Auto Switch 1
Auto Switch 1
Features :
! 3Ø - 3 wire input
! Phase sequence, Phase failure, Phase asymmetry,
Under voltage, Over voltage
! Modes: Auto, Manual, Bypass
! Pre-wired terminals
Display Analog Type Time setting For Auto, manual & By pass mode
Trip / Response time
Variable setting 1 POT - Power ON delay / Recovery time Over voltage
(For all modes)
Under voltage 3.5sec ±1.5sec
Voltage unbalance
LED indication chart (For Auto, Manual & Bypass mode)
Phase reversal
Condition Indication Instantaneous (<400mesc)
Phase loss
Various condition ON LED (Green)
Healthy ON Power ON delay (min) 0-10min
Any fault present Recovery time (min) Knob setting : (0, 0.5, 1, 3, 5 & 10)
BLINK
No supply OFF
Functional specification
Input specifications
Auto switch-195/400V Auto switch-313/457V
Auto switch-195/400V Auto switch-313/457V Timing accuracy ±5% of reading
Operating voltage range 195V AC-400V AC (L-L) 313V AC-457V AC(L-L) Voltage accuracy ±1% of full scale (as per rated voltage)
VA rating Approx 20VA Healthy to trip ≥400V Healthy to trip ≥457V
Over voltage (OV)
Frequency 50-60Hz Trip to healthy ≤390V Trip to healthy ≤447V
Rated insulation voltage Ui (v) AC 500V Healthy to trip ≤195V Healthy to trip ≤313V
Under voltage (UV)
Rated impulse withstand Trip to healthy ≥205V Trip to healthy ≥323V
voltage (Uimp) 4kV
Voltage asymmetry Fixed : 50V
Phase loss Present
Output specifications Phase reversal Present
Auto manual / Bypass switch Max current (Ith) : 5A resistive Voltage hysteresis Fixed : 10V (for OV, UV & Voltage asymmetry)
Control output One 1NO relay from trip to healthy mode
Relay rating Contacts @ AC 15, 250V AC : 2A Relay mode Fail safe mode only
Contacts @ AC 12, 250V AC : 5A Operating modes Auto / Manual / Bypass
Terminal connections 1. Red wire (Red wire : 1sq.mm) : R phase voltage
supply
Environmental specifications
2. Yellow wire (Yellow wire : 1sq. mm) : Y phase
voltage supply Temperature Operating temperature : -5oC to +65oC
3. Blue wire (Blue wire : 1sq. mm) : B phase Storage temperature : -20oC to +70oC
voltage supply Humidity (non-condensing) Up to 95% RH
4. Green wire (Green wire : 1sq. mm) : Auto Pollution degree
mode For PCB 2
5. White wire (White wire : 1sq. mm) : Relay - Com For Product 3
6. Pink wire (Grey wire : 1sq. mm) : Bypass mode
(Each wire fixed length of 300mm)
Mechanical specifications
www.selec.com 1
AUTO SWITCH AUTO SWITCH
85
Product code Supply Voltage Certification
Auto switch-195/400V 195V AC - 400V AC (L-L)
21
Auto switch-313/457V 313V AC - 457V AC (L-L)
74 35
76
20.5
L3
www.selec.com 2