Aircon Midterm Ipapasa
Aircon Midterm Ipapasa
Aircon Midterm Ipapasa
CONDITIONS DB %RH
OUTDOOR 37 70
ROOM 25 50
DIFFERENCE 12 20
SIDE OF NO. OF
NO. OF WALL NO. OF DOOR
THE WINDOW & AREA
FLOOR DIRECTION & IT’S & IT’S
BUILDI IT’S in m2
DIMENSIONS DIMENSIONS
NG DIMENSIONS
2 3.5 x 2 1 D1
Front East - - 23
1 2.5 x 2
Ground Rear West - - 3 3.5 x 2 1 D2 23
Floor Right
North - - 2 2.5 x 2 1 D2 12
Side
Left Side South - - 3 2.5 x 2 1 D1 19
Front East 6 W3 1 2.5 x 4 6 D2 40
Typical
4 D2
2nd Floor Rear West 4 W3 - - 24
and 3rd 1 D1
Floor Right
North 2 W2 - - - - 4.2
Side
Left Side South 2 W2 - - - - 4.2
Eugenio I T. Gonzalo BSME IV-A
Thermal
fo fi
Material Conductivity, k
Density W/m2K W/m2K
(W/m⁰K)
Concrete 1.73 1920
23 5
Plaster 8.65 1885
Roof Materials
Thermal
Material Density
Conductivity,k (W/m⁰K)
Concrete 1.73 1920
Plywood 0.1 544
PUF (Polyurethane Foam) 0.0173 30
Eugenio I T. Gonzalo BSME IV-A
Wall Details
Wall height: Ground Floor 5m
Second & third floor 4m
Concrete thickness: 15cm (all floors)
Plaster thickness: 0.015cm (all floors)
Formula:
1 1 ∆ x concrete ∆ x plaster 1
= + + +
U f i k concrete k plaster f o
1 1 0.15 0.015 1
= + + +
U 5 1.73 8.65 23
U =3.01W /m2 K
∆ t 'e =4.225
kg
mass of wall per area= 1920
( m3 )
( 0.15 m+0.015 m )
kg
mass of wall per area=317
m3
Roof Details
15 cm RCC slab with 4 cm PUF (Polyurethane Foam) & 7mm Plywood
Formula:
1 1 ∆x ∆x ∆x 1 1
U = = + concrete + Polyurethane Foam + Plywood + +
R f i k concrete k Polyurethane Foam k Plywood f o airgap
1 1 0.15 0.04 0.007 1 1
U= = + + + + +
R 23 1.73 0.0173 0.1 2.2 4.8
U =3.18/m 2 K
Eugenio I T. Gonzalo BSME IV-A
kg
(
mass ofroof per area= 1920
m3 )
∗0.15 + ( 30∗0.04 ) + ( 544∗0.007 )
kg
mass ofroof per area=293.008
m3
Te @ 3 PM (⁰C): 17.47
Te’ @ 3PM (⁰C): 17.47 + 4.225=21.69
GROUND FLOOR
2ND FLOOR
OCCUPANCY LOAD
Degree of No. of Person Sensible Heat Latent Heat Heat Gain (W)
SH LH
Eugenio I T. Gonzalo BSME IV-A
Standing,
Walking 10 70 60 700 600
slowly
Note:
Value of Sensible and Latent Heat was taken from this address
http://www.engineeringtoolbox.com/metabolic-heat-persons-d_706.html
LIGHTING LOAD
Type of Lamp Used: Fluorescent
HEAT
Eugenio I T. Gonzalo BSME IV-A
LOAD
ILLUMINATIO FROM HEAT GAIN
FLOOR PLACE N LIGHTS AREA
(lumens/m2) (W)
(W/m2) (m2)
132
1st Floor RESTAURANT 500 16.65 2197.8
3.35
DRUG STORE 150 24 80.4
SUB-TOTAL: 6700.575
nd
TYPICAL 2
To 3rd Floor ROOMS 500 16.65 300 4995
LOBBY 250 8.35 54 450.9
HALLWAYS 200 6.7 60 402
SUB-TOTAL OF TYPICAL 2nd To 3rd Floor 11695.8
TOTAL HEAT GAIN= 1.25 x 18396.375 = 22995.47W 22995.47
APPLIANCE LOAD
HEAT GAIN
SENSIBLE LATENT
SH LH
FLOOR APPLIANCE QUANTITY HEAT HEAT
(W) (W)
(W) (W)
Eugenio I T. Gonzalo BSME IV-A
COFFEE
3 1050 450 2100 1350
MAKER
-
FREEZER 2 320 320
-
REFRIGERATOR 2 690 690
COMPUTER 18 75 2250
SUB
12198 1350
TOTAL
TYPICAL
rd TELEVISION 14 75 - 2100
FLOOR
FL
TOTAL HEAT GAIN 14298 1350
HEAT
NO. OF CMM/ VENTILATION, TEMP DIFF/
APPLICATION FACTOR GAIN , REMARKS
PERSONS PERSON cmm HUM DIFF
W
HEAT
NO. OF CMM/ VENTILATION, TEMP DIFF/
APPLICATION FACTOR GAIN , REMARKS
PERSONS PERSON cmm HUM DIFF
W
HEAT
NO. OF CMM/ VENTILATION, TEMP DIFF/
APPLICATION FACTOR GAIN , REMARKS
PERSONS PERSON cmm HUM DIFF
W
62.53
( cmm )d∨Q v =
( 0.0204 ) ( 25−7 )( 1−0.1 )
Q v =189.21 cmm∨3.15 m 3 /s
A
(Reference: Refrigeration and Air Conditioning by C.P. Arora Table 21.8, Page 731)
SUPPLY DUCT
FROM Fig. 21.15 Duct friction chart
FRICTION LOSS = 1.7 Pa/m
DUCT DIAMETER = 0.63m = 63cm
RECTANGULAR DUCT = 70cm x 48cm
RETURN DUCT
Q v =¿ 189.21 – 51.47= 137.74 cmm = 2.29m3/s
A
43.23
( cmm )d∨Q v =
( 0.0204 ) ( 25−7 )( 1−0.3 )
Q v =168.18 cmm∨2.8 m3 / s
A
(Reference: Refrigeration and Air Conditioning by C.P. Arora Table 21.8, Page 731)
SUPPLY DUCT
FROM Fig. 21.15 Duct friction chart
FRICTION LOSS = 0.3 Pa/m
DUCT DIAMETER = 0.83m = 83cm
RECTANGULAR DUCT = 90cm x 64cm
RETURN DUCT
Eugenio I T. Gonzalo BSME IV-A
59.23
( cmm )d∨Q v =
( 0.0204 ) ( 25−8 )( 1−0.3 )
Q v =243.99 cmm∨4.1 m3 /s
A
(Reference: Refrigeration and Air Conditioning by C.P. Arora Table 21.8, Page 731)
SUPPLY DUCT
FROM Fig. 21.15 Duct friction chart
FRICTION LOSS = 0.24 Pa/m
DUCT DIAMETER = 1.3m = 130cm
RECTANGULAR DUCT = 96cm x 88cm
RETURN DUCT
Q v =¿ 243.99 – 33.38= 210.61 cmm = 3.5m3/s
A