Conexion y Programacion Panel VISTA48 MINI014GV2

The document provides instructions for wiring an MN01-4G cellular communicator to a Vista 15P/20P alarm panel and programming the panel. Key steps include: 1) Connecting the cellular communicator wires to terminals on the panel board for power, phone lines, and a programmable output. 2) Programming a zone (e.g. zone 3) for the cellular communicator trigger input and selecting a zone type, partition, and report code. 3) Programming the programmable output to activate for the selected zone type and partition. 4) Configuring the panel's telephone settings including number, account, and reporting format.

Uploaded by

Ulises Gonzalez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
141 views3 pages

Conexion y Programacion Panel VISTA48 MINI014GV2

The document provides instructions for wiring an MN01-4G cellular communicator to a Vista 15P/20P alarm panel and programming the panel. Key steps include: 1) Connecting the cellular communicator wires to terminals on the panel board for power, phone lines, and a programmable output. 2) Programming a zone (e.g. zone 3) for the cellular communicator trigger input and selecting a zone type, partition, and report code. 3) Programming the programmable output to activate for the selected zone type and partition. 4) Configuring the panel's telephone settings including number, account, and reporting format.

Uploaded by

Ulises Gonzalez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Vista 15P/20P

Wiring the MN01-4G Cellular Communicator


and Programming the Panel

Wiring the MN01-4G to the Alarm Panel

*IN1 and OUT1 – optional terminals for the remote arm/disarm feature

 Connect RED wire to terminal 5 (12 volt + aux power )


 Connect BLACK wire to terminal 4 ( 12 volt – aux power )
 Connect GREEN wire to terminal 24 ( panel phone line ring )
 Connect YELLOW wire to terminal 23 ( panel phone line tip )
 Connect WHITE wire to PGM output 2 (location 18) post # 5 (green wire of harness connector)
 Connect ORANGE wire (O1) to the desired trigger zone input terminal (can use any available on board zone
2-8 / DO NOT USE zone 1 due to fact it is a Power Limited Circuit)
We have selected Zone 3 as an example.
Programming the Alarm Panel
Enter in programming mode. There are two ways to do that:

1) Up to 30 seconds after you restart the panel hold “#” and “*” keys;
2) Enter the [Installer Code] + [8] + [0] + [0] keys. The default installer code is 4112

Press: [4112][8][0][0][*][56][*] to enter in the Zone Programming menu:


SET TO CONFIRM?
Set 1 to confirm, 0 to reject
0 = NO 1 = YES

As an example we will program Zone 3


Note: Use a zone number other than Zone 1 due to the fact that Zone 1 is power limited circuit!

1) Enter [03][*]
ZN ZT P RC HW: RT [03] for Zone 3
03 77 1 00 EL:1 [*] to save

2) Enter [*][77][*]
ZN ZT P RC HW: RT [*] to go on the next section
03 77 1 00 EL:1 [77] to choose the type of the zone – 77 is a keyswitch zone
[*] to save

3) Enter [*][1][*]
ZN ZT P RC HW: RT
[*] – to enter the next section
03 77 1 00 EL:1
[1] – to choose Partition 1
[*] – to save

4) Enter [*][03][*]
ZN ZT P RC HW: RT
[*] – to enter the next section
03 77 1 03 EL:1
[03] – to choose the report code for Zone 03
[*] – to save

5) Enter [*][00] to quit

Programming the Digital Output of the Alarm Panel

Press: [4112][8][0][0][*][80][*] to enter in the Output programming menu

1) Enter [01][*]
OUTPUT FUNCT #
[01] – to choose the function output number
OO=QUIT 01
[*] – to save and continue

2) Enter [2][*]
01 A E P TRIG
[2] – to choose to activate the output by zone type
01 2 0 – ZN=OO
[*] – to save and continue

3) Enter [78][*]
01 A E P TRIG [78] – to select the zone type - 78 = Keyswitch Red LED (Armed), 79 = Keyswitch
01 2 78 – ZN=OO Green LED (Disarmed)
[*] – to save and continue

4) Enter [1][*]
01 A E P TRIG
[*] – to enter the next section
01 2 78 1 ZN=OO
[1] – to choose Partition 1
[*] – to save
5) Enter [18][*]
01 A E P TRIG
[18] – to choose to activate OUTPUT 2 of the panel, which is located on the 5th pin of
01 2 78 1 18
the terminal rail (for more details you can check the detailed scheme)
[*] – to save

6) Enter [*][00] to exit the output configuration

Configuring the Telephone Communicator of the Alarm Panel

1. Enter: [4112][8][0][0][*][41] [1234567][*] to enter the primary telephone number:


[1234567] - the telephone number that we set
[*] - to save

2. Enter: [4112][8][0][0][*][43][1111][*] to set the primary account number:


[1111] – the account number that we set
[*] – to save

3. Enter: [4112][8][0][0][*][47][1][*] to set type of the service:


[1] – to choose tone dial
[*] – to save

4. Enter: [4112][8][0][0][*][48][7][7][*] to choose the reporting format for the primary and secondary
telephone numbers:
[7][7] – to choose the reporting format Contact ID for the primary and secondary telephone number
[*] – to save

Enabling the OPEN/CLOSE Reporting Codes

1. Enter: [4112][8][0][0][*][65][1][1][1][*] to enable the OPEN report code for the three partitions:
[1] To enable [0] To disable
[1] – to enable OPEN report code for partition 1
[1] – to enable OPEN report code for partition 2
[1] – to enable OPEN report code for the common partition

2. Enter: [4112][8][0][0][*][66][1][1][1][1][1][1][*][99] to enable Away/Stay Arm report codes for the


three partitions:
[1][1][1][1][1][1] – to enable Arm Away/Stay report code
[*][99] – to save and exit