Basic Objects
Reference Manual
Version 6.0/3
CONTENT
1 SUMMARY ................................................................................................................ 5
2 COMMON DATA ....................................................................................................... 5
2.1 BASIC DESCRIPTION ..................................................................................... 5
2.2 CONTROL ....................................................................................................... 6
2.2.1 Library location .................................................................................... 6
2.2.2 Control modes ..................................................................................... 6
2.2.3 PCC, Interlock Bus (Process Control Connection)............................... 6
2.2.4 Simulation Mode ............................................................................... 11
2.3 OPERATION.................................................................................................. 11
2.3.1 Properties.......................................................................................... 11
3 AI Analogue Input .................................................................................................. 15
3.1 BASIC DESCRIPTION ................................................................................... 15
3.2 CONTROL ..................................................................................................... 16
3.2.1 Diagram Graphical Representation AIS ............................................. 16
3.2.2 Diagram Graphical Representation AIC............................................. 16
3.2.3 Parameter description ....................................................................... 16
3.2.4 Data Type description ....................................................................... 21
3.2.5 Project Constants .............................................................................. 23
3.2.6 Time Diagram.................................................................................... 23
3.2.7 PCC Interlock Limitations for AIS and AIC......................................... 24
3.3 OPERATION.................................................................................................. 25
3.3.1 Graphic elements .............................................................................. 25
3.3.2 Faceplate .......................................................................................... 33
3.3.3 Faceplate Control Permission ........................................................... 42
3.3.4 Alarm & Event List............................................................................. 43
4 AO Analogue Output.............................................................................................. 45
4.1 BASIC DESCRIPTION ................................................................................... 45
4.2 CONTROL ..................................................................................................... 45
4.2.1 Diagram Graphical Representation AOS ........................................... 45
4.2.2 Diagram Graphical Representation AOC ........................................... 45
4.2.3 Parameter description ....................................................................... 46
4.2.4 Data Type description ....................................................................... 47
4.3 OPERATION.................................................................................................. 49
4.3.1 Graphic elements .............................................................................. 49
4.3.2 Graphic Element PIDLimitAndUnit..................................................... 54
4.3.3 Faceplate .......................................................................................... 55
4.3.4 Alarm & Event List............................................................................. 60
5 DI Digital Input........................................................................................................ 61
5.1 BASIC DESCRIPTION ................................................................................... 61
5.2 CONTROL ..................................................................................................... 62
5.2.1 Diagram Graphical Representation DIS............................................. 62
5.2.2 Diagram Graphical Representation DIC ............................................ 62
5.2.3 Parameter description ....................................................................... 62
5.2.4 Data Type description ....................................................................... 64
5.2.5 Project Constants .............................................................................. 65
5.2.6 Time Diagram.................................................................................... 65
5.2.7 PCC Interlock Limitations .................................................................. 66
5.3 OPERATION.................................................................................................. 67
5.3.1 Graphic elements .............................................................................. 67
5.3.2 Faceplate .......................................................................................... 72
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 2
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 3
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 4
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
1 SUMMARY
This document contains a detailed description of the following Basic Objects:
·AI (Analog Input)
·AO (Analog Output)
·DI (Digital Input)
·DO (Digital Output)
Additionally, some PCC specific Function Blocks and Control Modules are described
·PCC_Connect
·PCC_Connect_6
·PCC_Threshold_AND3
·PCC_Intlk
·PCC_Connect_2 (Obsolete)
2 COMMON DATA
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 5
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
2.2 CONTROL
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 6
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
cBMI.Std_Type: 0
Motor is not running, NC Valve is closed, NO Valve is Open, for PCC connected to
Group: if Group is not started
cBMI.Std_Type: 1
Same as Std_Type 0 but always alarm on all Objects if Group is started and
Consumer preselected. In case object is standby preselected alarm priority is
automatically reduced from Failure to Warning.
PCCAEListFrcEn = true
Automatic alarm disabling switched off. This option shall be used in cases a signal
has to alarm independent from the status of its parent, e.g. a Silo Level.
IntlkDir Description
Configuration Option
acknowledged but the value returned to Normal Position.
DirXStartnoAck Same as DirXnoAck, but once the parent is running in direction X
(or has reached end position X) the interlock is disabled.
DirYStartnoAck Same as DirYnoAck, but once the parent is running in direction Y
(or has reached end position Y) the interlock is disabled.
DirXYStartnoAck Same as DirXYnoAck, but once the parent is running in direction
X/Y (or has reached end position X/Y) the interlock is disabled.
DirFBXnoAck Combination of FB and noAck for Direction X.
DirFBYnoAck Combination of FB and noAck for Direction Y.
DirFBXYnoAck Combination of FB and noAck for Direction X/Y.
DirXFastnoAck Combination of Fast and noAck for Direction X.
DirYFastnoAck Combination of Fast and noAck for Direction Y.
DirXYFastnoAck Combination of Fast and noAck for Direction X/Y.
DirFBXFastnoAck Combination of FB and Fast and noAck for Direction X.
DirFBYFastnoAck Combination of FB and Fast and noAck for Direction Y.
DirFBXYFastnoAck Combination of FB and Fast and noAck for Direction X/Y.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 9
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
The following Table lists the supported Directions per Signal Control Module:
IntlkDir PCC_Com PCC_Thresho
PIDCtrl
Configuration Option AIS AIC DIS DIC _Drive ld_AND_3
PIDAdvCtrl
(ComError) & PCC_Intlk
DirX Yes Yes Yes Yes Yes Yes Yes
DirXStart Yes Yes Yes Yes Yes Yes Yes
DirY Yes Yes Yes Yes Yes Yes Yes
DirYStart Yes Yes Yes Yes Yes Yes Yes
DirXY Yes Yes Yes Yes Yes Yes Yes
DirXYStart Yes Yes Yes Yes Yes Yes Yes
DirFBX Yes Yes Yes Yes - Yes Yes
DirFBY Yes Yes Yes Yes - Yes Yes
DirFBXY Yes Yes Yes Yes - Yes Yes
DirXFast - - Yes (Alarm) - - - -
DirYFast - - Yes (Alarm) - - - -
DirXYFast - - Yes (Alarm) - - - -
DirFBXFast - - Yes (Alarm) - - - -
DirFBYFast - - Yes (Alarm) - - - -
DirFBXYFast - - Yes (Alarm) - - - -
DirXnoAck Yes Yes Yes Yes - - Yes
DirYnoAck Yes Yes Yes Yes - - Yes
DirXYnoAck Yes Yes Yes Yes - - Yes
DirXStartnoAck Yes Yes Yes Yes - - Yes
DirYStartnoAck Yes Yes Yes Yes - - Yes
DirXYStartnoAck Yes Yes Yes Yes - - Yes
DirFBXnoAck Yes Yes Yes Yes - - Yes
DirFBYnoAck Yes Yes Yes Yes - - Yes
DirFBXYnoAck Yes Yes Yes Yes - - Yes
DirXFastnoAck - - Yes (Alarm) - - - -
DirYFastnoAck - - Yes (Alarm) - - - -
DirXYFastnoAck - - Yes (Alarm) - - - -
DirFBXFastnoAck - - Yes (Alarm) - - - -
DirFBYFastnoAck - - Yes (Alarm) - - - -
DirFBXYFastnoAck - - Yes (Alarm) - - - -
For more details about PID refer to the Loop Object Reference manual document ID:3BHS
161562.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 10
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
In case any of output objects (DOS and AOS) are connected to the
hardware all the changes to them will be written to the hardware.
For safety reason we advise to disconnect the Profibus, Modulebus and
any other hardware interface before enabling Simulation Mode.
2.3 OPERATION
Details on all available graphic elements for the basic objects are available in the
operation chapter of the individual object type e.g. Analog Input.
2.3.1 Properties
Below is an overview of the properties that are applicable for the graphic elements that
represent basic objects.
IndicationType
Name DataType Default Value Description
IndicationType IndicationTypeEnum A03_MotorM Symbol type selection
Name Values
IndicationTypeEnum A00_Rectangle.
A01_Motor.
A03_MotorM.
A04_Pump.
A05_Fan.
A06_RotaryFeeder.
E77_BeltCleaner.
A02_Valve.
B11_Damper.
B14_LouvreDamper.
B16_PropRoller.
B15_AirslideDiverter.
B12_Shut.
B13_Diverter.
E21_GearwheelPump.
C31_Valve3way.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 11
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
C32_ValveMan.
C33_ValveAuto.
E41_Generator.
E42_Switch.
E07_Triangle.
E08_Lollipop.
E09_Diamond.
E99_TagName.
F00_None.
With this property the type of graphic symbol that shall represent a DI or DO object can
be selected.
Not applicable for AI / AO objects.
EnableLimitLabel
Name DataType Default Value Description
EnableLimitLabel Boolean True Show limit labels
When set to “True”, the alarm limits are visible next to the graphic element.
Only applicable for AI objects.
NumberOfDigits
Aspect: AISandUnit, AICandUnit, AOSandUnit, AOCandUnit
Name DataType Default Value Description
NumberOfDigits Integer 4 Number of presented digits
Used for setting how many digits need to be shown.
This is only applicable for AI / AO objects.
Not applicable for the bar graph.
EnableUnit
Aspect: AISandUnit, AICandUnit, AOSandUnit, AOCandUnit, PIDCtrl
Name DataType Default Value Description
EnableUnit Boolean True Show units
When set to “true”, the engineering units are visible next to the graphic element.
This is only applicable for AI / AO / PID objects.
TextIndAbnormalPos / TextIndNormalPos
Aspect: DISTxt, DICTxt, DOSTxt, DOCTxt
Name DataType Default Value Description
TextIndAbnormalPos String "On" Text for abnormal position
TextIndNormalPos String "Off" Text for normal position
With these properties a text can be added for abnormal position and normal position.
This text will be represented on the graphic symbol for DI / DO objects.
Orientation
Name DataType Default Value Description
Orientation Integer 0 Obsolete property used for migration
only, Orientation in degrees, clockwise.
Obsolete property used for migration only, Orientation in degrees, clockwise.
Orientation is still used (to rotate the symbol indication) in the following Generic
Elements core:
· DigitalCmdButtonCore
· DigitalCore
· DriveCmdButtonCore
· DriveCore
· SymbolCore
SymbolSize
Name DataType Default Value Description
SymbolSize Integer 12 Defined the square size in case of
IndicationType = 10
Size of the symbol in the graphic display.
E.g. Symbol size in pixel: 8 = Little
12 = Small
16 = Standard
20 = Large
24 = XXL
EnableFitToBestSize
Name DataType Default Value Description
EnableFitToBestSize Boolean True Set best unit size
When set to “True”, the unit size is calculated to best size according to the string.
Not applicable for the bar graph.
EnableLogicalColor
Name DataType Default Value Description
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all
used colors are logical colors. The
logical color reference is equal to the
default logical color used in the color
properties. To use an individual color
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 13
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
set it to false.
When set to “True”, the colors are based on logical colors.
Not applicable for the PID object.
ValueColor
Name DataType Default Value Description
ValueColor Color BMIvalueMV Value color. Only applied if
(AI) EnableLogicalColor is set to false.
BMIvalueOUT
(AO)
When EnableLogicalColor set to “False”, the ValueColor is used to show the value color or
Bar color with the defined ValueColor.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 14
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
3 AI Analogue Input
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 15
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
3.2 CONTROL
Parameter AIS
No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the AIS (allowed deliminators
are "_" or "." or "-", no blanks,":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the AIS
3 IO AISData 1 in_out IN/OUT: Connection to AISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus, Priority
a Command/Interlock to motors, valves or groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
7 Lim2Tr dint 3 0 in INIT: Alarm L2/H2 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
8 Lim1Tr dint 2 0 in INIT: Alarm L1/H1 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
9 ROCLimTr dint -1 0 in INIT: ROC limit treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
10 PLimTr dint 0 0 in INIT: Process limit treatment: -1 no AE; 0 =
Event
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 16
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 17
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Parameter AIC
No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the AIC (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the AIC
3 IO AISData Default 1 in_out IN/OUT: Connection to AISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus,
a PriorityCommand/Interlock to motors, valves or
groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 Min real 0 1 in INIT: Scaling Parameter Range.
7 Max real 100 1 in INIT: Scaling Parameter Range Max.
8 Unit string '%' 1 in INIT: Scaling Parameter Unit.
9 Fraction dint 1 1 in INIT: Fraction (Number of Decimals).
10 SignalError bool false 1 in IN false: Input for calculated signal error
indication
11 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
12 Lim2Tr dint 3 0 in INIT: Alarm L2/H2 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
13 Lim1Tr dint 2 0 in INIT: Alarm L1/H1 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
14 ROCLimTr dint -1 0 in INIT: ROC limit treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
15 PLimTr dint 0 0 in INIT: Process limit treatment: -1 no AE; 0 =
Event
16 StatusTr bool true 0 in IN: True enables events on Forced value
changes
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 18
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 19
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 20
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 21
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PanelLinkAIS; components
Name Data Attributes Initial Description
Type Value
1 Status dint Retain Object Status (Ready, H,HH,Phi,Plo etc.)
nosort
hidden
2 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
3 SignalValue real Retain Signal Value to Process Panel
nosort
hidden
4 Blink bool Retain Enabling of Basic Object Blinking
nosort
hidden
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 22
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
FDStatusNC defines the Value that is used to detect that no Status is connected to the
Module. Note that this Value should be “impossible” to be sent at any time by a Field
Device.
IO.<Limit>.Normal
FALSE
TRUE
IO.<Limit>.Value
FALSE
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 23
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
With Fast
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 24
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
3.3 OPERATION
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 25
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
AISandUnit or AICandUnit
The value and unit presents the measured value, alarm limits and status information.
Presentation
Indication Type Description Example
Status
Object status Symbol color
Labels
Description Indication
Signal blocked
Limit High 2
Limit High 1
Limit Low 1
Limit Low 2
Rate of Change
Example:
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 26
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Properties
Name DataType Default Value Description
EnableDisplayBackgroundColor Boolean False Show display background color as
symbol background
EnableFitToBestSize Boolean True Set best unit size
EnableLimitLabel Boolean True Show limit labels
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all
used colors are logical colors. The
logical color reference is equal to the
default logical color used in the color
properties. To use an individual color
set it to false.
EnableUnit Boolean True Show units
NumberOfDigits Integer 4 Number of presented digits
UnitSize Integer 8 Unit size in pixel: 7 = Small, 8 =
Standard, 10 = Large, 12= XXL
ValueColor Color BMIvalueMV Value color. Only applied if
EnableLogicalColor is set to false.
ValueSize Integer 12 Value size in pixel: 8 = Small, 10
Medium, 12 = Standard, 14 = Large,
16 = XXL
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 27
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
AISTxt or AICTxt
AIS and AIC text can be used to show alarm limits of analogue inputs as labels. The label
text can be customized. The text appearance can be configured to show the text only on
alarm, depending on the value, always but with different colours depending on value or
alarm condition.
Presentation
Indication Type Description Example
Status
Object status Symbol color
Normal Position for
Appearance Types, 0 = Alarm, 2 Gray dimmed (semitransparent)
= value
Normal Position for
Appearance Types, 10 = Alarm, Green
12 = Value interlock
Normal Position for
Appearance Types, 0 = Alarm, 2 Red
= value
Labels
Description Indication
Status blocked
Example:
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 28
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Properties
Name DataType Default Value Description
AppearanceType Integer 0 0 = Alarm, 2 = Value, 3 = Value custom
color, 10 = Alarm interlock, 12 Value
interlock
ColorAbnormalPos Color Lime Used for AppearanceType 3 = Value
custom color
ColorNormalPos Color RGB(159,159,159) Used for AppearanceType 3 = Value
custom color
EnableFont Boolean False Enable the Font property
EnableLogicalColor Boolean True To use an individual color set it to false
EnableNormalPos Boolean True Hide symbol in normal position
Font Font Font( “Arial” ,10 Text font I EnableFont is true
,Regular, Bold)
IndicationType Integer 0 0 = Text with background color, 10 =
Square in front of text, 20 = Text colored
IndicationValue Integer 1 0 = All, 1 = H2, 2 = H1, 3 = PH2, 4 = PH1,
5 = PL1, 6 = PL2, 7 = L1, 8 = PL2
NormalPos Boolean False Used for AppearanceType 2 = Value, 3 =
Value custom color
SymbolSize Integer 12 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
TextBold Boolean True Text style is bold
TextColor Color BMIstaticTextOff Text color
TextIndTrH1AbnormalPos String “H1” TextIndTrH1AbnormalPos
TextIndTrH1NormalPos String “H1” TextIndTrH1NormalPos
TextIndTrH2AbnormalPos String “H2” TextIndTrH2AbnormalPos
TextIndTrH2NormalPos String “H2” TextIndTrH2NormalPos
TextIndTrL1AbnormalPos String “L1” TextIndTrL1AbnormalPos
TextIndTrL1NormalPos String “L1” TextIndTrL1NormalPos
TextIndTrL2AbnormalPos String “L2” TextIndTrL2AbnormalPos
TextIndTrL2NormalPos String “L2” TextIndTrL2NormalPos
TextIndTrPH1AbnormalPos String “PH1” TextIndTrPH1AbnormalPos
TextIndTrPH1NormalPos String “PH1” TextIndTrPH1NormalPos
TextIndTrPH2AbnormalPos String “PH2” TextIndTrPH2AbnormalPos
TextIndTrPH2NormalPos String “PH2” TextIndTrPH2NormalPos
TextIndTrPL1AbnormalPos String “PL1” TextIndTrPL1AbnormalPos
TextIndTrPL1NormalPos String “PL1” TextIndTrPL1NormalPos
TextIndTrPL2AbnormalPos String “PL2” TextIndTrPL2AbnormalPos
TextIndTrPL2NormalPos String “PL2” TextIndTrPL2NormalPos
TextSize Integer 10 Text size in pixel: 8 = Small, 10 =
Standard, 12 = Large, 16 = XXL
TextSource Integer 1 0 = None, 1 = TextIndAbnormalPos /
TextIndNormalPos, 2 = OPC Text, 3 =
NLS Text
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 29
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
AISBar or AICBar
AIS and AIC bar presents the analogue value as bar. Alarm or process limits are graphical
shown and different bar graph appearances are possible.
Presentation
Appearance Description Example
Standard
This is the standard appearance of the bar graph. The value will
0 be indicated in relation to the maximum and minimum range. The
green bar will always start from the minimum range.
Inverse
2 The bar will be inverse to the standard appearance.
Line
3 The value will be indicated as a small line instead of a bar.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 30
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Status
Example Object status Symbol color
Labels
Description Indication
Signal blocked
Limit High 2
Limit High 1
Limit Low 1
Limit Low 2
Example:
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 31
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Properties
Name DataType Default Value Description
Appearance Integer 0 0 = Standard, 1 = Start from Pivot, 2 = Inverse,
3 = Line
BarColorCustom Color BMIbarMV Bar color. Only applied if EnableLogicalColor is
set to false.
EnableLimitLabel Boolean True Show limit labels
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all used
colors are logical colors. The logical color
reference is equal to the default logical color
used in the color properties. To use an
individual color set it to false.
EnableManualRange Boolean False If set to true, the bar’s range can be set
manually
Pivot Real 0. Used together with Appearance = 1 (Start from
Pivot). The bar will start from the value set as
Pivot.
RangeMax Real 100. Maximum range if EnableManualRange is true
RangeMin Real 0. Minimum range if EnableManualRange is true
SubscriptionRate Integer 0 The update rate for all aspect object properties
subscribed for
SymbolSize Integer 14 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
VerticalBar Boolean True VerticalBar: True = vertical appearance, false =
horizontal appearance.
AISLimitAndUnit or AICLimitAndUnit
This Element shows the Limit Value and related Alarm Status for the MV
LimitValueEnum
The Value shown can be configured from the following Selection:
Value Description
A1_Limit_H2 MV High 2 Limit
A2_Limit_H1 MV High 1 Limit
A4_Limit_PH1 MV Process High Limit
A5_Limit_PL1 MV Process Low Limit
A7_Limit_L1 MV Low 1 Limit
A8_Limit_L2 MV Low 2 Limit
A9_Limit_Hysteresis MV Limits Hysteresis Value
B1_ROC_HighLimit Rate of Change High Limit
B2_ROC_Hysteresis Rate of Change Limit Hysteresis
B3_FilterTime Signal Filter Time
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 32
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
3.3.2 Faceplate
Event List
Operators Note
Default View
Tagname
&
Description
Measured Value
&
alarm indication
Mini Trend
Measure Value
Graphical Bar
Measured Value
&
alarm limits
Apply Button
Extended View
for detailed
information and
settings
Some Indications are given in the Faceplate via Yellow Labels above the Value.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 33
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Label Description
Simulation The Signal is simulated (via the Group Member – PCC Connection)
Block Input The Signal Value is Blocked. In this case the Faceplate shows both the
Value from the Hardware “IO” and the Value used in the Application “MV”
Error The Signal Value is Blocked because of a Signal Status Error Condition.
Control The replacement Value is applied automatically. If the Signal Status is
good again, the IO Value will automatically be used again.
Block Limit One of the Limits is Blocked from the Application (see the “Limits” Tab for
Details about which Limits are blocked)
Sig Err The Signal Quality is not ok (see the “MVStatus” Tab for detailed Status
information)
Start Inhibit The PCC Interlocks and Limits are blocked because of a configured
Active PCCStartInhibit Time and the Consumer connected via PCC is not
running
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 34
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Extended View
The faceplate extended view gives more detailed information about the Analogue Input.
Reduced View
default
Additional information for the AIS is structured in tabs. The available tabs and a short
description of the contained information are shown below.
Tab Description
Trend Mini trend of filtered measured value, IO value and rate of change
Limit Limits and alarm delay settings for the measured value
ROC Rate of change settings
Block - Input Blocking
- Alarm Blocking
MVStatus Sub status for DP, PA and FF Field Devices
PCC - PCC interlock configuration summery
- Link to connected consumer or consumer overview list
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 35
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Trend
On-Line single Triple trend and log Configuration aspect with the actual values: Signal,
FilterdSignal and RateofChange.
Move over the trend area and a cursor will appear, showing enabled traces’ value and
record time.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 36
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Reference Table
Description
B Indication that the corresponding alarm limit has been blocked. Yellow
means that the alarm limit is blocked (disabled)
H2 2nd High limit (H2) – Failure
H1 1st High limit (H1) – Warning
Phigh Process High Limit
Plow Process Low Limit
L1 1st Low limit (L1) – Warning
L2 2nd Low limit (L2) – Failure
Alarm Delay Time delay before alarm message will be send to the operator station.
Check below the special mode for 6 alarm limits.
Hysteresis Alarm Hysteresis in %
F When limits are changed from the faceplate, you must take into consideration that
these values will be overwritten again with the initial values when a cold restart /
reset is performed and the coldretain files are not available for the corresponding
controller.
To avoid this, you need to update the initial values for the corresponding AIS/AIC
control module instance with Control Builder, after changing the Values from the
Faceplate.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 37
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
ROC
Description
ROC High Limit Rate Of Change in % of Total Range per seconds High Limit
ROC Hysteresis ROC Alarm Hysteresis in %
Filter Time Filter time to be applied to the IO.<AISTag>.FilteredValue
F When limits are changed from the faceplate, you must take into consideration that
these values will be overwritten again with the initial values when a cold restart /
reset is performed and the coldretain files are not available for the corresponding
controller.
To avoid this, you need to update the initial values for the corresponding AIS/AIC
control module instance with Control Builder, after changing the Values from the
Faceplate.
Block / Override
Block / Force Input
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 38
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Block Alarm
MVStatus
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 39
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
All Substatus for DP, PA and FF Field Devices will generate error control when quality is
Bad or Uncertain for AIS Control Module.
An Aspect Link giving access to the “Device Management” Object can be configured via
the “BMI DTM Link” General Properties Aspect.
Description
Signal Error Time between the Signal Error occurs until the Value is forced to
Delay ErrValue. Only available for AIS Module.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 40
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PCC
PCC interlock configuration
The PCC interlock configuration tab shows the actual configuration and a link to the
parent object.
If the configuration via control module parameters “IntlkType” and “IntlkDir” is wrong, the
error message “PCC Intlk Param Error” will be displayed in the Faceplate.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 41
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
F Note that forcing to a Value in the Faceplate does require Write permission for
IO.FilteredSignal.Value and IO.Signal.Forced, these are not set on IntPar Variables.
Instead those are defined on the “Property Attribute Override” Aspect on the Object
Type, by default with Write Permission “Supervise”.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 42
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Alarm Messages
For the AIS and AIC we have basically 3 main conditions for the alarm messages
§ Limit H2 or L2
§ Limit H1 or L1
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 43
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
F Notice that Process Limit (Plo/Phi) does not create any alarm. The maximum
indication treatment for the Process Limit is 0 (event) as described in the parameter
description.
For the alarm limits (Limits H2, L2, H1 and L1) the message will always be:
[LIMIT TYPE]: [LIMIT VALUE]
[LIMIT TYPE] Description
L1 Low limit 1 is reached
L2 Low limit 2 is reached
H1 High limit 1 is reached
H2 High limit 2 is reached
Phi Process limit high is reached
Plo Process limit low is reached
Limit Value is the number defined over the Lim1 and Lim2 Tab for each Limit Type.
ROC is the rate of change for the MV values in a normal scale (0-100% of the total range).
It will create an alarm after the rate of change in seconds for the MV value is higher then
the one defined in the faceplate over the Lim2 tab.
When a ROC appears, the following message is shown in the alarm list:
ROC [ROC HIGH LIMIT]
Where the ROC HIGH LIMIT is the value set over Lim2 faceplate tab.
The signal error alarm is created every time a hardware failure which that analog input is
connected is encountered. If the configured Signal Error Delay Time is bigger than 0
seconds, a warning alarm will be sent immediately. The message for both, the warning
and the alarm, is defined as:
SigErr
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 44
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
4 AO Analogue Output
4.2 CONTROL
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 45
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Parameter AOS
No Name Data Type Initial Value Port Direction Description
1 Name string ‘Name’ 1 in INIT: Tag name of the AOS (allowed deliminators
are “.” and “-“, no blanks “:” or “;” allowed)
2 Description string ‘Description’ 1 in IN: Description text of the AOS
3 IO AOSData 1 in_out IN/OUT: Connection to AOSData variable (do not
connect to PID or VVVF !)
4 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
5 ModeTr bool true 0 in IN: True enables events on mode change
6 StatusTr bool true 0 in IN: True enables events on output value changes
in Manual Mode
7 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =
COLD INIT can be used as external limits
8 OutpH real 100 0 in COLD INIT: External and initial high limit for
output limitation
9 OutpL real 0 0 in COLD INIT: External and initial low limit for
output limitation
10 Simulation bool false 0 in IN: TRUE = override signal error indication in
Operate IT, used for simulations only
Parameter AOC
No Name Data Type Initial Value Port Direction Description
1 Name string ‘Name’ 1 in INIT: Tag name of the AOC (allowed deliminators
are “.” and “-“, no blanks “:” or “;” allowed)
2 Description string ‘Description’ 1 in IN: Description text of the AOC
3 IO AOSData default 1 in_out IN/OUT: Connection to AOSData variable
4 Min real 0 1 in INIT: Scaling Parameter Range.
5 Max real 100 1 in INIT: Scaling Parameter Range Max.
6 Unit string ‘%’ 1 in INIT: Scaling Parameter Unit.
7 Fraction dint 1 1 in INIT: Fraction (Number of Decimals).
8 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
9 ModeTr bool true 0 in IN: True enables events on mode change
10 StatusTr bool true 0 in IN: True enables events on output value changes
in Manual Mode
11 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =
COLD INIT can be used as external limits
12 OutpH real 100 0 in COLD INIT: External and initial high limit for
output limitation
13 OutpL real 0 0 in COLD INIT: External and initial low limit for
output limitation
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 46
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 47
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PanelLinkAOS; components
Name Data Attributes Initial Description
Type Value
1 Status dint Retain Object Status (NoError, SignalErr)
nosort
hidden
2 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
3 ManOut real Coldretain Manual Output Signal from Process Panel to
nosort Basic Object
hidden
4 EnManOutFld bool Retain Enabling of Input Field (Manual Output)
nosort
hidden
Status; Bits
Name Bit
Position
1 NoError 0
2 SignalErr 1
Cmd; Bits
Name Bit
Position
1 Auto 0
2 Man 1
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 48
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
4.3 OPERATION
AOCActuator or
Position status indication
AOSActuator
AOCLimitAndUnit or
Limits Value and status indication
AOSLimitAndUnit
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 49
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
AOSandUnit or AOCandUnit
The value and unit presents the output value, it allows direct entry of the value.
Presentation
Indication Type Description Example
Value indication.
Value and Unit Used in Graphic Displays.
Status
Object status Symbol color
Labels
Description Indication
Mode auto No indication of the default mode
Mode manual
Examples:
Properties
Name DataType Default Value Description
EnableBackAppearance Boolean False Switch on the value and unit back
appearance
EnableFitToBestSize Boolean True Set best unit size
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all
used colors are logical colors. The
logical color reference is equal to the
default logical color used in the color
properties. To use an individual color
set it to false.
EnableModeManualLabel Boolean True Show mode manual label
EnableUnit Boolean True Show units
NumberOfDigits Integer 4 Number of presented digits
UnitSize Integer 8 Unit size in pixel: 7 = Small, 8 =
Standard, 10 = Large, 12= XXL
ValueColor Color BMIvalueOUT Value color. Only applied if
EnableLogicalColor is set to false.
ValueSize Integer 12 Value size in pixel: 8 = Small, 10
Medium, 12 = Standard, 14 = Large,
16 = XXL
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 50
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
AOCBar or AOSBar
AOS and AOC bar presents the analogue value as bar. Alarm or process limits are
graphical shown and different bar graph appearances are possible.
Presentation
Appearance Description Example
Standard
This is the standard appearance of the bar graph. The value will
0 be indicated in relation to the maximum and minimum range. The
green bar will always start from the minimum range.
Inverse
2 The bar will be inverse to the standard appearance.
Line
3 The value will be indicated as a small line instead of a bar.
Status
Example Object status Symbol color
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 51
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Labels
Description Indication
Output Signal is Blocked /
Forced
Mode manual
Example:
Properties
Name DataType Default Value Description
Appearance Integer 0 0 = Standard, 1 = Start from Pivot, 2 =
Inverse, 3 = Line
BarColorCustom Color BMIbarOUT Bar color. Only applied if
EnableLogicalColor is set to false.
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all used
colors are logical colors. The logical color
reference is equal to the default logical
color used in the color properties. To use
an individual color set it to false.
EnableManualRange Boolean False If set to true, the bar's range can be set
manually
EnableModeManualLabel Boolean True Show mode manual label
Pivot Real 0. Used together with Appearance = 1 (Start
from Pivot). The bar will start from the
value set as pivot.
RangeMax Real 100. Maximum range if EnableManualRange is
true
RangeMin Real 0. Minimum range if EnableManualRange is
true
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
SymbolSize Integer 14 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
VerticalBar Boolean True VerticalBar: True = vertical appearance,
false = horizontal appearance
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 52
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
AOCIncDecButton or AOSIncDecButton
Command button to increase or decrease the object value.
Presentation
IndicationType Example
1
Status
Status Example
Ready
Disabled
Action in Progress
(Feedback active)
Properties
Name DataType Default Value Description
Action Action Direct Controls the action type, i.e. whether the button
has direct or applied (two step oparation) action.
ButtonType Integer 0 0 = Increase, 1 = Decrease
IndicationType Integer 1 1 = Arrow, 2 = OpenArrow, 3 = StealthArrow, 4 =
Diamond, 5 = Rectangle, 6 = Oval, 7 = Line, 8 =
Triangle
SubscriptionRate Integer 0 The update rate for all aspect object properties
subscribed for
SymbolOrientation Real 0. Orientation in degree, clockwise
SymbolSize Integer 12 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 53
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
AOCActuator or AOSActuator
This Element corresponds to the Status Graphic Element for the Consumer Objects. It
indicates Position X or Y depending on the Value of the AOC and can be used to
represent an Actuator if it is controlled directly with the AOS / AOC without its own Control
Module.
Properties
Name DataType Default Value Dynamicity Description
IndicationType IndicationTy B11_Damper InitOnly Symbol Type Selection: A02_Valve,
peEnum B11_Damper
StatusPosXLimit Real 98. Dynamic Signal Value in Percentage of the
Range above which Pos X will be
indicated
StatusPosYLimit Real 2. Dynamic Signal Value in Percentage of the
Range below which Pos Y will be
indicated
TagName String “” Dynamic TagName to show on Group’s
ShowTagName Function, overwrites
the PIDCtrl name
LimitValueEnum
The Value shown can be configured from the following Selection:
Value Description
A2_Limit_High Value High Limit
A2_Limit_Low Value Low Limit
A3_Speed Value Rate of Change Limitation
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 54
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
4.3.3 Faceplate
Event List
Single Trend
Operators Note
Default View
Tagname
&
Description
Operation Mode
indication
Output Value
indication Mini Trend
Output Value
Graphical Bar
Output value and
limits
Extended View
for detailed
information and
settings
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 55
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Extended View
Auto Mode
F Operation Mode Auto: output value (OUT) written from the application. The value of
the AOS/AOC actually corresponds to the output value.
Manual Mode
F Operation Mode Man: output value (OUT) entered from the faceplate. The value of the
AOS/AOC corresponds to the output value. The Auto value indicates the actual value
coming from the application.
The last entered value in Man mode will be preserved during a cold restart.
Furthermore, the faceplate extended view gives more detailed information about the
Analog Output, such as:
Tab Description
Trend Mini trend of output value, IO value and auto value
Limit Limits for output value
Block - Output Blocking
- Alarm Blocking
IOStatus Sub status for IO and FF Field Devices
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 56
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Trend
On-Line trend with actual output value and auto value.
Move over the trend area and a cursor will appear, showing enabled traces’ value and
record time.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 57
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Description
Max Increase The Direct Entry Window’s high limit is set to the current Value plus the
Value given here
Max Decrease The Direct Entry Window’s low limit is set to the current Value minus the
Value given here
Block / Override
F The IO value (process output value) indicates the “frozen” output value before forcing.
The Auto value indicates the actual value coming from the application.
IOStatus
All Sub-statuses for IO Devices in Quality Bad or Uncertain will be indicated as Signal
Error in the Faceplate.
An Aspect Link giving access to the “Device Management” Object can be configured via
the “BMI DTM Link” General Properties Aspect. See AIS MVStatus for details.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 58
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
F Note that forcing to a Value in the Faceplate does require Write permission for
IO.Signal.IOValue and IO.Signal.Forced, these are not set on IntPar Variables.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 59
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Alarm Messages
For the AOS and AOC object there is not generation of alarms.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 60
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
5 DI Digital Input
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 61
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
5.2 CONTROL
Parameter DIS
No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DIS (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the DIS
3 IO DISData 1 in_out IN/OUT: Connection to DISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus,
a PriorityCommand/Interlock to motors, valves or
groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 ExtTimeStamp bool false 0 in INIT: False = Signal is monitored; True =
SignalID is monitored with external time stamp
7 SignalID string '' 0 in INIT: Identifier of the signal with external time
stamp. Valid when ExtTimeStamp = True
8 UseSigToInit bool false 0 in INIT: True = Use Signal to get an init value. Valid
when ExtTimeStamp = True
9 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
10 AETxt string cBMI.Empty 1 in INIT: Alarm Message description (e.g. Pull Rope
_str Switch, Level High) for NLS support use
||AE_NLS_ preffix and no space in the text
11 ValTr dint 3 0 in INIT: Alarm Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
12 WarnValTr dint 2 0 in INIT: Warning Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 62
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.
Parameter DIC
No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DIC (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the DIC
3 IO DISData 1 in_out IN/OUT: Connection to DISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus,
a PriorityCommand/Interlock to motors, valves or
groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
7 AETxt string cBMI.Empty 1 in INIT: Alarm Message description (e.g. Pull Rope
_str Switch, Level High) for NLS support use
||AE_NLS_ preffix and no space in the text
8 ValTr dint 3 0 in INIT: Alarm Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
9 WarnValTr dint 2 0 in INIT: Warning Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
10 NormPos bool true 1 in IN: Normal position of the DI signal. Alarm is
activated when signal is not in this position.
11 IntlkTypeAlarm dint No_Interlock 1 in INIT:
PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 63
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 64
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PanelLinkDIS; components
Name Data Attributes Initial Description
Type Value
1 Status dint Retain Object Status (Ready,Event, Warning etc.)
nosort
hidden
2 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
3 SignalValue bool Retain Signal Value to Process Panel
nosort
hidden
4 Blink bool Retain Enabling of Basic Object Blinking
nosort
hidden
Cmd; Bits
Name Bit
Position
1 AlarmAck 0
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 65
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
The NormPos is a parameter set thru Control Builder in order to define the normal position
for the signal, which means, the value of the signal that will not create any warning or
alarm.
The PCC Interlock Condition follows the Signal.Normal, however with the “NoAck” Option,
e.g. PCC Interlock Direction configured as “DirXYNoAck”, the Interlock Condition is not
considering any Ready Delay as shown in the Diagram “PCC with NoAck”.
Note that when using the “Fast” Option for DIS Alarm, Delays are not supported.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 66
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
5.3 OPERATION
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 67
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
DIS or DIC
This element presents the value and alarm of a digital input as symbol.
Presentation
Indication Type Example
A00_Rectangle
A01_Motor
A02_Valve
A03_MotorM
A04_Pump
A05_Fan
A06_RotaryFeeder
B11_Damper
B12_Shut
B13_Diverter
B14_LouvreDamper
B15_AirslideDiverter
B16_PropRoller
C31_Valve3way
C32_ValveMan
C33_ValveAuto
E07_Triangle
E08_Lollipop
E09_Diamond
E21_GearwheelPump
E41_Generator
E42_Switch
E77_BeltCleaner
E99_TagName
F00_None
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 68
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Status
Object status Symbol color
OFF Grey
ON Green
Labels
Description Indication
Status blocked
Example:
Properties
Name DataType Default Value Description
IndicationType IndicationTypeEnum A00_Rectangle Symbol type selection
Inverse Boolean False Inverse indication of on/ off status
MirrorPosition Boolean False Mirrors position left / right and open / close
indication
Orientation Integer 0 Rotate symbol clockwise 0 - 360 °
SensorText String "X" Sensor text if IndicationType = E08_Lollipop
SymbolSize Integer 16 8 = Litle, 12 = Small, 16 = Standard, 20 =
Large, 24 = XXL
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 69
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
DISTxt or DICTxt
Digital Input text can be used to create small error labels on process graphic displays, or
overlap displays with meaningful interlock texts. The text appearance can be configured to
show the text only on alarm, depending on the value, always but with different colours
depending on value or alarm condition.
Presentation
Indication Type Example
Text colored
Status
Object status Symbol color
Normal Position for
Appearance Types, 0 = Alarm, 2 Gray dimmed (semitransparent)
= value
Normal Position for
Appearance Types, 10 = Alarm, Green
12 = Value interlock
Labels
Description Indication
Status blocked
Example:
Properties
Name DataType Default Value Description
AppearanceType Integer 0 0 = Alarm, 2 = Value, 3 = Value custom color,
10 = Alarm interlock, 12 Value interlock
ColorAbnormalPos Color Lime Used for AppearanceType 3 = Value custom
color
ColorNormalPos Color RGB(159,159,159) Used for AppearanceType 3 = Value custom
color
EnableFont Boolean False Enable the Font property
EnableLogicalColor Boolean True To use an individual color set it to false
EnableNormalPos Boolean True If false, symbol and text are not visible in
NormalPos.
Font Font Font( "Arial" ,10 Text font when EnableFont is true
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 70
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
DISAlarmDelay or DICAlarmDelay
This element features the same Presentations and Properties as the DISTxt / DICTxt, but
additionally displays the Remaining Time until while the Warning is active. The objects
AlarmDelay must be set bigger than the WarningDelay for this to work.
Properties
Name DataType Default Value Description
EnableAlarmDelayIndication Boolean true Show remaining Delay Time until Alarm
EnableWarningDelayIndication Boolean false Show remaining Delay Time until Warning
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 71
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
5.3.2 Faceplate
Event List
Operators Note
Default View
Tagname
&
Description
Alarm or Event
Message Text
Extended View
for detailed
information and
settings
Some Indications are given in the Faceplate via Yellow Labels above the Value.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 72
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Label Description
Simulation The Signal is simulated (via the Group Member – PCC Connection)
Block Input The Signal Value is Blocked
IO Alarm Blocked The Alarm is Blocked from the Application code
Sig Err The Signal Quality is not ok (see the “MVStatus” Tab for detailed
Status information)
Start Inhibit Active The PCC Interlocks and Limits are blocked because of a configured
PCCStartInhibit Time and the Consumer connected via PCC is not
running
Extended View
The faceplate extended view gives more detailed information about the Digital Input,
such as:
Tab Description
Trend Mini trend of output value and value from process (DIS) or application
(DIC)
Parameter Alarm, Warning and Ready Delay
Block - Input Blocking
- Alarm Blocking
PCC - PCC interlock configuration summery
- Link to connected consumer or consumer overview list
Trend
On-Line trend with actual input value.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 73
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Move over the trend area and a cursor will appear, showing enabled traces’ value and
record time.
Parameters
Setting of Alarm, Warning and Ready Delay
Block / Override
Block / Force Input
Block Alarm
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 74
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PCC
PCC interlock configuration:
The PCC interlock configuration tab shows the actual configuration and a link to the
parent object. If the PCC interlock configuration via parameter
“IntlkTypeAlarm”/“IntlkDirAlarm” resp. “IntlkTypeWarn”/“IntlkDirWarn” is wrong, a yellow
coloured error message “PCC Intlk Param Error” will be displayed.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 75
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
F Note that forcing to a Value in the Faceplate does require Write permission for
IO.SigHW.Value and IO.SigHW.Forced, these are not set on IntPar Variables.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 76
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Alarm Messages
For the DIS, an alarm message is generated when the Signal.Value is different of
NormPos parameter and the AlarmDelay time is elapsed. Then the message is the
following:
[AETxt] + [Severity]
Where AETxt is a parameter defined over DIS parameters in the Control Builder and for
severity the text can also be changed but then over BMIConstAndVar constants,
depending on the severity.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 77
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
6 DO Digital Output
6.2 CONTROL
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 78
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Parameter DOS
No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DOS (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the DOS
3 IO DOSData 1 in_out IN/OUT: Connection to DOSData variable
4 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
5 ModeTr bool true 0 in IN: True enables events on mode change
6 StatusTr bool true 0 in IN: True enables events on status (on/off)
change
7 Simulation bool false 0 in IN: TRUE = override signal error indication in
Operate IT, used for simulations only
Parameter DOC
No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DOC (allowed
deliminators are "." and "-", no blanks ":" or ";"
allowed)
2 Description string 'Description' 1 in IN: Description text of the DOC
3 IO DOSData default 1 in_out IN/OUT: Connection to DOSData variable
4 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
5 ModeTr bool true 0 in IN: True enables events on mode change
6 StatusTr bool true 0 in IN: True enables events on status (on/off)
change
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 79
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PanelLinkDOS; components
Name Data Attributes Initial Description
Type Value
1 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
2 SignalValue bool Retain Signal Value to Process Panel
nosort
hidden
3 ConEn bool Retain Enabling of Control
nosort
hidden
Cmd; Bits
Name Bit
Position
1 On 0
2 Off 1
3 Auto 2
4 Man 3
5 AlarmAck 4
6.3
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 80
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
6.3 OPERATION
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 81
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
DOS or DOC
Presentation
Indication Type Example
A00_Rectangle
A01_Motor
A02_Valve
A03_MotorM
A04_Pump
A05_Fan
A06_RotaryFeeder
B11_Damper
B12_Shut
B13_Diverter
B14_LouvreDamper
B15_AirslideDiverter
B16_PropRoller
C31_Valve3way
C32_ValveMan
C33_ValveAuto
E07_Triangle
E08_Lollipop
E09_Diamond
E21_GearwheelPump
E41_Generator
E42_Switch
E77_BeltCleaner
E99_TagName
F00_None
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 82
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Status
Object status Symbol color
OFF Grey
ON Green
Labels
Description Indication
Status blocked
Mode auto
No indication of the default mode
Mode manual
Example:
Properties
Name DataType Default Value Description
EnableModeManualLabel Boolean True Show mode manual label
EnableObjectStatusColor Boolean False If set to false, the status color
depends on the indication type, else
the logical DO colors are used.
IndicationType IndicationTypeEnum A00_Rectangle Symbol type selection
Inverse Boolean False Inverse indication of on/ off status
MirrorPosition Boolean False Mirrors position left / right and open /
close indication
Orientation Integer 0 Orientation
SymbolSize Integer 16 SymbolSize
For common settings and symbol logical colors please refer to [1] Minerals Library
Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 83
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
DOSTxt or DOCTxt
Presentation
Indication Type Example
Text colored
Status
Object status Symbol color
Normal Position
(Appearance Type: Value Green
interlock)
Labels
Description Indication
Status blocked
Example:
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 84
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Properties
Name DataType Default Value Description
AppearanceType Integer 0 2 = Value, 3 = Value custom color, 12
Value interlock
ColorAbnormalPos Color Lime Used for AppearanceType 3 = Value
custom color
ColorNormalPos Color RGB(159,159,159) Used for AppearanceType 3 = Value
custom color
EnableFont Boolean False Enable the Font property
EnableLogicalColor Boolean True To use an individual color set it to false
EnableModeManualLabel Boolean True Show mode manual label
EnableNormalPos Boolean True Hide symbol in normal position
Font Font Font( "Arial" ,10 Text font when EnableFont is true
,Regular, Bold)
IndicationType Integer 0 0 = Text with background color, 10 =
Square in front of text, 20 = Text colored
NormalPos Boolean False Used for AppearanceType 2 = Value, 3
= Value custom color
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
SymbolSize Integer 12 Defined the square size in case of
IndicationType = 10
TextBold Boolean True Text style is bold
TextIndAbnormalPos String "On" Text for abnormal position
TextIndNormalPos String "Off" Text for normal position
TextSize Integer 10 Text size in pixel: 8 = Small, 10 =
Standard, 12 = Large, 16 = XXL
TextSource Integer 1 0 = None, 1 = TextIndAbnormalPos /
TextIndNormalPos, 2 = OPC Text, 3 =
NLS Text
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 85
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
DOSButton or DOCButton
Digital Output buttons allow sending of commands from the operator station. The type of
the command e.g. toggle, pulse, while down can be selected by properties. The button
can contain a symbol showing the feedback or text. The bar on top of the button can be
switched off.
Presentation
Indication Type Description Example
Status
Object status Symbol color
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 86
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Properties
Name DataType Default Value Description
Action Action SystemDefault Controls the action type, i.e.
whether the button has direct or
applied (two step oparation)
action. Used only for ButtonType
= 0 (toggle) and ButtonType = 1
(single pulse)
ButtonType Integer 0 0 = toggle, 1 = single pulse, 2 =
while down: set signal, 3 = while
down: alternate, 4 = set signal, 5
= reset signal
EnableColorBar Boolean True If true the colored bar on top of
the button is presented.
EnableObjectStatusColor Boolean False If set to false, the status color
depends on the indication type,
else the logical DO colors are
used.
EnableStoreMode Boolean True After an action the original mode
will be restored
EnableSymbol Boolean True Show button with symbol
EnableWriteWhenAuto Boolean True If true, the button is enabled in
manual and auto mode
FeedBackSignal Boolean False If property FeedBackType = 1
then this property is used as the
feed back signal
FeedBackType Integer 0 0 = DO value, 1 = feedback
signal
IndicationType IndicationTypeEnum A00_Rectangle Symbol type selection
PulseTime Integer 1 Pulse time in seconds
SymbolPos Integer 5 1 = top left, 2 = top center, 3 =
top right, 4 = center left, 5 =
center center, 6 = center right, 7
= bottom left, 8 = bottom center,
9 = bottom right
SymbolSize Integer 10 8 = small, 10 = standard, 12 =
large, 14 = XXL
Text String "Text" Description text
TextAlign Integer 5 1 = top left, 2 = top center, 3 =
top right, 4 = center left, 5 =
center center, 6 = center right, 7
= bottom left, 8 = bottom center,
9 = bottom right
TextBold Boolean True Enable text style bold
TextSize Integer 10 8 = small, 10 = standard, 12 =
large, 14 = XXL
TextSource Integer 0 0 = None, 1 = Manual, 2 = OPC,
3 = NLS
For common settings and Symbol Logical colors please refer to [1] Minerals Library
Overview (3BHS 161555).
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 87
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
6.3.2 Faceplate
Event List
Operators Note
Default View
Tagname
&
Description
Operation Mode
indication
Extended View
for detailed
information and
settings
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 88
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Extended View
AUTO Mode
MAN Mode
F Operation Mode Man: Output controlled from the faceplate via the buttons ON and
OFF. The Auto value indicates the actual value coming from the application.
The last entered value in Man mode will be preserved during a cold restart.
Furthermore, the faceplate extended view gives more detailed information about the
Digital Output, such as:
Tab Description
Trend Mini trend of output value and value from process (DOS) or application
(DOC)
Block Output Blocking
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 89
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Trend
On-Line trend with actual output value and IO value.
Move over the trend area and a cursor will appear, showing enabled traces’ value and
record time.
F The IO value (process output value) indicates the “frozen” output value before forcing.
The Auto value indicates the actual value coming from the application.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 90
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
F Note that forcing to a Value in the Faceplate does require Write permission for
IO.SigHW.IOValue and IO.SigHW.Forced, these are not set on IntPar Variables.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 91
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
[MODE] + [VALUE]
[MODE] Description
Aut Auto Mode
Man Manual Mode
And the value can be true or false depending on its status during the mode change
Alarm Messages
For the DOS and DOC object, no alarms are generated.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 92
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
7 PCC_Connect_6
7.2 CONTROL
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 93
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Project Constants are used to ease the reading of the most common configurations
Constant Name Value Description
Transparent 2047 / 16#5FF All defined interlocks on the signal are
forwarded to the consumer
NoInterlockForwarding 0 / 16#0 Regardless of the configuration on the signal
no interlock is forwarded to the consumer. If
the Active Alarm (highest Prio) is an Interlock,
the Alarm Indication will not be forwarded
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 94
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Custom masks can be created in the project library if desired. The added up values of the
actions to be forwarded shall be defined as dword in hex format.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 95
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
7.3 OPERATION
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 96
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
8 PCC_Connect
8.2 CONTROL
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 97
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 98
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
8.3 OPERATION
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 99
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
9 PCC_Threshold_AND3
DriveCond =
SubCond1 or
SubCond2 or
SubCond3
SubCond1 =
CondA1 and
CondB1 and
CondC1
CondA1
CondB1
CondC1
SubCond2 =
CondA2 and
CondB2 and
CondC2
CondA2
CondB2
CondC2
SubCond3 =
CondA3 and
CondB3 and
CondC3
CondA3
CondB3
CondC3
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 100
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
9.2 CONTROL
For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 102
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 103
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 104
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
9.3 OPERATION
9.3.1 Faceplate
Operators Note
Default View
AND
sub condition status
Threshold
main condition status
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 105
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
CondA1 ok Green
DriveCond ok Green
CondA2 not ok Gray
Ok
CondA1 not ok (B) Green
As long the condition Green
CondA2 not ok Gray
is blocked
CondA1 ok Green
DriveCond ok Green
CondB1 ok Green
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 106
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Parameters
On/Off delay settings for the interlock output.
Reference Table
Description
On Delay Time On Delay for interlock output
Off Delay Time Off Delay for interlock output
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 107
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PCC
PCC interlock configuration
The PCC interlock configuration tab shows the actual configuration and a link to the
parent object. For explanation of the different configuration options see chapter PCC
Interlock Parameter Description.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 108
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Maintenance
Last Trip Information: Name and Reason of the Signal that caused the last DriveCond =
false change.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 109
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Block List contains the List of Blocked Conditions in the Form 1A 1B 1C 2A etc.
Example:
On Blk: 2A 2B
The Interlock is not active and the first and second Condition on the second “AND” are
Blocked.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 110
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Above example will present as below in the PCC Viewer. The configured Sub-Conditions
are shown as separate Lines under the actual Interlock Condition of the
PCC_Threshold_AND3, but the Status Color Red for Active Conditions is shown half-
transparent.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 111
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
In the following example air slide 591-AS2.M1 and distribution gate 591-DG1.M1 on
position to silo 1 or air slide 591-AS3.M1 and distribution gate 591-DG1.M1 on position to
silo 2 / 3 or air slide 591-AS2.M1 and air slide 591-AS3.M1 must be running for the air
slide 591-AS1.M1 to start/run.
In this example the interlock condition is not ok.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 112
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
10 PCC_Intlk
10.2 CONTROL
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 113
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
PCC_IntlkInput; components
PCC_IntlkOutput; components
10.3 OPERATION
Tagname
PCC Viewer
&
Overview of all
Description
connected Signals
Actual State
indication Block Indication
Any Interlock
blocked
Extended View
for detailed
information and
settings
Extended View
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 115
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
The faceplate extended view gives more detailed information about the state of the
PCC_Intlk:
Tab Description
PCC Interlock State of the Interlocks connected via PCC to this PCC_Intlk
Parameters Alarm Delay configuration
PCC Information about the configured Interlock Type and Link to the PCC
Parent
Maintenance Interlock Blocking and Last Trip Information
PCC Interlock
Parameters
Parameter Description
Ready Delay Delay until the PCC_Intlk is healthy again after all Interlock conditions
are ok and the Interlock is released
Alarm Delay Delay until the PCC_Intlk trips and the Interlock is activated
PCC
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 116
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Parameters
Parameter Description
Last Trip Reason The active Alarm at the Time of the Last Trip
Last Trip Time Date and Time of the Last Trip
Block Interlock Block the PCC_Intlk trip, disables the Interlock to the PCC Parent
F Per Default, the Block Indication in the reduced Faceplate is visible both if the
PCC_Intlk itself or any Signal connected to PCC is blocked.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 117
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 118
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
11 PCC_Connect_2 (OBSOLETE)
11.2 CONTROL
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 119
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2018 ABB. All rights reserved.
11.3 OPERATION
11.3.1 Faceplate
The Function Block contains one Graphic Element that links to all connected PCC
Consumer / Group Objects. As this Element is linked from the signals connected to the
PCCOut Bus, it allows to trace all connections in case a signal is connected to more than
one parent.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library Version 6.0/3
Document number
Lang. Rev. ind. Pages 120
ABB Switzerland Ltd 3BHS161556-603 en X No. of p. 121
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.