Miscellaneous File - 3 Elevated Water Tank Design - CHECKING

1. The document summarizes the design of a cylindrical elevated water tank and its supporting tower. 2. The tower is 6 m high and made of L 2 x 2 x 3/8 steel columns with an unbraced length of 3 m. 3. Analysis shows the columns meet the slenderness ratio requirement and have an allowable compressive strength of 23,401 N under the anticipated loads based on the properties of A36 steel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views1 page

Miscellaneous File - 3 Elevated Water Tank Design - CHECKING

1. The document summarizes the design of a cylindrical elevated water tank and its supporting tower. 2. The tower is 6 m high and made of L 2 x 2 x 3/8 steel columns with an unbraced length of 3 m. 3. Analysis shows the columns meet the slenderness ratio requirement and have an allowable compressive strength of 23,401 N under the anticipated loads based on the properties of A36 steel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

MISCELLANEOUS FILE -3

Elevated Water Tank Design -CHECKING


Tank: Cylindrical Pre-designed Tank (BesTank WT 4000)
Tower: Vertical water tank stand
Height of the tower: 6 m
Dimension of the tower: 2.55 m x 2.55 m
Unbraced Length: 3 m
Wind Load: 3,158.3 N
Columns used: L 2 x 2 x 3/8
Steel: A36
Weight of Water per post: 9,697.12 N
Weight of Water Tank per post: 392.33 N

Properties of Steel:
k = 0.65 E = 200GPa Fy = 248MPa rmin = 9.80 mm
2
Ag =883.9 mm

Slenderness Ratio: kL/r = 0.65(3)/ 9.80 = 198.9 < 200 (ok)


E 200,000
4.71
√ Fy
= 4.71

248
= 133.75

198.9 > 133.75 ∴elastic

p i2 E
2 ❑2 (200,000)
Fe = Kl = = 49,882.19 kPa
( )
r
( 198.90 )2
Fcr = 0.877Fe = 0.877(49.9) = 44,126.45 kPa

1. Nominal Strength (Pn) : FcrAg = 43.8(883.9) = 39,002.01 N


2. Design Strength (Pn) : FcrAg = 0.90(43.8)( 883.9) = 35,101.81 N
3. Allowable Stress (Fa) : 0.6Fcr = 0.60(43.8) = 26,475.87 kPa
4. Allowable Strength (FaAg) : FaAg = 26.3(883.9) = 23,401.20 N(compressive load capacity)

Maximum weight of the tank:

ASD:
M @ A’B’ = 0
P (7.2) + W (1.3) = C (1.8)
3,158.3(7.2) + W (1.3) = 23,401.20 (1.8) ∴ W = 15,354.37 N > 10,089.46 N (SAFE !)

LRFD:
M @ A’B’ = 0

P (7.2) + W (1.3) = C (1.8)


3,158.3(7.2) + W (1.3) = 35,101.81 (1.8) ∴ W = 31,959.14 N > 10,089.46 N (SAFE !)

All computations is based from the book of William T. Segui “Steel Design 4th Edition”