UEM40-2C R70: 40A Single Phase Energy Meter With Built-In Communication

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

MID Energy Meters

MID Energy Meters


UEM40-2C R70
40A single phase energy meter with built-in communication

• For RS485 Modbus RTU communication


• Direct connection up to 40 A
• Up to 70°C operating temperature
• Fully bi-directional 4-quadrant measurements for all
energies and powers
• High reliability
• 1 DIN module compact size
• Quick installation
• S0 output for energy pulse emission
• LCD display with 7 main digits
• Available with MID certification

» General features
1 DIN module energy meter for the energy measurement in industrial and civilian application, with RS485 Modbus RTU built-in
communication. Available with MID certification suitable for billing.
Besides the energy, the meter can measure the main electrical parameters and makes them available on the display and on the
built-in COM port. The COM port allows to manage the connected meter by a remote station and data is transmitted on a RS485
line. Moreover, a dedicated application for remote management is provided:
• Modbus Master software > for energy meter management by PC in RS485 Modbus network.
The meter is built according to EN 50470-1 standard. The active energy is compliant to IEC/EN 62053-21 class 1, but for MID
certified device it moreover fulfills class B requirements according to EN 50470-3. The accuracy of the reactive energy is compliant
to IEC/EN 62053-23 class 2.
Backlighted LCD display with clear graphic symbols comprehensible at a glance. Metrological LED on front panel and sealable
terminal covers. The analysis of the MTBF values, the accurate selection of components and the reduction of the internal working
temperatures together with strict production and control standards guarantee a product with an excellent quality and a long
lasting reliability.

» Applications » Benefits
• Totalization of the electric energy in the industry for • Up to 7 instantaneous measurements, complete set of
each single line or machine. energy counters and partial counters. Moreover partial
• Measurement of energy generated by renewable counters can be started, stopped or reset.
sources such as solar, eolic, etc. • Remote management through dedicated application.
• Accounting and billing of consumptions in camp sites, • Available MID according to Swiss market (MID S).
malls, residential areas, naval ports, etc. Reactive energy is not shown on energy meter display.
• Totalization of the electric consumption in hotels,
congress centers, exhibition fairs.
• Accounting of the consumptions in buildings with
executive office services.
• Internal allocation of the consumptions in timeshare
civilian and industrial buildings.
» Related products
• Realization of energy monitoring systems. • Modbus Master software (for Windows OS)
• Remote survey of the consumptions and compute
of the costs.

1
Innovative Electronic Systems
MID Energy Meters UEM40-2C R70

» Technical features
Power supply Accuracy
• Power supplied from the voltage circuit • Active energy class 1 according to IEC/EN 62053-21 (NO MID)
• Nominal measurement voltage ±20% • Active energy class B according to EN 50470-3 (MID)
• Max consumption: 1.5 VA - 1 W • Reactive energy class 2 according to IEC/EN 62053-23
• Nominal frequency: 50/60 Hz
S0 output
Voltage & frequency • Passive optoisolated
• Nominal values: 230 V 50/60 Hz • Maximum values: 27 VDC - 27 mA
• Meter constant: 1000 imp/kWh
Current The measuring unit (imp/kWh, imp/kvarh, imp/kVAh) changes according to the
assigned counter (kWh, kvarh, kVAh)
• Starting current Ist: 20 mA
• Pulse length: 100 ±0.5ms
• Minimum current Imin: 250 mA
• Transitional current Itr: 500 mA
Metrological LED
• Reference current Iref (Ib): 5 A
• Meter constant: 5000 imp/kWh
• Maximum current Imax: 40 A
• Pulse length: 4 ±0.1ms

RS485 Modbus communication Environmental conditions


• Port: RS485
• Operating temperature: -25°C ... +70°C
• Protocol: Modbus RTU
• Storage temperature: -40°C ... +75°C
• Communication speed: 2400, 4800, 9600, 19200, 38400 bps
• Humidity: 80% max without condensation
• Unit load: 1/8
• Protection degree: IP51 frontal part -IP20 terminals

» Technical drawing (mm)

2
Innovative Electronic Systems
MID Energy Meters UEM40-2C R70

» Measurements

MEASURE UNIT, COM


SYMBOL DISPLAY
VALUE or STATUS PORT
INSTANTANEOUS VALUES
Voltage V V  
Current I A  
Power factor PF -  
Active power P kW  
Apparent power S kVA  
Reactive power Q kvar  
Frequency f Hz  
 (display)
Power direction -  
+/- (port)
RECORDED DATA
Active energy kWh  
Inductive and capacitive apparent energy kVAh  
Inductive and capacitive reactive energy kvarh v 
Resettable energy counters (only NO MID package) kWh, kVAh, kvarh v 
Resettable partial energy counters kWh, kVAh, kvarh v 
OTHER INFORMATION
Partial counter status P/ P Start / Stop  
S0 output status  Active 

LEGEND:  = Available  = Bidirectional value v = varh not available for MID S meter

3
Innovative Electronic Systems
MID Energy Meters UEM40-2C R70

VOLTAGE AND COMMUNICATION PORT OPTIONS


ORDER FREQUENCY INPUT
CO D E
Self-powered RS485 MODBUS MID MID S RESET

UEM40-2C R70
1109.0019.0001 230V 50/60Hz
• •
1109.0020.0001 230V 50/60Hz
• •
1109.0021.0001 230V 50/60Hz
• •
LEGEND
MID: MID certified meter, with reset function only on partial counters.
MID S: MID certified meter, with reset function only on partial counters, without reactive energy counters on display (only SWITZERLAND ).
RESET: Meter without MID certification, with RESET function on ALL counters.
Softwares for meter remote management (MODBUS Master) downloadable for free at www.algodue.it, in the Client protected area.
A multilingual manual with English, German, Italian, French, Spanish is provided.

NOTE: Subject to change without notice

Innovative Electronic Systems

Via P. Gobetti, 16/F - 28014 Maggiora (NO) - Italy - Tel.: +39 0322 89307
[email protected] - www.algodue.com