Faults in LVDC Microgrids With Front-End Converters: G G DCN G G G
Faults in LVDC Microgrids With Front-End Converters: G G DCN G G G
3 Fault analysis
IGBT block, without ESS and PV plant and with Rg = 50 mΩ plant and with Rg = 1 mΩ
300 2000
1800
200
1600
1400
100
1200
1000
Isw2 [A]
Ig [A]
800
-100 600
400
-200
500
0
-300 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
0.4 0.45 0.5 0.55 0.6 0.65
t [s] t [s]
600
400
tional, since the grounding system has been designed
according to the relation:
200
120
0 ≤ [3.7]
-200
-400
the grounding resistance can exceed the value for which
0.4 0.45 0.5 0.55 0.6 0.65 the converter loses the control.
t [s]
To sum up, Figure 3.73 depicts the DC ground fault
Considering a bolted ground fault with Rg = 1 mΩ, we current values Ig as a function of the fault resistance Rg.
obtain a DC component of Ig (Figure 3.72) equal approxi- As we can see, with the decrease of Rg, the fault current
mately to 1600A (≈ 13 times Idcn), albeit IGBTs are blocked. may reach values even higher than 14 times the FEC
Such fault current value may jeopardize the integrity of nominal current on the DC side Idcn.
the freewheeling diodes. As a result, protective devices are required.
Compared to the bolted short circuit between the DC
Figure 3.73 - DC component values of the ground fault current Ig as a func-
poles, now the transient current peak due to the Cdc dis- tion of the fault resistance Rg in systems with the neutral point of the MV/
charge is lower, because now the discharge impedance LV transformer grounded (FEC contribution, Idcn = 125 A)
is not only Rsc, but it is equal to the sum Rg + Z/3 (where 2000
Z is the total AC grid equivalent impedance). Neverthe- 1800
less, now, the steady-state value of the fault current 1600
is higher by more or less 30% than the steady-state
1400
value in bolted short circuit condition (≈ 10 times Idcn):
1200
this is because the AC inductances do not create imped-
1000
ance to the DC component of the ground fault current
Ig [A]
800
flowing through the ground connection of the MV/LV
transformer neutral point. 600