HZJQ-X1: 80KV Transformer Oil BDV Tester

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

HZJQ-X1

Transformer Oil BDV Tester

HZJQ-X1: 80KV Transformer Oil BDV Tester

 Test voltage: 80KV

 Touch Screen

 CE Certificate and Calibration Certificate

 Standard: IEC 60156 ASTM1816

ASTM877

 Electrode: Mushroom,flat,spherical.

(optional)

 PC software (optional)

I. FEATURES
II. DISCRIPTION

1. Test voltage range of 0~80KV


Many power systems, railway systems,
large-scale petrochemical plants and enterprises 2. Display by large-screen LCD English menu.
have a lot of electrical equipment whose internal 3. Automatically complete the withstand
insulation are mostly oil-filled insulation type, voltage test from 1 to 9 times. After the test, the
and therefore, test on insulating oil dielectric
thermal printer will print each breakdown
strength is common and necessary. To meet the
needs of the market, we have developed and voltage value and average value.
produced a series of insulating oil dielectric 4. Power-down preservation. It can save 100
strength testers according to national standard tested results.
GB/T507-2002, industry standard DL429.9-91
5. Adopt a single-chip microcomputer to boost
and the latest Electric Power Industry Standard
DL/T846.7-2004 by ourselves. This instrument, the voltage at an even speed. The voltage is
by using a single-chip microcomputer as the accurate at 50HZ, ensuring the whole process
core, can operate in full automation with high easy for control.
accuracy, greatly improving work efficiency and
6. Equipped with over-voltage, over-current
reducing the labor intensity of workers.
Moreover, it is small in size and convenient to and limit protections to ensure the safety of
carry. operators.
7. With the function of displaying the measured
temperature and system clock.
8. Communicate with computer with a standard
RS232 interface.
III. THECHNICAL PARAMETER

Type HZJQ-X1

Output voltage 0~80KV

Voltage distortion rate <3%

Voltage raising speed 0.5~5 KV/S (adjustable)

Standing time: 15min (adjustable)

Boosting interval 5 min (adjustable)

Boosting frequency 1~9 time(s) (optional)

Booster capacity 1.5KVA

Measuring accuracy ±3%

Supply voltage AC220V±10% 50Hz±1 Hz (110V 120V 60HZ optional)

Power 200W

Applicable temperature: 0℃~45℃

Applicable humidity: <85%RH

Overall dimension 465×385×425mm