Technical Specification: Ection

Download as pdf or txt
Download as pdf or txt
You are on page 1of 22
At a glance
Powered by AI
The document outlines technical specifications for 33/11kV power transformers that will operate in tropical climates with high temperatures, humidity, and rainfall.

The transformers need to be suitable for operating in tropical climates with maximum temperatures up to 40°C, minimum temperatures down to 3°C, relative humidity between 50-100%, annual rainfall of 3454mm, and wind velocities up to 200km/hr.

The transformers need to conform to IEC standards including IEC 76 for power transformers, IEC 137 for bushings, IEC 156 for insulating oils, IEC 296 for unused mineral oils, and IEC 551 for sound levels.

Technical Specification

SECTION 07

TECHNICAL SPECIFICATIONS OF

33/11KV, 16/20MVA POWER TRANSFORMER

16/20mva_x-former_spc_ajgar_design2 1
7.0 Technical Specification of 33/11 KV, 16/20 MVA Power Transformer

7.1 GENERAL
This section of the document includes the design, manufacture, testing & inspection of
33/11KV, 16/20 MVA, Power transformers as specified.

7.2 CLIMATE DATA


The distribution transformers to be supplied against this tender shall be suitable for satisfactory
use under the following climatic condition:

Climate : Tropical, intense sunshine, heavy rain, humid.


Maximum Temperature : 400 C
Minimum Temperature : 030 C
Maximum yearly weighted average temperature : 300 C
Relative Humidity : 50-100%
Annual mean Relative Humidity : 75%
Average annual rain fall : 3454 mm
Maximum wind velocity : 200 km/ hour
Maximum altitude above the sea level : Sea level to 300 metres
Atmospherically, Mechanical and Chemical impurities : Moderately polluted

The information is given solely as a guide for Tenders and no responsibility for its, accuracy
will be accepted nor will any claim based on the above be entertained.
Transformer supplied under this contract will be installed in tropical locations that can be
considered hostile to its proper operation. Particular problems that shall receive special
consideration relate to operation in a hot environment and presence of the insects and vermin.

7.3 SYSTEM PARTICULARS


SL.
SYSTEM C HARACTERISTICS VOLTAGE LEVEL
NO.
1. Normal System Voltage, kV (Voltage Class) 230 132 33 11
3. Maximum System Voltage, kV 245 145 36 12
4. System Frequency, Hz 50 50 50 50
5. Phase Rotation (Anti-Clock wise) RST RST RST RST
6. Type of System Grounding Solid Solid Solid Solid
7. Rated Fault Level (3-Phase Symmetrical), MVA 3 sec. 16300 6000 1500 500
8. Basic Insulation Level, kV 750 650 170 75

7.4 STANDARDS
The equipment specified in this Section of the contract shall conform to the latest edition of the appropriate
IEC specifications and other recognized international standard. In particular:

IEC 76-1 Power transformers (General).


IEC 76-2 Power transformers (Temperature Rise).
IEC 76-3 Power transformers (Insulation Levels, Dielectric Tests and External Clearance in air).
IEC 76-5 Power transformers (Ability to Withstand short circuit)
IEC 137 Bushings for alternating voltages above 1 kV.
IEC 156 Method of determination of electrical strength of insulating oils.
IEC 296 Specification for unused mineral insulating oils for transformers and switchgear.
IEC 551 Measurement of transformer and reactor sound levels.
IEC 616 Terminal and tapping markings for power transformers.
IEC 722 Guide to lightning and switching impulse testing of power transformers.
IEC 5493 Protective coating of iron and steel structures against corrosion.

16/20 mva x-former_spec & gtp_ajgar_design2 2


7.5 Technical Specification :
1. Rated MVA (ONAN/ONAF) 16/20MVA
2. Number of Phases 3 (Three)
3. Frequency 50 Hz
4. Winding Insulation Uniform
5. Normal Transformation Ratio at No-load 33/11 KV
6. Rated HT Voltage (Phase to Phase) 33 KV
7. Maximum HT Voltage (Phase to Phase) 36 KV
8. Rated LT Voltage (Phase to Phase) 11 KV
9. Maximum LT Voltage (Phase to Phase) 12 KV
10. Rated Current HT ( ONAN/ONAF) 280/ 350 Amps
11. Rated Current LT (ONAN/ONAF) 840/1050 Amps
12. Basic Insulation Level :
a) High voltage winding 170 KV
b) Low voltage winding 75 KV
13. Installation Outdoor, Tropical, High rainfall & Humidity.
14. Type Core, Conservator & Oil Immersed
15. Type of Windings Double Wound of Electrolytic Copper, free from burs
and splinter.
16. Type of Cooling ONAN/ ONAF
17. Coolant Mineral Oil as per IEC-60296
18. Type of System Earthing Effectively Earthed
19. Bushing Material Porcelain
20. Type of Base On WheelsOn wheels with adequate size and 10M
length of rails and fixing arrangement.
21. Direction of Normal Power Flow HT-LT
22. Phase connection :(∆ -Υ)
a) 33 KV winding with bushing CT Delta
b) 11 KV winding with bushing CT Star
23. Vector Group Dyn11
24. Neutral to be brought out :
a) HT Nil
b) LT Yes
25. Neutral Insulation Full insulation and 100% loading capacity
26. Maximum Temperature rise over 400C ambient at
full load & tap change is at normal position :
a) Winding by Resistance (0C) 650C
b) Oil by Thermometer (0C) 60 0C
27. Impulse Front Wave Test Voltage (1.2/50 Micro
Sec. Wave Shape) :
a) High voltage side 170 KV
b) Low voltage Side 75 KV
28. Power Frequency withstand Test Voltage for 1
(one) Minute :
a) High voltage side 70 KV
b) Low voltage Side 28 KV
29. Impedance Voltage at 750C, at normal ratio and 8.5%
rated frequency, and at ONAN condition.
30. Type of tap changer control
Features The tap changer will be on load auto regulation,
remote control and manual. The on load tap changer
will immersed in the transformer tank. The diverter
switch compartment will be provided with its own oil
conservator which, will not be connected to the
transformer oil tank.
16/20 mva x-former_spec & gtp_ajgar_design2 3
The diverter switch can easily be lifted out of its tank
for maintenance and inspection without opening the
transformer cover. The on load tap changer will
operate by means of a motor drive unit. This unit will
install on the side of the transformer.

On Load Tap changer with motor drive unit MR, Germany/ABB, Sweden
manufacturer’s name & country
Tapping Range :
a) HT 17 Tapping ± 10% in steps of 1.25% i.e. 33 KV ± 8 x
1.25%
b) LT Nill
31. Bushing CT for differential protection 400/5A on HV, 1200/5A on LV of accuracy class
5P20, burden 20 VA.
32. Neutral Bushing CT for Standby Earth Fault (SEF) 1200/5-5A on LV neutral of accuracy class 5P20,
& Restricted Earth Fault (REF) protection burden 20 VA.

33. Standard Design, Manufacture, Testing, Installation and


Performance shall be in accordance to the latest
editions of the relevant IEC standards.
34. Transformer Oil
Application Insulating mineral oil for TransformerIt will be free
from PCB (polychlorinated biphenyl)
Grade of oil Class-1
PHYSICAL PROPERTIES
Appearance Liquid and free from suspended matter or sediment
Density at 200 C 0.895 g/cm3 (maximum)
Flash point (Closed cup) 1400 C (minimum)
Kinematics Viscosity at -150 C 800 cSt. (Maximum)
Kinematics Viscosity at 200 C 40 cSt. (Maximum)
Pour point -300 C (maximum)
ELECTRICAL PROPERTIES
Dielectric Strength at 50 Hz (with 2.5 mm standard New untreated oil, shall go through filtration treatment
gap and 40 mm standard depth) before the oil are introduced into the apparatus or
equipment. The break down voltage of this oil shall
be at least 50KV.

Loss tangent/Dielectric dissipation factor at temp. 0.005 (maximum)


900 C, stress 500V/mm to 1000 v/mm and
frequency 40 Hz to 62 Hz.
CHEMICAL PROPERTIES
Neutralization value 0.03 mg KOH/g (maximum)
Neutralization value after oxidation 0.40 mg KOH/g (maximum)
Total sludge after oxidation 0.10% weight (maximum)
PCB Content Free from PCB
STANDARDS Performance and testing of oil shall comply with the
latest revision of the relevant standards BS 148 :
1972, IEC-60296 or latest revision there on.

16/20 mva x-former_spec & gtp_ajgar_design2 4


35. FEATURES & A CCESSORIES OF TRANSFORMER:
a) Bushing Insulator on HT and LT.
b) Arcing horns on HT and LT bushings.
c) Remote Tap Changer Control (RTCC) facility in Transformer HT incoming PCM Panel.
d) Oil conservator.
e) Buchholz relays in main conservater oil pipe.
f) Tap Changer Protective Relay in between conservative and tap changer oil pipe.
g) Conservator drain valve, breather and oil level gauge with alarm contact.
h) Pressure Relief Device (PRD).
i) Dial type thermometers with alarm and trip contracts.
j) CT for winding temperature shall be located at mid-phase (Y-phase) of the transformer.
k) Radiators.
l) One inspection hole with cover.
m) Facilities for lifting cover and coil assembly from tank.
n) Lifting lugs for lifting complete Transformer.
o) Base designed for rollers with bi-directional flanged rollers parallel to either Centre line.
p) Tank oil sampling, draining valve and oil centrifuging outlets.
q) Tank earthing points.
r) Fans for forced cooling (ONAF).
s) All mounting accessories including rails (2 Nos. rails each 10 Meter long).
t) All equipment should be fully tropicalized.
u) Painting to approved colour and shade.
v) Rating nameplate and diagram plate of stainless steel having engraved letters filled with black
enamel paint.
w) The oil shall be supplied/ delivered in non-returnable sealed containers/ drums.
x) The oil shall be fresh, unused, cleaned and free from suspended matter or sediment.
y) The test shall be carried out on the oil as to be supplied without drying and degassing.
z) Uninhibited oils must not contain anti-oxidant additives.
aa) Laminated, detailed Schematic Diagram of Control Circuit of Transformer & Tap changer inside
Marshalling kiosk.
7.6 INFORMATION REQUIRED
The Bidder/ Manufacturer as per tender requirements shall provide all information. The following
information/documents has to be submitted along with the tender otherwise the bid will be
rejected:
a) The Tenderer/Manufacturer shall submit the testing procedure & list of testing/measuring equipment,
meters etc for offered typed transformer used for Factory test witness.
b) Construction ,Installation, Operation & Maintenance Manual of offer typed Power transformer.
c) Manufacturer’s valid ISO Certificate.
7.7 DOCUMENTATION
The following Drawings, Technical Documents and Information shall be submitted with the offer for the
offered type 33/11kV, 16/20 MVA Power Transformeror higher MVA rating of same voltage class,
otherwise the bid will be rejected:-
A. C OMMERCIAL
Tenderer shall be eligible as per ITT Clause No. 4 and they should submit Bid validity, Bid Bond, Bid
Bond validity, Price Schedule, Delivery Schedule, Authorisation of the signatory, Tender Submission
Sheet, Tenderer Information Sheet & Documentary evidence for establishing the Tenderer’s
Qualifications, etc. and all other documents including information related to rejection clause as per Tender
Document.

16/20 mva x-former_spec & gtp_ajgar_design2 5


B. TECHNICAL
a) Letter of authorization from the Manufacturers, in case, the bidder is not the
manufacturer, in prescribed Form (G-5).
b) Manufacturer's authorization Letter in prescribed Form G-5 for Tap Changer (MR
Germany/ ABB, Sweden).
c) Minimum 3(Three) nos. of Manufacturer’s Supply recordfor similar or higher MVA
rating of same voltage class of offered type Power Transformerswithin the last 5
(five) years from the date of tender openingin the following format (The supply
record covering at least 25% of the total offered amount/ tendered quantity in a
single contract will be considered only):
Sl. Name, Address, Contract Contract Description of Date of
No Phone & Fax No. No. & Value Materials with Completion
. of the Consumer Date Quantity of Supply

d) Satisfactory Performance certificates (SPC) issued within the last 5 years from at
least 2 End users depicting that the offered type 33/11kV, 16/20 MVA Power
Transformers or higher MVA rating of same voltage class, has been in service for
at least 3 years. End user must be an Electricity Utility Service.
e) Guaranteed Technical Particulars (GTP) shall be properly filled up with submission
of related supporting documents & signed by the Manufacturer & Tenderer.
f) Outline and General Arrangement drawings of the offered type Power Transformer.
g) Cross-section Drawing showing the arrangement of core and windings of the
offered type Transformer.
h) Manufacturer’s Printed Catalogue describing specification and technical data for
crucial components (i.e. Bushings, OLTC, PRD, Buchholz, Dial type Temp. Meters,
etc.) of offered type equipment.
i) Submission of Special & Type Test Reports as stated in Clause 7.8.2. & 7.8.3. and
GTP, as per relevant IEC or other equivalent Standards from KEMA, Netherlands;
CESI, Italy; CPRI, India; China National Transformer Quality Supervision Testing
Center (CTQC), China; China Electric Power Research Institute (CEPRI), China;
BRTC, BUET..
j) Bidder shall declare guaranteed No Load Loss and Full Load Loss value in GTP.
Any Tenderer quoted the No Load Loss & Full Load Loss above the upper limit of
the loss as mentioned in GTP (Section 8, Clause 8.01, Sl No.3.9) in Tender
Document will not be considered for further evaluation & treated as non-
responsive. The Tenderer who will quote the No Load Loss & Full Load Loss below
the lower limit of No Load Loss & Full Load Loss as mentioned in GTP (Section 8,
Clause 8.01, Sl No.3.9) In that case during evaluation Capitalization cost will be
calculated only on the basis of the lower limit of No Load Loss & Full Load Loss.
Their quoted loss will not be considered for evaluation of capitalization cost.
Tenderer who quoted No Load Loss & Full Load Loss do not support with loss
calculation & type test report will also be treated as non- responsive.
k) Bidders declared/ guaranteed Percentage Impedance value shall be within the
specified value.
L) Local manufacturers, who have supplied the same offered item to BPDB within
the last 5 (five) years from the date of opening, need not to submit any Manufacturer's
Supply Record, Satisfactory Performance Certificate & Type Test report with the
tender proposal. In that case, they have to submit Satisfactory Performance Certificate
(taken at a date after the tender invitation) from Director, Purchase, BPDB, Dhaka, for
the same offered item.
16/20 mva x-former_spec & gtp_ajgar_design2 6
7.8 TEST REPORTS:
The following test reports/certificates including their test results for the routine and type
tests prescribed in "relevant IEC Standard" for the offered type rating transformer of
same voltage Class are to be furnished with the Bid, otherwise the bid will be treated
as non-responsive and will not consider for further evaluation.
7.8.1 ROUTINE TESTS
a) Measurement of insulation resistance.
b) Measurement of Voltage ratio test.
c) Measurement of winding resistance at Each Tap position.
d) Vector group test.
e) Measurement of no-load loss & current.
f) Measurement of short circuit impedance and load loss.
g) Power frequency (Separate source voltage) withstands test.
h) Transformer oil test.
7.8.2 TYPE TESTS
a) Temperature Rise Test
b) Lightning Impulse Test
7.8.3 SPECIAL TESTS
a) Short circuit withstands test report of HV-LV.
Note:
l) Type Tests and Special Tests Reports as per relevant IEC shall be submitted from KEMA,
Netherlands; CESI, Italy; CPRI, India; China National Transformer Quality Supervision Testing Center
(CTQC), China; China Electric Power Research Institute (CEPRI), China; BRTC, BUET. otherwise
the bid will be rejected. Evidences of accredited laboratory are to be submitted with the bid.

7.9 CAPITALIZED C OST:


Bidder shall declare guaranteed No Load Loss and Full Load Loss value in GTP. Any Tenderer
quoted the No Load Loss & Full Load Loss above the upper limit of the loss as mentioned in
GTP (Section 8, Clause 8.01, Sl No.3.9) in Tender Document will not be considered for further
evaluation & treated as non- responsive. The Tenderer who will quote the No Load Loss & Full
Load Loss below the lower limit of No Load Loss & Full Load Lossas mentioned in GTP (Section
8, Clause 8.01, Sl No.3.9) In that case during evaluation Capitalization cost will be calculated
only on the basis of the lower limit of No Load Loss & Full Load Loss. Their quoted loss will not
be considered for evaluation of capitalization cost. Tenderer who quoted No Load Loss & Full
Load Loss do not support with loss calculation & type test report will also be treated as non-
responsive.
The fixed and running losses are to be low as consistent with reliable and economical use of materials.
The cost of losses is to be minimized and the following capitalized parameters will be used in the
evaluation of the transformer:
C = 68,706 x e x P0 + 54,964 x e x PFL
Where,
C = Capitalized cost of transformer loss in Bangladesh Taka.
e = Energy Cost, Tk. 6.00/KWh
PFL = Full Load losses at rated voltage, normal ratio and rated frequency in ONAF condition at 750C
in KW + Auxiliary loss in KW
P0 = No load losses at rated voltage, normal ratio and rated frequency in KW
The cost of energy (C) will be added to the quoted prices to arrive at the evaluated cost of the
transformer. The contract will be cancelled if losses exceed the guaranteed value by an amount in excess
of followings:

Total losses : 10%


Component : 15% of each component loss (Unless the total losses exceeds 10%).
16/20 mva x-former_spec & gtp_ajgar_design2 7
7.10 SHIPPING:
All the delicate components shall be dismantled and packed in strong wooden boxes having inside lined
with metallic sheets with proper sealing to protect the content from accidental direct exposure to weather
during storage. The holes of the transformer tank shall be sealed with proper metal plate and gaskets to
prevent leakage of oil and its contamination with atmospheric moisture. The transformer shall be shipped
with radiators, busing conservator etc. dismantled but the tank filled with oil. The transformer oil from
radiators and conservator shall be shipped in non-returnable drums.The bushing shall be shipped in oil
sealed containers to avoid moisture absorption during shipment and storage. Oil shall be complying with
IEC-60296.
7.11 HT B USHING :
Provide 3 porcelain outdoor type, oil filled, impulse tested bushing with arcing horns of standard gap and
bolted type terminal connectors, with head shrink rubber insulated cap suitable for connection to the
incomes leads of ACSR Gross Beak (636 MCM) conductor.
7.12 LT B USHING:
Provide 4 porcelain outdoor type bushing with bolted type connectors, suitable for connection to outgoing
leads of two numbers of 240 Sq.mm XLPE, single core copper conductors per phase and suitable for
head shrink termination.

7.13 FAULT C ONDITIONS:


The transformer shall be capable of withstanding, on any tapping, for three seconds without damage an
external short circuit between phases. The transformer winding shall be capable of withstanding for three
seconds without damage a short circuit between one phase and earth with the neutral of the transformer
directly earthed. For the purposes of this clause a fault level of 1500 MVA at the transformer 33KV
terminals shall be assumed.
Evidence shall be submitted with the Tender as to the extent to which the manufacturer has provided or is
able to prove either by calculation or test the ability of the specified transformers to withstand on any
tapping, without damage under service conditions, the terminal and dynamic effects of external short
circuit.
The Bid shall state tin the Technical Schedule a brief description of those transformers or parts thereof,
which have been subjected to short circuit tests or for which short circuit calculations are available. It is
preferred that this information relates to designs comparable with the transformers bidder but in the event
this is not so the Engineer reserves the right to require calculating to prove that the design of transformers
tendered will satisfactorily comply with this clause : such calculations being in accordance with the latest
revision of IEC/ BS standard.
7.14 NOISE :
Vibration and noise levels of all transformers and auxiliary plant shall be in accordance with the NEMA
TRI 1962. The contract price shall include noise level tests to be carried out on one transformer.
7.15 HARMONIC SUPPRESSION:
Transformer shall be designed with particular attention to the suppression of harmonic voltages especially
the third and fifth harmonics and to minimize the detrimental effects resulting there from.
7.16 IMPEDANCE AND REGULATION:
The Bidder shall state in the Technical Schedules guaranteed values of impedance measured on normal
and extreme tapping and the voltage regulation from no load to CMR at unity power factor and at 0.9
lagging power factor with constant voltage across the higher voltage windings.

7.17 MAGNETIC C IRCUIT:

The design of the magnetic circuit shall be such as to avoid static discharge development of short circuit
paths internally or to the earthed clamping structure and the production of flux components normal to the
plane of the laminations. Each lamination shall be insulated with a material stable under the action of
pressure and hot oil.
16/20 mva x-former_spec & gtp_ajgar_design2 8
The winding structure and major insulation shall be designed to permit an unobstructed flow of cooling oil
through core cooling oil ducts to ensure efficient core cooling.

The magnetic circuit shall be insulated from all structural parts and shall be capable of withstanding a test
voltage to core bolts and to the frame of 2000 volts rms for one minute.

7.18 FLUX DENSITY:

Cores shall constructed from clod rolled grain oriented steel sheets. Provided the contractor can provide
adequate evidence that there will be no adverse effects due to stray flux heating of core with the quality of
steel employed, designs may be offered such that when operating under the most onerous conditions, flux
density in any part of the magnetic circuit does not exceed 1.7 Tesla.

The Contractor shall determine the operating conditions under which the maximum flux density will be
attained within the following simultaneously applied limits.

- Frequency : 50 Hz
- LV and HV Voltage : Up to but not exceeding the specified maximum System voltage.
- Load : The transformer may be subjected to intermittent overloading of 150%
rated MVA at 0.8 power factor lagging in accordance with IEC-60035.

The maximum flux densities anticipated under these conditions are to be stated in Technical Schedules
(GTP).

7.19 WINDINGS:
The transformer windings shall have uniform insulation as defined in the latest revision of IEC standard.
The transformers shall be designed to withstand the impulse voltage levels and the power frequency
voltage tests specified in the Technical Schedules.
The winding shall be located in a manner which will ensure and that they remain Electro-statically
balanced and that their magnetic centers remain coincident under all conditions of operation.
The winding shall also be thoroughly seasoned during manufacture by the application of axial pressure at
a high temperature for such length of time as will ensure that further shrinkage is unlikely to occur in
service.
All electrical connections within windings shall be brazed to withstand the shocks, which may occur
through rough handling and vibration during transport switching and other transient service conditions.
Coil clamping rings shall be of the on on-magnetic steel or insulating materials built up from flat
laminations. Auxiliary laminated material other then Bakelite paper is not to be used.
Where Bakelite paper rings are used with the layers of paper lying in the axial direction, the rings may be
relied upon to provide the major insulation between the windings and frame subject to there being
adequate creepage distance.
Any metal pieces in contact with laminated rings shall be designed and secured so that they do not
weaken the electrical or the mechanical properties of the rings.
If the winding is built up of section or of disc-coils separated by spacers, the clamping arrangement shall
be ensure that equal pressure are applied to all columns of spacers.

7.20 INTERNAL E ARTHING A RRANGEMENT:

All metal parts of the transformer with the exception of the individual core lamination, core bolts
and associated individual clamping plates, shall be maintained at some fixed potential.
The top main core clamping structure shall be connected to the tank body by a copper strap and the
bottom main core clamping structure shall be earthen by one or more of the following methods:
- by connection through vertical tie rods to the top structure.
- by direct metal-to-metal contact with the tank base maintained by the weight of the core and
windings.
- by connection to the top structure on the same side of the core as the main earth connection to
the tank.
The magnetic circuit shall be earthed to the clamping structure at one point through a removable link
placed in an accessible position just beneath an inspection opening in the tank cover and which, by
disconnection, will enable the insulation between the core and clamping plates, etc. to be tested at
voltages up to 2 KV for the purpose of checking deterioration during service. The connection to the link
shall be on the same side of the core as the main earth connection. These requirements are mandatory.
16/20 mva x-former_spec & gtp_ajgar_design2 9
Magnetic circuits having an insulated sectional construction shall be provided with a separate link for each
individual section and the arrangement of the connections shall be subject to the approval of the
Engineer.
Where oil ducts or insulated barriers parallel to the plane the laminations divide the magnetic circuits into
two or more electrically separates parts, the ducts and insolating barriers which have the thickness
greater than 0.25, mm are to be bridged with tinned copper strips so inserted as to maintain electrical
continuity.
Where coil-clamping rings are of metal at each potential, each rings shall be connected to the adjacent
core clamping structure on the same side of the transformer as the main earthing connection.
Main earthing connections shall be a cross-sectional area of not less than 100mm2 but connections
inserted between laminations may have cross sectional areas reduced 20mm2 when in close thermal
contact with the core.

7.21 TRANSFORMER TANK


The Transformer Tank shall be welded construction fabricated from high tensile steel plate and shall be
designed to withstand full vacuum. The transformer shall have air seal type oil conservator tank at the top.

7.22 OIL
All transformers shall be filled to the required level with new, unused, clean, standard mineral oil after
treatment in compliance with IEC 60296 & BS 148.

7.23 GASKETS
Any gaskets provided with the transformers shall be suitable for making oil tight joints, and there shall be
no deleterious effects of either gaskets or oil when the gaskets are continuously in contact with hot oil. No
gaskets shall be used in which the material of the material of the gasket is mounted on a textile backing.
Exterior gaskets shall be weatherproof and shall not be affected by strong sunlight.
7.24 EVALUATION CRITERIA
a) The Tenders will be evaluated on the basis of the capitalized cost of the Transformer losses.
b) Bidder will declared/ guaranteed No-Load loss and Full load loss value, otherwise the bid will be
rejected.
c) Bidders declared/ guaranteed percentage impedance value shall be within the specified value,
otherwise the bid will be rejected.

7.25. ACCEPTANCE CRITERIA OF TRANSFORMER LOSS AND PERCENTAGE IMPEDANCE


DURING FACTORY TEST
Transformer will be tested during technical orientation & quality acceptance and will be accepted if the measured
transformer losses are within the offered value or within the following tolerance with deduction of amount from the
contract price as below:
i) Any component loss (No load loss or Full load loss) may exceed up to 15% of the offered component loss,
provided that the total loss((No load loss + Full load loss) shall not exceed 10% of the offered total loss. If any
component loss exceeds 15% of the offered component loss, the full consignment will be rejected.
ii) Total loss (No load loss + Full load loss) may exceed up to 10% of the offered total loss. If it exceeds 10%, the
full consignment will be rejected.
iii) Percentage Impedance may vary up to ±10% of the specified value. If the value exceeds the tolerance (±10%),
the full consignment will be rejected.
Transformer will be tested during factory test witness and will be accepted if the measured transformer losses are
within the offered value or within the acceptable limit as specified in (i), (ii) and (iii) provided an amount will be
deducted from the Contract price for the loss(s) exceeding the offered/declared loss(s) according to the following
formula:-
Amount to be deducted from the Contract price
= Contract Price x {(Measured loss - Specified offered /declared loss) ÷ Specified loss} X
%MT
Where,
Measured Loss (in KW) = Measured Average No load Loss* 1+ Measured Average Full Load
Loss* 2.
Offered Loss (in KW) = Offered No Load Loss + Offered Full load loss
16/20 mva x-former_spec & gtp_ajgar_design2 10
Transformer Economic Life = 20 Years

%MT (Percentage of Monetized Transformer) = % of the Monetized Transformer found during factory test witness
by BPDB's inspection team whose measured loss(s) (No load loss or Full load loss or Both) exceed the offered
loss (No load loss or Full load loss or Both) but remain within acceptable limit. For example : If total no. of
transformers to be inspected is 80 and the no. of selected transformers during QAT/pre-delivery inspection is 8, 6
nos. are found within the offered losses and 2 nos. are found exceeding the offered losses then the %MT will be
(2/8)x100=25%
* 1Measured Average No Load Loss = [Sum of the measured No-load losses of the tested
transformer(s) exceeding the offered No-load loss ÷ Nos.
of tested transformer(s) which exceeds the offered No-
load loss]
* 2Measured Average Full Load Loss = [Sum of the measured Full-load losses of the tested
transformer(s) which exceeding the offered Full-load loss
÷ Nos. of tested transformer(s) which exceeds the offered
Full-load loss

7.26 RECOMMENDED SPARE PARTS :


With the tender the manufacturers shall supply list of recommended spare parts for 5 years operation and
maintenance with unit price quoted for each item, which shall be valid for a period of 2 years from the date
of signing Contract.

7.27 APPROVAL OF DRAWINGS


Design, Drawing diagrams, Specification and Technical Particulars & Guarantees etc, shall be submitted
to the Engineer, Director, Design & Inspection–II, BPDB by the Bidder for approval, prior to the
manufacturing of the goods. The Tenderer shall have to submit 3 (three) sets of the same for approval
within 15 (fifteen) days from the date of signing Contract. The submittal shall include Calculation for the
Max. Temp. Rise of Winding & Oil over 400C ambient supported by Load Losses and Heat Dissipation by
Radiator and also Short Circuit Calculation along with thermal & mechanical calculations on the basis of
proposed Design Data.
No work shall be performed in connection with the fabrication and manufacture of the Testing Equipment
until the technical data and drawings have been approved.
The cost of supplying drawings and specifications shall be borne by the supplier.
At the time of delivery of Equipment, the supplier shall supply three (3) sets of all approved technical data
and drawings in bound book form along with manufacturer’s original catalogue of the Equipment to the
office of Director, Design & Inspection-II, BPDB, 9/B, Motijheel C/A, Dhaka, Bangladesh, Telephone # 88-
02-9550404.
7.28 TESTS AT MANUFACTURERS WORKS:
7.28.1 G ENERAL
Functional electrical, material, mechanical and hydraulic tests shall be carried out at manufacturers’
premises. The extent and method of recording the results shall be agreed by the Purchaser in ample time
to enable the tests to be satisfactorily witnessed or to make any changes to the proposed program of
tests.
7.28.2 MATERIAL TESTS:
The supplier shall provide test pieces free of charge as required to enable the quality of the material to be
determined at the supplier’s expense. Purchaser may at its own discretion and by specific arrangement
accept certified particulars of tests carried out in the absence of his authorized representative.
7.28.3 TYPE TEST:
Type tests are required on all items to prove the general design of the goods offered. The Bidders shall
submit the type test report of offered item from internationally reputed independent testing laboratory.
7.28.4. ROUTINE TESTS:
16/20 mva x-former_spec & gtp_ajgar_design2 11
All items shall be subjected to routine tests in accordance with the relevant latest version of IEC, BS &
BDS standards at the manufacturers works and shall include, but not be limited to, an operational test.
7.29 TECHNICAL O RIENTATION AND Q UALITY TEST WITNESS :
The Purchaser shall have the right to inspect/test the goods/materials to confirm their conformity to the
specification. The purchaser shall be entitled at all reasonable time during manufacture to inspect,
examine and test of goods/materials at the manufacturers’ premises, workmanship and performance.
The following test (not limited to) shall be carried out as per latest version of IEC or equivalent standard
unless otherwise mentioned at the manufacturer premises or other places where the test facilities are available:-
Acceptance Tests:-
1. Measurement of turn ratio test;
2. Vector group test;
3. Measurement of winding resistance;
4. Measurement of insulation resistance;
5. Measurement of no load loss & no-load current;
6. Measurement of impedance voltage & load loss;
7. Dielectric withstands Tests;
8. Transformer oil test;
9. Temperature rise test.

The purchaser can carryout the testing of any no. of transformers during Quality Test Witness. But, the
testing of transformers during Quality Test Witness will not be less than 10% at random basisofthe
transformer ready for inspection but in any case it will not be less than 3 nos. The manufacturer will
provide all arrangements for the testing of transformers desired by the purchaser in his factory.

The Supplier shall, after consulting the purchaser, give the Purchaser reasonable notice in writing of the
date on and the place at which any material or equipment will be ready for testing as provided in the
contract and unless the purchaser shall attend at the place so named on date, which the supplier has
stated in his notice, the supplier may proceed with the tests, which shall be deemed to have been made in
the purchaser’s presence, and shall forth with forward to the purchaser duly certified copies of test
readings.

When the purchaser intends to attend the test he shall promptly inform the supplier accordingly in writing,
so that he can take action. The purchaser shall give the supplier timely notice in writing of his intention to
attend the test.

Where the supplier provides for tests on the premises of the supplier or of any manufacturer of the
supplier, except where otherwise specified, shall provide free of charge such assistance, labor, materials,
electricity, fuel, stores, apparatus and instruments as may be requisite and as may be reasonably
demanded to carry out such test efficiently. These test shall be performed as per relevant IEC/BS
Standard or equivalent and only routine tests as agreed upon, will be performed.

As and when the purchaser is satisfied that any materials/equipment shall have passes the tests referred
to in this clause, purchaser shall notify the contractor in writing to that effect.

Should any inspected/tested goods fail to conform to the specification, the Purchaser shall have the right
to reject any of the item or complete batch if necessary. In that case Supplier have to replace the
Equipment and to make good of them without any financial involvement to the Purchaser. In case any of
the Equipment found not conforming with the specification at the time of post landing Inspection, the
supplier will in no way be relieved from the responsibility of replacing them on making them good at their
own cost, despite the Equipment were found good at the time of Factory Acceptance Test. Nothing in this
clause shall in any way release the supplier from any warranty or other obligations under the contract.
BPDB’s Inspection Team of at least 03(Three) Engineers shall have to conduct Technical Orientation
and Quality Test Witness at the manufacturer’s factory premises. The cost incurred for this purpose shall
be borne by the contractor and shall be deemed the cost in this regard is included in the offered price.

16/20 mva x-former_spec & gtp_ajgar_design2 12


The cost of Air Tickets (both way) from Bangladesh to Manufacturer’s Country (place of Technical
Orientation and Quality Test Witness), Hotel Accommodation etc. will be borne by the contractor. Other
than this the contractor will pay a standard amount of pocket money per day (Excluding journey period).
The period for this purpose is more or less 07 (Seven) days. All the cost of this purpose shall be deemed
is included in the offered price.
No goods shall be packed, prepared for shipment/delivery unless it has been approved and written
instruction have been received by the Purchaser.

7.30 POST LANDING INSPECTION:

Post landing inspection shall be done immediately after arrival of the goods/materials at the designated
store of BPDB; the Engineer & representative from consignee shall conduct Post Landing Inspection in
presence of the representative of Supplier. The program of such inspection shall be intimated to the
representative of Supplier by BPDB upon arrival of the materials at BPDB store of the Inspector(s) to be
selected for test witnessing. Any defect or damage have been found at post-delivery inspection, the
defective or damaged panels/ materials/ goods to be repaired/ replaced by the Bidder/ supplier at his own
cost.

16/20 mva x-former_spec & gtp_ajgar_design2 13


SECTION 08

G UARANTEED TECHNICAL PARTICULARS (GTP) FOR

33/ 11 KV, 16/20 MVA POWER TRANSFORMER

16/20 mva x-former_spec & gtp_ajgar_design2 14


8.01 MANUFACTURER’S GUARANTEED TECHNICAL DATA SCHEDULE
FOR 33/11KV, 16/20 MVA POWER TRANSFORMER
(To be filled up by the Manufacturer in Manufacturer Letterhead Pad, otherwise the bid shall be rejected.)
Manufacturer's
Sl. BPDB's
Description Unit Guaranteed
No. Requirement
Particulars
1. RATING AND PERFORMANCE
1.1 Manufacturer’s name & country - To be mentioned
1.2 Manufacturer’s Model no. - To be mentioned
1.3 Continuous maximum rating (ONAN / ONAF) MVA 16/20
1.4 No. of phases Nos. 3
1.5 Rated frequency Hz 50
1.6 Normal transformation ratio at No-load kV 33/11
1.7 Rated HT voltage (phase to phase) kV 33
1.8 Maximum HT voltage (phase to phase) kV 36
1.9 Rated LT voltage (phase to phase) kV 11
1.10 Maximum LT voltage (phase to phase) kV 12
1.11 Installation - Outdoor
1.12 Type of Transformer - Core, Conservator,
Oil immersed
1.13 Direction of normal power flow - HT-LT
1.14 No of windings Nos. 2
1.15 Bushing materials - Porcelain
1.16 Type of cooling - ONAN/ONAF
1.17 Coolant - Mineral Oil free from
PCB as per IEC-296

1.18 Type of earthing - Effectively earth


1.20 Type of base - On wheels with
adequate size and
10M length of rails
and fixing
arrangement
1.21 Phase connection:
a) 33 KV winding with bushing CT - Delta
b) 11KV winding with bushing CT - Star
1.22 Vector group - Dyn11
1.23 Neutral to be brought out :
a) HT - Nil
b) LT - Yes
1.24 Basic Insulation Level (BIL) :
a) High voltage winding KV 170
b) Low voltage winding KV 75
1.25 Max. Temp. Rise over 400C of ambient (at CMR & normal tap change position) supported by Design
Calculation sheet (to be enclosed) on the basis of Design Data:-
a) Winding Temp. Rise 0C 65
b) Top Oil Temp. Rise 0C 60

16/20 mva x-former_spec & gtp_ajgar_design2 15


Manufacturer's
Sl. BPDB's
Description Unit Guaranteed
No. Requirement
Particulars
TEST VOLTAGE :
1.26 Impulse front wave test voltage (1.2/50 micro sec. wave
shape) :
a) High voltage side kV 170
b) low voltage side kV 75
1.27 Power Frequency withstand test voltage for 1 (one)
minute :
a) High voltage side kV 70
b) Low voltage side kV 28
1.28 Short circuit MVA available :
a) at 33 KV MVA 1500
b) at 11KV MVA 500
1.29 Impedance voltage at 75 0C and at normal ratio and % 8.5%
rated frequency and at ONAN condition.
2. VOLTAGE C ONTROL (OLTC)
2.1 Type of Tap Changer control - On load auto
regulation and remote
& manual control

2.2 OLTC, MDU & AVR Manufacturer's name & country - MR Germany/ ABB,
Sweden
2.3 Nos. of tapping - 17
2.4 Tapping steps - +10% in steps of
1.25% 17 tapping (i.e.
33+8x1.25%)
2.5 HV or LV winding - HV winding
2.6 Power Frequency withstand test voltage between first kV 75
and last contracts of the selector switch between
diverter and switch contract.

3. G ENERAL
3.1 Manufacturer’s Name & Address To be mentioned
3.2 Material of core & grading To be mentioned
3.3 Core Loss/ Kg, supported by Characteristic Curve (to To be mentioned
be submitted )
3.4 Thickness of core, mm To be mentioned
3.5 Core Dia, mm To be mentioned
3.6 Total weight of core, Kg To be mentioned
3.7 Maximum flux density in iron at normal voltage and
frequency and at normal ratio (ONAF condition)
a) Cores Tesla < 1.7
b) Yokes Tesla To be mentioned
3.8 Magnetizing current (approx.) % To be mentioned

16/20 mva x-former_spec & gtp_ajgar_design2 16


Manufacturer's
Sl. BPDB's
Description Unit Guaranteed
No. Requirement
Particulars
3.9 a) No load losses at rated voltage, ratio and KW 10-17
frequency.
b) Full Load losses at rated voltage, normal ratio & KW To be mentioned
frequency in ONAN condition at 750C.
c) Full Load losses at rated voltage, normal ratio & KW 80-100
frequency in ONAF condition at 750C.
d) Auxiliary Losses KW To be mentioned
e) Total Loss (a+c+d) KW To be mentioned
3.10 Maximum current density in core at CMR A/mm2 To be mentioned
4. DETAILS OF CONSTRUCTION
4.1 Types of winding: - To be mentioned
a) HV
b) LV
4.2 Copper Conductor's Manufacturer Name & Address To be mentioned
4.3 Material of windings - copper
4.4 Winding resistance of :
a) H.T. winding, Ohm. To be mentioned
b) L.T. winding, Ohm. To be mentioned
4.5 Current density of :
a) H.T. winding, Amps/sq. mm A/mm2 To be mentioned
b) L.T. winding, Amps/sq. mm A/mm2 To be mentioned
4.6 Outer, Inner & Mean dia of copper winding:
a) H.T. winding, mm To be mentioned
b) L.T. winding, mm To be mentioned
4.7 Size of Copper conductor/bar :
a) H.T. winding SWG, dia. in mm / area in mm2 To be mentioned
b) L.T. winding SWG, area in mm2 To be mentioned
4.8 Number of Turns :
a) HT winding. nos. To be mentioned
b) LT winding nos. To be mentioned
4.9 Copper weight of windings :
a) HT winding Kg To be mentioned
b) LT winding Kg To be mentioned
4.10 Total weight of copper windings Kg To be mentioned
4.11 Type of insulation of : -
a) Tapping To be mentioned
b) Tapping connections
c) Core bolts
d) Core bolt washers
e) Side plates
f) Core laminations

16/20 mva x-former_spec & gtp_ajgar_design2 17


Manufacturer's
Sl. BPDB's
Description Unit Guaranteed
No. Requirement
Particulars
4.12 Type of winding connections - To be mentioned
(crimped or brazed )
4.13 Thickness of transformer tank:
a) Top mm To be mentioned
b) Sides mm To be mentioned
c) Bottom mm To be mentioned
4.14 Material used for gaskets for oil tight joints mm To be mentioned
5. RADIATORS
5.1 Thickness of radiator plates/ cooling tubes mm To be mentioned
5.2 Equipment for ON cooling state
a) radiators on main tank - To be mentioned
b) separate cooler banks - To be mentioned
5.3 Number of coolers/ radiators or cooler banks per Nos. To be mentioned
transformer
5.4 Rating of each cooler /radiator bank KW To be mentioned
6. Oil Volume and Weight
6.1 Type of oil Class-1 grade,
insulating mineral
oil, free from PCB
(polychlorinated
biphenyl)
6.2 Breakdown Voltage at 2.5mm gap between >50 kV
electrodes
6.3 Total oil required including cooler system Litres To be mentioned
6.4 Volume of oil above of the top yoke Litres To be mentioned
6.5 Total volume of conservator Litres To be mentioned
6.6 Weight of core and winding assembly Tones To be mentioned
6.7 Weight of each oil cooler bank complete with oil if Tones To be mentioned
mounted separately from transformer
6.8 Total weights of complete transformer, including Tones To be mentioned
attached coolers, voltage regulating equipment ,all
fittings and oil
6.9 Weight of transformer arranged for transport Tones To be mentioned
6.10 Brief description of transformer or parts thereof - To be mentioned
subjected to short-circuit test or for which short-
circuit calculations are available

16/20 mva x-former_spec & gtp_ajgar_design2 18


Manufacturer's
Sl. BPDB's
Description Unit Guaranteed
No. Requirement
Particulars
7. TRANSFORMER B USHING INSULATORS
7.1 Manufacture’s name & country - To be mentioned
7.2 Insulator material - Porcelain
7.3 Bushing Current Rating at 75˚C A To be mentioned
7.4 Insulator type and rated voltage - To be mentioned
7.5 Pitch circle diameter and drilling of flange mm To be mentioned
approx.
7.6 Length of Insulator (overall ) mm To be mentioned
7.7 Weight of Insulator kg To be mentioned
7.8 One minute 50 Hz dry withstand routine test KV To be mentioned
voltage
7.9 Lightning Impulse flashover voltage (1.2/50 wave ) KV To be mentioned
7.10 Fullwave Lightning Impulse Voltage withstand KV To be mentioned
7.11 50 Hz wet withstand voltage across arcing horns KV To be mentioned
7.12 Under oil flashover voltage type test KV To be mentioned
7.13 Total creepage distance of shedding mm To be mentioned
7.14 Protected creepage distance of shedding mm To be mentioned
8. BUSHING CTS 33 KV FOR DIFFERENTIAL PROTECTION
8.1 Manufacturer’s name & country - To be mentioned
8.2 Ratio A 400/5
8.3 Rated output VA 20 VA
8.4 Accuracy class - 5P20
9. BUSHING CTS 11 KV FOR DIFFERENTIAL PROTECTION
9.1 Manufacturer’s name & country - To be mentioned
9.2 Ratio A 1200/5
9.3 Rated output VA 20 VA
9.4 Accuracy class - 5P20
10. NEUTRAL B USHING CTS 11 KV FOR SEF & REF PROTECTION
10.1 Manufacturer’s name & country - To be mentioned
10.2 Ratio A 1200/5-5A
10.3 Rated output VA 20 VA
10.4 Accuracy class - 5P20

16/20 mva x-former_spec & gtp_ajgar_design2 19


8.02 SCHEDULE OF MANUFACTURER’S NAME AND PLACES OF MANUFACTURE & TESTING:

Sl. Manufacturer’s Name & Place of Place of


Description
No. Country Manufacture Testing & Inepection
1. 33/11 KV , 3 PHASE ,16/20 MVA
POWER TRANSFORMER

Seal & Signature Seal & Signature


of the Manufacturer of the Bidder

16/20 mva x-former_spec & gtp_ajgar_design2 20


8.03. SCHEDULE OF
PROPOSED STANDARDS IN WHICH TRANSFORMERS& PANELS SHALL BE PROVIDED

The Bidder shall indicate the standard to which the materials offered by him conform to.

Should these standards differ from the specified standard in any respect the Bidder shall detail
the differences between the proposed and specified standard.

Item Description Standard


No
1. 33/11k V, 3-Phase, 16/20 MVA
Power Transformer

16/20 mva x-former_spec & gtp_ajgar_design2 21


Section - 9

DRAWINGS
To be submitted by the Bidder

16/20 mva x-former_spec & gtp_ajgar_design2 22

You might also like