SH5.0RT / SH6.0RT / SH8.0RT / SH10RT: User Manual 3-Phase Hybrid Inverter
SH5.0RT / SH6.0RT / SH8.0RT / SH10RT: User Manual 3-Phase Hybrid Inverter
SH5.0RT / SH6.0RT / SH8.0RT / SH10RT: User Manual 3-Phase Hybrid Inverter
User Manual
SH5.0RT / SH6.0RT / SH8.0RT / SH10RT
WWW.SUNGROWPOWER.COM SH5.0_6.0_8.0_10RT-UEN-Ver12-202007
All Rights Reserved
I
About This Manual
The manual mainly describes the product information, guidelines for installation,
operation and maintenance. The manual cannot include complete information about the
photovoltaic (PV) system. The reader can get additional information about other devices
at w w w . s u n g r o w p o w e r . c o m or on the webpage of the respective component
manufacturer.
Validity
This manual is valid for the following inverter models:
• SH5.0RT
• SH6.0RT
• SH8.0RT
• SH10RT
• qualified personnel who are responsible for the installation and commissioning of the
inverter; and
• inverter owners who will have the ability to interact with the inverter.
How to Use This Manual
Read the manual and other related documents before performing any operation on the
inverter. Documents must be stored carefully and be available at all times.
Contents may be periodically updated or revised due to product development. The
information in this manual is subject to change without notice. The latest manual can be
acquired at h t t p : / / s u p p o r t . s u n g r o w p o w e r . c o m / .
Symbols
Safety instructions will be highlighted with the following symbols.
Symbol Explanation
Indicates a hazard with a high level of risk that, if not avoided, will
result in death or serious injury.
Indicates a hazard with a medium level of risk that, if not avoided,
could result in death or serious injury.
Indicates a hazard with a low level of risk that, if not avoided, could
result in minor or moderate injury.
II
Symbol Explanation
Indicates a situation that, if not avoided, could result in equipment or
property damage.
III
Contents
All Rights Reserved .....................................................................................................I
About This Manual .....................................................................................................II
1 Safety .............................................................................................................. 1
1.1 PV Panels..................................................................................................... 1
1.2 Utility Grid .................................................................................................... 1
1.3 Inverter ........................................................................................................ 2
1.4 Batteries ...................................................................................................... 3
1.5 Skills of Qualified Personnel.......................................................................... 4
2 System Solution ........................................................................................... 5
2.1 Product Introduction..................................................................................... 5
2.1.1 Model Description............................................................................... 5
2.1.2 Appearance........................................................................................ 6
2.1.3 Dimensions ........................................................................................ 6
2.1.4 LED Indicator...................................................................................... 6
2.1.5 DC Switch........................................................................................... 7
2.2 PV Energy Storage System (PV ESS)............................................................ 7
2.3 Retrofitting the Existing PV System ............................................................. 11
3 Function Description ................................................................................ 13
3.1 Safety Function.......................................................................................... 13
3.1.1 Protection......................................................................................... 13
3.1.2 Earth Fault Alarm.............................................................................. 13
3.2 Energy Conversion and Management......................................................... 13
3.2.1 Power Derating................................................................................. 13
3.2.2 DRM (“AU”/“NZ”)...................................................................... 14
3.2.3 Regular Operational Voltage Range .................................................. 14
3.2.4 Regular Operational Frequency Range.............................................. 15
3.2.5 Reactive Power Regulation ............................................................... 15
3.2.6 Load Control..................................................................................... 15
3.3 Battery Management.................................................................................. 15
3.3.1 Charge Management........................................................................ 16
3.3.2 Discharge Management ................................................................... 17
V
3.4 Communication and Configuration ............................................................. 18
4 Unpacking and Storage ........................................................................... 19
4.1 Unpacking and Inspection .......................................................................... 19
4.2 Identifying the Inverter ................................................................................ 19
4.3 Scope of Delivery ....................................................................................... 21
4.4 Inverter Storage ......................................................................................... 21
5 Mechanical Mounting .............................................................................. 23
5.1 Safety during Mounting .............................................................................. 23
5.2 Location Requirements .............................................................................. 23
5.2.1 Installation Environment Requirements ............................................. 23
5.2.2 Carrier Requirements........................................................................ 24
5.2.3 Installation Angle Requirements ........................................................ 24
5.2.4 Installation Clearance Requirements ................................................. 24
5.3 Installation Tools......................................................................................... 25
5.4 Moving the Inverter .................................................................................... 26
5.5 Installing the Inverter .................................................................................. 27
6 Electrical Connection ............................................................................... 29
6.1 Safety Instructions...................................................................................... 29
6.2 Terminal Description................................................................................... 29
6.3 Electrical Connection Overview .................................................................. 31
6.4 Additional Grounding Connection ............................................................... 34
6.4.1 Additional Grounding Requirements.................................................. 34
6.4.2 Connection Procedure ...................................................................... 34
6.5 AC Cable Connection ................................................................................. 35
6.5.1 AC Side Requirements ...................................................................... 35
6.5.2 Assembling the AC Connector .......................................................... 36
6.5.3 Installing the AC Connector............................................................... 37
6.6 DC Cable Connection ................................................................................. 39
6.6.1 PV Input Configuration ...................................................................... 40
6.6.2 DC Side Requirements...................................................................... 41
6.6.3 Assembling the PV Connector........................................................... 41
6.6.4 Installing the PV Connector ............................................................... 42
6.7 Communication Connection ....................................................................... 43
6.7.1 Ethernet Connection ......................................................................... 44
6.7.2 WLAN Connection ............................................................................ 46
6.7.3 RS485 Connection ........................................................................... 47
VI
6.8 Smart Energy Meter Connection................................................................. 49
6.9 Battery Connection..................................................................................... 50
6.9.1 Connecting the Power Cable............................................................. 50
6.9.2 Connecting the CAN Cable ............................................................... 52
6.9.3 Connecting the Enable Cable............................................................ 52
6.10 DO Connection......................................................................................... 53
6.11 DI/DRM Connection ................................................................................. 54
6.11.1 Assembling the COM Connector ..................................................... 55
6.11.2 Installing the COM Connector ......................................................... 57
6.12 Backup Connection.................................................................................. 58
7 Commissioning ........................................................................................... 60
7.1 Inspection before Commissioning............................................................... 60
7.2 Commissioning Procedure ......................................................................... 60
8 iSolarCloud App ......................................................................................... 61
8.1 Brief Introduction........................................................................................ 61
8.2 Download and Install .................................................................................. 61
8.3 Login ......................................................................................................... 62
8.3.1 Requirements ................................................................................... 62
8.3.2 Login Steps ...................................................................................... 62
8.4 Initial Settings ............................................................................................. 64
8.4.1 Feed-in Limitation............................................................................. 64
8.4.2 Off-grid Mode .................................................................................. 64
8.4.3 Reactive Power Regulation Mode ..................................................... 64
8.5 Function Overview ..................................................................................... 67
8.6 Home......................................................................................................... 68
8.7 Run Information ......................................................................................... 69
8.8 Records ..................................................................................................... 70
8.8.1 Chart ................................................................................................ 70
8.8.2 Fault Alarm Record........................................................................... 71
8.9 More .......................................................................................................... 71
8.9.1 System Parameters .......................................................................... 72
8.9.2 Running Time ................................................................................... 73
8.9.3 Regular Parameters.......................................................................... 73
8.9.4 Off-grid Parameters.......................................................................... 74
8.9.5 Active Power Regulation ................................................................... 74
8.9.6 Reactive Power Regulation ............................................................... 75
VII
8.9.7 Battery Discharge Time..................................................................... 75
8.9.8 Battery Forced Charge Time ............................................................. 76
8.9.9 Load Regulation ............................................................................... 76
8.9.10 Communication Parameters ........................................................... 78
8.9.11 Firmware Update............................................................................ 79
8.9.12 Grounding Detection....................................................................... 80
9 System Decommissioning ...................................................................... 81
9.1 Decommissioning the Inverter .................................................................... 81
9.1.1 Disconnecting the Inverter ................................................................ 81
9.1.2 Dismantling the Inverter .................................................................... 82
9.1.3 Disposal of the Inverter ..................................................................... 82
9.2 Decommissioning the Battery ..................................................................... 83
10 Troubleshooting and Maintenance ................................................... 84
10.1 Troubleshooting ....................................................................................... 84
10.2 Maintenance ............................................................................................ 89
10.2.1 Routine Maintenance...................................................................... 89
10.2.2 Replacing the Button Cell ................................................................ 90
11 Appendix .................................................................................................... 91
11.1 Technical Data ......................................................................................... 91
11.2 Quality Assurance .................................................................................... 95
11.3 Contact Information ................................................................................. 96
VIII
1 Safety
The inverter has been designed and tested strictly according to international safety
regulations. Read all safety instructions carefully prior to any work and observe them at
all times when working on or with the inverter.
Incorrect operation or work may cause:
All detailed work-related safety warnings and notes will be specified at critical points in
corresponding chapters.
• The safety instructions in this manual cannot cover all the precautions that
should be followed. Perform operations considering actual onsite
conditions.
• SUNGROW shall not be held liable for any damage caused by violation of
the safety instructions in this manual.
1.1 PV Panels
PV strings will produce electrical power when exposed to sunlight and can
cause a lethal voltage and an electric shock.
• Always keep in mind that the inverter is dual power supplied. Electrical
operators must wear proper personal protective equipment: helmet,
insulated footwear, gloves, etc.
• The opeator must follow all warnings on the PV strings and in its manual.
1
1 Safety User Manual
1.3 Inverter
• Do not open the enclosure at any time. Unauthorized opening will void
warranty and warranty claims and in most cases terminate the operating
license.
• Wait at least 10 minutes for the internal capacitors to discharge after the
battery is powered off. Ensure that there is no voltage or current before
disconnecting any connectors.
2
User Manual 1 Safety
Warning Label
Label Description
1.4 Batteries
Batteries deliver electric power, resulting in burns or a fire hazard when they are
short circuited, or wrongly installed.
Lethal voltages are present at the battery terminals and cables connecting to
the inverter. Severe injuries or death may occur if the cables and terminals in the
inverter are touched.
3
1 Safety User Manual
4
2 System Solution
The inverter must only be operated with PV strings with class II protection in
accordance with IEC 61730, application class A. It is not allowed for the positive
pole or the negative pole of the PV strings or battery to be grounded. This can
cause the inverter to be destroyed.
Damages to the product due to a faulty or damaged PV installation are not
covered by warranty.
Any use other than the one described in this document is not permitted.
For the TT utility grid, the N line voltage to ground must be 30 V or less.
The three-phase hybrid inverters are applicable to both on-grid and off-grid PV systems.
With the integrated Energy Management System (EMS) , they can control and optimize
the energy flow so as to increase the self-consumption of the system.
5
2 System Solution User Manual
2.1.2 Appearance
F i g u r e 2 - 1 Appearance
* The image shown here is for reference only. The actual product received may differ.
2.1.3 Dimensions
The LED indicator on the front of the inverter can indicate the current working state of
the inverter.
6
User Manual 2 System Solution
2.1.5 DC Switch
Turn the DC switch to the “ON” position before restarting the inverter.
By directly connecting a battery module to the inverter, the conventional PV system can
be upgraded to be an Energy Storage System (ESS).
The system is capable of operating off-grid to ensure an emergency power supply for
protected loads in the event of a grid interruption or blackout, which may be caused by:
• islanding;
• under-voltage or over-voltage;
• under-frequency or over-frequency.
7
2 System Solution User Manual
For the TT utility grid, the N line voltage to ground must be 30 V or less.
The utility grid must be a TN system for the off-grid application. Especially when
the utility grid is TN-C system, N line and PE line need to be short circuited
externally when the inverter works as off-grid application.
The system is not suitable for supplying life-sustaining medical devices. It
cannot guarantee backup power in all circumstances.
1 For hybrid inverters, the electrical installation typically includes connection of the
inverter to both PV modules and batteries. If there is no available power from
batteries or PV modules in backup mode, the backup power supply will be
8
User Manual 2 System Solution
2 Normally, the Back-Up switching time is less than 20ms. However, some external
factors may cause the system to fail on Back-Up mode. Therefore, the users must
be aware of conditions and follow the instructions as below:
• Do not connect loads that are dependent on a stable energy supply for a reliable
operation.
• Do not connect the loads whose total capacity is greater than the maximum Back-
Up capacity.
• Do not connect the loads that may cause very high start-up current surges, such as
air-conditioner, high-power pump, and hair drier.
• Due to the condition of the battery itself, battery current might be limited by some
factors, including but not limited to the temperature and weather.
Declaration For Back-Up Overload Protection
The inverter will restart in case of overload protection. The time required for restarting
will increase (5min at most) if overload protection repeats. Try to reduce Back-Up load
power within maximum limitation or remove the loads which may cause very high start-
up current surges.
Energy Management
The battery discharges to provide energy to loads. If the battery is empty or there is not
enough power from the battery system, the grid shall supply the power, first to Backup
loads, then normal loads.
When the grid is present, the bypass function of the hybrid inverter is activated and the
Backup loads will be directly connected to the grid via the bypass switch integrated in
the inverter.
If the Smart Energy Meter is abnormal or not equipped, the inverter will run normally,
however, the battery can be charged but not allowed to discharge. In this case the feed-
in power setting will be ineffective, and the DO function for optimized mode will be
disabled.
Energy Management during Daytime
The energy management system (EMS) works in self-consumption mode by default.
– First,PV power will go to Backup loads first, then normal loads and the battery.
– Moreover,If the battery is fully charged, the excess will go to the grid. The feed-
in power will not surpass the feed-in limitation value in initial settings.
– Moreover,inverter will draw power from the mains if the power from the PV and
battery is less than the load power.
9
2 System Solution User Manual
During night, when the battery is empty, it will enter into standby mode. In this case, the
grid will supply all power for loads.
10
User Manual 2 System Solution
Note:
1 In zero-export scenario, the hybrid inverter can only ensure no power exported to
grid itself but does not ensure zero export for the PV inverter. Please contact the PV
inverter manufacturer for its zero-export solution.
11
2 System Solution User Manual
12
3 Function Description
Several protective functions are integrated in the inverter, including short circuit
protection, grounding insulation resistance surveillance, residual current protection, anti-
islanding protection, DC overvoltage / over-current protection, etc.
The inverter has integrated a multiple-function dry-contact (DO relay), which can be
used for the external alarm for earth fault. The external alarm needs to be powered by
the grid.
The additional equipment required is a light indicator and/or a buzzer.
If an earth fault occurs:
• the DO dry-contact will switch on automatically to signal the earth fault alarm;
• the Ethernet communication port can be used for transmitting the alarm remotely.
The inverter converts the DC power from the PV array or the battery to the AC power, in
conformity with the grid requirements. It also transmits the DC power from the PV panel
to the battery.
With the bidirectional converter integrated inside, the inverter can charge or discharge
the battery.
Two string MPP trackers are used to maximize the power from PV strings with different
orientations, tilts, or module structures.
Power derating is a way to protect the inverter from overload or potential faults. In
addition, the derating function can also be activated following the requirements of the
utility grid. Situations requiring inverter power derating are:
• grid under-voltage
• grid over-frequency
13
3 Function Description User Manual
• high altitude
The inverter provides a terminal block for connecting to a demand response enabling
device (DRED). The DRED asserts demand response modes (DRMs). The inverter
detects and initiates a response to all supported demand response commands within 2s.
For the connections, see "6.11 DI/DRM Connection".
The following table lists the DRMs supported by the inverter.
Mode Explanation
DRM0 The inverter is in the state of “Turn off”.
DRM1 The import power from the grid is 0.
The import power from the grid is no more than 50 % of the rated
DRM2
power.
The import power from the grid is no more than 75 % of the rated
DRM3
power.
The import power from the grid is 100 % of the rated power, but
DRM4
subject to the constraints from other active DRMs.
DRM5 The feed-in power to the grid is 0.
DRM6 The feed-in power to the grid is no more than 50 % of the rated power.
DRM7 The feed-in power to the grid is no more than 75 % of the rated power.
The feed-in power to the grid is 100 % of the rated power, but subject
DRM8
to the constraints from other active DRMs.
The DRED may assert more than one DRM at a time. The following shows the priority
order in response to multiple DRMs.
The inverters can operate within the allowable voltage range for at least the specified
observation time. The setting of the conditions depends on whether the connection is
due to a normal operational start-up or an automatic reconnection after tripping of the
interface protection.
When the voltage level is out of the operational levels, the inverter will disconnect from
the grid within the protection time. If a disturbance lasts less than the required protection
time, the inverter can reconnect to the grid once the voltage level goes back to normal
levels after the disturbance.
14
User Manual 3 Function Description
The inverter can operate within its frequency range for at least the specified observation
time. The setting of conditions depends on whether the connection is due to a normal
operational start-up or an automatic reconnection after tripping of the interface
protection.
When the frequency level is outside the operational levels, the inverter will disconnect
from the grid. If a disturbance lasts less than the required protection time, the inverter
can reconnect to the grid once the frequency level goes back to normal levels after the
disturbance.
The inverter is capable of operating in reactive power regulation modes for the purpose
of providing support to the grid. The reactive power regulation mode can be set via the
iSolarCloud App. For details, see "8.4.3 Reactive Power Regulation Mode".
The inverter has an integrated multiple-function dry-contact (DO relay), which can be
used for load control via a contactor. Refer to "6.10 DO Connection" for the cable
connection.
User may set the control mode according to individual demand. Refer to "8.9.9 Load
Regulation" for iSolarCloud App settings.
T i m i n g M o d e : Set the starting time and end time. The DO function will be enabled
during the time interval.
S w i t c h M o d e : The DO function can be enabled or disabled.
I n t e l l i g e n t M o d e : Set the starting time, end time, and the optimized power. During the
interval, when the export power reaches to the optimized power, the DO function will be
enabled.
Li-ion battery from LG and BYD are compatible with the PV ESS,further battery models
will be made compatible in the furture.
To maximize the battery life, the inverter will perform battery charge, discharge, and
battery maintenance based on the battery status communicated by the BMS.
15
3 Function Description User Manual
State Definition
In order to avoid overcharging or deep discharging of the battery, three battery statuses
according to different voltage ranges has been defined, as shown in the following table.
In the off-grid state, the LG battery can only supply power to loads of maximum 5KW.
For the first operation of the inverter with LG battery, either PV or grid needs to power
the inverter to activate the LG battery.
The SOC limits of Li-ion batteries can be modified via the iSolarCloud App by qualified
personnel.
16
User Manual 3 Function Description
Status Conditions
Either of the following conditions is met:
• SOC ≤ (Min. SOC) – 3% (valid only when the Min. SOC is ≥ 3 %).
Trigger
• A battery under-voltage warning is triggered.
• SOC ≥ (Min. SOC) – 1% (valid only when the Min. SOC is ≥ 3 %).
Finish • The battery under-voltage warning is cleared.
Table 3-4 Default SOC Conditions for Li-ion Battery Backup Charge
For this reason, the battery charge power may not reach the nominal power.
• If the PV voltage is higher than the upper limit value of MPP voltage (1000
V), the battery cannot charge.
• The hybrid inverter will start to charge the battery when the export power
value exceeds a pre-defined threshold value of 70 W.
Discharge management can effectively protect the battery from deep discharging.
The maximum allowable discharge current is limited to the smaller value among the
following:
17
3 Function Description User Manual
For this reason, the battery discharge power may not reach the nominal power.
• If the PV voltage is higher than the upper limit value of MPP voltage 1000 V,
the battery cannot discharge.
• The hybrid system will start to discharge the battery when the import power
value exceeds a threshold value of 70 W.
The inverter provides various ports for device and system monitoring, including RS485,
Ethernet, WLAN, and CAN; various parameters can be configured for optimal operation.
All the inverter information is accessible through the iSolarCloud App.
18
4 Unpacking and Storage
The inverter is thoroughly tested and strictly inspected before delivery. Damage may still
occur during shipping. For this reason, please conduct a thorough inspection after
receiving the device.
• Check the scope of delivery for completeness according to the packing list.
The nameplate can be found on both the inverter and the packing case. It provides
information on model of inverter, important specifications, marks of certification
institutions, and serial numbers which are available and identified by SUNGROW. Take
SH10RT as an example.
19
4 Unpacking and Storage User Manual
F i g u r e 4 - 1 Nameplate of Inverters
* The image shown here is for reference only. The actual product received may differ.
Item Description
1 SUNGROW logo and product model
2 Technical data of inverter
3 Instructions and marks of conformity
4 Company name, website and country of manufacture
Icon Description
20
User Manual 4 Unpacking and Storage
Icon Description
CE mark of conformity
F i g u r e 4 - 2 Scope of delivery
• Store the inverter in the original packing case with the desiccant inside.
21
4 Unpacking and Storage User Manual
• The storage temperature must be always between -30° C and +70° C, and the
storage relative humidity must be always between 0 and 95 %, non-condensing.
• In case of stacking storage, the number of stacking layers should never exceed the
limit marked on the outer side of the packing case.
• If the inverter has been stored more than half a year, the qualified personnel should
thoroughly check and test it before installation.
22
5 Mechanical Mounting
• Always follow the instructions when moving and positioning the inverter.
Select an optimal mounting location for safe operation, long service life and expected
performance.
• Install the inverter in a place convenient for electrical connection, operation, and
maintenance.
• The ambient temperature and relative humidity must meet the following
requirements
23
5 Mechanical Mounting User Manual
• Never install the inverter in living areas. The inverter will generate noise during
operation, affecting daily life
Never install the inverter horizontally, or with a forward tilt/backward tilt, or even upside
down.
24
User Manual 5 Mechanical Mounting
• Install the inverter at an appropriate height for ease of viewing LED indicators and
operating switches.
Installation tools include but are not limited to the following recommended ones. If
necessary, use other auxiliary tools on site.
25
5 Mechanical Mounting User Manual
No. Specification
a M4
b M4
c Drill bit: D10
d Crimp range: 4~6mm2
e Range ≥ 1000Vdc
f Opening: 16mm, 46mm
Before installation, remove the inverter from the packing case and move it to the
installation site. Follow the instructions below as you move the inverter:
26
User Manual 5 Mechanical Mounting
• Lift the inverter using the handles positioned on both sides of the inverter.
• Move the inverter by at least two people or by using a proper transport tool.
Install the inverter on the wall using the provided wall-mounting bracket and expansion
plug sets.
The expansion plug set shown below is recommended for the installation.
Note:
2 The air bubble in the bracket must be between the two lines in the red circles to
ensure the horizontal level.
Step 2 Mount the inverter to the bracket. Secure the inverter with two M4 screws and washers.
(1.5 N•m)
27
5 Mechanical Mounting User Manual
- - End
28
6 Electrical Connection
Prior to any electrical connections, keep in mind that the inverter has dual power
supplies. It is mandatory for the qualified personnel to wear personal protective
equipment (PPE) during the electrical work.
• The PV string will generate lethal high voltage when exposed to sunlight.
• Ensure that all cables are voltage free before performing cable connection.
• Any improper operations during cable connection can cause device damage
or personal injury.
Comply with the safety instructions related to the PV strings and the regulations
related to the utility grid.
• Only with the permission of the local utility grid company, the inverter can be
connected to the utility grid.
29
6 Electrical Connection User Manual
* The image shown here is for reference only. The actual product received may differ.
RS485 Enable
30
User Manual 6 Electrical Connection
Item Designation
A Router
B Battery
C PV string
D AC circuit breaker
E Smart Energy Meter
F Grid
G Backup loads
H Monitoring device
31
6 Electrical Connection User Manual
Spe cification
Outer
No. Cable Type Cross section
diameter
( m m 2)
(mm)
CAT 5E outdoor shielded
1 Ethernet cable 5.3 ~ 7 mm 8 * 0.2 mm²
network cable
Complying with 1,000V
4 mm²
and 35A standard
2 Power Cable 5.5 ~ 8 mm
Complying with 1,000V
6 mm²
and 40A standard
Outdoor multi-core
copper wire cable
3 DC cable 6 ~ 9 mm 4 ~ 6 mm²
Complying with 1,000V
and 30A standard
4 Outdoor multi-core 14 ~ 25 mm 6 ~ 10 mm²
AC cable *
5 copper wire cable 12 ~ 14mm 4 ~ 6 mm²
2 * (0.5 ~ 1.0)
Shielded twisted pair
Communicati- mm²
6 5.3 ~ 7 mm
on cable CAT 5E outdoor shielded
8 * 0.2 mm²
network cable
Additional
Outdoor single-core The same as that of the PE wire in
7 Grounding
copper wire cable the AC cable
cable *
* If local regulations have other requirements for cables, set the cable specification
according to the local regulations.
Backup Wiring Diagram
Neutral line of alternative supply must not be isolated or switched. (applies to wiring
rules AS/NZS_3000:2012 for Australia and New Zealand)
32
User Manual 6 Electrical Connection
Neutral line of alternative supply must be disconnected after the grid is off. (applies to
other countires)
33
6 Electrical Connection User Manual
• Since the inverter is transformerless , neither the negative pole nor the
positive pole of the PV string must be grounded. Otherwise, the inverter will
not operate normally.
All non-current carrying metal parts and device enclosures in the PV power system
should be grounded, for example, brackets of PV modules and inverter enclosure.
When there is only one inverter in the system, connect the additional grounding cable to
a nearby grounding point.
There are two additional grounding terminals located at the bottom and right side of the
inverter. Connect either one.
Additional grounding cable is prepared by customers.
34
User Manual 6 Electrical Connection
Step 2 Remove the screw on the grounding terminal and fasten the cable with a screwdriver.
- - End
• Never connect a load between the inverter and the circuit breaker.
35
6 Electrical Connection User Manual
The AC terminal block is on the bottom of the inverter. AC connection is the three-
phase-four-wire grid +PE connection (L1, L2, L3, N, and PE).
Step 2 ( O p t i o n a l ) Remove the inner rubber gasket if the external diameter of the to-be-used
AC cable ranges from 19~25mm.
Step 3 Thread the AC cable of appropriate length through the waterproof terminal.
Step 4 Remove the cable jacket by 80~90 mm, and strip the wire insulation by 12 mm.
Step 5 When using a multi-core multi-strand copper wire cable, connect the AC cable head to
the cord end terminal by appropriate torque.
36
User Manual 6 Electrical Connection
• In case of single-strand copper wire, skip installing any cord end terminal.
Step 6 Fix all cables to the corresponding terminals with torque of 1.2-1.5 N•m, according to
markings on the connector with a screwdriver, especially the “PE” cable. Avoid
connecting the phase line to the terminal of "PE" or "N" cable, and otherwise, the
inverter will be damaged.
Step 7 Pull cables outward to check whether they are firmly installed.
Step 8 Connect the front and the back parts until there is an audible click.
- - End
37
6 Electrical Connection User Manual
Step 3 Insert the AC connector into the G R I D terminal on the bottom of the inverter until there is
an audible sound.
Step 4 ( O p t i o n a l ) Insert the block into AC connector, as shown in the figure below.
38
User Manual 6 Electrical Connection
Observe the terminal layout on the block. Do not connect the phase wires to
"PE" terminal or PE wire to "N" terminal. Otherwise, unrecoverable damage to
the inverter may follow.
Step 8 Make sure all AC cables are firmly installed via the right torque tool or dragging the
cables slightly.
- - End
Make sure the PV array is well insulated to ground before connecting it to the
inverter.
Before connecting the PV array to the inverter, ensure that the impedances
between the positive terminals of the PV string and earth, and between the
negative terminals of the PV string and earth are larger than 1 M Ohm.
• Make sure the maximum voltage of each string is always less than 1,000 V.
• Make sure the maximum short circuit current on the DC side is within the
permissible range.
39
6 Electrical Connection User Manual
In Australia and New Zealand, ensure the DC power for any PV string never exceeds a
certain level with regards to the string voltage to avoid derating:
≤ 12.5 kW if string voltage is lower than 500 V
≤ 10 kW if string voltage is between 500 V and 800 V
≤ 8 kW if string voltage is between 800 V and 1000 V
For SH5.0/6.0/8.0RT, each PV input operates independently and has its own MPPT. In
this way, string structures of each PV input may differ from each other, including PV
module type, number of PV modules in each string, angle of tilt, and installation
orientation.
For SH10RT, each PV input area includes two PV inputs PV2 and PV3. For the best use
of PV power, PV2 and PV3 should be the same in PV string structure, including the type,
number, tilt, and orientation of the PV modules.
Prior to connecting the inverter to PV inputs, the following electrical specifications must
be met simultaneously:
40
User Manual 6 Electrical Connection
SUNGROW provides corresponding plug connectors in the scope of delivery for quick
connection of PV inputs. DC cables should be connected to the inverter via PV
connectors which are included in the scope of delivery.
To ensure IP65 protection, use only the supplied connector or the connector
with the same ingress of protection.
Use the MC4 DC terminal within the scope of delivery. Damage to the device
due to the use of incompatible terminal shall not be covered by the warranty.
41
6 Electrical Connection User Manual
Step 3 Lead the cable through cable gland. Insert the crimp contact into the insulator until it
snaps into place. Gently pull the cable backward to ensure firm connection. Tighten the
cable gland and the insulator (torque 2.5 N·m to 3 N·m).
For further assembly and connection instruction, please visit the website of
the device manufacturer.
- - End
Step 2 Check the cable connection of the PV string for polarity correctness and ensure that the
open circuit voltage in any case does not exceed the inverter input limit of 1,000V.
42
User Manual 6 Electrical Connection
Step 3 Connect the PV connectors to corresponding terminals until there is an audible click.
• Check the positive and negative polarity of the PV strings, and connect the
PV connectors to corresponding terminals only after ensuring polarity
correctness.
- - End
• Through the Modbus TCP/IP protocol, the EMS or the Logger from the third party
can fully control the on/off, derating, charging and discharging of the inverter.
43
6 Electrical Connection User Manual
RS485 function:
The RS485 communication interfaces are used to establish communication connection
with monitoring devices.
The following figure shows how the Ethernet connection may work with a router.
Skip step 1 if the standard network cable with RJ45 plug is prepared.
Step 1 ( O p t i o n a l ) Strip the insulation layer of the communication cable with an Ethernet wire
stripper, and lead the corresponding signal cables out. Insert the stripped
communication cable into the RJ45 plug in the correct order, and crimp it with a crimper.
44
User Manual 6 Electrical Connection
Step 4 Insert the RJ45 plug into the front plug connector until there is an audible click, and
install the rubber gasket.
- - End
Step 2 Insert the LAN connector into L A N terminal on the bottom of the inverter.
Step 3 Pull cables outwards to confirm whether they are fastened firmly, then tighten the swivel
nut with appropriate torque.
45
6 Electrical Connection User Manual
- - End
The following figure shows how the WLAN connection may work with the WiFi module.
Step 2 Install the WiFi module. Slightly shake it by hand to determine whether it is installed
firmly, as shown below.
Step 3 Refer to the quick guide for the WiFi module to configure the WLAN.
46
User Manual 6 Electrical Connection
- - End
The RS485 connection can establish the communication between an external device. In
Italy, the RS485 connection can be used to receive the command to shut down the
inverter remotely.
Step 3 Remove the seal and lead the cable through the cable gland.
Step 4 Remove the cable jacket and strip the wire insulation.
47
6 Electrical Connection User Manual
Step 5 Plug the wires into the R S 4 8 5 terminal according the labels on the bottom of the
inverter.
Step 6 Pull the wires outward to check whether they are firmly installed.
Step 7 Insert the terminal block into the connector until it snaps into place with an audible click.
- - End
48
User Manual 6 Electrical Connection
Step 2 Insert the COM connector into C O M terminal on the bottom of the inverter until there is
an audible click.
- - End
The inverter is equipped with the feed-in power limit function, so as to meet the
requirements of some national standards or grid standards for the output power at the
grid connection point. For the setting of feed-in power limit, refer to the section "8.4.1
Feed-in Limitation".
Contact SUNGROW to ensure that the Smart Energy Meter model is available
locally.
This section mainly describes the cable connections on the inverter side. Refer
to the quick guide delivered with the Smart Energy Meter for the connections
on the meter side.
Procedure
For detailed connection description of the Smart Energy Meter cable, refer to the
section "6.7.3 RS485 Connection". Plug the wires into the M e t e r terminal according the
labels on the bottom of the inverter.
49
6 Electrical Connection User Manual
This section mainly describes the cable connections on the inverter side. Refer to the
instructions supplied by the battery manufacturer for the connections on the battery
side.
Only use properly insulated tools to prevent accidental electric shock or short
circuits. If insulated tools are not available, use electrical tape to cover the entire
exposed metal surfaces of the available tools except their tips.
All power cables are equipped with water-proof direct plug-in connectors, which match
the battery terminals at the bottom of the inverter.
During assembly, be careful not to contaminate, pull out, or shift, the seal in the
cable gland. A contaminated or shifted seal impairs strain relief and leak
tightness.
50
User Manual 6 Electrical Connection
Step 2 Pry the connection open and pull the sleeve and the insert apart.
Step 3 Insert the stripped cable into the cable gland up to the stop. The stranded wire can be
seen inside the spring. Press the spring down until it audibly snaps into place.
Step 4 Push the insert into the sleeve and tighten the cable gland (torque 2 N·m).
51
6 Electrical Connection User Manual
- - End
Only connect these connectors with other SUNCLIX connectors. When making
the connections, always observe the specifications regarding nominal voltage
and nominal current. The smallest common value is permissible.
- - End
The CAN cable enables the communication between the inverter and the Li-ion battery
from BYD.
Procedure
For detailed connection description of the CAN cable, refer to the section "6.7.3 RS485
Connection". Plug the wires into the B M S / C A N terminal according the labels on the
bottom of the inverter.
The Enable cable along with the RS485 cable, are used for communication between the
inverter and the Li-ion battery from LG.
52
User Manual 6 Electrical Connection
Procedure
For detailed connection description of the RS485 cable, refer to the section "6.7.3
RS485 Connection".
For detailed connection description of the Enable cable, refer to the section "6.7.3
RS485 Connection". Plug the wires into the E n a b l e terminal according the labels on the
bottom of the inverter.
6.10 DO Connection
• Consumer load control. In this case the DO relay will control a contactor that will
open or close in certain condition. Please choose the appropriate contactor
according to the load power, e. g. the contactor types of the 3TF30 series from
SIEMENS (3TF30 01- 0X).
• Earth fault alarm. In this case, the additional equipment required is a light indicator
and/or a buzzer.
53
6 Electrical Connection User Manual
• The DO node is not controlled once the inverter is powered off. Connect the
AC contactor by the manual switch, so as to control the loads.
Procedure
For detailed connection description of the DO cable, refer to the section "6.7.3 RS485
Connection". Plug the wires into the D O terminal according the labels on the bottom of
the inverter.
The modes from DRM0 to DRM8 are supported by the inverter and the information is
marked on the label located in the top of COM terminal.
Wiring between the inverter and the DRED is as follows.
54
User Manual 6 Electrical Connection
The switches that need to be closed in the state of DRM0 ~ DRM8 are shown in the
table below.
Ripple Control
In Germany, the grid company uses the Ripple Control Receiver to convert the grid
dispatching signal and send it as a dry contact signal.
Wiring of the ripple control receiver dry contact catles is shown in the figure below:
NS Protection
Wiring of the NS Protection is shown in the figure below:
55
6 Electrical Connection User Manual
Step 3 Remove the seal and lead the cable through the cable gland.
Step 5 Plug the wires into the corresponding terminal according the labels on the bottom of the
inverter.
56
User Manual 6 Electrical Connection
Step 6 Pull the wires outward to check whether they are firmly installed.
Step 7 Insert the terminal block into the connector until it snaps into place with an audible click.
- - End
Step 2 Insert the COM connector into C O M terminal on the bottom of the inverter until there is
an audible click.
57
6 Electrical Connection User Manual
Step 3 Pull cables outwards to confirm whether they are fastened firmly.
Step 4 Connect the other end to the DRED / Ripple Control Receiver / NS Protection device.
- - End
Step 1 Assembling the BACK-UP Connector. Specifically, refer to "6.5.2 Assembling the AC
Connector".
The PE wire of Backup terminal is not required for Australia and New Zealand.
Step 3 Align the Backup connector and the B A C K - U P terminal and mate them together by
hand until a “Click” is heard or felt.
58
User Manual 6 Electrical Connection
Step 4 Pull all the lines outward to check whether they are firmly installed.
- - End
59
7 Commissioning
• The inverter is correctly connected to the external devices, and the cables are routed
in a safe place or protected against mechanical damage.
• The selection of the AC circuit breaker is in accordance with this manual and all
applicable local standards.
• All unused terminals at the bottom of the inverter are properly sealed.
If all of the items mentioned above meet the requirements, proceed as follows to start
up the inverter for the first time.
Step 2 ( O p t i o n a l ) Connect the external DC circuit breaker between the inverter and the battery
pack if a battery is equipped.
Step 4 Rotate the DC switch to “ON”. The DC switch may be integrated in the inverter or
installed by the customer,wait for at least 5 minutes.
Step 5 Establish communication connection between the mobile phone and WiFi wireless
communication module, and then set initial protection parameters. For details, please
refer to "8.3.2 Login Steps"~ "8.4 Initial Settings". If the irradiation and grid conditions
meet requirements, the inverter will normally operate. The connection time for inverter to
gird may take some minutes or even to more according to different country code
chosen in the initial settings and the real site grid condition.
Step 6 Observe the LED indicator to ensure that the inverter operates normally. (Refer to "Table
2-2 LED indicator description").
- - End
60
8 iSolarCloud App
The iSolarCloud App can establish communication connection to the inverter via the
WLAN, providing remote monitoring, data logging and near-end maintenance on the
inverter. Users can also view inverter information and set parameters through the App.
* To achieve direct login via WLAN, the WiFi wireless communication module developed
and manufactured by SUNGROW is required. The iSolarCloud App can also establish
communication connection to the inverter via wired Ethernet connection.
• This manual describes only how to achieve near end maintenance via
WLAN direct connection.
• Screenshots in this manual are based on the V2.1.6 App for Android
system, and the actual interfaces may differ.
61
8 iSolarCloud App User Manual
8.3 Login
8.3.1 Requirements
• The mobile phone is within the coverage of the wireless network produced by the of
the WiFi module.
Step 2 Open the App to enter the login screen, and tap "Local Access" to enter the next screen.
The default account is "user" and the initial password is "pw1111" which
should be changed for the consideration of account security.
62
User Manual 8 iSolarCloud App
F i g u r e 8 - 1 WLAN Direct
Step 4 If the inverter is not initialized, navigate to the quick setting screen to initialize protection
parameter. For details, please refer to "8.4 Initial Settings".
The "Country /Region" must be set to the country where the inverter is installed.
Otherwise, the inverter may report errors.
Step 5 After finishing settings, tap “TURN ON DEVICE” at the top right corner and the device
will be initialized. The App will send start instructions and the device will start and
operate.
Step 6 After initialization settings, the App will return automatically to the home page.
- - End
63
8 iSolarCloud App User Manual
The function of the feed-in limitation is to control the amount of power injected in the
grid by the plant. In some situations,this function is also called as "Export limitation" or
"Zero export". The feed-in limitation function requires the using of Smart Energy Meter.
Without the Smart Energy Meter, the feed-in limitation function will be unavailable.
Default value
Parameter Range
Germany Others
Feed-in Limitation On Off On / Off
Feed-in Limitation Rated power×70%
*
Rated power 0 ~ Rated power
Value
Feed-in Limitation
70.0%* 100.0% 0 ~ 100%
Ratio
Rated Power of
Original Power Depends on inverter power of other companies
Generation Systems
*If power control is regulated by a third party logger, please enable the power limitation
to 100% in default.
The off-grid mode is off by default, the user can set an amount of “Reserved Battery
SOC for Off-Grid”. The reserved battery SOC for Off-Grid is the minimum battery level
in the on-grid state. The reserved battery SOC for Off-Grid will be supplied to the
Backup loads in case of grid blackout.
The inverter provides a reactive power regulation function. Use the “Reactive Power
Regulation Mode” parameter to activate this function and select proper regulation
mode.
Mode Descriptions
Off The PF is fixed at +1.000.
The reactive power can be regulated by the parameter PF (Power
PF
Factor).
The reactive power can be regulated by the parameter Q-Var limits (in
Q(t)
%).
64
User Manual 8 iSolarCloud App
Mode Descriptions
Q(P) The PF changes with the output power of the inverter.
Q(U) The reactive power changes with the grid voltage.
“Off” Mode
The reactive power regulation function is disabled. The PF is limited to +1.000.
“PF” Mode
The power factor is fixed and reactive power setpoint is calculated according to the
current power. The PF ranges from 0.8 leading to 0.8 lagging.
Leading: the inverter is sourcing reactive power to the grid.
Lagging: the inverter is injecting reactive power into the grid.
“Q(t)” Mode
In the Q(t) mode, system rated reactive power is fixed, and the system injects reactive
power according to the delivered reactive power ratio. The "Reactive Power Ratio" is set
through the App.
The setting range of the reactive power ratio is 0~100% or 0~-100%, corresponding to
the ranges of inductive and capacitive reactive power regulation respectively.
“Q(P)” Mode
The PF of the inverter output varies in response to the output power of the inverter.
Default
Parameter Explanation Range
DE AU
Select corresponding curve
Q(P) Curve A A, B, C*
according to local regulations
Output power at P1 on the Q(P)
QP_P1 20% 25% 10% ~ 100%
mode curve (in percentage)
Output power at P2 on the Q(P)
QP_P2 50% 20% ~ 100%
mode curve (in percentage)
Output power at P3 on the Q(P)
QP_P3 100% 20% ~ 100%
mode curve (in percentage)
Power factor at P1 on the Q(P)
QP_K1 1
mode curve
Curve A/C: 0.8~1
Power factor at P2 on the Q(P)
QP_K2 1 Curve B:
mode curve
-0.6~0.6
Power factor at P3 on the Q(P)
QP_K3 0.95 0.90
mode curve
QP_ Voltage percentage for Q(P)
105% 100% ~ 110%
EnterVoltage function activation
QP_ Voltage percentage for Q(P)
100% 90% ~ 100%
ExitVoltage function deactivation
65
8 iSolarCloud App User Manual
Default
Parameter Explanation Range
DE AU
QP_ Power percentage for Q(P)
20% 1% ~ 20%
ExitPower function deactivation
QP_ Unconditional activation/
Yes Yes / No
EnableMode deactivation of Q(P) function
F i g u r e 8 - 2 Q(P) Curve
“Q(U)” Mode
The reactive power output of the inverter will vary in response to the grid voltage.
Default
Parameter Explanation Range
DE AU
Select corresponding curve
Q(U) curve A A, B, C*
according to local regulations
Hysteresis Voltage hysteresis ratio on the
0 0 ~ 5%
Ratio Q(U) mode curve
Grid voltage limit at P1 on the 80% ~
QU_V1 93% 90%
Q(U) mode curve 100%
Value of Q/Sn at P1 on the Q
QU_Q1 -60% -30% -60% ~ 0
(U) mode curve
Grid voltage limit at P2 on the 80% ~
QU_V2 97% 95.6%
Q(U) mode curve 110%
Value of Q/Sn at P2 on the Q
QU_Q2 0 -60% ~ 60%
(U) mode curve
Grid voltage limit at P3 on the 103- AU:108.7% 100% ~
QU_V3
Q(U) mode curve % NZ:108.6% 120%
Value of Q/Sn at P3 on the Q
QU_Q3 0 -60% ~ 60%
(U) mode curve
Grid voltage limit at P4 on the 107- AU:115.2% 100% ~
QU_V4
Q(U) mode curve % NZ:110.8% 120%
66
User Manual 8 iSolarCloud App
Default
Parameter Explanation Range
DE AU
Value of Q/Sn at P4 on the Q
QU_Q4 60% 30% 0 ~ 60%
(U) mode curve
QU_ Active power for Q(U) 20% ~
80%
EnterPower function activation 100%
Active power for Q(U)
QU_ExitPower 10% 1% ~ 20%
function deactivation
Yes / No /
QU_ Unconditional activation/
Yes Yes, Limited
EnableMode deactivation of Q(U) function
by PF
F i g u r e 8 - 3 Q(U) Curve
The App provides parameter viewing and setting functions, as shown in the following
figure.
67
8 iSolarCloud App User Manual
8.6 Home
F i g u r e 8 - 5 Home
68
User Manual 8 iSolarCloud App
If the inverter runs abnormally, the fault icon appears on the upper left corner of the
screen. Users can tap the icon to view detailed fault information and corrective
measures.
Tap "Run Information" on the navigation bar to enter the corresponding screen, as
shown in the following figure.
F i g u r e 8 - 6 Run Information
The run information includes the PV information, inverter information, input, output, grid
information, load information, and battery information.
69
8 iSolarCloud App User Manual
8.8 Records
Tap "Records" on the navigation bar to enter the screen, as shown in the following figure.
F i g u r e 8 - 7 Records
On “Records” screen, users can view chart and check fault alarm record.
8.8.1 Chart
Tap "Chart" to enter the screen showing daily power generation, as shown in the
following figure.
F i g u r e 8 - 8 Power Curve
The App displays power generation records in a variety of forms, including daily power
generation graph, monthly power generation histogram, annual power generation
histogram, and total power generation histogram.
Item Description
Daily power generation Indicates today power generation, charging, feed-in
graph power, and direct consumption power
Monthly power Indicates monthly power generation, charging, feed-in
generation histogram power, and direct consumption power
70
User Manual 8 iSolarCloud App
Item Description
Annual power generation Indicates annual power generation, charging, feed-in
histogram power, and direct consumption power
Total power generation Indicates total power generation, charging, feed-in power,
histogram and direct consumption power
Tap "Fault Alarm Record " to enter the screen, as shown in the following figure.
Click " " to select a time segment and view corresponding records.
Select one of the records in the list and click the record, to view the detailed fault info as
shown in following figure.
8.9 More
Tap "More" on the navigation bar to enter the screen, as shown in the following figure.
71
8 iSolarCloud App User Manual
F i g u r e 8 - 1 1 More
Tap "Settings -> System Parameters" to enter the screen, as shown in the following
figure.
F i g u r e 8 - 1 2 System Parameters
Boot/Shutdown
Tap "Boot/Shutdown", on which boot/shutdown instruction can be sent to the inverter.
For Australia and New Zealand, when the DRM state is DRM0, the “Boot” option will
be prohibited.
72
User Manual 8 iSolarCloud App
System Time
The correct system time is very important. Wrong system time will directly affect the
data logging and power generation value. The clock is in 24-hour format.
Tap "Settings -> Operation Parameters -> Running Time" to enter the corresponding
screen, on which you can set “Connecting Time” and “Reconnecting Time”.
F i g u r e 8 - 1 3 Running Time
Tap "Settings -> Operation Parameters -> Regular Parameters" to enter the screen, as
shown in the following figure.
F i g u r e 8 - 1 4 Regular Parameters
After connecting the load to the DO terminals, a relay control signal will be transmitted.
Users can flexibly set the control mode of DO configuration according to individual
demand.
73
8 iSolarCloud App User Manual
Tap "Settings -> Operation Parameters -> Off-grid Parameters" to enter the screen, as
shown in the following figure.
F i g u r e 8 - 1 5 Off-grid Parameters
Tap "Settings -> Power Regulation Parameters -> Active Power Regulation" to enter the
screen, as shown in the following figure.
74
User Manual 8 iSolarCloud App
Tap "Settings -> Power Regulation Parameters -> Reactive Power Regulation" to enter
the screen, as shown in the following figure.
Tap "Settings -> Energy Management Parameter-> Battery Discharge Time" to enter
the corresponding screen, as shown in the following figure.
75
8 iSolarCloud App User Manual
Tap "Settings -> Energy Management Parameter-> Battery Forced Charge Time" to
enter the corresponding screen.
When there is no PV power, the power imported from the grid charges the energy
system during the time period until the target SOC is reached.
It is recommended to set the time period in off-peak tariff time. The time period 1 is in
priority to the time period 2 if two periods overlap. The charging energy comes from the
excess PV energy in priority and then from the grid. The inverter will take charging
power from the grid in the case of PV energy shortage.
Tap "Settings -> Energy Management Parameter-> Load Regulation" to enter the
corresponding screen, on which you can set "Load 1 Regulation Mode". Load 1
Regulation Mode includes "Timing Mode", "Switch Mode", and "Intelligent Mode".
76
User Manual 8 iSolarCloud App
F i g u r e 8 - 2 0 Load Regulation
Timing Mode
In this mode, set the "Load 1 Timing Start Time" and "Load 1 Timing End Time", the
system will control the load operation during the interval. Take 09:00 am–09:30 am as
an example.
77
8 iSolarCloud App User Manual
• When the inverter is installed to retrofit an exisiting PV system, the upper limit of
optimized power is the sum of the rated power of the hybrid inverter and the rated
power of the existing PV inverter.
• Once the intelligent mode is enabled, the DO relay will remain connected for 20
minutes after the DO connection.
Tap "Settings -> Communication Parameters" to enter the screen, as shown in the
following figure.
78
User Manual 8 iSolarCloud App
F i g u r e 8 - 2 4 Communication Parameters
• The IP adress, gateway, subnet mask, preferred DNS server and alternate DNS
server can be modified only when the DHCP is set to Off.
• Acquire the IP adress, gateway, subnet mask, preferred DNS server and alternate
DNS server from the network professional.
Tap the icon in the upper right corner of the login screen and select “Firmware
Download”, to enter the “File List” tab. Select the desired upgrade package (. zip).
Tap the icon . The downloaded package can be found in the "Downloaded" tab.
Upgrade
Tap "Firmware Update" to enter the corresponding screen, as shown in the following
figure.
F i g u r e 8 - 2 5 Firmware upgrade
79
8 iSolarCloud App User Manual
Tap "More -> Settings -> Operation ParameterS -> Grounding Detection" to enter the
corresponding screen.
F i g u r e 8 - 2 6 Grounding Detection
If the grounding detection is enabled, the DO relay will switch on automatically to signal
the external alarm if the value exceeds the grounding detection alarm value. The buzzer
inside the inverter will beep.
The PV insulation resistance fault (fault sub-code 039) will trigger the DO relay to signal
the external alarm.
80
9 System Decommissioning
Please strictly follow the following procedure. Otherwise it will cause lethal
voltages or unrecoverable damage to the inverter.
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power sources.
Lethal voltages or damage to the inverter will follow if otherwise.
Step 1 Stop the inverter via the iSolarCloud App. For details, see "8.9.1 System Parameters".
Step 2 Disconnect the external AC circuit breaker and secure it against reconnection.
Step 3 Rotate the DC switch to the “OFF” position and then disconnect all of the PV string
inputs.
Step 4 Disconnect the DC circuit breaker between the battery and the inverter.
Do not power on the system again for 1 minute after the disconnection.
Step 5 Wait about 1 0 minutes until the capacitors inside the inverter completely discharge.
Step 6 Measure and ensure that no voltage is present at the AC output on the inverter.
Step 8 Insert the Slotted screwdriver into one of the two openings and press the screwdriver
with an appropriate force to remove the AC connector.
81
9 System Decommissioning User Manual
Step 9 Insert a MC4 wrench into the notch and press the wrench with an appropriate force to
remove the DC connector.
Step 10Use the multimeter to measure the port voltage of the battery. Disconnect the power
cables after the voltage is zero.
- - End
Step 1 Refer to "Electrical Connection" for the inverter disconnection of all cables in reverse
steps.
Step 4 If the inverter will be reinstalled in the future, please refer to "Inverter Storage" for a
proper conservation.
- - End
Some parts and devices of the inverter, such as the capacitors, may cause
environment pollution.
Do not dispose of the product together with household waste but in accordance
with the disposal regulations for electronic waste applicable at the installation
site.
82
User Manual 9 System Decommissioning
Decommission the battery in the system after the inverter is decommissioned. Proceed
as follows to decommission a Li-ion battery.
Step 1 Disconnect the DC circuit breaker between the battery and the inverter.
Step 2 Disconnect the communication cable between the battery and the inverter.
Step 3 ( O p t i o n a l ) Turn off the switch on LG Li-ion battery or BYD Li-ion battery, if applicable.
Step 4 Wait for about 1 minute and then use the multimeter to measure the port voltage of the
battery.
Step 5 If the battery port voltage is zero, disconnect the power cables from the battery module.
- - End
83
10 Troubleshooting and Maintenance
10.1 Troubleshooting
When an alarm occurs, the alarm information can be viewed through the App.
Alarm ID and corrective measures are as follows:
84
User Manual 10 Troubleshooting and Maintenance
85
10 Troubleshooting and Maintenance User Manual
86
User Manual 10 Troubleshooting and Maintenance
87
10 Troubleshooting and Maintenance User Manual
88
User Manual 10 Troubleshooting and Maintenance
10.2 Maintenance
10.2.1 Routine Maintenance
Item Method Period
89
10 Troubleshooting and Maintenance User Manual
Disconnect the inverter from the grid first, then the PV strings and the battery
before any maintenance work.
Lethal voltage still exists in the inverter. Please wait at least 10 minutes and then
perform maintenance work.
There is a button cell on the inner PCB board. Contact SUNGROW for replacement
when the relevant fault alarm occurs.
Check the fastener, appearance, voltage, and resistance quarterly and annually.
90
11 Appendix
91
11 Appendix User Manual
92
User Manual 11 Appendix
93
11 Appendix User Manual
94
User Manual 11 Appendix
When product faults occur during the warranty period, SUNGROW will provide free
service or replace the product with a new one.
Evidence
During the warranty period, the customer shall provide the product purchase invoice
and date. In addition, the trademark on the product shall be undamaged and legible.
Otherwise, SUNGROW has the right to refuse to honor the quality guarantee.
Conditions
95
11 Appendix User Manual
• The customer shall give SUNGROW a reasonable period to repair the faulty device.
Exclusion of Liability
In the following circumstances, SUNGROW has the right to refuse to honor the quality
guarantee:
• The free warranty period for the whole machine/components has expired.
• The installation and use range are beyond stipulations of relevant international
standards.
For faulty products in any of above cases, if the customer requests maintenance, paid
maintenance service may be provided based on the judgment of SUNGROW.
Should you have any question about this product, please contact us.
We need the following information to provide you the best assistance:
• Fault code/name
96
User Manual 11 Appendix
97
11 Appendix User Manual
[email protected]
Poland
+48 221530484 -
[email protected]
98