This document outlines the recommended technical specifications for tariff meters to be installed at two substations in Bangladesh. It lists 25 specification requirements and whether the bidder's product, a Prometer 100 digital tariff meter made by CEWE in the UK, meets each requirement. The manager of CEWE international marketing signs off at the end, authorizing the specifications response.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
116 views2 pages
GTP - Prometer 100
This document outlines the recommended technical specifications for tariff meters to be installed at two substations in Bangladesh. It lists 25 specification requirements and whether the bidder's product, a Prometer 100 digital tariff meter made by CEWE in the UK, meets each requirement. The manager of CEWE international marketing signs off at the end, authorizing the specifications response.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2
RECOMMENDED GTP FOR TARIFF METER ( kWh and kVARh) of 230kV/33kV GIS
Substation AT MIRSHARAI AND EXISITING 230/33kV BSRM SUBSTATION
S Description Unit PGCB's requirements Bidder's Data No CEWE/ Elster/ Landis Gyr/ EDMI/ 1 Manufacturer's Name CEWE or other reputed Manufacturer France/UK/ USA/Switzerland/ 2 Country of Origin Sweden/ Germany/ India / Made in UK China/Bangladesh 3 Type, model Should be filled up by bidder Prometer 100 4 Meter Type Digital Digital Complied, Programmable 3P3W 5 Connection Type CT/VT Operated , 3 Phase 4 Wire & 3P4W Complied, CT ratio is 6 Current Range A 1(2)/5(10) , User Programmable Programmable Continuous Thermal 7 A 2*In or Higher Complied Current Rating Short Time Thermal 8 A 40*In or Higher for 1sec Complied Rating 9 Voltage Range V AC 50 to 82.5(P-N) or Higher Range Complied 10 Overload Voltage V AC 1.3*Vn, Continuous Complied Separate CT Cores for Main & 11 CT Connections Check meters or as per the Complied contract agreement 80V to 240V AC or Higher range , Complied, 60-240 V AC/DC 12 Auxiliary Supply Range 100-125 VDC or as per the (±20%) contract document 13 Operating Frequency 50Hz(±10%) Complied 14 Measuring mode True 4 Quadrant Complied Complied, 0.2s for kWh, 0.5s for 15 Accuracy class 0.2 for kWh, 0.5 for kVARh kVARh Option for quick reading scroll and 16 Display Option Complied reset have to be available. Optical port & RS232/RS485/ Complied, Optical 17 Local communication Ethernet Port+RS232+RS485 Local communication Should be supplied free of cost by 18 Complied cord the bidder 19 Remote communication Standard metering protocol Complied, IEC-DLMS & MODBUS Software Interfacing 20 Should be available Complied facility Should be free of cost and without 21 Software Availability Complied any time bounded license Should be available for 22 Password Protection programming , configuration complied and read out meter data. Complied, TTB Supply under scope Should be available with online 23 Online testing facility of M/s Energypac Engineering Ltd, CT Shorting facility with TTB Bangladesh Should be provided exclusive Complied, Under the scope of M/s 24 Tariff metering panel for tariff metering and with Energypac Engineering Ltd, security sealing provisions. Bangladesh At least 32 MB of Non Volatile memory for data storage and Complied, capable of simultaneously Meter can record 100 Channels 25 Data Storage record 4 load profile recorders (2 LoggerX50 Channels) for 192 x 16 channels for at least 90 days at 30 minute time intervals. days at 30 minute intervals.
Name: Sandip Kumar
Title: Manager - International Marketing ( SEA)
Duly authorize to sign this Authorization on behalf of CEWE, Sweden Date: 10th April’2018