XQ1475G-50 HZ Spec Sheet
XQ1475G-50 HZ Spec Sheet
XQ1475G-50 HZ Spec Sheet
CONTINUOUS 1475 kW
50 Hz
Frequency Voltage Continuous
(Hz) (V) kW (kVA)
50 Hz 400/230V 1475 (1844)
Generator Double bearing SR-4B brushless, form wound, permanent magnet excited, three-phase with Cat digital voltage
regulator (Cat DVR), space heater, 6-lead design, Class H insulation operating at Class F temperature for
extended life, winding temperature detectors and anti-condensation space heaters (120/240V 1.2 kW).
Generator equipped with System 4 insulation protection.
Containerized Module 40' ISO high cube container, 9-high stack CSC certified
Four (4) sound attenuated air intake louvers and 3 lockable personnel doors with panic release
Interior walls and ceilings insulated with 100 mm of acoustic paneling
Floor of container is undercoated for corrosion protection
Side bus bar access door, external access load connection bus bars
Shore power connection via distribution block connections for jacket water heater, battery charger, generator
space heaters, and generator condensate heaters
Six (6) DC lights
3” ANSI flange customer fuel connection with cover to prevent vandalism
Energized-to-run (ETR) shutoff valve (double solenoid, low/high pressure switch, CSA/FM approved)
Cat Brand fuel filter, wall mounted and gas pressure regulator
Lube oil level regulator with makeup tank
Sound attenuated 72 dB(A) @ 15 m (50 ft)
Four (4) oversized maintenance-free batteries, battery rack and 20-Amp battery charger
Critical grade exhaust silencer with vertical discharge and single 2 m (6.5 ft.) stack
Vibration isolators, stainless steel fastening hardware and hinges
External drain access to standard fluids
One 4.5 kg (10 lb) carbon dioxide fire extinguisher
Standard Cat rental decals and painted standard Cat power module white
LH and RH engine service panels integrated into container side walls
110% spill containment system for on-board engine fluids
3
Cooling Standard cooling provides 38C (100F) ambient capability with 500mg/Nm NOx at 100% Continuous
Horizontally mounted radiator with vertical air discharge
Variable frequency drive (VFD) for optimal partial load fuel consumption
Generator Controls Controls provide auto paralleling AGC-4 controller, CAN-bus, ethernet comm, PWM and analog outputs, legacy
and Protection analog load sharing; includes PL1000E gas engine Advisor panel for operational/diagnostic information;
cabinet houses shore power transformer, distribution, protection, and internal/external power selector switch
EMCP 4.2 genset mounted controller
Automatic start/stop with cool down timer
Generator Protection features: 25, 32, 40, 46, 47, 50/51, 27/59, 81 O/U
Reverse compatibility for interface to legacy power modules
3200A IEC rated generator circuit breaker with LSIG trip unit w/ammeter
Multi-mode operation (island, multi-island and utility parallel), load sharing (multi-unit only)
Manual and automatic paralleling capability
Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchroscope
Quality Factory testing of standard generator set and complete power module
UL, NEMA, ISO and IEEE standards
O&M manuals
LEHX0010-02 2
XQ1475G RENTAL
SPECIFICATIONS
GENERATOR CAT G3516C LOW EMISSIONS GAS ENGINE
Frame Size . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . 826 Number of Cylinders. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..V16
Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.6667 Bore – mm (in). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170 (6.7)
No. of poles . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . .. . . . . . . . 4 Stroke – mm (in) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 (7.5)
Excitation . . . . . . . . . . . . Static regulated brushless PM excited Displacement – L (cu in) . . . . . . . . . . . . . . . . . . . . . . . . . 69 (4,210)
Constructions . . . . . . . . . . . . . . . Double bearing, close coupled Compression ratio. . . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . . . . 11.3:1
Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class H Engine Speed (rpm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Drip proof IP22 Aspiration. . . . . . . . . . . . Turbocharged Separate Circuit Aftercooled
Temperature rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 deg C Aftercooler Inlet (deg C) . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . 92
Alignment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pilot shaft Jacket Water Outlet (deg C). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Overspeed capability – % of rated . . . . . . . . . . . . 125% of rated Exhaust Manifold . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . Dry
Voltage regulator . . . . . 3 phase sensing with Volts-per-Hertz Fuel system . . . . . . . . . . .Cat Low Pressure w/ Air Fuel Ratio Control
Voltage regulation. . . . . . . . . . . . . Less than ± 0.5% voltage gain Governor type . . . . . . . . . . . . . . . . . Cat ADEM™ A3 Control System
Adjustable to compensate for engine speed droop and line loss Combustion . . . . . . . . . . . . . . . . . . . . . . . .. . .. . . . . . . . Low Emission
Wave form deviation . . . . . . . . . . . . . . . Less than 3% deviation Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . .. . . . . Natural Gas
Telephone Influence Factor (TIF). . . . . . . . . . . . . . . Less than 50 Fuel Pressure Range (PSI) . . . . . . . . . . . . . .. . . . . . . . .. . . . . . . ..3-7
Harmonic Distortion (THD). . . . . . .. . .. . . . . . . . . Less than 5% Methane Number . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . .. . . 55-100
TECHNICAL DATA*
Generator Set Technical Data Units 50 Hz Continuous
LEHX0010-02 3
XQ1475G RENTAL
METHANE NUMBER OPERATION GUIDELINES**
**This table shows the derate factor required for a given fuel. Note that deration occurs as the methane number decreases. Methane number is a scale to measure
detonation characteristics of various fuels. The methane number of a fuel is determined by using the Cat Methane Number Calculation program.
STANDARD FEATURES
XQ1475G Fuel Usage Guidelines
Cat Methane Number 30 35 40 45 50 55 60 65 70 75 80 85 to 100
Contact Contact Contact Contact Contact
Ignition Timing Factory Factory Factory Factory Factory 20 22 24 28 28 28 28
Contact Contact Contact Contact Contact
Deration Factor Factory Factory Factory Factory Factory 0.9 0.91 0.93 1.00 1.00 1.00 1.00
LEHX0010-02 4
XQ1475G RENTAL
OVERALL PACKAGE DERATE GUIDANCE:
To determine the actual package rating at site conditions, one must consider, separately, limitations due to fuel characteristics
and air system limitations. The Fuel Usage Guide deration establishes fuel limitations while the Altitude/Temperature deration
factors and RPC (reference the Cat Methane Program) establish air system limitations. RPC is considered when the
Altitude/Temperature deration is less than 1.0 (100%). Under this condition, add the two factors together. When the site
conditions do not require an Altitude/Temperature derate (factor is 1.0), it is assumed the turbocharger has sufficient capability to
overcome the low fuel relative power and RPC is ignored.
To determine the actual power available, take the lowest rating between 1) and 2) below:
STANDARD FEATURES
LEHX0010-02 5
XQ1475G RENTAL
BUS BARS VOLTAGE REGULATION AND POWER FACTOR
Three phase, plus full rated neutral, bus bars are CONTROL CIRCUITRY
tin-plated copper with NEMA standard hole pattern Generator mounted automatic voltage regulator,
for connection of customer load cables and microprocessor based
generator cables. Manual raise/lower voltage adjust capability and
Bus bars are sized for full load capacity of the VAR/power factor control circuitry, all via AGC-4,
generator set at 0.8 power factor. for maintaining constant generator power factor
Includes ground bus, tin-plated copper, for while paralleled with utility
connection to the generator frame ground and field Includes RFI suppression, exciter limiter and
ground cable. exciter diode monitoring
CURRENT TRANSFORMERS
CONTAINER CT’s rated 3500:5 with secondary wired to
40’ ISO high cube container, CSC 9-High Stack shorting terminal strip protection
Certified
Painted standard Cat Power Module White per AC DISTRIBUTION
Caterpillar Specifications 50/60 Hz Transformer distributes utility voltage or
Standard air intake louvers customer supplied line voltage, which is
Three (3) lockable personnel doors with panic selectable via onboard switch, for the Power
release Module AC auxiliaries .
Fire extinguisher Provides 240/120 VAC for all module accessories
LH and RH engine service panels integrated into except Jacket water heater (400V). Includes
container side walls controls to de-energize jacket water heaters and
110% spill containment system for on-board engine generator space heater when the engine is
fluids running
LEHX0010-02 6
XQ1475G RENTAL
RATING DEFINITIONS AND CONDITIONS
Continuous — Output available without varying load for an unlimited time. Continuous power is in accordance with ISO8528,
AS2789, and BS5514. Fuel stop power is in accordance with ISO03036. Natural gas ratings have been established on natural
gas with net calorific Low Heat Value (LHV) of approximately 35.6 MJ/Nm3 (905 Btu/cu ft) and 80 Methane Number (MN). For
values in excess of altitude, ambient temperature, inlet/exhaust restriction, or different from the conditions listed, contact your
local Cat dealer.
LEHX0010-02 7
XQ1475G RENTAL
EQUIPMENT LAYOUT
LEHX0010-02 8
XQ1475G RENTAL
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the “Power Edge” trade dress as well as corporate
and product identify used herein, are trademarks of Caterpillar and may not be used without permission
www.Cat-ElectricPower.com
©2013 Caterpillar.
All rights reserved.
LEHX0010-02 (09/13)