XQ1475G-50 HZ Spec Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

XQ1475G RENTAL

CONTINUOUS 1475 kW

50 Hz
Frequency Voltage Continuous
(Hz) (V) kW (kVA)
50 Hz 400/230V 1475 (1844)

FEATURES COOLING SYSTEM


 Horizontally mounted radiator with vertical
FUEL/EMISSIONS STRATEGY discharge
 Meets most worldwide emissions requirements  Sized compatible to rating with energy efficient
down to 250 mg/Nm3 NOx level without after electric drive fan and core.
treatment  Provides 38C (100F) ambient capability with
500 mg/Nm3 NOx (1g/hp-hr) at 100%
SINGLE-SOURCE SUPPLIER continuous rating before derate
 Generator set manufactured in ISO 9001:2000  Variable frequency drive fan controls improve
compliant facility partial load fuel consumption
 Package factory designed and production tested
 Generator set and components meet or exceed the CAT GENERATOR
following specifications:AS1359, AS2789, BS4999,  Cat SR4B 826 frame generator designed to
DIN6271,DIN6280, EGSA101P, JEM1359,IEC match the performance and output
34/1, ISO3046/1, ISO8528, NEMA MG1-22 characteristics of the Cat gas engine
 Double bearing, wye-connected, static
WORLDWIDE PRODUCT SUPPORT regulated, brushless, permanent magnet
 Cat® dealers provide extensive post sale support excited
including maintenance and repair agreements
 Supported 100% by the Cat dealer with warranty ON PACKAGE CONTROL PANEL SYSTEM
on parts and labor  Provides auto paralleling using package
mounted controls
CAT G3516C ISLAND MODE GAS ENGINE  EMCP 4.2 offers engine and generator
 Compact, four-stroke-cycle gas engine provides monitoring and protection
exceptional dependability, fuel economy and  PL1000E Controller
power density  Engine Advisor Panel
 Robust kilowatt based air to fuel ratio control  AGC-4 provides paralleling, load sharing, VFD
system yields enhanced system performance control, and primary generator protection
 Designed for maximum performance on low
pressure pipeline natural gas (3-7 psi), (0.21 CAT DIGITAL VOLTAGE REGULATOR (Cat
kg/cm² - 0.49 kg/cm²) to the container) with a DVR)
methane number range of 55-100 (derate occurs  Three-phase sensing with adjustable volts-per-
with methane numbers <55) hertz regulation
 Island mode feature improves engine’s capability  Provides precise control and constant voltage
to handle electrical loading and unloading in the normal operating range.
REDUCED ENVIRONMENTAL IMPACT SOUND ATTENUATED CONTAINER
 110% spill containment of onboard engine fluids  Provides 9-high stack CSC rated enclosure for
 Positive crankcase fumes ventilation ease of transportation and protection.
 Meets 72 dB(A) at 15 meters or below per SAE
J1074 measurement procedure at prime rating
LEHX0010-02 1
XQ1475G RENTAL
FACTORY INSTALLED STANDARD EQUIPMENT

SYSTEM STANDARD EQUIPMENT


3 3
Engine Cat G3516C Island Mode Gas Engine (Operates on 31.5 to 47.2 MJ/Nm (800 to 1200 btu/ft ) dry pipeline
natural gas)
Cat Engine Advisor Panel provides engine diagnostics and full text descriptions
Cat Gas Engine Control Module (Cat GECM) includes electronic speed governor with hydrax actuator and
provides transient richening and turbo bypass control
Electronic Ignition System (controlled by ECM)
Individual cylinder Detonation Sensitive Timing (DST)
Engine installed electronic fuel metering valve
Hydraulic actuated throttle plate electronically controlled by ECM
Heavy duty, single element canister type air cleaner with service indicator
Charging Alternator, 60-Amp
Dual 24V electric starting motors
Integral lube oil cooler, lube oil pump, oil filter, filler, and dipstick and oil drain lines routed to engine rail
Prelube Pump, 24VDC continuous type
Jacket Water Heater, 9kW, 400/480V, 50/60 Hz, 3-phase with isolation valves

Generator Double bearing SR-4B brushless, form wound, permanent magnet excited, three-phase with Cat digital voltage
regulator (Cat DVR), space heater, 6-lead design, Class H insulation operating at Class F temperature for
extended life, winding temperature detectors and anti-condensation space heaters (120/240V 1.2 kW).
Generator equipped with System 4 insulation protection.

Containerized Module 40' ISO high cube container, 9-high stack CSC certified
Four (4) sound attenuated air intake louvers and 3 lockable personnel doors with panic release
Interior walls and ceilings insulated with 100 mm of acoustic paneling
Floor of container is undercoated for corrosion protection
Side bus bar access door, external access load connection bus bars
Shore power connection via distribution block connections for jacket water heater, battery charger, generator
space heaters, and generator condensate heaters
Six (6) DC lights
3” ANSI flange customer fuel connection with cover to prevent vandalism
Energized-to-run (ETR) shutoff valve (double solenoid, low/high pressure switch, CSA/FM approved)
Cat Brand fuel filter, wall mounted and gas pressure regulator
Lube oil level regulator with makeup tank
Sound attenuated 72 dB(A) @ 15 m (50 ft)
Four (4) oversized maintenance-free batteries, battery rack and 20-Amp battery charger
Critical grade exhaust silencer with vertical discharge and single 2 m (6.5 ft.) stack
Vibration isolators, stainless steel fastening hardware and hinges
External drain access to standard fluids
One 4.5 kg (10 lb) carbon dioxide fire extinguisher
Standard Cat rental decals and painted standard Cat power module white
LH and RH engine service panels integrated into container side walls
110% spill containment system for on-board engine fluids
3
Cooling Standard cooling provides 38C (100F) ambient capability with 500mg/Nm NOx at 100% Continuous
Horizontally mounted radiator with vertical air discharge
Variable frequency drive (VFD) for optimal partial load fuel consumption

Generator Controls Controls provide auto paralleling AGC-4 controller, CAN-bus, ethernet comm, PWM and analog outputs, legacy
and Protection analog load sharing; includes PL1000E gas engine Advisor panel for operational/diagnostic information;
cabinet houses shore power transformer, distribution, protection, and internal/external power selector switch
EMCP 4.2 genset mounted controller
Automatic start/stop with cool down timer
Generator Protection features: 25, 32, 40, 46, 47, 50/51, 27/59, 81 O/U
Reverse compatibility for interface to legacy power modules
3200A IEC rated generator circuit breaker with LSIG trip unit w/ammeter
Multi-mode operation (island, multi-island and utility parallel), load sharing (multi-unit only)
Manual and automatic paralleling capability
Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchroscope

Quality Factory testing of standard generator set and complete power module
UL, NEMA, ISO and IEEE standards
O&M manuals

LEHX0010-02 2
XQ1475G RENTAL
SPECIFICATIONS
GENERATOR CAT G3516C LOW EMISSIONS GAS ENGINE
Frame Size . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . 826 Number of Cylinders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..V16
Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.6667 Bore – mm (in). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170 (6.7)
No. of poles . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . 4 Stroke – mm (in) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 (7.5)
Excitation . . . . . . . . . . . . Static regulated brushless PM excited Displacement – L (cu in) . . . . . . . . . . . . . . . . . . . . . . . . . 69 (4,210)
Constructions . . . . . . . . . . . . . . . Double bearing, close coupled Compression ratio. . . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . . . . 11.3:1
Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class H Engine Speed (rpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drip proof IP22 Aspiration. . . . . . . . . . . . Turbocharged Separate Circuit Aftercooled
Temperature rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 deg C Aftercooler Inlet (deg C) . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . 92
Alignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pilot shaft Jacket Water Outlet (deg C). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Overspeed capability – % of rated . . . . . . . . . . . . 125% of rated Exhaust Manifold . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . Dry
Voltage regulator . . . . . 3 phase sensing with Volts-per-Hertz Fuel system . . . . . . . . . . .Cat Low Pressure w/ Air Fuel Ratio Control
Voltage regulation. . . . . . . . . . . . . Less than ± 0.5% voltage gain Governor type . . . . . . . . . . . . . . . . . Cat ADEM™ A3 Control System
Adjustable to compensate for engine speed droop and line loss Combustion . . . . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . Low Emission
Wave form deviation . . . . . . . . . . . . . . . Less than 3% deviation Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . .. . . . . Natural Gas
Telephone Influence Factor (TIF). . . . . . . . . . . . . . . Less than 50 Fuel Pressure Range (PSI) . . . . . . . . . . . . . .. . . . . . . . .. . . . . . . ..3-7
Harmonic Distortion (THD). . . . . . .. . .. . . . . . . . . Less than 5% Methane Number . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . .. . . 55-100

TECHNICAL DATA*
Generator Set Technical Data Units 50 Hz Continuous

Power Rating ekW 1475


Lubrication System
Lube Oil Refill Volume with filter change for standard sump L (gal) 416 (110)
Fuel System
Fuel Consumption (ISO 3046/1) Max VFD Power (50kW) Min VFD Power (8 kW)
100% load MJ/ekW-hr 9.37 9.09
75% load MJ/ekW-hr 9.66 9.29
50% load MJ/ekW-hr 10.37 9.76
Altitude Capability
At 25° C (77°) ambient, above sea level m (ft) 1500 (4921)
Cooling System
Package ambient capability ° C (° F) 38 (100)
Jacket water temperature (maximum outlet) ° C (° F) 99 (210)
System coolant capacity L (gal) 770 (203)
3
System required airflow m /min (ft³/min) 2209 (77,998)
Exhaust System
3
Combustion air inlet flow rate m /min (ft³/min) 109.2 (3855.8)
Exhaust stack gas temperature ° C (° F) 464 (867)
3
Exhaust gas flow rate Nm /min 116.4
Sound Performance
Noise rating @ 15 m (per SAE J1074) dB(a) 72
Emissions at 100% Load
3
Nox (as NO2)(corr. 5% O2) mg/Nm (dry) 500
3
CO (corr. 5% O2) mg/Nm (dry) 906
3
THC (corr. 5% O2) mg/Nm (dry) 2556
3
NMHC (corr. To 5% O2) mg/Nm (dry) 383
Exhaust O2 % (dry) 10
*Materials and specifications are subject to change without notice.
Reference SRR GR-3500-157-01 For Max VFD Power and SRR GR-3500-158-01 for Min VFD Power Data.

LEHX0010-02 3
XQ1475G RENTAL
METHANE NUMBER OPERATION GUIDELINES**
**This table shows the derate factor required for a given fuel. Note that deration occurs as the methane number decreases. Methane number is a scale to measure
detonation characteristics of various fuels. The methane number of a fuel is determined by using the Cat Methane Number Calculation program.

STANDARD FEATURES
XQ1475G Fuel Usage Guidelines
Cat Methane Number 30 35 40 45 50 55 60 65 70 75 80 85 to 100
Contact Contact Contact Contact Contact
Ignition Timing Factory Factory Factory Factory Factory 20 22 24 28 28 28 28
Contact Contact Contact Contact Contact
Deration Factor Factory Factory Factory Factory Factory 0.9 0.91 0.93 1.00 1.00 1.00 1.00

Altitude XQ1475G 1500rpm (50 Hz) Altitude / Ambient Derate Chart


Meters Feet Switchable Cams & High Ambient Air Intake System
2,400 7,874 84.9% 66.3% 62.0% 61.2% 59.5% 57.9% 56.3% 54.7% 53.0% 42.4% 31.8% 21.2% 10.6% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
2,250 7,382 88.0% 71.6% 66.7% 65.8% 64.1% 62.5% 60.9% 59.2% 57.6% 46.1% 34.6% 23.0% 11.5% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
2,000 6,562 92.0% 79.3% 75.3% 74.4% 72.6% 70.8% 68.9% 67.1% 65.3% 52.2% 39.2% 26.1% 13.1% 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
1,750 5,741 97.1% 85.9% 82.7% 82.1% 80.0% 78.0% 76.0% 73.9% 71.9% 68.8% 65.8% 62.7% 59.7% 56.6% 45.3% 34.0% 22.6% 11.3% 0.0%
1,500 4,921 100.0% 92.7% 89.8% 89.2% 87.3% 85.3% 83.4% 81.5% 79.5% 76.5% 73.4% 70.4% 67.3% 64.2% 56.6% 48.9% 41.3% 33.6% 26.0%
1,250 4,101 100.0% 99.1% 96.8% 96.4% 94.5% 92.7% 90.9% 89.0% 87.2% 84.3% 81.4% 78.5% 75.6% 72.7% 69.3% 65.9% 62.6% 59.2% 55.8%
1,000 3,281 100.0% 100.0% 100.0% 100.0% 100.0% 99.2% 97.8% 96.5% 95.1% 92.0% 89.0% 85.9% 82.8% 79.8% 76.3% 72.8% 69.4% 65.9% 62.4%
900 2,953 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.5% 98.7% 97.9% 94.8% 91.8% 88.7% 85.7% 82.6% 79.1% 75.7% 72.2% 68.7% 65.3%
800 2,625 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 97.9% 94.8% 91.8% 88.7% 85.7% 82.2% 78.7% 75.3% 71.8% 68.3%
700 2,297 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.9% 96.4% 93.8% 91.3% 88.7% 85.1% 81.6% 78.0% 74.4% 70.9%
600 1,969 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 97.9% 95.8% 93.8% 91.8% 88.1% 84.4% 80.8% 77.1% 73.4%
500 1,640 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.9% 97.4% 95.8% 94.3% 90.9% 87.4% 83.9% 80.5% 77.0%
400 1,312 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 98.9% 97.9% 96.9% 93.6% 90.3% 87.1% 83.8% 80.6%
300 984 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 99.4% 96.8% 94.1% 91.5% 88.8% 86.2%
200 656 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 97.9% 95.8% 93.8% 91.8%
100 328 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
0 0 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
Ambient (C) 20 25 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Chart applicable to 1g/bhp-hr operation only.
For derates less than 50%, refer to partial load operation section in OMM.

Altitude XQ1475G 1800rpm (60 Hz) Altitude / Ambient Derate Chart


Meters Feet Switchable Cams & High Ambient Air Intake System
2,400 7,874 84.9% 80.7% 76.8% 76.0% 74.0% 72.1% 70.1% 68.1% 66.1% 56.8% 47.4% 38.0% 28.7% 19.3% 14.8% 10.2% 5.7% 1.1% 0.0%
2,250 7,382 88.0% 83.8% 80.5% 79.8% 77.7% 75.6% 73.5% 71.4% 69.3% 66.1% 63.0% 59.8% 56.6% 53.5% 42.1% 30.7% 19.3% 7.9% 0.0%
2,000 6,562 92.0% 89.7% 86.8% 86.2% 84.0% 81.9% 79.8% 77.7% 75.6% 72.4% 69.3% 66.1% 63.0% 59.8% 47.1% 34.5% 21.8% 9.2% 0.0%
1,750 5,741 97.1% 95.0% 92.1% 91.4% 89.5% 87.6% 85.7% 83.8% 81.9% 78.8% 75.6% 72.4% 69.3% 66.1% 63.0% 59.8% 56.6% 53.5% 50.3%
1,500 4,921 100.0% 100.0% 98.2% 97.7% 95.9% 94.0% 92.1% 90.2% 88.3% 85.3% 82.4% 79.4% 76.5% 73.5% 69.9% 66.3% 62.7% 59.2% 55.6%
1,250 4,101 100.0% 100.0% 100.0% 100.0% 100.0% 99.0% 97.5% 96.1% 94.6% 91.4% 88.3% 85.1% 81.9% 78.8% 75.2% 71.6% 68.0% 64.4% 60.9%
1,000 3,281 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 97.7% 94.6% 91.4% 88.3% 85.1% 81.5% 77.9% 74.3% 70.8% 67.2%
900 2,953 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.6% 95.9% 93.1% 90.4% 87.6% 84.0% 80.3% 76.6% 73.0% 69.3%
800 2,625 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.4% 97.1% 94.8% 92.5% 90.2% 86.4% 82.7% 78.9% 75.1% 71.4%
700 2,297 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.2% 96.3% 94.4% 92.5% 88.8% 85.1% 81.3% 77.6% 73.9%
600 1,969 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.0% 97.5% 96.1% 94.6% 91.0% 87.5% 84.0% 80.4% 76.9%
500 1,640 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.9% 98.8% 97.7% 96.7% 93.3% 89.9% 86.6% 83.2% 79.8%
400 1,312 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.4% 98.8% 95.9% 93.1% 90.2% 87.3% 84.5%
300 984 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 98.6% 96.2% 93.8% 91.5% 89.1%
200 656 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 96.9% 95.2% 93.5%
100 328 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
0 0 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 99.6% 99.0% 98.3% 97.6% 97.0% 96.3%
Ambient (C) 20 25 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Chart applicable to 1g/bhp-hr operation only.
For derates less than 50%, refer to partial load operation section in OMM.

LEHX0010-02 4
XQ1475G RENTAL
OVERALL PACKAGE DERATE GUIDANCE:
To determine the actual package rating at site conditions, one must consider, separately, limitations due to fuel characteristics
and air system limitations. The Fuel Usage Guide deration establishes fuel limitations while the Altitude/Temperature deration
factors and RPC (reference the Cat Methane Program) establish air system limitations. RPC is considered when the
Altitude/Temperature deration is less than 1.0 (100%). Under this condition, add the two factors together. When the site
conditions do not require an Altitude/Temperature derate (factor is 1.0), it is assumed the turbocharger has sufficient capability to
overcome the low fuel relative power and RPC is ignored.

To determine the actual power available, take the lowest rating between 1) and 2) below:

1) Fuel Usage Guide Deration


2) 1-((1-Altitude/Temperature Deration) + (1-RPC))

STANDARD FEATURES

EMCP 4.2 LOCAL CONTROL PANEL AGC-4/EMCP 4.2 PROTECTIVE RELAYING


 Generator mounted EMCP 4.2 provides power  Generator protective features
metering, protective relaying and engine and  25 sync-check ( AGC-4)
generator control and monitoring.  32 rev. power (EMCP 4.2 and AGC-4)
 Convenient service access for Cat service tools  40 loss of excitation (Cat DVR and AGC-4
(not included). impedance based)
 Integration with the Cat DVR provides enhanced  50/51 Inst. and time overcurrent (GCB trip
system monitoring. unit and AGC-4)
 Ability to view and reset diagnostics of all controls  47 Negative Voltage Sequence (AGC-4)
networked on J1939 datalink eliminates need for  46 Negative Sequence Current (AGC-4)
separate service tools for troubleshooting.  27/59 phase under/over voltage (EMCP 4.2
 Real-time clock allows for date and time-stamping and AGC-4)
of diagnostics and events.  81O/U under/over frequency (EMCP 4.2 and
 True RMS AC metering, 3 phase: L-L volts, L-N AGC-4)
volts, Phase, Amps, Hz, ekW, kVA, kVAR, kWHr,  Package mounted AGC-4 controls provides auto
% kW, PF paralleling, CAN-bus, Ethernet communications,
PWM and Analog outputs, and legacy analog
EMCP 4.2 ENGINE OPERATOR INTERFACE load sharing (real and reactive)
 Graphical display with positive image, transflective  AGC-4 main display/ AOP secondary display
LCD, adjustable white backlight/contrast.
 Digital indication for CIRCUIT BREAKER
- RPM - DC Volts  3200A IEC rated, fixed type, 3 poles, genset
- Operating hours - Oil pressure mounted, electrically operated.
- Coolant Temperature - Oil Temperature  Solid state trip unit for overload (time overcurrent)
 Two LED status indicators (1 red, 1 amber) and fault (instantaneous) overcurrent protection.
 Engine cool-down timer LSIG is standard.
 Engine cycle crank  Includes DC shunt trip coil activated on any
 Three engine control keys and status indicators monitored engine or electrical fault and DC
(Run/Auto/Stop). undervoltage release trip coil (UVR), 65 KA-
 Lamp test and Alarm acknowledgement keys interrupting capacity at 480 VAC.
 Warnings/shutdowns with indicating text for:  Ground fault sensing/trip (optional ground CT)
- Low oil pressure - Overspeed
- High Oil Temperature - Overcrank
- Emergency stop - AGC-4
 Emergency stop pushbutton
 Display navigation keys including two shortcut keys
for Engine Parameters or Generator Parameters

LEHX0010-02 5
XQ1475G RENTAL
BUS BARS VOLTAGE REGULATION AND POWER FACTOR
 Three phase, plus full rated neutral, bus bars are CONTROL CIRCUITRY
tin-plated copper with NEMA standard hole pattern  Generator mounted automatic voltage regulator,
for connection of customer load cables and microprocessor based
generator cables.  Manual raise/lower voltage adjust capability and
 Bus bars are sized for full load capacity of the VAR/power factor control circuitry, all via AGC-4,
generator set at 0.8 power factor. for maintaining constant generator power factor
 Includes ground bus, tin-plated copper, for while paralleled with utility
connection to the generator frame ground and field  Includes RFI suppression, exciter limiter and
ground cable. exciter diode monitoring

CURRENT TRANSFORMERS
CONTAINER  CT’s rated 3500:5 with secondary wired to
 40’ ISO high cube container, CSC 9-High Stack shorting terminal strip protection
Certified
 Painted standard Cat Power Module White per AC DISTRIBUTION
Caterpillar Specifications  50/60 Hz Transformer distributes utility voltage or
 Standard air intake louvers customer supplied line voltage, which is
 Three (3) lockable personnel doors with panic selectable via onboard switch, for the Power
release Module AC auxiliaries .
 Fire extinguisher  Provides 240/120 VAC for all module accessories
 LH and RH engine service panels integrated into except Jacket water heater (400V). Includes
container side walls controls to de-energize jacket water heaters and
 110% spill containment system for on-board engine generator space heater when the engine is
fluids running

INTERNAL LIGHTING MODES OF OPERATION


 Six (6) compact LED type internal DC lights with  Provides for single unit stand-alone operation,
timers located at each personnel door island mode paralleling and load sharing with
 One (1) duplex service receptacle other power modules, and single unit-to-utility
mode paralleling for base load control (with open
BATTERY CHARGER AND BATTERIES transition between paralleling modes)*
 24 VDC/20A battery charger with float/equalize  Island mode paralleling features:
modes and charging ammeter  AGC-4 control allows single unit to connect
 Four oversized maintenance free batteries to a dead bus
 Auto synchronization (voltage & phase
EMERGENCY STOP PUSHBUTTON matching)
 Single emergency stop pushbuttons (ESP) located  Load sharing (kW) analog signal (like units &
on rear face of generator set controls area legacy compatible)
 Load sharing (kVAR) analog signal (like units
EXHAUST SILENCER only)
 Critical grade, internally mounted rectangular  Utility mode paralleling features:
exhaust silencers with vertical discharge  Auto synchronization (voltage & phase
 2 m high vertical discharging exhaust stack located matching)
in radiator discharge area  Base-load control (selectable: programmable
set-point or potentiometer adjust)
TRAILER (optional)  Soft load/unload (programmable, shared set-
 Three axle with Anti-lock brake system point)
 Goodyear G314 295/75R225 Load Range G  Power Factor control (programmable set-
point)

LEHX0010-02 6
XQ1475G RENTAL
RATING DEFINITIONS AND CONDITIONS
Continuous — Output available without varying load for an unlimited time. Continuous power is in accordance with ISO8528,
AS2789, and BS5514. Fuel stop power is in accordance with ISO03036. Natural gas ratings have been established on natural
gas with net calorific Low Heat Value (LHV) of approximately 35.6 MJ/Nm3 (905 Btu/cu ft) and 80 Methane Number (MN). For
values in excess of altitude, ambient temperature, inlet/exhaust restriction, or different from the conditions listed, contact your
local Cat dealer.

WEIGHTS AND DIMENSIONS

Length Width Height Weight with Lube oil and Coolant


Model
mm (in) mm (in) mm (in) kg (lb)

XQ1475G 12192 (480) 2438 (96) 2896 (114) 31,920 (70,372)

LEHX0010-02 7
XQ1475G RENTAL
EQUIPMENT LAYOUT

LEHX0010-02 8
XQ1475G RENTAL

Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the “Power Edge” trade dress as well as corporate
and product identify used herein, are trademarks of Caterpillar and may not be used without permission

www.Cat-ElectricPower.com
©2013 Caterpillar.
All rights reserved.

LEHX0010-02 (09/13)
LEHX0010-02 9