Product Data Sheet: Circuit Breaker Masterpact NW25H1 - 2500 A - 4 Poles - Drawout - W/o Trip Unit

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Product data sheet 48303

Characteristics circuit breaker Masterpact NW25H1 - 2500 A - 4


poles - drawout - w/o trip unit

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Masterpact NW
Product or component type Basic frame
Device short name Masterpact NW25
Circuit breaker name Masterpact NW25H1
Poles description 4P
Neutral position Right
Network type AC
Breaking capacity code H1
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B

Complementary
Network frequency 50/60 Hz
Control type Push-button
Mounting mode Drawout
[In] rated current 2500 A at 40 °C
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
[Icm] rated short-circuit making 143 kA 525 V AC at 50/60 Hz
capacity 143 kA 690 V AC at 50/60 Hz
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit breaker CT rating 2500 A
Breaking capacity 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2

Nov 11, 2020


1
65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Protection type Without protection
Mechanical durability 10000 cycles without maintenance conforming to IEC 60947-2
20000 cycles with maintenance conforming to IEC 60947-2
Electrical durability AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm
[Icw] rated short-time withstand current 65 kA 1 s conforming to IEC 60947-2
65 kA 3 s conforming to IEC 60947-2
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 439 mm
Width 556 mm
Depth 394.5 mm

Environment
Standards IEC 60947-2
Product certifications ASTA
Pollution degree 4 conforming to IEC 60664-1
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -40…85 °C

Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure Product Environmental Profile
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
PVC free Yes

Contractual warranty
Warranty 18 months