Chapter 1 Introduction To Process System
Chapter 1 Introduction To Process System
Controlled variable:
Temperature in the room
Manipulated variable:
Speed of the fan
Disturbance:
Weather
Exercise I
Steam out
Steam in
(Manipulated variables)
(Controlled variables)
Fluid in Fluid out
Heat Exchanger
Ti T desired
(Load disturbances )
Steam out
(Uncontrolled variables)
Measurement (M)
◦ measure the variable to be controlled.
sensor-transmitter combination
Decision (D)
◦ Controller decides what to do to maintain the variables
at its desired value
feedback controller
Action (A)
◦ System must take an action based on controller’s
decision
control valve (final control element)
Another important term
TT Measure
Fluid in Fluid out
Heat Exchanger
Ti T desired
Steam out
Steam in
TC
(Manipulated variables)
TT
Fluid in Fluid out
Heat Exchanger
Ti T desired
How it is done?
Standard symbols and notations representing instruments or control devices are placed to the
pipings and vessels.Standard symbols and notations are available from ISA‐5.1(1984) standard.
Methodology?
PG
Symbols
Instruments / control devices:
A circle representing locally A circle with horizontal line A circle with horizontal line
mounted instrument representing control room inside a square representing
panel mounted instrument. its function in DCS.
Function devices
√ < I
P
Square root Integrator Low selector Current to Pneumatic
extractor Converter
Signals
Electrical signal (low current
or low voltage e.g. 4‐20 mA).
Straight dashed line
Pneumatic signal e.g.
// // // // 3‐15 psig or 0‐60 psig.
Straight line with //
© Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
Unit 1: Process & Instrumentation Diagram
Control
valves =
Manual = O
valve R Not darkened
Always open
Manual = O
valve
Darkened Always
R closed
Solenoid =
valve
Naming rule
Instruments or devices are noted by 2 to 4 letters.
Examples
See Smith & Corripio (2006) as in Appendix A, Table A‐1
LT LT LC
120 120 120
© Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
Unit 1: Process & Instrumentation Diagram
Naming rule
1 2 3 4
Measurement Device Device / Condition Condition
P Pressure C Controller C Controller H High
T Temperature T Transmitter T Transmitter L Low
L Level R Recorder R Recorder
F Flow I Indicator H High
A Analysis A Alarm L Low
S Switch / V Valve
G Safety
Gauge
Complete guide on P&ID symbols & notations are available from ISA 5.1 (R1984)
Examples
Examples
Unit 1: Process & Instrumentation Diagram
LT
120
Unit 1: Process & Instrumentation Diagram
LT
120
P&ID
Examples
thin process line
LT
120
thick process line
© Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
3 principle type of signals in process industries
Pneumatic 3 – 15 psig
Electrical 4 – 20 mA
1 to 5 V
Digital/discrete
Example of transducer
Current to pneumatic (I/P)
Digital-to-analog (D to A)
Pneumatic to current (P/I)
Steam in
I/P TC
(Manipulated variables)
TT
Fluid in Fluid out
Heat Exchanger
Ti T desired
TT TC
B
FO
Process control loop
T C I/P
Flow control loop
Flow
Unit 1: Process Control Loop
Process control loop
Pressure
Flow
Level
Process Temperature
pH
dP cell
Capacitance I/P
Sensor Radar, Sonic
Magnetic
Resistance
IR/Laser
Transmitter 4‐20 mA
1‐5 Vdc
Controller PID
Fuzzy logic
4‐20 mA
Transducer 3‐15 psig
Linear
Control valve Equal percentage
© Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
1.3.4 Logic Diagrams
Overview
Most continuous process control scheme includes on‐off control.
On‐off control can start and stop a single motor or to initiate an orderly shut down of an entire plant upon
detection of an unsafe condition.
P&IDs were developed to show a continuous process but on‐off control can be shown by logic diagrams.
Logic Diagrams
A conceptual document that defines the on‐off state of a process, and depicts the scheme necessary for control.
The basis of the information refer to ISA‐5.2‐1976‐(R1992) – Binary logic diagrams for process operations.
1.3.4 Logic Diagrams
Logic Diagrams: AND & OR
Logic Diagrams: AND & OR. A Logic Diagram
is set up with the inputs or actions on the
left side of the drawing and the result, or
results, on the right side. The AND symbol
signifies that all inputs must exist (or all
actions must be taken) before the result
occurs.
“C” occurs if and only if “A” and “B” exist or
if action “A” and action “B” have both been
taken. If there are more actions feeding into
an AND, all actions must have taken place
to get the desired result. There is no limit to
the number of actions feeding into an AND.
The OR symbol signifies that one or more
inputs must exist (or one or more actions
must be taken) if the result is to occur.
“C” occurs if, and only if, “A” and/or “B”
exist or if action “A” and/or “B” have been
taken. If there are actions “A” through “Z”
feeding into an OR, one or more of the
actions must have taken place to get the
desired result.
1.3.4 Logic Diagrams
Logic Diagrams: NOT & Basic Memory
Figure shows the NOT gate and the Basic
memory symbols.
The NOT symbol reverses the input. If the
action has taken place and is fed through a
NOT, no result will occur. If the action has
not taken place and is fed through a NOT,
the result will occur.
“B” exists if and only if “A” does not exist.
The Basic memory symbol is more complex.
If an action has been taken, the result will
occur and continue to occur until another
action takes place. The symbol has two
outputs, and they flip‐flop. If one shows the
action, the other will show no result.
“C” exists as soon as “A” exists and
continues independent of “A” until “B”
exists. “D” exists when “C” does not.
1.3.4 Logic Diagrams
Example of Logic Diagram: Motor Start Circuit and Logic
Logic Diagram:
For the pump to start, all three inputs to
the AND are necessary.
The first action is to actuate the start
button.
The next action (as “action” is used in
connection with binary logic) is not to
actuate the stop button. This action is
reversed by the NOT, and so the top two
inputs are satisfied.
Including the “not stopped” allows you to
have a separate action to stop the motor.
The motor is not overloaded; there is no
input, and therefore, no output.
However, there is a NOT in the line which
Explanation on electrical drawing. reverses the “no output” and the pump
To start the motor, someone depresses the start button starts.
located next to the motor or on the starter housing itself. If In the MEMORY, a small o is placed around
the overload relay contacts are closed—that is, if the motor is or next to the S. This means that the starter
not overloaded—this action completes the circuit to the coil overload relay overrides the starter reset. In
in the motor contactor. As the coil is energized, coil contact real terms, this means that if the starter
“C” closes, or “seals” the start, and the motor starts. To stop overload relay shows an overload, the reset
the motor, the stop button is depressed. This interrupts the button will not start or jog the motor.
circuit to the contactor coil, which opens the contacts and
removes power to the motor.
For process that the controlled variable
deviates from set point because of
disturbance – regulatory control
Terminology I/P TC
Manipulated variable Heat exchanger TT
(saturated steam)
100°C 80°C
30°C
100 L/min controlled variable
(temperature of
Load variable sterilised saline)
95°C
(Flow, temperature Uncontrolled variable
of saline solution)
(Saturated steam)
Controlled Manipulated variable Load variable Set point
variable
Sym: m, CO, MV Sym: Sym: r, SP, SV
Sym: c, PV
A process being “All other The desired
“The parameters adjusted (controlled) affecting operating
that indicate by a final control variable, other condition.
product quality or element (such as than the one
the operating control valve, being
condition of the damper, motor manipulated.”
process.” (L.M. speed). (L.M. Gordon)
Gordon)
Chapter 4
Chapter 4
Positive Feedback
Negative Feedback
For example Heat Exchanger :
If the inlet temperature decreases, thus
creating a disturbance, its effect must
propagate through the heat exchanger before
the outlet temperature decreases.
Deviation from set point has occurred and it
must compensate for the disturbance by
manipulating the steam valve.
Controller signals the valve to increase its
opening and thus increase the steam flow.
It is a trial-and-error operation until the
temperature reaches and remains at set
point.
Chapter 4
Unit 1: Control strategies
Heat exchanger TT
Manipulated variable
(saturated steam) 100°C 80°C
30°C controlled variable
Load variable
100 L/min (temperature of
(Flow of saline solution)
sterilised saline)
Merit?
Simple design. Easy to tune (for linear, fast & The Process
short deadtime processes: flow, level & Saline solution at 30°C is sterilized by
pressure). heating the solution in a heat-exchanger
system to 80°C. The temperature of the
Demerits? sterilized saline solution is maintained by
Slow recovery for slow process such as regulating the control valve of steam input
temperature control upon load disturbance or to the heat-exchanger.
change in setpoint. A process with long deadtime
may exhibit oscillatory process response with
long settling time.
Advantages:
Corrective action occurs as soon as the
controlled variable deviates from the set
Chapter 4
point.
Feedback control requires minimal
knowledge about the process to be
controlled; it particular, a mathematical
model of the process is not required,
although it can be very useful for control
system design.
Disadvantages:
No corrective action is taken until after a
deviation in the controlled variable occurs.
Chapter 4
Manipulated variable
(saturated steam) Heat exchanger 80°C
FT TT
30°C controlled variable
Load variable
100 L/min (temperature of
(Flow of saline solution)
sterilised saline)
Demerits?
Cannot work if any of the sensors fail esp. load
variable.
Requires process model in order to design
feedforward system.
Advantage:
Measure important disturbance variables
and take corrective action before they
Chapter 4
FT Heat exchanger TT
Manipulated variable
(saturated steam) 100°C 80°C
30°C controlled variable
Load variable
100 L/min (temperature of
(Flow of saline solution)
sterilised saline)
temperature, Tc.
Therefore, the feedback controller effective in
compensating for changes in Ti and less
effective in compensating for changes in Tc.
Chapter 4
Measuring Tc and taking the control action
before its effect has been felt by the reacting
mixture.
Chapter 4
Cascade control
Chapter 4
DI DII
Set point + +
Process II + Process I +
GcI(s)
+
-
Measuring
device
Primary Loop
Chapter 4
DI DII
Secondary Loop
Set point + +
GcI(s) GcII(s) Process II + Process I +
+
- -
Measuring device
Measuring device
Cascade Control (multi-loop)
• Distinguishing features:
1. Two FB controllers but only a single control valve (or
other -final control element).
2. Output signal of the "master" controller is the set-
Chapter 4
• Terminology
Feedforward/ +
I/P TC
Feedback control +
Ws
Cp
Wp T2 T1
FFC
Hs TT
Manipulated variable
(saturated steam) Heat exchanger 80°C
FT TT
Load variable 30°C controlled variable
100 L/min (temperature of
(Flow of saline solution)
sterilised saline)
Merit?
Feedforward control compensates for major
disturbances, while feedback control compensates
for all other disturbances.
Chapter 4
Unit 1: Control strategies
Merit?
Keep two flow in proportion.
Demerits?
Inherits PID characteristics
Ratio Control
divider
Keep a constant ratio between the feed flow
rate and the steam in the reboiler of a
distillation column
Hold constant the reflux ratio in a distillation
column
Control the ratio of 2 reactants entering
reactor at desired value
Keep ratio of fuel/air in a burner at its
optimum value
Hold the ratio of a purge stream to the
recycle stream constant
Required to blend 2 liquid streams, A and
B in some ratio
R=FB/FA
The flow of stream B must vary, as the flow rate of stream A is varies
Feedback control D
Y(s)
Y
Feedback Process
controller
•Feedforward control
D
Y(s) Y
Feedforward Process
controller
•Cascade control
Y(s)
Primary Secondary Y
Process II Process I
controller controller
Question
- How to ensure that the level in the tank remains at
or near the set point? Propose the following control
strategy:
- Feedback
- Feedforward
Chapter 4
Purposes :
• ➢Normal operation:
• One process variable is the controlling variable
• ➢Abnormal operation:
• Some other process variable becomes the controlling variable to
• prevent it from exceeding a process or equipment limit
FC
101
I/P
101
PROCESS
CONTROL FT
LOOP 102 101
TY
PROCESS
LT
101 102 CONTROL
LOOP 101
TT
102
LC TC TR
102 102 102
PUMP SWITCH
PANEL
BOX
Can be at plant site or
control room © Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
Unit 1: Control System Configuration
DCS (Distributed control system). Unlike SCADA, DCS system monitors and controls processes. Field controllers
are replaced with a single computer. Server can run processes when computer breakdown, but change on SP, A to
M to A or P, I, & D cannot be made.
I/P
101
PROCESS
CONTROL FT
LOOP 102 101
TY
PROCESS
LT
101 102 CONTROL
LOOP 101
TT
102
Server
Fieldbus or mA
© Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
Unit 1: Control System Configuration
Computer control. Very much like DCS system: monitors and controls processes. Field controllers are replaced
with a single computer. A “fundamental and crude” version of DCS.
I/P
101
PROCESS
CONTROL FT
LOOP 102 101
TY
PROCESS
LT
101 102 CONTROL
LOOP 101
TT
102
Signals based on card I/O
DAQ PCI card
© Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
Unit 1: Control System Configuration
SCADA (supervisory control and data acqusiition) is a control configuration system whereby a computer is used
to monitor the process variables (PV). It is also possible to change the controller set point (SP) and control the
process manually by opening /closing the control valve (MV). However, the computer has no capability of
controlling the process. Suitable for medium scale industries. Can switch to ‘LOCAL’ control when computer /
software break down. FC
101
R/L
I/P
101
PROCESS
CONTROL FT
LOOP 102 101
TY
PROCESS
LT
101 102 CONTROL
LOOP 101
TT
102
DAQ card
LC TC TR
102 102 102
DAQ card
PUMP SWITCH
PANEL
BOX
Can be at plant site or
control room © Abdul Aziz Ishak, Universiti Teknologi MARA Malaysia (2009)
Data acquisition (DAQ) is the process of measuring an
electrical or physical phenomenon such as voltage, current,
temperature, pressure, or sound with a computer. A DAQ
system consists of sensors, DAQ measurement hardware, and
a computer with programmable software.
A PROGRAMMABLE LOGIC CONTROLLER (PLC) is an industrial
computer control system that continuously monitors the
state of input devices and makes decisions based upon a
custom program to control the state of output devices.
Advantages :
Able to change and replicate the operation or process while
collecting and communicating vital information
It is modular ; can mix and match the types of Input and
Output devices to best suit your application.
The Central Processing Unit, the CPU, contains an
internal program that tells the PLC how to perform
the following functions:
Execute the Control Instructions contained in the
User's Programs. This program is stored in
"nonvolatile" memory, meaning that the program
will not be lost if power is removed
Communicate with other devices, which can include
I/O Devices, Programming Devices, Networks, and
even other PLCs.
Perform Housekeeping activities such as
Communications, Internal Diagnostics, etc.
Figure 1 shows a stirred chemical reactor where cooling water flows
through the reactor jacket to regulate the reactor temperature. An
increase in the cooling water temperature can cause unsatisfactory
performance in this reaction. The resulting increase in the reactor
temperature, due to a reduction in heat removal rate, may occur
slowly. The corrective action taken will be delayed if the dynamic
lags occur in the jacket as well as in the reactor. In order to
overcome this problem, design a suitable control configuration for
this process and justify your answer.