Extensive Review on Laminated Bus Bar for Low and High Power
Applications
Prashant B. T. Singh
University of Hyderabad
K. Suresh
University of Hyderabad
Benny J. Varghese
Utah State University
Recommended Citation
Singh, Prashant B.T., Bobba, Phaneendra Babu, Suresh, K., and Varghese, Benny J. “Extensive Review on
Laminated Bus Bar for Low and High Power Applications.” E3S Web of Conferences, vol. 87, 2019, pp. 1-6.
doi:10.1051/e3sconf/20198701009
Extensive review on Laminated bus bar for low and high power
applications
Prashant Singh B.T.1,*, Phaneendra Babu Bobba2, Suresh K.3 and Benny J. Varghese4
1,2 Dept
of Electrical Engineering, GRIET, Hyderabad, Telangana, India
3CEO, MasterPCB PVT.LTD, KPHB, Hyderabad, Telangana, India
4PhD Student, UtahState, University, Logan, USA
Abstract. This paper explains about wide range of applications for Laminated Bus Bar used for high and
low power applications. Authors also explains ways to effective utilize laminated bus bar when compared to
conventional bus bar. Laminated bus bars are designed with low stray inductance and high capacitance with
a uniform current distribution in conducting plate. Parameters like Length, Width, material thickness and
other miscellaneous parameters effect Laminated bus bar performance. With a proper design of Laminated
bus bar it can best utilized , laminated bus bar are suitable for many low and high power applications which
are discussed in this paper. Replacing conventional bus bar with laminated bus bar additional advantages are
achieved like lighter weight, less space and lower maintenance.
*
Corresponding author:[email protected]
© The Authors, published by EDP Sciences. This is an open access article distributed under the terms of the Creative Commons Attribution License 4.0
(http://creativecommons.org/licenses/by/4.0/).
E3S Web of Conferences 87, 0100 9 (2019) https://doi.org/10.1051/e3sconf/20198701009
SeFet 2019
Fig.1. Inverter PCB with Laminated bus bar the load or motor performance. The spike in the DC
links is due to the high stray inductance [10]. By using
2.2 Battery Bank Laminated bus bars with low stray inductance and also
high capacitance the spikes are reduced. These two
Many applications make use of energy storage device to parameters make the spike lower under disturbance or
fulfill the excess demand power requirement or as transient state of operation.
primary power sources like Electric vehicles. For a
dynamic grid and a renewable plant with dynamic power 2.6 Power Distribution
provider gives a challenging issue. With the growth in Higher power systems which carry more power faces
battery technology [4], it is possible to store fluctuating issues like spark at joints, transient spike from supply,
energy in battery and utilize it later. But dealing with more weight and more space. To avoid such problems
such high power requires huge batteries and also create laminated bus bars can be used. Due to low stray
the transient peaks in voltages. Battery banks serve as a inductance and high capacitance in laminated bus bar
primary source of energy for electric vehicles [5] which spikes are observed lower in transients state [11]. In
are in KWH. With growth in Electric Vehicle (EV) industries, high power requirement makes the
technology and awareness of global warming [6] conventional bus bar requirement huge and add addition
automobile industries are shifting toward electric vehicle problems. Laminated bus bars occupy less space for
with batteries as a primary energy source. Use of same power constraints.
laminated bus bars in EV make the power source free
from wiring problems occurring due to vibrations in 2.7 Industrial Automation
heavy vehicles[7] and also a good quality source free
from large transient spikes. Using the Laminated bus bar Robots which runs with huge power in industries uses
for battery bank makes them safer and allows for longer conventional bus bars [12]. But due to high power bus
operating time and posses a lighter weight. bar weights high and being dynamic in nature of work
makes potential create a hazard after a certain operation
period of time. On replacing conventional bus bars with
2.3Super Capacitor Banks laminated bus bars, weight reduction and hazardous
Supercapacitor (SC) have high power density and low situations reduce. Due to lower weight, industry energy
response time when compared to other power source like demands lower power for the same task. This makes the
batteries, Alternators, fuel cells and so on. SCs are used industries demands for lower energy and also reduce for
as a power source to fulfill high power demand in a short hazard situation due to dynamic body behaviour of
time generally at transient state. SC can also be used to robut. Save in energy due to lighter laminated bus bar of
meet dynamic power demand of the grid to balance same constraints make the lower power consumption
divergence of power between power plants and loads lower te energy bills and power demand.
with laminated bus bars possessing lower stray
inductance and high capacitance provide spike free
voltage in a short span of time. By using Laminated bus 3 EFFECTS ON LAMINATED BUS BAR DUE TO
bars spike free voltage is pumped to the grid in a short VARIOUS PARAMETERS
span of time. SC banks are utilized as hybrid energy
sources where weight is reduced [8] by replacing certain 3.1 Effect of Physical dimensions
range of battery with SC and life of primary power
3.1.1 Model A
source is also increased.
Generally models designed with lower dimension faces
non-uniform crowing [13] of flux and current in
conducting plates. Fig. 2a &b. shows a model and
2.4 Data Centers
current plot for the model respectively. On observing
Data centers where data is stored in a voltaic memory the current distribution the current is non- uniformly
which demands for a pure and constant voltage [9]. So, distributed which can be seen in Fig. 2b.
laminated bus bar as a power source distributer can make
the transient spike lower and in turn make data centers
safe by protecting them from fluctuations and providing
spike free voltage waves. Use of laminated bus bar in
data centers lead to safe and risk free operation, free
from wiring hazard situations which can also be
observed in conventional bus bars.
(a) (b)
Fig. 2. Model with lower dimensions and current plot.
2.5 DC Links
DC links used in industries or for inverters with a A new model was designed to make the current
conventional bus bar contains ripples and also add a uniformly distributed. Fig. 3a&b. shows the modified
spike in supply by which the wave disturbance disturbs model and current plots respectively. The current
2
E3S Web of Conferences 87, 0100 9 (2019) https://doi.org/10.1051/e3sconf/20198701009
SeFet 2019
crowding is seen to be uniformly distributed and current crowding and uniformly distribute the current.
utilizing the whole conducting plate. Change in Flexible terminals are perpendicular to the plate so as
dimension make the plate to crowd uniformly and utilize make the terminal joints easy to connect. Fig.6. shows
effectively. the flexible terminals perpendicular to the plate.
(a) (b)
Fig. 3. Modified model of lower dimension model and current Fig. 6. Laminated bus bar with flexible terminals.
plot
3
E3S Web of Conferences 87, 0100 9 (2019) https://doi.org/10.1051/e3sconf/20198701009
SeFet 2019
(a)
(b)
3.4 Effects of Stray Inductance Fig. 11. Effect of distance between plate on stray inductance.
Laminated bus bars need to possess low stray inductance Apertures in model cause the inductance to reduce but only up
when compared to conventional bus bar. Laminated bus to a certain limit. Fig. 9. shows a variation of stray inductance
due to the apertures. Initially inductance had reduced to a
bar current and flux are not uniform. The stray
14.0nH from 17.1nH. In another model due to apertures, the
inductance analytical formula [16] is given by effect of inductance variation can be seen due to change with
frequency. Fig.12a &b. show the model and variation of
nH (1) inductance respectively between a apertures and a non-
aperture model. Change in operating frequency make
L= stray inductance of Laminated bus bar
inductance to effect suitable material need to be designed to
l= length of Laminated bus bar in inches operated as required [15].
a= dielectric thickness in inches
d= width of laminated bus bar in inches
Design 1 Design 2
Fig. 10. Laminated bus model with insulation and conducting
(a)
plate.
4
E3S Web of Conferences 87, 0100 9 (2019) https://doi.org/10.1051/e3sconf/20198701009
SeFet 2019
(b)
Fig. 12.Effect of aperture on inductance
5
E3S Web of Conferences 87, 0100 9 (2019) https://doi.org/10.1051/e3sconf/20198701009
SeFet 2019
REFERENCES
[1] J. M. Allocco, "Laminated bus bars for power
system interconnects," Proceedings of APEC 97 -
Power Electro. Conf., pp. 585-589 vol.2, 1997.
[2] M M. Stibgen, "Applying laminated busbars to
enhance DC power distribution systems,"
International Telecom. Energy Conf. (INTELEC),
pp. 537-541, 2004.
[3] ChengfeiGengID ,Fengyou He, Jingwei Zhang and
Hongsheng Hu- "Partial Stray Inductance Modeling
and Measuring of Asymmetrical Parallel Branches
on the Bus-Bar of Electric Vehicles". Energies 2017,
10, 1519; doi:10.3390/en10101519
[4] M. H. Miles, "Recent advances in lithium battery
technology," GaAs IC Symposium. IEEE Gallium
Arsenide Integrated Circuit Symposium, pp. 219-
222, 2001.