Anchorage Detail

The document provides design details for the anchorage of post-tensioning tendons in a concrete beam. It includes details of the tendon force, concrete grade, reinforcement details, prestressing strand details, local and general zone designs, and checks for bearing resistance, bursting resistance, edge tension forces, and spalling resistance. All design checks were found to be satisfactory and within code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
427 views3 pages

Anchorage Detail

The document provides design details for the anchorage of post-tensioning tendons in a concrete beam. It includes details of the tendon force, concrete grade, reinforcement details, prestressing strand details, local and general zone designs, and checks for bearing resistance, bursting resistance, edge tension forces, and spalling resistance. All design checks were found to be satisfactory and within code requirements.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

33m box

402
375

375
Fig. Anchorage Details

Tendon force applied, Pu = 2343 kN


Design forces due to jacking = 2812 kN (Cl. 3.4.3.2)
Web inclination = 69.00 degree
Web thickness = 500 mm
Web height = 2300 mm
No of anchorages in web =4 nos.
C/C anchorage = 402 mm
< 2 aeff, closely spaced

Material details
Concrete details:
Concrete grade = M45
Reinforcement details:
Grade of reinforcement = Fe500
Stress in steel = 500 MPa

Prestressing strand details


Typical cable identification 19T15
Duct dia including sheathing = 107.00 mm
Width of anchorage plate = 250.00 mm
Depth of anchorage plate = 300.00 mm
Minimum clear cover = 75.00 mm
Clear distance between cables = 107.00 mm
Effective cover for anchorage = 235.00 mm
Effective depth of anchorage = 500.00 mm
Effective width of anchorage = 500.00 mm
Exit angle = 8.98 degree
Ultimate tensile strength f pk = 1860.00 MPa
Modulus of elasticity = 195.00 GPa

Local Zone Design


Width of local zone = 470 mm (Cl. 5.10.9.7.1)
Depth of local zone = 402 mm
Length of local zone = 705 mm
a) Bearing Resistance

Resistance factor, Φ = 0.70 (Cl. 5.5.4.2.1)


2
Gross area of the bearing plate, Ag = 75000 mm
Maximum loaded area, A = 200840 mm2
Net area of the bearing plate, Ab = 66008 mm2
Nominal concrete strength = 45 MPa
fn is the lesser of: a. 0.7 fci' √(A/Ag) = 52 MPa (Cl. 5.10.9.7.2-2)
b. 2.25 fci' = 101 MPa (Cl. 5.10.9.7.2-3)
Factored bearing resistance of anchorages = 2382 kN (Cl. 5.10.9.7.2-1)
Safe in bearing
General Zone Design
Width of general zone = 500 mm (Cl. 5.10.9.7.1)
Depth of anchorage zone = 2300 mm
Length of general zone = 3450 mm

a) Compressive force
Compression check of concrete compressive stresses is not required for basic anchorage (C5.10.9.6.2)
devices satisfying bearing resistance.

b) Bursting Resistance

402
a' = 102 mm
1.5 x a' = 153 mm
300 102 300 Design for single anchorage
Along web
Resistance factor, Φ = 0.90
Lateral dimension of anchorage device, a = 250 mm
Depth of the bursting zone, b = 402
Lateral dimension of in considered direction, h = 500 mm
Cable eccentricity =0 mm
Location of bursting force, dburst = 250 mm (Eq. 5.10.9.6.3-2)
Bursting force in anchorage zone, T burst = 571 kN OK
Stress in steel, fs = 140 MPa (Cl. 5.10.10.1)
Required area of steel, As = 4078 mm2 (Eq. 5.10.9.6.3-1)
Extent of bursting rebar, lc = 625 mm (C5.10.9.3.2-1)
Diameter of spirals bars = 16 mm
Pitch = 50 mm
Provided area of steel = 5027 mm2 OK
Diameter of spirals = 350 mm (C5.10.9.6.3-1)

c) Edge Tension Forces


0.4 x Depth of the section = 900 mm
Design for multiple Anchorage

Edge tension force = 703 kN


Area of steel required = 1406 mm2
Diameter of bars = 20 mm
Nos. =5 mm
Provided area of steel = 1571 mm2 OK

d) Spalling Resistance
Spalling force = 56 kN (Cl. 5.10.9.3.2)
Area of steel required = 112 mm2
Diameter of bars = 16 mm
Nos. =2 mm
Provided area of steel = 402 mm2 OK