Availability
Dual mains input Increases availability by allowing the UPS to be connected to two separate
power sources.
Scalable runtime Allows additional run time to be quickly added as needed.
Hot-swappable Ensures clean, uninterrupted power to protected equipment while batteries
batteries are being replaced
Generator Compatible Ensures clean, uninterrupted power to protected equipment when generator
power is used.
Automatic internal Supplies utility power to the connected loads in the event of a UPS overload
bypass condition or fault.
Battery modules Delivers higher availability through redundant batteries.
connected in parallel
Serviceability
User-replaceable Increases availability by allowing a trained user to perform upgrades and
batteries replacements of the batteries reducing Mean Time to Repair (MTTR)
Battery replacement Allows quick, easy battery replacement.
without tools
Automatic self-test Periodic battery self-test ensures early detection of a battery that needs to be
replaced.
Shippable with Enables pre-installation UPS staging and testing and faster installation.
modules installed
Modular design Provides fast serviceability and reduced maintenance requirements via self-
diagnosing, field-replaceable modules.
Manageability
Network manageable Provides remote management of the UPS over the network.
InfraStruXure Enables centralized management via the APC InfraStruXure® Manager.
Manager Compatible
LCD display Alpha-Numeric Display which displays system parameters and alarms.
Audible Alarms Provides notification of changing utility power and UPS conditions.
Programmable Ensures compatibility with different input frequencies.
frequency
LED status indicators Quickly understand unit and power status with visual indicators.
SmartSlot Customize UPS capabilities with management cards.
Total Cost of Ownership
Input power factor Minimizes installation costs by enabling the use of smaller generators and
correction cabling.
Temperature- Prolongs battery life by regulating the charge voltage according to battery
compensated battery temperature.
charging
Manual maintenance Reduces installation costs by eliminating the need for an external mechanical
bypass bypass.
Intelligent Battery Maximizes battery performance, life, and reliability through intelligent,
Management precision charging.
Protection
Frequency and voltage Gives higher application availability by correcting poor frequency and
regulation voltage conditions without using the battery.
Safety-agency Ensures the product has been tested and approved to work safely with the
approved connected service provider equipment and within the specified environment.
UL, FCC, CE, C-Tick approvals.
Cold-start capable Provides temporary battery power when the utility power is out.
Output
Output Power Capacity 8000 Watts / 10 kVA
Max Configurable Power 8000 Watts / 10 kVA
Nominal Output Voltage 120V,208V,208V 3PH
Output Voltage Note Configurable for 208 and 220V - 3 Phase
Efficiency at Full Load 93%
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 57 - 63 Hz for 60 Hz nominal
Crest Factor Unlimited
Waveform Type Sine wave
Output Connections (1) Hard Wire 5-wire (3PH + N + G)
(1) Screw Terminals
Bypass Built-in Maintenance Bypass,Built-in Static Bypass
Input
Nominal Input Voltage 208V 3PH
Input Frequency 40 - 70 Hz (auto sensing)
Input Connections Hard Wire 5-wire (3PH + N + G)
Input voltage range for main 165 - 240V
operations
Other Input Voltages 220
Maximum Input Current 27A
Input Breaker Capacity 35A
Physical
Maximum Height 1499.00 mm
Maximum Width 356.00 mm
Maximum Depth 925.00 mm
Net Weight 305.00 KG
Shipping Weight 335.92 KG
Shipping Height 1643.00 mm
Shipping Width 650.00 mm
Shipping Depth 1062.00 mm
Color Black
Units per Pallet 1.00
Environmental
Operating Environment 0 - 40 °C
Operating Relative Humidity 0%
Operating Elevation 0-999.9 meters
Storage Temperature -50 - 40 °C
Storage Relative Humidity 0%
Storage Elevation 0-15000 meters
Audible noise at 1 meter from 54.00 dBA
surface of unit
Online Thermal Dissipation 2047.00 BTU/hr
Protection Class NEMA 1
Conformance
Regulatory Approvals cUL Listed,ISO 14001,ISO 9001,UL 1778
Standard Warranty 1 year repair or replace,Start-Up Service
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full