VRF System Selection Report

This document provides a VRF system selection report for a villa project in Asia. It includes: 1) A system selection with recommended outdoor and indoor units. 2) A system design outlining the outdoor and indoor units for System 1. 3) Piping and wiring designs including diagrams, rules, load calculations, and recommendations for System 1. 4) An equipment list and information on outdoor units, indoor units, branch kits, control boxes, and required field materials.

Uploaded by

theng ngy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
305 views16 pages

VRF System Selection Report

This document provides a VRF system selection report for a villa project in Asia. It includes: 1) A system selection with recommended outdoor and indoor units. 2) A system design outlining the outdoor and indoor units for System 1. 3) Piping and wiring designs including diagrams, rules, load calculations, and recommendations for System 1. 4) An equipment list and information on outdoor units, indoor units, branch kits, control boxes, and required field materials.

Uploaded by

theng ngy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

VRF 

System Selection Report   

VRF System Selection Report


Project Name :Villa.03.10.20

Region :ASIA

Selection Mode :Cooling+Heating


Sales Engineer :
Company:
Address:
Phone No:
Order Date : 01/10/2020
Delivery required date : 01/10/2020
Client Name :
Post Code :
Tel :
Mail :

Update Date: 03/10/2020       
Project Revision:   
Global Selection Software version: 4.8.1       
VRF System Selection Report   

CONTENTS
LIMITS OF LIABILITY ............................................................................................................................................................................... 1 
License Contract ................................................................................................................................................................................... 1 
Reports ................................................................................................................................................................................................. 1 
SYSTEM SELECTION .............................................................................................................................................................................. 2 
Outdoor Units........................................................................................................................................................................................ 2 
Indoor Units .......................................................................................................................................................................................... 2 
SYSTEM DESIGN..................................................................................................................................................................................... 4 
SYS1 ..................................................................................................................................................................................................... 4 
Outdoor Units of the system ............................................................................................................................................................ 4 
Indoor Units of the system ............................................................................................................................................................... 4 
PIPING DESIGN ....................................................................................................................................................................................... 5 
SYS1 ..................................................................................................................................................................................................... 5 
Piping Diagram ................................................................................................................................................................................. 5 
SYS1 ..................................................................................................................................................................................................... 6 
Piping Rules ..................................................................................................................................................................................... 6 
Refrigerant Load & Pipe size ........................................................................................................................................................... 6 
Recommendation ............................................................................................................................................................................. 6 
WIRING DESIGN ...................................................................................................................................................................................... 7 
SYS1 ..................................................................................................................................................................................................... 7 
Wiring Diagram ................................................................................................................................................................................ 7 
SYS1 ..................................................................................................................................................................................................... 8 
Power Supply ................................................................................................................................................................................... 8 
RCS link description ......................................................................................................................................................................... 8 
Central Controller ................................................................................................................................................................................. 9 
H-Link2 communication line description .......................................................................................................................................... 9 
EQUIPMENT LIST AND INFORMATION ............................................................................................................................................... 10 
Outdoor Units...................................................................................................................................................................................... 10 
Indoor Units ........................................................................................................................................................................................ 10 
Branch Kit ........................................................................................................................................................................................... 10 
Pipe connection kit ......................................................................................................................................................................... 10 
JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the accuracy  Project name: Villa.03.10.20
or completeness of the data given and therefore the answers obtained by this software.   
Global Selection Software version: 4.8.1 
 
 
VRF System Selection Report   

Multikit ............................................................................................................................................................................................ 10 


CH Box................................................................................................................................................................................................ 11 
Field Providing .................................................................................................................................................................................... 11 
Piping Materials.............................................................................................................................................................................. 11 
Refrigerant...................................................................................................................................................................................... 11 
Appendix –Equipment list for SYS1........................................................................................................................................................ 12 
Field Providing ............................................................................................................................................................................... 12 

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the accuracy  Project name: Villa.03.10.20
or completeness of the data given and therefore the answers obtained by this software.   
Global Selection Software version: 4.8.1 
 
 
VRF System Selection Report   

LIMITS OF LIABILITY

License Contract

By using the Global VRF Selection Software, you agree to abide by the terms of this End User License Agreement.
This software is not intended to provide highly accurate or certifiable results taking into account all the factors involved
in complex or sophisticated installations.
Hitachi makes no warranties regarding the accuracy of the results obtained from the use of this software.
In fact, this software is not able to take into account all the site-specific factors that may influence the proper
functioning of the selected device (e.g. piping or wiring lengths on site, third party AHU, geometry of the piping
network, operating temperatures…).
It may also contain technical inaccuracies or errors, and improvements or modifications may be made to the software
by Hitachi at any time without prior notice.
This software is not intended to replace a thorough evaluation by a professional of the HVAC field.
Accordingly, you are advised not to rely solely on the reports produced by the software to select the appropriate
equipment.

Reports

The report is the result of the information transferred and input by the User of the Global VRF Selection Software.
HITACHI assumes no kind of liability regarding the pre-existing data and information in the Software, as well as the
data and information input by the User, and in particular in relation to:
1. The static part of the Software including the information required to carry out the calculations corresponding to each
project through preset parameters; this information merely includes the parameters for the preparation of the report in
line with the model designed by and with the knowledge of Hitachi, without this implying any kind of guarantee for the
user regarding the precision and reliability of the results of the report.
2. The dynamic part of the Software, which is the result of the information input by the User in correspondence with
the said parameters; the User is on all accounts exclusively liable for the accuracy of the information being input in the
Software.
3. The failure to include any legal aspects that may correspond or be required according to current laws.
The Software and the issuing of this report are merely informative tools to assist the User in the planning and
implementation of a project.

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
1  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

SYSTEM SELECTION

Outdoor Units

Model
Pictures Description Quantity Components
Identification
RAS-16HNBCMQ

Commercial VRF HP, RAS-16HNBCMQ


RAS-32HNBCMQ 1
HNCQ -

RAS-32HNBCMQ
Specifications
Power supply 380~415V/3Ph/50Hz

Cooling 90.0kW
Nominal capacity
Heating 100.0kW

EER
COP
SEER
SCOP

Sound power dB(A)

Height 1,725mm
Dimensions Width 1218+1218mm
Depth 782mm
Net Weight 310+310kg

Indoor Units

No Room

Indoor Unit Nominal Cap. (kW) Control


Accessories
Picture Ident. Description - Model Cool Heat Picture Model Gp
Low Static Ducted
GF 5.6 6.5
RPIL-2.0HNAUNQ

Low Static Ducted


GF2 4.3 4.9
RPIL-1.5HNAUNQ

Low Static Ducted


GF5 14.2 16.3
RPIL-5.0HNAUNQ

Low Static Ducted


GF6 14.2 16.3
RPIL-5.0HNAUNQ

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
2  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

Indoor Unit Nominal Cap. (kW) Control


Accessories
Picture Ident. Description - Model Cool Heat Picture Model Gp
Low Static Ducted
GF3 3.6 4.2
RPIL-1.3HNAUNQ

Low Static Ducted


GF4 2.8 3.3
RPIL-1.0HNAUNQ

Low Static Ducted


1F8 4.3 4.9
RPIL-1.5HNAUNQ

Low Static Ducted


1F9 16.0 18.0
RPIL-6.0HNAUNQ

Low Static Ducted


1F10 8.4 9.6
RPIL-3.0HNAUNQ

Low Static Ducted


1F11 3.6 4.2
RPIL-1.3HNAUNQ

Low Static Ducted


1F7 8.4 9.6
RPIL-3.0HNAUNQ

Low Static Ducted


Ind11 3.6 4.2
RPIL-1.3HNAUNQ

Low Static Ducted


2F 5.6 6.5
RPIL-2.0HNAUNQ

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
3  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

SYSTEM DESIGN

SYS1

Working Condition Outdoor (Air) Indoor (Air)

27.0 °C DB
Cooling 35.0 °C DB
19.6 °C WB (50% RH)

7.0 °C DB
Heating 20.0 °C DB
3.1 °C WB (51% RH)

Note:
- Actual capacity takes into account all correction factors, including defrosting in heating mode.
- Each Indoor unit’s temperature condition might be different. Software uses minimum wet bulb temperature of indoor for
system cooling process and uses maximum dry bulb temperature of indoor for system heating process.

Outdoor Units of the system

Outdoor Unit (SYS1) Connect. Rate (%) Cooling Capacity (kW) Heating Capacity (kW)
Ref + Description Ident. Actual Max Nominal Actual Required Nominal Actual Required
Commercial VRF HP, HNCQ RAS-32HNBCMQ 106 110 - 87.8 - - 92.6 -

Total - 87.8 - - 92.6 -

Indoor Units of the system

Indoor Unit (SYS1) Sound Pressure Air Flow Cooling Capacity (kW) Heating Capacity (kW)
Ref + Description Ident. dB(A) Speed m³/min Actual Sensible Required Actual Required
Total 87.8 62.6 0.0 92.6 0.0
Low Static Ducted RPIL-2.0HNAUNQ GF 34 High 15.0 5.2 3.8 0.0 5.5 0.0
Low Static Ducted RPIL-1.5HNAUNQ GF2 34 High 13.0 3.9 2.8 0.0 4.1 0.0
Low Static Ducted RPIL-5.0HNAUNQ GF5 44 High 36.0 12.9 8.9 0.0 13.7 0.0
Low Static Ducted RPIL-5.0HNAUNQ GF6 44 High 36.0 12.9 8.9 0.0 13.7 0.0
Low Static Ducted RPIL-1.3HNAUNQ GF3 34 High 13.0 3.4 2.5 0.0 3.6 0.0
Low Static Ducted RPIL-1.0HNAUNQ GF4 28 High 9.0 2.6 1.9 0.0 2.7 0.0
Low Static Ducted RPIL-1.5HNAUNQ 1F8 34 High 13.0 3.9 2.8 0.0 4.1 0.0
Low Static Ducted RPIL-6.0HNAUNQ 1F9 46 High 42.0 15.5 11.2 0.0 16.4 0.0
Low Static Ducted RPIL-3.0HNAUNQ 1F10 38 High 29.0 7.8 5.5 0.0 8.2 0.0
Low Static Ducted RPIL-1.3HNAUNQ 1F11 34 High 13.0 3.4 2.5 0.0 3.6 0.0
Low Static Ducted RPIL-3.0HNAUNQ 1F7 38 High 29.0 7.8 5.5 0.0 8.2 0.0
Low Static Ducted RPIL-1.3HNAUNQ Ind11 34 High 13.0 3.4 2.5 0.0 3.6 0.0
Low Static Ducted RPIL-2.0HNAUNQ 2F 34 High 15.0 5.2 3.8 0.0 5.5 0.0

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
4  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

PIPING DESIGN

SYS1

Piping Diagram

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
5  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

SYS1

Piping Rules

Project Max
Commercial VRF HP, HNCQ RAS-32HNBCMQ OK
m m
Total pipe length 142 1,000

Maximum piping length (Actual length) 40 165

Maximum piping length (Equivalent length) 43 190


Length
Maximum Piping Length between Multi-kit of 1st Branch and Each Indoor Unit 30 90

Maximum Piping Length between Each Multi-kit and Each Indoor Unit 12 40

Piping Length between Piping Connection Kit 1 and Each Outdoor Unit 2 10

Height Difference between (O.U. is Upper) 0 50

Height Height Difference between (O.U. is Lower) 0 40

Height Difference between Indoor Units 0 30

IU connectable ( Min / recommended / Max) 13 1 / 32 / 53


Connected Cap. (Min-Max) 106% 50%-130%

Refrigerant Load & Pipe size

Refrigerant Type: R410A


Commercial VRF HP, HNCQ RAS-32HNBCMQ
kg

OU refrigerant load (Charge before shipment) 19.8

Installation Additional refrigerant load (OU + Piping) 16.2

Total 36.0

Recommendation

- If pipe size 1'' is not available in your country, please use 1''1/8 as replacement.

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
6  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

WIRING DESIGN

SYS1

Wiring Diagram

 
 

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
7  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

SYS1

Power Supply

Input power Max current


Model Power supply
kW A

RAS-32HNBCMQ (RAS-16HNBCMQ +
380~415V/3Ph/50Hz 13.43+13.43 35.5+35.5
RAS-16HNBCMQ)

RPIL-2.0HNAUNQ 220~240V/1Ph/50Hz 0.09 0.41

RPIL-1.5HNAUNQ 220~240V/1Ph/50Hz 0.12 0.51

RPIL-5.0HNAUNQ 220~240V/1Ph/50Hz 0.29 1.32

RPIL-1.3HNAUNQ 220~240V/1Ph/50Hz 0.12 0.51

RPIL-1.0HNAUNQ 220~240V/1Ph/50Hz 0.06 0.27

RPIL-6.0HNAUNQ 220~240V/1Ph/50Hz 0.38 1.64

RPIL-3.0HNAUNQ 220~240V/1Ph/50Hz 0.25 1.13

RCS link description

- Minimum recommended section (up to 500 m): 2 x 0.75 mm² connected to earth at one point.
- Cable characteristics: non polar, twisted shielded pair of cable.
- One Remote Control Switch can control up to 16 Indoor Units as a maximum.
- Two Remote Control Switch can be connected in the same unit or unit group.
- The second one is a subsidiary remote control switch.

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
8  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

Central Controller

H-Link2 communication line description

- Minimum recommended section: 2 x 0.75 mm² connected to earth at one point. Shielding must be renewed every 300m.
- Transmitting wires: non polar, twisted shielded pair of cable.
- Maximum H-Link2 communication line length is 1000 m but can be increased until 5.000m using optional relay PSC-5HR.
- Several refrigerant systems can be connected together on a bus with H-LINK2 wiring using an open loop
- Maximum number of Outdoor Units is 64.
- Maximum number of Indoor Units is 160.
- Number of central controller: 0

JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
9  accuracy or completeness of the data given and therefore the answers obtained by this software. 
  Global Selection Software version: 4.8.1     
VRF System Selection Report   

EQUIPMENT LIST AND INFORMATION

Outdoor Units

Model & Components System Name Description Quantity

RAS-32HNBCMQ SYS1 Commercial VRF HP, HNCQ 1

RAS-16HNBCMQ - Components 2

Indoor Units

Model Description Quantity

RPIL-1.0HNAUNQ Low Static Ducted 1


RPIL-1.3HNAUNQ Low Static Ducted 3
RPIL-1.5HNAUNQ Low Static Ducted 2
RPIL-2.0HNAUNQ Low Static Ducted 2
RPIL-3.0HNAUNQ Low Static Ducted 2
RPIL-5.0HNAUNQ Low Static Ducted 2
RPIL-6.0HNAUNQ Low Static Ducted 1

Branch Kit

Pipe connection kit

Model Description Quantity

M-30SNQ Outdoor units piping connection kit 1

Multikit

Model Description Quantity

E-302SN Line branch kit 1


E-162SN Line branch kit 6
E-102SN Line branch kit 5

1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software. 
 0  Global Selection Software version: 4.8.1     
VRF System Selection Report   

CH Box

Field Providing

Piping Materials

Length
Pipe size(mm)
m
6.35 51
9.52 50
12.7 67
19.05 10
15.88 58
22.2 7
25.4 23
28.58 8
31.75 10

Refrigerant

Quantity to be provided
Refrigerant Type
kg
R410A 16.2

1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software. 
 1  Global Selection Software version: 4.8.1     
VRF System Selection Report   

Appendix –Equipment list for SYS1

Category Model Description Quantity

Outdoor Units RAS-32HNBCMQ Commercial VRF HP, HNCQ 1


RAS-16HNBCMQ component 2

Indoor Units RPIL-1.0HNAUNQ Low Static Ducted 1


RPIL-1.3HNAUNQ Low Static Ducted 3
RPIL-1.5HNAUNQ Low Static Ducted 2
RPIL-2.0HNAUNQ Low Static Ducted 2
RPIL-3.0HNAUNQ Low Static Ducted 2
RPIL-5.0HNAUNQ Low Static Ducted 2
RPIL-6.0HNAUNQ Low Static Ducted 1

Piping Connection Kit M-30SNQ Outdoor units piping connection kit 1

MultiKit E-302SN Line branch kit 1


E-162SN Line branch kit 6
E-102SN Line branch kit 5

Field Providing

Pipe size(mm) Length

6.35 51
9.52 50
12.7 67
19.05 10
15.88 58
22.2 7
25.4 23
28.58 8
31.75 10

Quantity to be provided
Refrigerant Type
kg

1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software. 
 2  Global Selection Software version: 4.8.1     
VRF System Selection Report   

Quantity to be provided
Refrigerant Type
kg
R410A 16.2

1 JOHNSON CONTROLS‐HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the  Project name: Villa.03.10.20
accuracy or completeness of the data given and therefore the answers obtained by this software. 
 3  Global Selection Software version: 4.8.1     