Chapter 5 Final Control Elements
Chapter 5 Final Control Elements
CEV544
PROCESS CONTROL AND
INSTRUMENTATIONS
LEARNING OUTCOMES
At the end of this chapter, student should be
able to:
Explain the working principles of several
types of final control element.
Calculate the correct size of control valve
for a given flow
VALVE
VALVE
Unit 1: Process Control Loop
Pressure
Flow
Level
Process Temperature
pH
dP cell
Capacitance
I/P
Sensor Radar, Sonic
Magnetic
Resistance
IR/Laser
Transmitter 4-20 mA
1-5 Vdc
Controller PID
Fuzzy logic
Transducer 4-20 mA
3-15 psig
Linear
Control valve Equal percentage
• Purpose
to regulate flow of any phase (liquid, gas, fluid
and mixed phases) that could pass through it.
At the moment, solid phase (such as sand,
flour, sugar) is not possible.
• Symbols
=
Construction
Actuator
Body
Plug
Seat
The control valve actuator
compare
compare
compare
compare
• What we want each valves to do if the
3 electrical or air supply were fail?
• 1‐fail‐closed –prevent high steam flow
that could vaporize all the liquid and
overheat the coil
• 3‐ fail‐open – allow the vapor to flow
out and prevent the vapor pressurized
2
the tank
• The action of the valve determine the sign of the
gain of the valve
• Air‐to‐open valve has a positive gain
• Air to‐closed valve has a negative gain
• Formula relating valve position to the controller
output
Exercise
– If 10 psig is sent to the control valve, what is the
valve position?
• For air‐to‐close system
• For air‐to‐open system
TYPE OF CONTROL VALVES
• Purpose of control valve
• For throttling purposes and general flow
control
• Control valve is classify into 2 categories:
• Reciprocating stem
• Rotating stem
• Reciprocating stem
– globe valve
» the most common valves in existence.
» The globe valve derives its name from
the globular shape of the valve body.
» The essential principle of globe valve
operation is the perpendicular
movement of the disk away from the
seat.
» Valve is divided into 2 areas:
• Actuator – converts the energy
input into mechanical motion
• Body
• Example of globe valve
– Single seated sliding stem globe valve
– Double seated sliding stem globe valve
• Reciprocating stem
– Three way valves
» Split one stream into two other stream
» Blend two steam into one stream
– Y‐style valves
» Commonly used in molten metal or cryogenic service
– Pinch or diaphragm valves
» Consist of some kind of flexure that can be moved
together to open or close the area of flow.
» Commonly used for highly corrosive fluids, slurries,
high‐viscosity liquids, some food processing
– Gate valves
» Mainly used as block valve
» Fully open or fully closed services.
Gate valve Y type valve
• Current is passed through S.V and get energized.
Solenoid
valve
• The magnetic field is generated to trigger plunger.
• Move upward / downward to open and close
Plunger orifice
• Open/Close based on the plunger movement
Orifice
Control valve
Capacity and sizing
CONTROL VALVE CAPACITY AND SIZING
Control valve capacity and sizing
• To regulate flow, the flow capacity of the control valve
varies from zero when the valve is closed to a maximum
when the valve is fully opened.
• Flow capacity of a control valve is determine by its capacity
factor or flow coefficient, Cv
• Cv is the flow in US gallon per minute (gpm) that flow
through the valve at a pressure drop of 1 psi across the
valve.
• e.g valve with Cv of 25 can deliver 25 gpm of water when it
has a 1 psi pressure drop.
• Liquid
‐Liquid flow through the valve
Conversion unit
Mass flow , lb/h =
• Compressible flow (Gas or vapor)
‐equation of gas or vapor flow in cubic feed per hour, at
o
standard conditions of one atm and 60 F
• Mass rate through the valve:
•
w is gas flow in lb/h
Mw is average molecular weight of the gas
A 3‐in Masoneilan valve with full trim has a capacity factor of 110 gpm/(psi)1/2 when
fully opened. The pressure drop across the valvel is 10 psi. Calculate the flow of a gas
with average molecular weight of 35 when the valve inlet conditions are 100 psig
and 100 oF
Gas Mw=35, G=35/29 = 1.207, P1=100+14.7 =114.7 psia, T=100+460
=560 oR, Cf=0.9
Sizing of control valves
• Sizing control valve for liquid service
– Flow through the valve
– Pressure drop across the valve
– Specific gravity of the liquid
• Sizing control valve for compressible flow
– Flow through the valve
– Pressure drop across the valve
– Specific gravity of the liquid
– Inlet pressure and temperature
– Average molecular weight of the fluid
• For sizing the valve, use the information to calculate
the Cv coefficient
• Once the Cv coefficient is known select a valve that is
large enough for the service.
• Generally, the calculated Cv falls between two
different valve sizes. Select the larger valve.
• Capacity factor/ flow coefficient =
f = flow through the valve at nominal production rate (nominal flow )
‐ obtained from the process steadystate design conditions.
pv = pressure drop across the valve, psi
Gf =specific gravity of liquid
• The valve coefficient must be greater than the one
calculated from the equation
• Ratio of the valve coefficient when the valve is fully open
opened to the valve coefficient at nominal flow =
overcapacity factor of the valve
• Calculate the overcapacity factor of the valve,
Cv ,max
Cv
• Overcapacity factor 1.5 for 50% overcapacity
• Overcapacity factor 2 for 100% overcapacity
Example
A control valve is to regulate the flow of steam into a
distillation column reboiler with a design nominal flow of
16,100 lb/h. The supply steam is saturated at 20 psig. Size
the control valve for a pressure drop of 5 psi and 100%
overcapacity. Assume Cf = 0.8. Given the molecular weight
of steam, Mw is 18lb/mole. The steam saturation
temperature is 259oF.
• Answer
• The valve pressure is 20+14.7 =34.7 psia,
• The specific gravity is G=18/29 =0.621, assuming Cf =0.8
• The Tinlet = 259 + 460 = 719 oR
• For 100% overcapacity, the valve coefficient when fully opened
Masoneilan’s valve catalog
• Cv, max is between 640 and 1000
• Therefore valve size is 10 inch
Exercise
• A control valve is used to regulate the flow of steam. The
nominal flow of the steam is 180,000scfh. The valve condition
are 100 psig and 60oF, and the outlet pressure is 80 psig. Size
the control valve for 100% overcapacity. Steam MW= 18 and
Cf=0.8. (Masoneilan)
Selection Criteria
Capacity and sizing
P in psi
P
Q Cv
S .G . Fluid S.G. Q
Flowrate
In gpm
Example
Select an equal percentage control valve for the following condition. (S.G=1)
Maximum 120 10 80
Normal 42 15 50
Minimum 13 20 20
Flow condition Flowrate, Pressure Valve Cv Cv
gpm drop, psi lift, % calculated actual
Erosion
What causing flashing and
cavitation in a control valve?
• Flashing • Cavitation
Pressure of the liquid falls below If pressure recovery experienced by
its vapor pressure, liquid change the liquid is enough to raise the
phase to vapor phase. pressure above the vapor pressure
of the liquid, the vapor bubbles will
start collapsing/imploding
What causing flashing and cavitation
in a control valve?
INSTALL VALVE CHARACTERISTICS
• When the pressure drop in the line and equipment in series
with a valve is significant compared with pressure drop across
the valve, the valve pressure drop varies with the flow
through the line.
• Variation of flow with valve position to be different from the
variation of the Cv coefficient.
• Installed flow characteristics of the valve are different from
the inherent Cv characteristic.
There is total pressure drop , Δ po that is independent of
flow
kL= constant friction coefficient for the line, fitting, equipment psi/(gpm)2
• Maximum flow
• Rangeability
Control valve characteristic
• The Cv coefficient (flow coefficient) of a control valve depends
on the valve position.
• Varies from zero (when the valve is closed, vp=0) to a
maximum value, Cv,max (when the valve is fully opened)
• The variation in the Cv allows the valve to continuously
regulate the flow
• The particular function relating the Cv coefficient to the valve
position is known as inherent valve characteristics.
• 3 common valve characteristics: quick‐opening, linear, equal
percentage.
Selection Criteria
Valve characteristics: Linear, equal percentage and quick opening.
What make a control valve becomes linear, equal
percentage or quick opening control valve?
• linear
– The function for linear characteristics
Cv (vp)=Cv,max vp
‐ Produce a coefficient proportional to the valve opening
‐ Used when the process is linear and the pressure drop
across the valve do not vary with flow
‐ 50% valve position = 50% Cv of its maximum coefficient
• equal percentage
– The function for equal percentage characteristics
Cv (vp)=Cv,max αvp‐1 α = rangeability parameter having a
value of 50 or 100
50 is most common
‐ Produce a exponential function to the valve opening
result in equal relative / percentage increments
‐ Used when the pressure drop across the valve do not vary
with flow, and with process which the gain decreases
when the flow through the valve increases.
‐ Exponential function has a property that equal increments
in valve position result in equal relative or percentage
increments in the valve coefficient
‐ When increasing the valve position by 1% the flow
increases by 1% of its value at the past valve position.
Question
Valve characteristics: Linear, equal percentage and quick opening.
Quick opening
Flow coef. =
6 gpm
Flowrate =
Linear
Flow coef. = 4 gpm
Flowrate =
– Another definition uses 90 and 10% valve
positions
• If the pressure drop across the valve is independent
of flow, the flow through the valve is proportional to
its Cv coefficient. We can calculate the valve
rangeability from its inherent characteristics.
• linear characteristic Cv (vp)=Cv,max vp
– Rangeability = 0.95/0.05 = 19
• Equal percentage characteristic
– Rangeability =α‐0.05 / α‐0.95 = α 0.9
• α = 50 , rangeability =33.8 Cv (vp)=Cv,max αvp‐1
• α = 100 , rangeability =63.1
• Quick opening characteristic
– Rangeability = 3 (small range)
CONTROL VALVE GAIN & TRANSFER
FUNCTION
Control valve gain and transfer function
Gain
• Gain of the valve – change in output divided by the
change in the input
• Output of valve – flow
• Input of the valve is the controller output signal (in
percent controller output)
df gpm Ib/hr or scfh
Kv
dm %CO
• The valve gain obtained from three term
– Dependence of the valve position on the controller output
– Dependence of the Flow coefficient, Cv on the valve position
– Dependence of the Flow on the flow coefficient , Cv
dvp dCv df
Kv
dm dvp dCv
• Dependence of the valve position on the controller
output
– Simply the conversion of percent controller output to
fraction valve position
– +ve sign for valve fails closed (air‐to‐open)
– ‐ve sign for valve fails open (air to close)
=
• Dependence of the Flow coefficient, Cv on the
valve position
– Linear characteristic
‐ Equal percentage
• Dependence of the Flow on the flow coefficient , Cv
– For liquid service
• Constant valve pressure drop
• Variable valve pressure drop
Constant valve pressure drop
• The gain of a valve with linear characteristic
=
The gain of a valve with equal percentage
characteristic
Variable valve pressure drop
• The gain of a valve with linear characteristic
• The gain of a valve with equal percentage
characteristic
•
Question 1
• Find the gain and the valve position
• Cv,max=2000
• Cv=500
• Density of liquid =800kg/m3
• Inlet pressure =100 psig
• Outlet pressure =80 psig
• α (rangeability parameter) = 50
• Consider both a valve with linear characteristics
and equal percentage valve
• Transfer function
Question 2
• Using the valve gain obtained in Question 1,
1. Write the transfer function of the valve if the
time constant of the valve actuator is 0.3 min
2. Draw the block diagram of the valve