THE AUXILIARY VOLTAGE IS TOO LOW AT TERMINAL X99 ON PIN-4 OR POW-4 BOARD .
THE DRIVE CANNOT COMMUNICATE WITH A PREVIOUSLY KNOWN OPTION BOARD SUCH AS COM-8X, RAIO, RDIO, IOB-2, IOB-
3, RTAC, OR DSL-4.
THE MAINS VOLTAGE IS BELOW THE FAULT LIMIT OR THE MAINS VOLTAGE IS BELOW THE ALARM LIMIT FOR AN EXCESSIVE
AMOUNT OF TIME
THE MAINS VOLTAGE IS ABOVE THE FAULT LIMIT FOR MORE THAN 10 SECONDS.
DSL-L INK COMMUNICATION BETWEEN THE DRIVE AND THE FIELD SUPPLY (E XCITER) HAS STOPPED FOR A TIME LONGER THAN THE
FAULT LIMIT.
DSL-L INK COMMUNICATION BETWEEN THE DRIVE AND THE FIELD SUPPLY (E XCITER) HAS STOPPED FOR A TIME LONGER THAN THE
FAULT LIMIT.
ONE OR MORE FIELD SUPPLY (EXCITER) FAULTS IS PRESENT FOR THE MOTOR CURRENTLY SELECTED (M1 OR M2), INCLUDING :
(FOR M1) F515, F516, F529, F537 AND /OR F541; (FOR M2) F518, F519, F530, F538 AND /OR F542.
SPEED FEEDBACK FROM A TACHOMETER OR ENCODER IS CONTINUOUSLY COMPARED TO EMF FEEDBACK WHILE RUNNING. A
FAULT INDICATES THAT THE EMF WAS ABOVE A LIMIT (30.15) WHILE THE MOTOR SPEED WAS BELOW A LIMIT (30.14).
THE FAN A CKNOWLEDGE DIGITAL INPUT WAS LOST OR WAS NOT SET WITHIN 10 SECONDS.
THE MAIN CONTACTOR A CKNOWLEDGE DIGITAL INPUT WAS LOST OR WAS NOT SET WITHIN 10 SECONDS.
ON D1, D2, D3, OR D4 MODULES , THE CURRENT AND VOLTAGE RANGE OF THE TYPE CODE SETTING IS LIMITED TO 1000 A DS
AND 600 VAC. A FAULT INDICATES THE EXISTING SETTING IS OUT OF RANGE .
THE CONVERTER FAN A CKNOWLEDGE DIGITAL INPUT WAS LOST OR WAS NOT SET WITHIN 10 SECONDS.
FIELDBUS COMMUNICATIONS HAVE BEEN INTERRUPTED FOR A PERIOD LONGER THAN A TIME LIMIT AFTER THE FIRST DATA SET
FROM THE OVERRIDING CONTROL HAS BEEN RECEIVED .
A FAULT WAS DETECTED BY THE MOTOR 1 FIELD SUPPLY (EXCITER) DURING ITS SELF DIAGNOSIS OR THERE WAS A POWER FAILURE
IN FIELD SUPPLY 1.
A FAULT WAS DETECTED BY THE MOTOR 2 FIELD SUPPLY (EXCITER) DURING ITS SELF DIAGNOSIS OR THERE WAS A POWER FAILURE
IN FIELD SUPPLY 2.
THE MEASURED SPEED IS LESS THAN THE STALL SPEED AND THE TORQUE IS GREATER THAN THE STALL TORQUE FOR A TIME
GREATER THAN THE STALL TIME .
ON 12- PULSE SYSTEMS , ARMATURE CURRENT DIRECTION DID NOT CHANGE FOR A PERIOD LONGER THAN A TIME LIMIT AFTER
ZERO CURRENT HAS BEEN DETECTED .
FOR SYSTEMS CONFIGURED FOR 12- PULSE PARALLEL OPERATION , THE CURRENT DIFFERENCE HAS EXCEED THE LIMIT FOR A PERIOD
LONGER THAN THE LIMIT .
ON 12- PULSE SYSTEMS , DCS-L INK COMMUNICATIONS BETWEEN THE MASTER AND THE FOLLOWER DRIVE HAVE BEEN
INTERRUPTED FOR A PERIOD LONGER THAN THE LIMIT .
MOTOR 1 FIELD SUPPLY (EXCITER) HAS LOST THE READY -FOR OPERATION MESSAGE WHILE RUNNING . THE AC SUPPLY VOLTAGE
MAY BE MISSING OR NO LONGER IN SYNC .
MOTOR 2 FIELD SUPPLY (EXCITER) HAS LOST THE READY -FOR OPERATION MESSAGE WHILE RUNNING . THE AC VOLTAGE MAY BE
MISSING OR NO LONGER IN SYNC .
THE CURRENT THROUGH THE DRIVE HAS RISEN TOO QUICKLY , EXCEEDING THE LIMIT . THIS MAY BE CAUSED BY A SHORT CIRCUIT
OR INCORRECT TUNING .
THE MOTOR 1 FIELD CURRENT IS BELOW THE CURRENT LIMIT FOR A PERIOD LONGER THAN A TIME LIMIT .
THE MOTOR 2 FIELD CURRENT IS BELOW THE CURRENT LIMIT FOR A PERIOD LONGER THAN A TIME LIMIT .
OVERRIDING CONTROL AND /OR MASTER- FOLLOWER COMMUNICATIONS THROUGH CHANNEL 0 OR 2 OF THE COM-8 HAVE BEEN
INTERRUPTED FOR A PERIOD LONGER THAN THE LIMIT .
DCS-LINK FOR FIELDBUS COMMUNICATIONS HAVE BEEN INTERRUPTED FOR A PERIOD LONGER THAN THE LIMIT .
COMMUNICATIONS HAVE BEEN INTERRUPTED WITH THE CONTROL PANEL , DRIVE WINDOW , OR DRIVE WINDOW LIGHT WHILE IN
L OCAL CONTROL MODE .
F547 – HARDWARE FAILURE
FIRMWARE FAILURE HAS BEEN DETECTED OR FIRMWARE DID NOT LOAD CORRECTLY .
READING THE ACTUAL PARAMETER SET OR A USER PARAMETER SET FROM EITHER FLASH OR THE MEMORY CARD FAILED . CHECK
THAT U SER1 AND/OR U SER2 HAVE BEEN SAVED PROPERLY USING A PPLMACRO (99.08). A LSO CHECK THE SDCS-MEM-8
MEMORY CARD . MAY ALSO REQUIRE REPLACING THE SDCSCON-4 BOARD .
THE ACKNOWLEDGE SIGNAL FOR BRAKE OPEN OR BRAKE ENGAGED IS MISSING FOR A PERIOD LONGER THAN THE OPEN OR ENGAGE
LIMIT.
SPEED FEEDBACK POLARITY FROM A TACHOMETER OR ENCODER IS CONTINUOUSLY COMPARED TO EMF FEEDBACK POLARITY
WHILE RUNNING . A FAULT INDICATES THAT THE TWO RAN IN OPPOSITE DIRECTIONS WHILE THE MOTOR FEEDBACK SPEED AND
EMF SPEED WERE ABOVE ABSOLUTE LIMITS . IF THIS OCCURRED DURING START UP , TRY REVERSING POLARITY OF THE MOTOR OR
THE TEACH /ENCODER. IF THIS OCCURRED WHILE IN PRODUCTION , THE TEACH /ENCODER MAY BE FAULTY .
THE SIGNAL FROM THE TACHOMETER ANALOG INPUT HAS EXCEEDED A LIMIT . IF THIS OCCURRED DURING START UP , CONNECT THE
TEACH TO THE NEXT HIGHER VOLTAGE TERMINAL ON DRIVE CONNECTOR X3 TERMINALS 1, 2 OR 3.
THE TORPOR SIGNAL HAS NOT BEEN SET WITHIN A TIME LIMIT AFTER THE RUN COMMAND (7.01 BIT3) HAS BEEN SET .
A RMATURE CURRENT DIRECTION DID NOT CHANGE FOR A PERIOD LONGER THAN A TIME LIMIT AFTER ZERO CURRENT WAS
DETECTED . FOR MOTORS WITH HIGH INDUCTANCE ( E . G., LARGE MOTORS ) OR IF MOTOR IS HIGH VOLTAGE COMPARED TO THE
MAINS VOLTAGE , TRY DECREASING R EVD LY (43.14), THEN INCREASING THE LIMIT
L OGGED
DRIVES- TECHNICIAN
VIEW PROFILE
FOR NON -US DYNAMIC BRAKING , THE DAYBREAK INPUT IS SET WHILE IN THE ON STATE
DCS-LINK OR FIELDBUS COMMUNICATIONS HAVE BEEN INTERRUPTED FOR A PERIOD LONGER THAN THE LIMIT .
OVERRIDING CONTROL AND /OR MASTER- FOLLOWER COMMUNICATIONS THROUGH CHANNEL 0 OR 2 OF THE COM-8
CURRENT REFERENCE DIFFERS FROM CURRENT ACTUAL BY MORE THAN A LIMIT FOR LONGER THAN A TIME LIMIT . SEE ALARM
DESCRIPTION IN DCS800 FIRMWARE MANUAL FOR WHAT TO CHECK IN THE EVENT OF A FAULT .
IF THIS ALARM IS PRESENT FOR LONGER THAN 10 SECONDS, THE SIGNAL FROM THE TACHOMETER ANALOG INPUT EXCEEDED A
LIMIT. I F PRESENT FOR 10 SECONDS AND THEN IT CLEARS , IT IS AN INDICATION THAT M1O VRS PEED (30.16) OR M2O VRS PEED
(49.21) HAS CHANGED AND A NEW TEACH FINE TUNING IS REQUIRED.
DC CURRENT RIPPLE EXCEEDS THE LIMIT . IF THIS OCCURS DURING START UP , THEN CURRENT CONTROLLER GAIN MAY BE SET TOO
HIGH . OTHERWISE , THIS IS OFTEN AN INDICATION THAT ONE OR MORE THERMISTORS IS NOT WORKING OR A FUSE IS BLOWN .
THE APPLICATIONS PREVIOUSLY LOADED TO THE DRIVE AND THE ONE ON THE SDCS-MEM8 DO NOT MATCH .
THE OVERVOLTAGE PROTECTION UNIT , DCF506- XXXX-51 IS ACTIVE , SO THE CONTROLLER IS BLOCKING THE CONVERTER OUTPUT .
A CTIVE ONLY WHEN BRAKE FAULTFUNC (42.06) ? FAULT, THE ACKNOWLEDGE SIGNAL FOR BRAKE OPEN OR BRAKE ENGAGED IS
MISSING FOR A PERIOD LONGER THAN THE OPEN OR ENGAGE LIMIT . O R TORQUE ACTUAL DOES NOT REACH THE TORQUE LIMIT ,
USED , FOR EXAMPLE , FOR CRANES WITH A HANGING LOAD .
SEE : MOTOR 1: 50.01, 20.01, 20.02, 99.04 AND MOTOR 2: 49.22, 49.03, 49.19, 49.20
SPEED FEEDBACK FROM A TACHOMETER OR ENCODER IS CONTINUOUSLY COMPARED TO EMF FEEDBACK WHILE RUNNING. A
FAULT INDICATES THAT THE EMF VOLTAGE WAS ABOVE A VOLTAGE LIMIT (30.15) WHILE THE MOTOR SPEED WAS BELOW A
SPEED LIMIT (30.14). T HIS USUALLY INDICATES THERE IS A PROBLEM WITH THE TACHOMETER OR ENCODER .
FIELDBUS COMMUNICATIONS HAVE BEEN INTERRUPTED FOR A PERIOD LONGER THAN A TIME LIMIT AFTER THE FIRST DATA SET
FROM THE OVERRIDING CONTROL HAS BEEN RECEIVED.
THE PARAMETERS FOUND IN FLASH WERE INVALID AT POWER -UP (CHECKSUM FAULT). A LL PARAMETERS WERE RESTORED FROM
THE PARAMETER BACKUP .
COMMUNICATIONS HAVE BEEN INTERRUPTED WITH THE CONTROL PANEL , DRIVE WINDOW , OR DRIVE WINDOW LIGHT WHILE IN
L OCAL CONTROL MODE
THE RETAINED DATA WAS INVALID AT POWER -UP; THE BACKUP DATA WAS USED. BACKUP DATA REFLECTS THE STATUS DURING
THE PREVIOUS POWER -UP. RETAINED DATA INCLUDES : FAULT LOGGER DATA , D ATA 1 (19.01) THRU D ATA 4 (19.04), I/O
OPTIONS ( SEE GROUP 98), PARAMETERS DEFINED BY MEANS OF DCS800 CONTROL B UILDER WHEN THE RETAIN BOX IS
CHECKED .
WHEN DOWNLOADING PARAMETER SETS OR DURING POWER UP THE FIRMWARE ATTEMPTS TO WRITE THE PARAMETERS . IF
SETTING OF A PARAMETER IS NOT POSSIBLE OR NOT COMPATIBLE , THE PARAMETER IS SET TO DEFAULT .
THE CHECKSUM VERIFICATION FAILED FOLLOWING A PARAMETER UPLOAD OR DOWNLOAD . PLEASE TRY AGAIN
THE TASK TIME FOR A DAPTIVE PROGRAMMING IS NOT SET WHEN THE USER ATTEMPTED TO START IT .
DRIVE WAS RESTARTED BEFORE THE MOTOR DECELERATED BELOW THE ZERO SPEED LIMIT .
BIT 1 FROM THE MAIN CONTROL WORD IS NOT SET , CAUSING A START INHIBIT CONDITION .
BIT 2 FROM THE MAIN CONTROL WORD IS NOT SET , CAUSING AN ESTOP CONDITION .
THE FIELDBUS PARAMETERS IN GROUP 51 (FIELDBUS) ARE NOT SET ACCORDING TO THE FIELDBUS ADAPTER OR THE DEVICE HAS
NOT BEEN SELECTED.
INVALID COMBINATION OF DRIVE (SDCS-CON-4) FIRMWARE AND SDCS-COM-8 FIRMWARE . D RIVE FIRMWARE 3.7 IS
COMPATIBLE WITH SDCS-COM-8 FIRMWARE 1.80 OR HIGHER. S EE FIRMWARE RELEASE NOTES FOR COMPLETE COMPATIBILITY
LIST . T YPICALLY REQUIRES UPGRADING TO A NEWER SDCSCOM-8 BOARD
A CONTROL B UILDER APPLICATION HAS BEEN LOADED IN THE DRIVE BUT THE MEMORY CARD BELONGING TO THAT APPLICATION
HAS NOT BEEN FOUND.
THE DATA FOUND IN THE MEMORY CARD WAS INVALID (CHECKSUM FAULT ).
L OGGED
DAVE 2
*
POST COUNT 3
VIEW PROFILE