VRF System Selection Report
VRF System Selection Report
System Selection Report
Region :ASIA
Update Date: 03/10/2020
Project Revision:
Global Selection Software version: 4.8.1
VRF System Selection Report
CONTENTS
LIMITS OF LIABILITY ............................................................................................................................................................................... 1
License Contract ................................................................................................................................................................................... 1
Reports ................................................................................................................................................................................................. 1
SYSTEM SELECTION .............................................................................................................................................................................. 2
Outdoor Units........................................................................................................................................................................................ 2
Indoor Units .......................................................................................................................................................................................... 2
SYSTEM DESIGN..................................................................................................................................................................................... 4
SYS1 ..................................................................................................................................................................................................... 4
Outdoor Units of the system ............................................................................................................................................................ 4
Indoor Units of the system ............................................................................................................................................................... 4
PIPING DESIGN ....................................................................................................................................................................................... 5
SYS1 ..................................................................................................................................................................................................... 5
Piping Diagram ................................................................................................................................................................................. 5
SYS1 ..................................................................................................................................................................................................... 6
Piping Rules ..................................................................................................................................................................................... 6
Refrigerant Load & Pipe size ........................................................................................................................................................... 6
Recommendation ............................................................................................................................................................................. 6
WIRING DESIGN ...................................................................................................................................................................................... 7
SYS1 ..................................................................................................................................................................................................... 7
Wiring Diagram ................................................................................................................................................................................ 7
SYS1 ..................................................................................................................................................................................................... 8
Power Supply ................................................................................................................................................................................... 8
RCS link description ......................................................................................................................................................................... 8
Central Controller ................................................................................................................................................................................. 9
H-Link2 communication line description .......................................................................................................................................... 9
EQUIPMENT LIST AND INFORMATION ............................................................................................................................................... 10
Outdoor Units...................................................................................................................................................................................... 10
Indoor Units ........................................................................................................................................................................................ 10
Branch Kit ........................................................................................................................................................................................... 10
Pipe connection kit ......................................................................................................................................................................... 10
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the accuracy Project name: Villa.03.10.20
or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the accuracy Project name: Villa.03.10.20
or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
LIMITS OF LIABILITY
License Contract
By using the Global VRF Selection Software, you agree to abide by the terms of this End User License Agreement.
This software is not intended to provide highly accurate or certifiable results taking into account all the factors involved
in complex or sophisticated installations.
Hitachi makes no warranties regarding the accuracy of the results obtained from the use of this software.
In fact, this software is not able to take into account all the site-specific factors that may influence the proper
functioning of the selected device (e.g. piping or wiring lengths on site, third party AHU, geometry of the piping
network, operating temperatures…).
It may also contain technical inaccuracies or errors, and improvements or modifications may be made to the software
by Hitachi at any time without prior notice.
This software is not intended to replace a thorough evaluation by a professional of the HVAC field.
Accordingly, you are advised not to rely solely on the reports produced by the software to select the appropriate
equipment.
Reports
The report is the result of the information transferred and input by the User of the Global VRF Selection Software.
HITACHI assumes no kind of liability regarding the pre-existing data and information in the Software, as well as the
data and information input by the User, and in particular in relation to:
1. The static part of the Software including the information required to carry out the calculations corresponding to each
project through preset parameters; this information merely includes the parameters for the preparation of the report in
line with the model designed by and with the knowledge of Hitachi, without this implying any kind of guarantee for the
user regarding the precision and reliability of the results of the report.
2. The dynamic part of the Software, which is the result of the information input by the User in correspondence with
the said parameters; the User is on all accounts exclusively liable for the accuracy of the information being input in the
Software.
3. The failure to include any legal aspects that may correspond or be required according to current laws.
The Software and the issuing of this report are merely informative tools to assist the User in the planning and
implementation of a project.
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
1 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
SYSTEM SELECTION
Outdoor Units
Model
Pictures Description Quantity Components
Identification
RAS-16HNBCMQ
RAS-32HNBCMQ
Specifications
Power supply 380~415V/3Ph/50Hz
Cooling 90.0kW
Nominal capacity
Heating 100.0kW
EER
COP
SEER
SCOP
Height 1,725mm
Dimensions Width 1218+1218mm
Depth 782mm
Net Weight 310+310kg
Indoor Units
No Room
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
2 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
3 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
SYSTEM DESIGN
SYS1
27.0 °C DB
Cooling 35.0 °C DB
19.6 °C WB (50% RH)
7.0 °C DB
Heating 20.0 °C DB
3.1 °C WB (51% RH)
Note:
- Actual capacity takes into account all correction factors, including defrosting in heating mode.
- Each Indoor unit’s temperature condition might be different. Software uses minimum wet bulb temperature of indoor for
system cooling process and uses maximum dry bulb temperature of indoor for system heating process.
Outdoor Unit (SYS1) Connect. Rate (%) Cooling Capacity (kW) Heating Capacity (kW)
Ref + Description Ident. Actual Max Nominal Actual Required Nominal Actual Required
Commercial VRF HP, HNCQ RAS-32HNBCMQ 106 110 - 87.8 - - 92.6 -
Indoor Unit (SYS1) Sound Pressure Air Flow Cooling Capacity (kW) Heating Capacity (kW)
Ref + Description Ident. dB(A) Speed m³/min Actual Sensible Required Actual Required
Total 87.8 62.6 0.0 92.6 0.0
Low Static Ducted RPIL-2.0HNAUNQ GF 34 High 15.0 5.2 3.8 0.0 5.5 0.0
Low Static Ducted RPIL-1.5HNAUNQ GF2 34 High 13.0 3.9 2.8 0.0 4.1 0.0
Low Static Ducted RPIL-5.0HNAUNQ GF5 44 High 36.0 12.9 8.9 0.0 13.7 0.0
Low Static Ducted RPIL-5.0HNAUNQ GF6 44 High 36.0 12.9 8.9 0.0 13.7 0.0
Low Static Ducted RPIL-1.3HNAUNQ GF3 34 High 13.0 3.4 2.5 0.0 3.6 0.0
Low Static Ducted RPIL-1.0HNAUNQ GF4 28 High 9.0 2.6 1.9 0.0 2.7 0.0
Low Static Ducted RPIL-1.5HNAUNQ 1F8 34 High 13.0 3.9 2.8 0.0 4.1 0.0
Low Static Ducted RPIL-6.0HNAUNQ 1F9 46 High 42.0 15.5 11.2 0.0 16.4 0.0
Low Static Ducted RPIL-3.0HNAUNQ 1F10 38 High 29.0 7.8 5.5 0.0 8.2 0.0
Low Static Ducted RPIL-1.3HNAUNQ 1F11 34 High 13.0 3.4 2.5 0.0 3.6 0.0
Low Static Ducted RPIL-3.0HNAUNQ 1F7 38 High 29.0 7.8 5.5 0.0 8.2 0.0
Low Static Ducted RPIL-1.3HNAUNQ Ind11 34 High 13.0 3.4 2.5 0.0 3.6 0.0
Low Static Ducted RPIL-2.0HNAUNQ 2F 34 High 15.0 5.2 3.8 0.0 5.5 0.0
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
4 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
PIPING DESIGN
SYS1
Piping Diagram
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
5 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
SYS1
Piping Rules
Project Max
Commercial VRF HP, HNCQ RAS-32HNBCMQ OK
m m
Total pipe length 142 1,000
Maximum Piping Length between Each Multi-kit and Each Indoor Unit 12 40
Piping Length between Piping Connection Kit 1 and Each Outdoor Unit 2 10
Total 36.0
Recommendation
- If pipe size 1'' is not available in your country, please use 1''1/8 as replacement.
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
6 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
WIRING DESIGN
SYS1
Wiring Diagram
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
7 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
SYS1
Power Supply
RAS-32HNBCMQ (RAS-16HNBCMQ +
380~415V/3Ph/50Hz 13.43+13.43 35.5+35.5
RAS-16HNBCMQ)
- Minimum recommended section (up to 500 m): 2 x 0.75 mm² connected to earth at one point.
- Cable characteristics: non polar, twisted shielded pair of cable.
- One Remote Control Switch can control up to 16 Indoor Units as a maximum.
- Two Remote Control Switch can be connected in the same unit or unit group.
- The second one is a subsidiary remote control switch.
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
8 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
Central Controller
- Minimum recommended section: 2 x 0.75 mm² connected to earth at one point. Shielding must be renewed every 300m.
- Transmitting wires: non polar, twisted shielded pair of cable.
- Maximum H-Link2 communication line length is 1000 m but can be increased until 5.000m using optional relay PSC-5HR.
- Several refrigerant systems can be connected together on a bus with H-LINK2 wiring using an open loop
- Maximum number of Outdoor Units is 64.
- Maximum number of Indoor Units is 160.
- Number of central controller: 0
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
9 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.8.1
VRF System Selection Report
Outdoor Units
RAS-16HNBCMQ - Components 2
Indoor Units
Branch Kit
Multikit
1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software.
0 Global Selection Software version: 4.8.1
VRF System Selection Report
CH Box
Field Providing
Piping Materials
Length
Pipe size(mm)
m
6.35 51
9.52 50
12.7 67
19.05 10
15.88 58
22.2 7
25.4 23
28.58 8
31.75 10
Refrigerant
Quantity to be provided
Refrigerant Type
kg
R410A 16.2
1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software.
1 Global Selection Software version: 4.8.1
VRF System Selection Report
Field Providing
6.35 51
9.52 50
12.7 67
19.05 10
15.88 58
22.2 7
25.4 23
28.58 8
31.75 10
Quantity to be provided
Refrigerant Type
kg
1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software.
2 Global Selection Software version: 4.8.1
VRF System Selection Report
Quantity to be provided
Refrigerant Type
kg
R410A 16.2
1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software.
3 Global Selection Software version: 4.8.1