0% found this document useful (0 votes)
241 views2 pages

Auto Switch 1

The document provides specifications for an auto switch that can automatically switch between three modes - auto, manual, and bypass. It monitors 3-phase power for faults like under voltage, over voltage, phase sequence, and phase failure. Key features include adjustable power on delay and recovery time, LED indicators, DIN rail or screw mounting, and protection up to IP20. It is available in variants for 195-400V or 313-457V 3-phase input voltages.

Uploaded by

deepak_singla227
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
241 views2 pages

Auto Switch 1

The document provides specifications for an auto switch that can automatically switch between three modes - auto, manual, and bypass. It monitors 3-phase power for faults like under voltage, over voltage, phase sequence, and phase failure. Key features include adjustable power on delay and recovery time, LED indicators, DIN rail or screw mounting, and protection up to IP20. It is available in variants for 195-400V or 313-457V 3-phase input voltages.

Uploaded by

deepak_singla227
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

AUTO SWITCH AUTO SWITCH

Features :
! 3Ø - 3 wire input
! Phase sequence, Phase failure, Phase asymmetry,
Under voltage, Over voltage
! Modes: Auto, Manual, Bypass
! Pre-wired terminals

Display specifications Functional specification

Display Analog Type Time setting For Auto, manual & By pass mode
Trip / Response time
Variable setting 1 POT - Power ON delay / Recovery time Over voltage
(For all modes)
Under voltage 3.5sec ±1.5sec
Voltage unbalance
LED indication chart (For Auto, Manual & Bypass mode)
Phase reversal
Condition Indication Instantaneous (<400mesc)
Phase loss
Various condition ON LED (Green)
Healthy ON Power ON delay (min) 0-10min
Any fault present Recovery time (min) Knob setting : (0, 0.5, 1, 3, 5 & 10)
BLINK
No supply OFF
Functional specification
Input specifications
Auto switch-195/400V Auto switch-313/457V
Auto switch-195/400V Auto switch-313/457V Timing accuracy ±5% of reading
Operating voltage range 195V AC-400V AC (L-L) 313V AC-457V AC(L-L) Voltage accuracy ±1% of full scale (as per rated voltage)
VA rating Approx 20VA Healthy to trip ≥400V Healthy to trip ≥457V
Over voltage (OV)
Frequency 50-60Hz Trip to healthy ≤390V Trip to healthy ≤447V
Rated insulation voltage Ui (v) AC 500V Healthy to trip ≤195V Healthy to trip ≤313V
Under voltage (UV)
Rated impulse withstand Trip to healthy ≥205V Trip to healthy ≥323V
voltage (Uimp) 4kV
Voltage asymmetry Fixed : 50V
Phase loss Present
Output specifications Phase reversal Present
Auto manual / Bypass switch Max current (Ith) : 5A resistive Voltage hysteresis Fixed : 10V (for OV, UV & Voltage asymmetry)
Control output One 1NO relay from trip to healthy mode
Relay rating Contacts @ AC 15, 250V AC : 2A Relay mode Fail safe mode only
Contacts @ AC 12, 250V AC : 5A Operating modes Auto / Manual / Bypass
Terminal connections 1. Red wire (Red wire : 1sq.mm) : R phase voltage
supply
Environmental specifications
2. Yellow wire (Yellow wire : 1sq. mm) : Y phase
voltage supply Temperature Operating temperature : -5oC to +65oC
3. Blue wire (Blue wire : 1sq. mm) : B phase Storage temperature : -20oC to +70oC
voltage supply Humidity (non-condensing) Up to 95% RH
4. Green wire (Green wire : 1sq. mm) : Auto Pollution degree
mode For PCB 2
5. White wire (White wire : 1sq. mm) : Relay - Com For Product 3
6. Pink wire (Grey wire : 1sq. mm) : Bypass mode
(Each wire fixed length of 300mm)
Mechanical specifications

Screw tightening torque 0.6 NM


Degree of protection of device IP20
Mounting 22.5mm DIN rail + Screw mounting
Weight Approx. 115 gms

www.selec.com 1
AUTO SWITCH AUTO SWITCH

Dimensions (All are in mm) Ordering information

85
Product code Supply Voltage Certification
Auto switch-195/400V 195V AC - 400V AC (L-L)
21
Auto switch-313/457V 313V AC - 457V AC (L-L)

74 35
76

20.5

Wiring diagram (For both the variants)

L3

www.selec.com 2

You might also like