Ch5 SinglePhaseTrans Tutorial
Ch5 SinglePhaseTrans Tutorial
Presented by
Prof. M. L. Chen
Dept. of Building services Engineering
The Hong Kong Polytechnic University
1
Transformer Parameters
2
Transformer Equivalent Circuit
Referred to Primary:
V’2 =nV2, I’2=I2/n
R2’ = n2R2, x2’ = n2x2
Xm’ = nXm, ZL’ =n2ZL
Ri’ : core loss
Referred to secondary:
V”1 =V1/n, I”1=nI1
R1” =R1/n2, x1” = x2/n2
Xm” = Xm /n
Ri” =Ri/n2 , ZL : load
3
Open-circuit test
Open-circuit test for the excitation branch (Poc , Voc , Ioc)
Req=R1+n2R2:equivalent resistance
Psc I Req
2
sc
referred to the primary;
Vsc xeq=x1+n2x2: equivalent reactance
Z sc Req2 xeq2
I sc referred to primary.
5
Per-unit System
Actual value of quantity
Definition: Quantity per unit
base value of quantity
Pbase = Qbase = S base Vbase I base
Vbase
Z base
I base 1. Normally the base value is equal
I base to its nominal value.
Ybase 2. The base value will be different in
Vbase
both sides.
Z base
Vbase 2
3. For the single-phase system, we
S base have the left equations.
6
Transformer Efficiency
Pout
100%
Pin
Pout
100%
Pout Ploss
VS I S cos
100%
PR Pcore VS I S cos
VS I S cos
100%
I S Req Poc VS I S cos
2 '
7
Transformer Voltage Regulation (VR)
When a transformer feeds a varying load, the
terminal voltage VS may change as a function of the
load current IS, if the primary maintains at the rating
level. The change in voltage between no load
(secondary is opened) and full load is described by
voltage regulation VR, defined as follows:
VS ,nl VS , fl
VR 100%
VS , fl
VS, nl is the terminal voltage at no-load condition, and
VS, fl is the terminal voltage at full-load condition.
8
Transformer Voltage Regulation
Equivalent circuit, Phasor diagram
For a load:
power factor = cos
VS,fl = Vs, the secondary rating voltage
IS,fl = Is, the secondary rating current
R’eq, X’eq, equivalent impedance referred to secondary
Then,
VS, nl = (VS cos + ISR’eq) +j(VS sin +ISX’eq)
9
Transformer Specifications
Rated Power: 2000kVA
Rated High Voltage: 10000V ±2.5% ± 5%
Rated Low Voltage: 400V
Frequency: 50Hz
Impedance at 75°C: 5%
No-Load Losses: 1kW
Load Losses at 75°C: 5kW
10
Specification (calculation)
Transformer Impedance (referred to LV):
Irated=Srated/(Vrated)=2000kVA/400=2500A.
Zbase =V2/Srated=4002/2000kVA =80 m.
ZT =5%*Zbase=4 m.
RT =P/(I2) = 5000/(25002) = 0.8 m.
XT =(ZT2-RT2) = 15.36 = 3.919 m.
11
Tutorial Example
Q. A single-phase cast-resin transformer with –2.5%
tapping is installed to supply electricity to various
loads. It is assumed that the supply voltage at primary
side is maintained at 11 kV.
Specifications:
Rated Power: 2000 kVA
Rated High Voltage: 11000 V ±2.5% ± 5%
Rated Low Voltage: 400 V
Frequency: 50 Hz
Impedance at 75°C: 6%
No-Load Losses: 3350 W
Load Losses at 75°C: 17800 W 12
Tutorial Example (continue)
13
Tutorial Example -Answer
(a) Efficiency
Transformer impedance referred to secondary:
Irated=Srated/Vrated=2000kVA/400V =5kA.
Zbase/rated =V2/Srated=400V2/2000kVA =80 m.
ZT =6%*Zbase=4.8 m.
RT =P/I2 = 17800/50002) = 0.712 m.
XT =(ZT2-RT2) =4.746 m.
Load Impedance:
PF =0.85, impedance phase angle = 31.8°
ZL=3802/SL= 3802/1500kVA = 96.27m
RL=ZL.PF = 81.83m
XL=ZL.(1-PF2 ) = 50.72m
14
Tutorial Example -Answer (continue)
Load Current:
Vs =400(1-2.5%) =390V
Is =Vs /(ZT +ZL) = Vs /[(RT +RL)+j(XT +XL)]
=390/(82.54+j55.47) =3.92kA-33.9.
Efficiency:
Pout= Is2 RL=(3.92kA)2*81.83m =1249.29kW
Ploss=Piron+ Ip2 RT
=(3.35kW)+(3.92kA)2*0.712m = 14.29kW
= Pout/(Pout +Ploss) = 1249.29/1263.58 =0.989
(b) Short-Circuit Currents:
Isc,s= Vs /ZT = 390V/4.8 m = 81.25kA.
Isc,p= Isc.s (400/11000) =2.95kA.
15
Tutorial Example- Answers (continue)
(c) VR at unity load:
At unity power factor , cos =1, sin =0
Secondary rating voltage, VS,fl = Vs = 400 V
Secondary rating current, IS,fl = Is = 5 kA,
Equivalent impedance referred to secondary,
R’eq= 0.712 m , X’eq=4.746 m.
No-load secondary voltage,
VS, nl = (VS cos + ISR’eq) +j(VS sin +ISX’eq)
VS ,nl VS , fl
VR 100%
VS , fl
16