What Is Building Automation System
What Is Building Automation System
Jun '18
Mike
Complete autonomous control of an entire facility is the goal that any modern
automation system attempts to achieve. The distributed control system – the
computer networking of electronic devices designed to monitor and control the
mechanical, security, fire, lighting, HVAC and humidity control and ventilation
systems in a building or across several campuses.
Its core functionality is to keep building climate within a specified range, light
rooms based on an occupancy schedule, monitor performance and device
failures in all systems and provide malfunction alarms.
Almost all multi-story green buildings are designed to accommodate a BAS for
the energy, air and water conservation characteristics. Electrical device
demand response is a typical function of a BAS, as is the more sophisticated
ventilation and humidity monitoring required of “tight” insulated buildings.
These accommodate typically only IP-based networking but can make use of
any existing wiring, and also integrate powerline networking over AC circuits,
power over Ethernet low power DC circuits, high-bandwidth wireless networks
such as LTE and IEEE 802.11n and IEEE 802.11ac and often integrate these
using the building-specific wireless mesh open standards.
Digital outputs are used to open and close relays and switches. An
example would be to turn on the parking lot lights when a photocell
indicates it is dark outside.
Devices
Controllers
The outputs allow the controller to send command and control signals to slave
devices, and to other parts of the system. Inputs and outputs can be either
digital or analog. Digital outputs are also sometimes called discrete depending
on manufacturer.
Terminal Unit controllers usually are suited for control of lighting and/or simpler
devices such as a package rooftop unit, heat pump, VAV box, or fan coil, etc.
The installer typically selects 1 of the available pre-programmed personalities
best suited to the device to be controlled, and does not have to create new
control logic.
Air handlers
Most air handlers mix return and outside air so less temperature/humidity
conditioning is needed. This can save money by using less chilled or heated
water (not all AHUs use chilled/hot water circuits).
Some external air is needed to keep the building’s air healthy. To optimize
energy efficiency while maintaining healthy indoor air quality (IAQ), demand
control (or controlled) ventilation (DCV) adjusts the amount of outside air
based on measured levels of occupancy. Analog or digital temperature
sensors may be placed in the space or room, the return and supply air ducts,
and sometimes the external air.
Actuators are placed on the hot and chilled water valves, the outside air and
return air dampers. The supply fan (and return if applicable) is started and
stopped based on either time of day, temperatures, building pressures or a
combination.
Constant volume air-handling units
The less efficient type of air-handler is a “constant volume air handling unit,” or
CAV. The fans in CAVs do not have variable-speed controls. Instead, CAVs
open and close dampers and water-supply valves to maintain temperatures in
the building’s spaces.
They heat or cool the spaces by opening or closing chilled or hot water valves
that feed their internal heat exchangers. Generally one CAV serves several
spaces
A more efficient unit is a “variable air volume (VAV) air-handling unit,” or VAV.
VAVs supply pressurized air to VAV boxes, usually one box per room or area.
A VAV air handler can change the pressure to the VAV boxes by changing the
speed of a fan or blower with a variable frequency drive. The amount of air is
determined by the needs of the spaces served by the VAV boxes.
Each VAV box supply air to a small space, like an office. Each box has a
damper that is opened or closed based on how much heating or cooling is
required in its space. The more boxes are open, the more air is required, and
a greater amount of air is supplied by the VAV air-handling unit. Some VAV
boxes also have hot water valves and an internal heat exchanger.
The valves for hot and cold water are opened or closed based on the heat
demand for the spaces it is supplying. These heated VAV boxes are
sometimes used on the perimeter only and the interior zones are cooling only.
A minimum and maximum CFM must be set on VAV boxes to assure adequate
ventilation and proper air balance.
Chilled water is often used to cool a building’s air and equipment. The chilled
water system will have chiller(s) and pumps. Analog temperature sensors
measure the chilled water supply and return lines. The chillers are sequenced
on and off to chill the chilled water supply.
Chilled water distribution is not constrained by the 100 foot separation limit
that applies to DX systems, thus chilled water-based cooling systems are
typically used in larger buildings. Capacity control in a chilled water system is
usually achieved through modulation of water flow through the coils; thus,
multiple coils may be served from a single chiller without compromising control
of any individual unit.
Reciprocating chillers are commonly used for capacities below 200 tons.
centrifugal chillers are normally used to provide higher capacities; rotary and
screw chillers are less commonly used, but are not rare. Heat rejection from a
chiller may be by way of an air-cooled condenser or a cooling tower (both
discussed below).
The hot water system supplies heat to the building’s air-handling unit or VAV
box heating coils, along with the domestic hot water heating coils (Calorifier).
The hot water system will have a boiler(s) and pumps.
Analog temperature sensors are placed in the hot water supply and return
lines. Some type of mixing valve is usually used to control the heating water
loop temperature. The boiler(s) and pumps are sequenced on and off to
maintain supply.
The installation and integration of variable frequency drives can lower the
energy consumption of the building’s circulation pumps to about 15% of what
they had been using before. If that sounds hard to believe, I’ll explain, and we
can do the math.
Variable frequency drives are able to decrease the output and energy
consumption of motors by lowering the frequency of the electricity provided to
the motor, however the relationship between motor output and energy
consumption is not a linear one.
If the variable frequency drive provides electricity to the motor at 30 Hertz, the
output of the motor will be 50% because 30 Hertz divided by 60 Hertz is 0.5 or
50%. The energy consumption of a motor running at 50% or 30 Hertz will not
be 50%, but will instead be something like 18% because the relationship
between motor output and energy consumption are not linear.
The exact ratios of motor output or Hertz provided to the motor (which are
effectively the same thing), and the actual energy consumption of the variable
frequency drive / motor combination depend on the efficiency of the variable
frequency drive.
For example, because the variable frequency drive needs power itself to
communicate with the building automation system, run it’s cooling fan, etc., if
the motor always ran at 100% with the variable frequency drive installed the
cost of operation or electricity consumption would actually go up with the new
variable frequency drive installed.
The amount of energy that variable frequency drives consume is nominal and
is hardly worth consideration when calculating savings, however it did need to
be noted that VFD’s do consume energy themselves.
Due to the fact that the variable frequency drives rarely ever run at 100% and
spend most of their time in the 40% output range, and the fact that now the
pumps completely shut down when not needed, the variable frequency drives
have reduced the energy consumption of the pumps to around 15% of what
they had been using before.