed by the contents of the TEDS EEPROM.
NOTE: The 1st byte of the DS2430A EEPROM data should contain the checksum of both the Application
Register contents and the EEPROM contents if the TEDS is IEEE 1451.4 compliant. No attempt is made to
validate or interpret the TEDS data.
Setting:
N/A – Command is Read only
Query:
The RTED query returns the TEDS data associated with the specified channel. This command must be directed
to a specific channel. It will return an indicator that specifies if the DS2430A Application register has been used
to store the basic TEDS data and up to 40 bytes in ASCII Hex format (8 bytes of Application register content if
it was burned and 32 bytes of the EEPROM content).
Query: 1:1:RTED?
Response: (for TEDS chip on channel 1 with valid app register data)
1:RTED:1=1:168010a00975000012648016a88ae8e112801f2000f60ec4046dd18737f3206a380555e76
5390800
ALLC
The ALLC command is used to read several channel settings at once.
Setting:
N/A – Command is Read only
Query:
This command must be a directed command use of the global channel indicator is not allowed.
NOTE: Some items returned may not be applicable for every model
RBIA
The RBIA command is used to read all channels Bias Levels.
MODEL 483C41 GENERAL OPERATION MANUAL 27
Setting:
N/A – Command is Read only
Query:
This command is a global command and will return all channel bias readings regardless of the channel id in the
command.
STUS
The STUS command is used to read the unit and all channel status indicators.
Setting:
N/A – Command is Read only
Query:
This command is a global command and will return all channel bias readings regardless of the channel id in the
command.
Where :
Unit Bit 0 = 1= BAD EEPROM read for channel settings on power up
Unit Bit 1 = 1= BAD EEPROM read for Unit options on power up
Unit Bit 2 = 1= BAD EEPROM read for cal factors on power up
For Unit bit map 0=no errors
Channel Bit 0= Open input fault (0=Fault; 1 = no fault)
Channel Bit 1= Short input fault (0=Fault; 1 = no fault)
Channel Bit 2= Overload condition (0=Overload; 1 = no Overload)
For channel bit map 7=no errors
UNIT
Query:
The UNIT query returns the unit configuration information which includes the installed options, unit number,
Model id and starting channel number
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:Model string:Firmware Ver string: Serial Number:Cal Date:
Unit#:#channels:Starting Ch#: Gain Option byte, Input Option Byte, Filter option byte,Misc1 option byte,Misc2
option byte: fixed or 1st option of input Filter corners: output filter corners<cr><lf>
Query: 1:1:UNIT?
Response :1:UNIT:483C41\s\s\s\s\s\s\s\s\s\s:FW\sVer\s4.00\s\s\s\s\s:12345:06-28-
2011:1:4:1:16,10,16,140,132:30.00000:30.00000:30.00000:30.00000:0.00000:0.00000:0.00000:0.00000:\r\n
UNID
The UNID command is used to set the units ID number. The Unit Id number is critical to remote
communications since it indicates to the unit which commands it should accept and respond to. Units are
typically shipped with a unit id of 1. If more than one unit is in the system and they will be communicated with
remotely the user must set a unique id in each unit. This can be done through the front panel interface, if one
exists, or by connecting to each unit individually and sending this command.
Setting:
1:1:UNID= 2\r\n ( unit 1, channel 1, New ID=2 )
Query:
This command can be sent as a query but its usefulness is marginal being as it is a directed command and as
such it is necessary to include the Unit Id in the command and the response will simply validate the commands
unit id parameter.
Query Format: Unit#:Ch#:UNID?
Response format: Unit#:Cmd:Ch#:=unit id
Query: 2:1:UNID?
Query Response: 2:UNID:1=2;
LPCR
Query:
The LPCR query returns the unit low pass filter corners
Query Format: Unit#:Ch#:CMD?
Response format: Unit#:Cmd:,<num corners>< n filter corners> <cr><lf>
Query: 1:1:LPCR?
Response: 1:LPCR:6.000:30.000:10.000:3.000:1.000:0.300:0.100:\r\n
Global Query: 1:0:LPCR?
Global Response 1:LPCR:6.000:30.000:10.000:3.000:1.000:0.300:0.100:
6.000:30.000:10.000:3.000:1.000:0.300:0.100:6.000:30.000:10.000:3.000:1.000:0.300:0.100:
6.000:30.000:10.000:3.000:1.000:0.300:0.100:\r\n
CAUTION! Query only - The user should NEVER send this as a setting command as these values depend on the
HW installed and will be set at the factory.
LEDS
The LEDS command is used to test the LED functionality of the front panel. When sent as a command the
LED’s on the front panel will flash 3 times. This command invokes a function and therefore has no query
capability.
MODEL 483C41 GENERAL OPERATION MANUAL 29
Setting:
2:1:LEDS= 0\r\n ( unit 2, channel 1, Any value )
Query:
N/A
RSET
The RSET command is used to restore the factory default channel settings. This command invokes a function
and therefore has no query capability.
Setting:
2:1:RSET = 0\r\n ( unit 2, channel 1, Any value )
Query:
N/A
SAVS
The SAVS command is used to store the current channel setting as the default settings that will be restored on
power up. This command invokes a function and therefore has no query capability.
Setting:
2:1:SAVS = 0\r\n ( unit 2, channel 1, Any value )
Query:
N/A
Communication Responses
Typically the unit will return <Unit>:<Cmd String>:OK when the command is successful. Errors are indicated with
negative numbers. The unit may return one of the following:
D D
EXTERNAL AC POWER
INPUT AND FUSE
ETHERNET INPUT
16X BNC CONNECTORS
C 17.0 C
[432]
12.00
[304.7] 13.7
[347]
1.00
[25.3]
B B
18.3
[465]
1.73
[43.9] 1.25
[31.8]
A A
4 3 2 1