SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
• ACU+ (Advanced Control Unit Plus)
The ACU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions,
monitoring functions, and local/remote alarms as well as PCU control, data
acquisition, system alarm management, and advanced battery and energy
management. The ACU+ contains an LCD display and keypad for local access. It
provides connection for binary inputs, programmable relay outputs, and a charge
control function. The controller also supports rectifier temperature compensation if
the system is equipped with a temperature probe (or multiple temperature probes
connected via Temperature Concentrators (SiteWeb™ TEMP), and ambient air
temperature monitoring if equipped with a second temperature probe. The ACU+
provides Ethernet connection and supports software upgrade via its USB port. It also
comes with a comprehensive web page and SNMP capability for remote system
management.
• SCU+ (Standard Control Unit Plus)
The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions,
monitoring functions, and local/remote alarms. The SCU+ contains an LCD display
and keypad for local access. It provides connection for binary inputs, programmable
relay outputs, and a charge control function. The controller also supports rectifier
temperature compensation if the system is equipped with a temperature probe (or
multiple temperature probes connected via Temperature Concentrators (SiteWeb™
TEMP), and ambient air temperature monitoring if equipped with a second
temperature probe. The SCU+ also provides Ethernet connection and SNMP
capability.
• Distribution Unit
Various Distribution Unit options are available, as described in this document. The
Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) contactor.
Family: NETSURE™
Spec. No.: 582136600
Model: 211NGFB
Input Voltage Nominal 120/208/240 volts AC, single phase, 3-wire, 50/60 Hz, with an
operating range of 100 to 250 volts. Acceptable input frequency range is
45 to 65 Hz.
Output Voltage: -48 Volts DC
Output Capacity:
Rectifier Module: 500W @ Vout >48Vdc (10.5A @ -48Vdc)
or
1000W @ Vout >48Vdc (20.9A @ -48Vdc)
Page 2 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
System: See the following table.
Page 3 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Distribution Unit with (13) GMT Fuse Load Positions and with
Low Voltage Battery Disconnect (LVBD), 2RU High Distribution
Unit with (13) GMT Fuse Load Positions and with Low Voltage Load
Disconnect (LVLD), 2RU High Distribution Unit with (13) GMT Fuse Load
Positions and w/out Low Voltage Disconnect, 1RU High Load Distribution
Panel with (20) GMT Fuse Load Positions
Accessory Options: Relay Racks, Mounting and Adapter Kits, Distribution Devices, AC Input
Cables and Line Cords, Ring & Distribution Module, External Battery
Disconnect Unit, Battery Cabinets, SiteWeb™ TEMP Temperature
Concentrator, Anderson Battery Connector, Digital Input and Relay
Output Cables, Replacement Modules, Wiring Notes, Wiring Illustrations
Environment: -40°C (-40°F) to +65°C (+149°F),
with deratings (see SPECIFICATIONS section)
Page 4 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
58213660001
Distribution Unit
58213660002
Distribution Unit
Rectifier Module
Side AC Input Connectors (500W)
(P/O List 2) and or
AC Input Cables/Line Cords Rectifier Module
(1000W)
Page 5 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
58213660005
Distribution Unit
Distribution Unit
Page 6 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
DISTRIBUTION UNIT (Lists 1 and 2)
Page 7 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Other List Options
List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions
(for use w/ Lists BC, LC, NC, BA, LA, and NA)
List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions
(for use w/ Lists BF, LF, and NF)
List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions
(for use w/ Lists BF, LF, and NF)
List 65: Shelf Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 66: Battery Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 67: Battery Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 71: Optional External Battery Cables with Anderson Connector
for (1) Battery String (for use w/ Lists BG and NG)
List 72: Optional External Battery Cables with Anderson Connector
for (2) Battery Strings (for use w/ Lists BG and NG)
List 89: Relay Rack Earthquake Anchor Kit
List 90: Temperature Probe (9 ft.)
List 91: Temperature Probe (30 ft.)
List 93: Battery Tray (23”)
List 94: Battery Tray (19”)
List KG: GMT Fuse Load Distribution Panel
Page 8 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
TABLE OF CONTENTS
Ordering Information
System Physical Size Related
Picture Specifications
Overview List Accessory Information Documentation
Descriptions Descriptions
SYSTEM OVERVIEW.................................................................................................................................................1
58213660001.........................................................................................................................................................5
TABLE OF CONTENTS .............................................................................................................................................9
ORDERING INFORMATION ....................................................................................................................................12
List Options........................................................................................................................................................12
Accessory Options ............................................................................................................................................16
LIST DESCRIPTIONS ..............................................................................................................................................17
List 1: 1RU High by 19” Wide Shelf...............................................................................................................17
List 2: 1RU High by 23” Wide Shelf...............................................................................................................18
List 5: 2RU High by 19” Wide Shelf...............................................................................................................19
List 6: 2RU High by 23” Wide Shelf...............................................................................................................20
Rectifier Module (500W), P/N 1R48500 .........................................................................................................21
Rectifier Module (1000W), P/N 1R481000 .....................................................................................................21
ACU+ (Advanced Control Unit Plus), P/N 1M820BNA ..................................................................................21
SCU+ (Standard Control Unit Plus), P/N 1M521BNA ....................................................................................22
List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions ...................................22
List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions .................................22
List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions ...................................23
List 65: Shelf Side Battery Cables, P/N 540814 ...........................................................................................23
List 66: Battery Side Battery Cables, P/N 540954 ........................................................................................23
List 67: Battery Cable, P/N 545709 ................................................................................................................24
List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String,
P/N 545493 ....................................................................................................................................................24
List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery
Strings, P/N 535124 .......................................................................................................................................24
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 ........................................................................25
List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe
side half, 9 ft. long) .........................................................................................................................................25
List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe
side half, 30 ft. long) .......................................................................................................................................25
List 93: Battery Tray for 23” Relay Rack .......................................................................................................26
List 94: Battery Tray for 19” Relay Rack .......................................................................................................29
List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery
Disconnect (LVBD).........................................................................................................................................32
List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load
Disconnect (LVLD) .........................................................................................................................................33
List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage
Disconnect......................................................................................................................................................34
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) .....................................................35
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and with Low Voltage Load Disconnect (LVLD).........................................................36
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and w/out Low Voltage Disconnect ............................................................................37
Page 9 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery
Disconnect (LVBD).........................................................................................................................................38
List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load
Disconnect (LVLD) .........................................................................................................................................39
List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage
Disconnect......................................................................................................................................................40
List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery
Disconnect (LVBD).........................................................................................................................................41
List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage
Disconnect......................................................................................................................................................42
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions ...............................................43
ACCESSORY DESCRIPTIONS ...............................................................................................................................44
Relay Racks .......................................................................................................................................................44
Mounting and Adapter Kits ..............................................................................................................................45
Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285 ....................................................................45
Optional 19” to 23” Rack Adapter Kit, P/N 540993 ........................................................................................45
Optional 19” to 23” Rack Adapter Kit, P/N 545728 ........................................................................................45
Rear Battery Cable Exit Kit P/N 547645 ........................................................................................................45
Distribution Devices ..........................................................................................................................................46
GMT Load Distribution Fuses ........................................................................................................................46
Bullet Nose-Type Circuit Breakers .................................................................................................................47
Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332 .................................................................48
Optional Bulk Output Busbar, P/N 535015 ....................................................................................................48
AC Input Cables and Line Cords .....................................................................................................................49
AC Input Cable Assembly, P/N 535232 .........................................................................................................49
AC Input Line Cord, 208/240VAC, P/N 540946 .............................................................................................49
AC Input Line Cord, 208/240VAC, P/N 545616 .............................................................................................50
AC Input Line Cord, 120VAC, P/N 545252 ....................................................................................................50
AC Input Line Cord, 120VAC, P/N 545478 ....................................................................................................51
AC Input Line Cord, 120VAC, P/N 545479 ....................................................................................................51
AC Input Line Cord, 208/240VAC, P/N 545480 .............................................................................................52
AC Input Line Cord, 120VAC, P/N 545481 ....................................................................................................52
AC Input Line Cord, 208/240VAC, P/N 545553 .............................................................................................53
AC Input Line Cord, 120VAC, P/N 547525 ....................................................................................................53
AC Input Line Cord, 120VAC, P/N 548457 ....................................................................................................54
AP6C57EA/EB Ring & Distribution Module ....................................................................................................55
External Battery Disconnect Unit, P/N 535282 ...............................................................................................57
NETSURE™ 201BC Battery Cabinet (Spec. No. 541434) ..................................................................................58
NETSURE™ 211BC Battery Cabinet (Spec. No. 545534) ..................................................................................59
NETSURE™ 211BC Battery Cabinet (Spec. No. 545506) ..................................................................................60
Site Web™ TEMP Temperature Concentrator (P/N 547490) .........................................................................61
Anderson Battery Connector ...........................................................................................................................62
Digital Input and Relay Output Cables ............................................................................................................63
Replacement Modules ......................................................................................................................................63
Wiring Notes ......................................................................................................................................................64
Shelf Frame Grounding Stud (List 1 and 2 Only) ...........................................................................................64
AC Input Branch Circuit Protection and Wiring ..............................................................................................64
External Alarm and Monitoring Wiring............................................................................................................64
Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) ....................................................................65
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) ..............................................................65
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA).................................................66
Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) ...................................66
Page 10 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) ..........................................66
Load Distribution Wiring (GMT Fuses) (List KG) ...........................................................................................68
CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA) ............................................................68
Input Battery Wiring (List BG and NG) ...........................................................................................................68
Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) ..................................68
Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC) .............................................69
Wiring Illustrations ............................................................................................................................................70
Shelf Frame Grounding Stud (List 1 and 2 Only) ...........................................................................................70
AC Input Wiring (Lists 1 and 2) ......................................................................................................................71
AC Input Wiring (Lists 5 and 6) ......................................................................................................................72
External Alarm and Monitoring Wiring (Lists 1 and 2)....................................................................................73
External Alarm and Monitoring Wiring (Lists 5 and 6)....................................................................................74
Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown) ................79
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown) ..........80
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,
List 5 shown) ..................................................................................................................................................81
Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) ............................................82
Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed
in a List 5 or 6, List 5 shown) .........................................................................................................................83
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground
Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)............................................................84
Load Distribution Wiring (GMT Fuses) (List KG) ...........................................................................................85
Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown) .............................................86
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and
CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown) .........................................87
SPECIFICATIONS....................................................................................................................................................88
1. System ...........................................................................................................................................................88
1.1 Environmental Ratings .............................................................................................................................88
1.2 Compliance Information ...........................................................................................................................88
1.3 Standard Features....................................................................................................................................89
2. Distribution Unit ............................................................................................................................................90
2.1 List BG and NG in a List 1 and List 2 Shelf ..............................................................................................90
2.2 List 5 and 6 Shelves .................................................................................................................................90
3. GMT Load Distribution Fuse Panel (List KG) .............................................................................................91
3.1 Electrical ...................................................................................................................................................91
PHYSICAL SIZE INFORMATION ............................................................................................................................92
Overall Dimensions – List 1 .............................................................................................................................92
Overall Dimensions – List 2 .............................................................................................................................93
Overall Dimensions – List 5 .............................................................................................................................94
Overall Dimensions – List 6 .............................................................................................................................95
Overall Dimensions – List KG ..........................................................................................................................96
Overall Dimensions – 19” Battery Tray ...........................................................................................................97
Overall Dimensions – 23” Battery Tray ...........................................................................................................98
BATTERY MANUFACTURER INFORMATION ......................................................................................................99
RELATED DOCUMENTATION................................................................................................................................99
REVISION RECORD ..............................................................................................................................................100
Page 11 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
ORDERING INFORMATION
List Options
Order the following by the items Part Number as specified in the following table.
When viewing electronically, click on the link to jump to the detailed description page.
List Part
Description
Number Number
Shelf Options
1RU 19” Mini Shelf.
1 58213660001 (Shelf requires one [1] AC Feed)
(Houses up to [2] Rectifiers, Controller, and Distribution Unit.)
1RU 23” Mini Shelf.
2 58213660002 (Shelf requires one [1] AC Feed)
(Houses up to [3] Rectifiers, Controller, and Distribution Unit.)
2RU 19” Mini Shelf.
5 58213660005 (Shelf requires two [2] AC Feeds)
(Houses up to [4] Rectifiers, Controller, and Distribution Unit.)
2RU 23” Mini Shelf.
6 58213660006 (Shelf requires two [2] AC Feeds)
(Houses up to [6] Rectifiers, Controller, and Distribution Unit.)
Controller Options
Order
1M820BNA ACU+ (Advanced Control Unit Plus)
by P/N
Order
1M521BNA SCU+ (Standard Control Unit Plus)
by P/N
Rectifier Options
Order
1R48500 Model R48-500 Rectifier Module (500W).
by P/N
Order
1R481000 Model R48-1000 Rectifier Module (1000W).
by P/N
Distribution Unit Options
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
• (13) GMT Fuse Load Positions
BF 582136600BF
(5) 0A to 15A
(8) 0A to 10A
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 5 AND 6.
Page 12 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
List Part
Description
Number Number
Distribution Unit Options (Cont’d)
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
• (13) GMT Fuse Load Positions
LF 582136600LF
(5) 0A to 15A
(8) 0A to 10A
• Low Voltage Load Disconnect (LVLD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
• (13) GMT Fuse Load Positions
NF 582136600NF
(5) 0A to 15A
(8) 0A to 10A
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
BC 582136600BC • (5) GMT Fuse Load Positions (0A to 10A)
• (4) Bullet-Nose Circuit Breaker Load Positions
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
LC 582136600LC • (5) GMT Fuse Load Positions (0A to 10A)
• (4) Bullet-Nose Circuit Breaker Load Positions
• Low Voltage Load Disconnect (LVLD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
NC 582136600NC • (5) GMT Fuse Load Positions (0A to 10A)
• (4) Bullet-Nose Circuit Breaker Load Positions
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.
Page 13 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
List Part
Description
Number Number
Distribution Unit Options (Cont’d)
Distribution Unit w/
• (1) Battery Shunt
• (5) GMT Fuse Load Positions (0A to 10A)
BA 582136600BA • (2) Bullet-Nose Circuit Breaker Load Positions
• (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (5) GMT Fuse Load Positions (0A to 10A)
• (2) Bullet-Nose Circuit Breaker Load Positions
LA 582136600LA
• (2) Bullet-Nose Circuit Breaker
Battery Disconnect Positions
• Low Voltage Load Disconnect (LVLD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (5) GMT Fuse Load Positions (0A to 10A)
NA 582136600NA • (2) Bullet-Nose Circuit Breaker Load Positions
• (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Set Battery Cables
BG 582136600BG • (10) GMT Fuse Load Positions (0A to 15A)
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 1 AND 2.
Distribution Unit w/
• (1) Set Battery Cables
NG 582136600NG • (10) GMT Fuse Load Positions (0A to 15A)
• NO Low Voltage Disconnect
FOR USE WITH LISTS 1 AND 2.
Other Options
Five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
60 58213660060 Leads are 12’ long and 16 AWG.
For use with Lists BC, LC, NC, BA, LA, and NA.
Eight (8) Load Lead Assemblies for 10A GMT Fuses Positions.
61 58213660061 Leads are 12’ long and 16 AWG.
For use with Lists BF, LF, and NF.
Page 14 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
List Part
Description
Number Number
Other Options (Cont’d)
Five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
62 58213660062 Leads are 12’ long and 14 AWG.
For use with Lists BF, LF, and NF.
Shelf Side Battery Cables. Cables are 3’ long and 2 AWG terminated in a
65 58213660065 2-position Anderson connector. Remaining end terminated in lugs for
connection to shelf. For use with Lists BF, LF, NF, BC, LC, and NC.
Battery Side Battery Cables. Cables are 12’ long and 2 AWG terminated in
66 58213660066 a 2-position Anderson connector. Remaining end un-terminated for
connection to batteries. For use with Lists BF, LF, NF, BC, LC, and NC.
Output Cable to Battery Cabinet – cables are 4’ long and 8 AWG
terminated in a 2-position Anderson connector. Remaining end terminated
67 58213660067
in lugs for connection to shelf. For Use with Lists BC, LC, NC, BF, LF, and
NF.
Optional External Battery Cables with Anderson Connector for (1) Battery
71 58213600071
String. For use with Lists BG and NG.
Optional External Battery Cables with Anderson Connector for (2) Battery
72 58213600072
Strings. For use with Lists BG and NG.
89 58213660089 Relay Rack Earthquake Anchor Kit.
90 58213660090 Temperature Probe, 9 ft long.
91 58213660091 Temperature Probe, 30 ft. long.
93 58213660093 Battery Tray (23”).
94 58213660094 Battery Tray (19”).
Distribution Panel w/
• (20) GMT Fuse Load Positions (0A to 15A)
KG 582136600KG
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.
Page 15 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Accessory Options
Order the following by the items Part Number as specified in the following table.
When viewing electronically, click on the link to jump to the detailed description page.
Page 16 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
LIST DESCRIPTIONS
List 1: 1RU High by 19” Wide Shelf
Features
♦ Consists of a 1RU high by 19” wide shelf.
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are
terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery
connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.
♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.
A mating half is available.
♦ The shelf houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 1 shelf holds up to two (2) Rectifier Modules.
Ordering Notes
1) Order List 1 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) per shelf. Also specify the appropriate configuration file
for your site.
3) Order up to two (2) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 1 shelf requires one (1) AC Input
Cable or Line Cord.
5) Order one (1) Distribution Unit (List BG or NG) per shelf.
6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
7) Order Relay Rack Anchor Kit(s) (List 89) as required.
8) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
9) Order Battery Trays (List 94) as required.
10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
Page 17 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List 2: 1RU High by 23” Wide Shelf
Features
♦ Consists of a 1RU high by 23” wide shelf.
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are
terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery
connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.
♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.
A mating half is available.
♦ The shelf houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 2 shelf holds up to three (3) Rectifier Modules.
Ordering Notes
1) Order List 2 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) per shelf. Also specify the appropriate configuration file
for your site.
3) Order up to three (3) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 2 shelf requires one (1) AC Input
Cable or Line Cord.
5) Order one (1) Distribution Unit (List BG or NG) per shelf.
6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
7) Order Relay Rack Anchor Kit(s) (List 89) as required.
8) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
9) Order Battery Trays (List 93) as required.
10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
Page 18 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 5: 2RU High by 19” Wide Shelf
Features
♦ Consists of a 2RU high by 19” wide shelf.
♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.
♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.
♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is
available. A “Digital Input Cable” (shelf side and customer side) is also available.
♦ The shelf houses up to four (4) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 5 shelf holds up to four (4) Rectifier Modules.
Ordering Notes
1) Order List 5 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) or (1) ACU+ controller (P/N 1M820BNA) per shelf. Also
specify the appropriate configuration file for your site.
3) Order up to four (4) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 5 shelf requires two (2) AC Input
Cables or Line Cords.
5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf.
6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.
Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
7) Order one (1) List KG Distribution Fuse Panel per shelf, as required.
8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66)
for each List BC, LC, NC, BF, LF, or NF ordered.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order one (1) for each battery cabinet feed required.
11) Order Relay Rack Anchor Kit(s) (List 89) as required.
12) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
13) Order Battery Trays (List 94) as required.
14) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
15) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
16) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
17) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
18) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
19) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 19 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List 6: 2RU High by 23” Wide Shelf
Features
♦ Consists of a 2RU high by 23” wide shelf.
♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.
♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.
♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is
available. A “Digital Input Cable” (shelf side and customer side) is also available.
♦ The shelf houses up to six (6) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 6 shelf holds up to six (6) Rectifier Modules.
Ordering Notes
1) Order List 6 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) or (1) ACU+ controller (P/N 1M820BNA) per shelf. Also
specify the appropriate configuration file for your site.
3) Order up to six (6) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 6 shelf requires two (2) AC Input
Cables or Line Cords.
5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf.
6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.
Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required.
8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66)
for each List BC, LC, NC, BF, LF, or NF ordered.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order Relay Rack Anchor Kit(s) (List 89) as required.
11) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
12) Order Battery Trays (List 93) as required.
13) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 20 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Rectifier Module (500W), P/N 1R48500
Features
♦ Provides one (1) Model R48-500, Spec. No. 1R48500,
500 watt / 48 volt Rectifier Module.
Restrictions
Each List 1 Shelf holds up to two (2) Rectifier Modules.
Each List 2 Shelf holds up to three (3) Rectifier Modules.
Each List 5 Shelf holds up to four (4) Rectifier Modules.
Each List 6 Shelf holds up to six (6) Rectifier Modules.
DO NOT install different wattage Rectifier Modules in same shelf.
Ordering Notes
1) Order by P/N (1R48500) as required.
Page 21 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
SCU+ (Standard Control Unit Plus), P/N 1M521BNA
Features
♦ Provides the SCU+ Controller.
♦ Factory programmed with the configuration file specified when ordered.
Restrictions
Each shelf must contain one (1) SCU+ or one (1) ACU+ Controller.
Ordering Notes
1) Order one (1) SCU+ Controller (P/N 1M521BNA) or one (1) ACU+ (P/N
1M820BMA) for each shelf.
For the SCU+ controller, specify also one of the following configurations.
Note: For custom SCU+ configurations, contact Emerson.
a) List 1 and 2 with Low Voltage Disconnect: 545304.
b) List 1 and 2 without Low Voltage Disconnect: 545305.
c) List 5 and 6 with Low Voltage Disconnect: 545298.
d) List 5 and 6 without Low Voltage Disconnect: 545299.
List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated
on one end with the appropriate mating connector to plug into the system’s
10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution
Unit, and are left un-terminated at the remaining end for connection into
customer loads.
Restrictions
For use with List BC, LC, NC, BA, LA, and NA Distribution units only.
Ordering Notes
1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA Distribution Unit.
Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206.
List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on
one end with the appropriate mating connector to plug into the system’s 10A
GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left un-
terminated at the remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 61 for each List BF, LF, or NF Distribution Unit.
Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206.
Page 22 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions
Features
♦ Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector to plug into the system’s 15A GMT fuse connector
on a List BF, LF, or NF Distribution Unit, and are left un-terminated at the
remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit.
Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988.
Page 23 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List 67: Battery Cable, P/N 545709
Features
♦ Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Anderson
connector on the battery side. Remaining end terminated in lugs for connection to shelf.
Restrictions
For use with P/N 541434, P/N 545534 or P/N 545506 Battery cabinets only.
For use with List BF, LF, NF, BC, LC, and NC Distribution units only.
Ordering Notes
1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
2) Order one (1) for each battery cabinet feed required.
Page 24 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167
Features
♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor.
Ordering Notes
1) Order as required.
Page 25 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Ordering Notes
1) Order up to two (2) Temperature Probes for each shelf, as required.
Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740.
2) For a Temperature Probe with a shorter cable see List 90.
Page 26 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required
for battery clearance. See table above.
Page 27 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
5) Battery lugs are provided, as specified from the following table.
P/N P/N
Ampere Ampere
Electrical/Mechanical Trip1 Electrical/Mechanical Trip1
Rating Rating
(Black Handle) (Black Handle)
1 256690300 35 256693500
3 256690700 40 256693900
5 256691100 50 256694300
10 256691500 60 256694700
15 256691900 70 256695100
20 256692300 75 256695500
25 256692700 100 256695900
30 256693100
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or
manual trip condition.
Page 28 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 94: Battery Tray for 19” Relay Rack
Features
♦ Provides one battery tray that mounts four (4) 12V front
terminal Valve Regulated Lead Acid (VRLA) batteries. P/N 362736700
Batteries are configured as one (1) 48V string.
♦ Accepts various VRLA batteries. See Ordering Notes
below.
♦ See Overall Dimensions - 19” Battery Tray under
PHYSICAL SIZE INFORMATION for battery tray
dimensions and typical arrangement. Note that three
battery trays are available to accommodate the various
size batteries listed in the Ordering Notes tables.
♦ Trays can be ordered with or without battery disconnect P/N 541036
circuit breakers. When circuit breakers are ordered, one
is provided in the -48V lead of each battery string (1 circuit
P/N 362736700
breaker per tray).
♦ Battery cables are available terminated at the power
system end in an Anderson connector. Battery lugs are
available for the remaining end.
Restrictions
For 19” relay racks only.
Maximum number of List 94’s per rack is three (3).
A single List 94 must mount at bottom of rack. Multiple List
94’s must mount starting at bottom of rack and working P/N 541034
upward.
Ordering Notes
1) Order multiples of List 94 for more than one (1) battery P/N 362736700
tray. See Restrictions above.
2) Order one (1) or more P/N 362736700 Cable Bracket(s)
as required.
3) Order batteries separately. The following tables list
batteries recommended for use with List 94.
P/N 540841
Page 29 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required
for battery clearance. See table above.
Page 30 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
5) Battery lugs are provided, as specified from the following table.
P/N P/N
Ampere Ampere
Electrical/Mechanical Trip1 Electrical/Mechanical Trip1
Rating Rating
(Black Handle) (Black Handle)
1 256690300 35 256693500
3 256690700 40 256693900
5 256691100 50 256694300
10 256691500 60 256694700
15 256691900 70 256695100
20 256692300 75 256695500
25 256692700 100 256695900
30 256693100
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or
manual trip condition.
Page 31 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List BF: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage
Battery Disconnect (LVBD), a battery shunt, (3)
battery connection points, and thirteen (13) GMT
fuse load distribution positions.
♦ Five (5) 0A to 15A GMT fuse load distribution
positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT
fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value.
In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent
to a 10A fuse. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty
space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a
GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List BF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
Page 32 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List LF: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery
connection points, and thirteen (13) GMT fuse load
distribution positions.
♦ Five (5) 0A to 15A GMT fuse load distribution
positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT
fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value.
In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent
to a 10A fuse. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty
space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a
GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List LF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
Page 33 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List NF: Distribution Unit with GMT Fuse Load Distribution Positions
and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, (3) battery connection
points, and thirteen (13) GMT fuse load distribution
positions.
♦ Five (5) 0A to 15A GMT fuse load distribution
positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT
fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value.
In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent
to a 10A fuse. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty
space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a
GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List NF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List NF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
Page 34 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, (3) battery
connection points, four (4) bullet nose-type circuit
breaker load distribution positions, five (5) GMT fuse
load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 35 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery
connection points, four (4) bullet nose-type circuit
breaker load distribution positions, five (5) GMT fuse
load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List LC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 36 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, (3) battery connection
points, four (4) bullet nose-type circuit breaker load
distribution positions, five (5) GMT fuse load
distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List NC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.
Page 37 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List BA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, two (2) bullet
nose-type circuit breaker load distribution positions, two
(2) bullet nose-type circuit breaker battery disconnect
positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
Page 38 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List LA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, two (2) bullet
nose-type circuit breaker load distribution positions,
two (2) bullet nose-type circuit breaker battery
disconnect positions, five (5) GMT fuse load
distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List LA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
Page 39 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List NA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, two (2) bullet nose-type
circuit breaker load distribution positions, two (2) bullet
nose-type circuit breaker battery disconnect positions,
five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.
Page 40 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List BG: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), battery cables, and ten (10) GMT
fuse load distribution positions (15A maximum).
♦ Two (2) 8 AWG 48” long battery cables are factory
connected inside the shelf. These cables are
terminated at the customer end in a Red SB50
Anderson battery connector. A mating Anderson
battery connector is provided [Housing: Emerson P/N
138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602,
Anderson Power Products P/N 5952].
♦ Ten (10) 0A to 15A GMT fuse load distribution positions.
Restrictions
For use with List 1 and 2 only.
The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A
fuses.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
Page 41 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List NG: Distribution Unit with GMT Fuse Load Distribution Positions
and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, battery cables, and ten
(10) GMT fuse load distribution positions (15A
maximum).
♦ Two (2) 8 AWG 48” long battery cables are factory
connected inside the shelf. These cables are
terminated at the customer end in a Red SB50
Anderson battery connector. A mating Anderson
battery connector is provided [Housing: Emerson P/N
138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602,
Anderson Power Products P/N 5952].
♦ Ten (10) 0A to 15A GMT fuse load distribution positions.
Restrictions
For use with List 1 and 2 only.
The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A
fuses.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.
Page 42 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions
Features
♦ 1U-high GMT fuse panel that provides Single Load
Distribution (-48V)
♦ Provides twenty (20) 0A to 15A GMT fuse load
distribution positions.
♦ Maximum Capacity: 80A @ +40°C and 80A @ +65°C
♦ Factory mounted and connected to List 5 or 6 shelf.
Restrictions
For use with List 5 and 6 only.
Mounts only immediately above List 5 or 6 shelf.
For use with List BA, BC, BF, NA, NC and NF only.
Maximum distribution current is 80A.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 5 or 6 shelf as required.
Also order the following as required.
2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section.
Page 43 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
ACCESSORY DESCRIPTIONS
Relay Racks
Features
♦ The following relay racks are available.
Restrictions
Customer must mount Power/Distribution Shelf in relay rack. If battery trays are ordered, they are factory
mounted in the relay rack.
Ordering Notes
1) Order from relay racks listed in Table 1.
Page 44 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Mounting and Adapter Kits
Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285
Features
♦ Allows for horizontal or vertical wall mounting.
Restrictions
For use with List 1 or 2 only.
Customer must supply mounting fasteners for attaching the Wall
Mount Bracket to the wall.
Ordering Notes
1) Order P/N 541285, which consists of two (2) P/N 545701 horizontal wall mounting brackets and two (2)
P/N 541284 vertical wall mounting brackets, and eight (8) 12-24 x ½” screws for attaching the brackets to
the shelf.
Page 45 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Distribution Devices
GMT Load Distribution Fuses
Features
♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8)
0-10A GMT load distribution fuses.
♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses.
♦ Each List BG and NG Distribution Unit holds up to ten (10) 0-15A GMT load distribution fuses.
♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere
fuses, for which load should not exceed 70% of device rating.
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (GMT Fuses) (Lists BG and NG only), Load Distribution Wiring (GMT
Fuses) (Lists BF, LF, and NF only), and Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA,
and NA) under WIRING NOTES for additional wiring restrictions.
Ordering Notes
1) Order GMT fuses per Table 2.
Page 46 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Bullet Nose-Type Circuit Breakers
Features
♦ Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit
breakers.
♦ Each List BA, LA, and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit
breakers and up to two (2) bullet nose-type load distribution circuit breakers.
Restrictions
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) and Input Battery
Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) under WIRING NOTES for additional
wiring restrictions.
Ordering Notes
1) Order circuit breakers per Table 3.
P/N
Ampere Electrical/
Rating Electrical Trip1
Mechanical Trip2
(White Handle)
(Black Handle)
1 102272 101596
3 102273 101597
5 102274 101598
10 102275 101599
15 102276 101600
20 102277 101601
25 102278 101602
30 102279 101603
35 102280 101604
40 102281 101605
45 121998 121997
50 102282 101606
60 102283 101607
70 102284 101608
75 102285 101609
80 121996 121995
100 102286 101610
See Table 6 for recommended wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Note that Electrical Trip only circuit breakers are not typically used for battery
disconnect circuit breakers.
Table 3
Bullet Nose-Type Circuit Breakers
Page 47 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332
Features
♦ Factory installed in a List BC, LC, NC, BA, LA,
and NA Distribution Unit.
♦ Provides six (6) 0A to 15A GMT fuse load
distribution positions.
♦ Screw clamp type load and load return terminals
provided.
♦ Includes six (6) dummy fuses equipped with
safety fuse covers.
Restrictions
For use with Lists BC, LC, NC, BA, LA, and NA.
Terminal block wire size capacity: 24 to 14 AWG.
Requires two (2) bullet device mounting positions.
Fuse Module has a 30A @ +40°C (+104°F) and +65°C (+149°F) maximum capacity. Maximum GMT fuse
size is 15A. Fuses are to be loaded from bottom to top with highest value in the lowest position.
Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Factory installed only.
Ordering Notes
1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required.
2) Order GMT fuses as required per Table 2.
Page 48 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Cables and Line Cords
AC Input Cable Assembly, P/N 535232
Features
♦ Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly;
♦ terminated on one end with a Molex plug which mates with AC
input receptacle on the Power/Distribution Shelf,
♦ and the remaining end un-terminated.
Restrictions
Rated for 30A.
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
Page 49 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Line Cord, 208/240VAC, P/N 545616
Features
♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-30P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 30A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
Page 50 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Line Cord, 120VAC, P/N 545478
Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 5-15P plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 equipped with R48-500 Rectifier Modules.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
Page 51 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Line Cord, 208/240VAC, P/N 545480
Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-15P twist-lock plug.
Restrictions
For 240 VAC only (rated for 15A at 208/240VAC).
For use with List 1 and 5.
For use with List 2 and 6 with R48-500 Rectifiers.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
Page 52 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Line Cord, 208/240VAC, P/N 545553
Features
♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on
the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-20P twist-lock plug.
Restrictions
For 240 VAC only (rated for 20A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.
Page 53 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Line Cord, 120VAC, P/N 548457
Features
♦ Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 5-15P plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 with R48-500 Rectifiers.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.
Page 54 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AP6C57EA/EB Ring & Distribution Module
Features
♦ When used with List 5 or 6, this module is designed to
supply a filtered and regulated –48 VDC source and a
continuous 20 Hz ringing supply source to imbedded
subscriber loop carrier telecommunication systems
(such as SLC-96 or SLC Series-5) requiring up to 45 A
of load capacity.
♦ Designed to mount in a 23” relay rack, the module is
one rack unit high, with 5” front projection.
♦ Includes two (2) 50VA ringers with automatic transfer
capability (N+1 redundancy).
♦ Provides 35 DC distribution fuse positions, configured
in five groups of seven, feeding five channel banks. Includes 35 dummy fuses.
♦ Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution
fuses are included with each cable assembly ordered.
♦ An Order Wire Option provides a connection interface for an analog communication link over a metallic
pair, with surge protection.
♦ See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete
specifications.
Restrictions
Cannot be used with Distribution units List BF, LF, or NF.
Ordering Notes
1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626).
2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order
AP6C57EB (A7000796).
3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable
assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable
assemblies can be mixed.
ORDERING CODE DESCRIPTION
P7000858 Cable assy for one SLC96 channel bank (8 ft.)
P7001139 Cable assy for one SLC96 channel bank (20 ft.)
P7000859 Cable assy for one SLC5 channel bank (8 ft.)
P7001136 Cable assy for one SLC5 channel bank (20 ft.)
P7000937* Cable assy for one channel bank, generic applications (8 ft.)
*Note: Each channel bank position on the panel has a maximum capacity of 11A.
4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect
between a power shelf and the DC input terminals of one (1) Ring & Distribution Module.
Page 55 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following
table.
ORDERING DESCRIPTION
CODE
Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2
battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution
547646
units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use
a flat washer, not provided.)
Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for
2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution
547647
units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use
a flat washer, not provided.)
6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the
following table.
ORDERING CODE DESCRIPTION
A0885525 1.33A Alarm SAN-O Fuse
A0885530 3A Alarm SAN-O Fuse
A0885531 5A Alarm SAN-O Fuse
A0885532 10A Alarm SAN-O Fuse
A7000627 (AP8C55AA) 50VA Ring Generator
Page 56 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
External Battery Disconnect Unit, P/N 535282
Features
♦ Battery Disconnect Unit with mounting tabs.
♦ Two 1/4-20 studs w/hardware provided for installation of single hole
battery lugs.
♦ One (10’ long) alarm lead provided.
Restrictions
Circuit breakers are ordered separately.
Maximum number of Battery Disconnect Units per system is three (3).
Ordering Notes
1) Order by P/N 535282 as required.
2) Order a circuit breaker for each Battery Disconnect Unit from Table 4.
3) Also order the following lug kits for each battery disconnect circuit
breaker ordered: 545581(for use with 8 AWG wire and List 71) or
540989 (for use with 10 AWG wire and List 72) and 541031 (wire with
lugs for connection from battery disconnect to battery string).
4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery
Disconnect Units are to be used (daisy-chains the alarm terminal of up Yellow Jumper/Alarm Lead (P/N 524384)
to three [3] Battery Disconnect Units). (Section of alarm lead between (for use when more than one Battery
Battery Disconnect Units is 30”, section of alarm lead between Battery Disconnect Units are ordered)
Disconnect Unit and system’s alarm terminal is 84”.)
P/N P/N
Ampere Electrical/Mechanical Ampere Electrical/Mechanical
Rating Trip1 Rating Trip1
(Black Handle) (Black Handle)
1 256690300 35 256693500
3 256690700 40 256693900
5 256691100 50 256694300
10 256691500 60 256694700
15 256691900 70 256695100
20 256692300 75 256695500
25 256692700 100 256695900
30 256693100
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
Table 4
Battery Disconnect Unit Circuit Breakers
Page 57 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
NETSURE™ 201BC Battery Cabinet (Spec. No. 541434)
Features
♦ The NETSURE™ 201BC Battery Cabinet can be
mounted in a 19” or 23” nominal relay rack, or
mounted to a suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere
battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided
to tie into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery
cable terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in
the table under Order Notes) into the Battery
Cabinet provided.
♦ Battery Cabinets can be paralleled to provide
greater reserve time. Battery cabinets contain a
second Anderson battery connector for plugging
one cabinet into another.
Ordering Notes
1) Order by Spec. No. 541434 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.
3) When ordering 139774 batteries, also order 545427 Battery Connection kit.
Page 58 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
NETSURE™ 211BC Battery Cabinet (Spec. No. 545534)
Features
♦ The NETSURE™ 211BC Battery Cabinet can be mounted
in a 19” or 23” nominal relay rack, or mounted to a
suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere battery
disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie into
the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the table
under Ordering Notes) into the Battery Cabinet provided.
♦ Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet into
another.
Ordering Notes
1) Order by Spec. No. 545534 as required.
2) Also order two (2) batteries per Battery Cabinet per the following table.
Page 59 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
NETSURE™ 211BC Battery Cabinet (Spec. No. 545506)
Features
♦ The NETSURE™ 211BC Battery Cabinet can be
mounted in a 23” nominal relay rack, or mounted to a
suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere
battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie
into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the
table under Ordering Notes) into the Battery Cabinet
provided.
♦ Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet
into another.
Ordering Notes
1) Order by Spec. No. 545506 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.
Page 60 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Site Web™ TEMP Temperature Concentrator (P/N 547490)
Features
♦ Allows for multiple temperature probes to be used for temperature
compensation. Compensation can be based on highest probe
temperature or average probe temperature.
♦ Provides (8) temperature probe inputs per SiteWeb™ TEMP.
♦ Can be cascaded up to (8) SiteWeb™ TEMP modules,
connecting up to 64 temperature probes.
♦ Provides CAN output for ACU+ and analog output for all
controllers.
Restrictions
Concentrator needs to plug into analog temp input on IB2 board.
Ordering Notes
1) Order P/N 547490.
2) Order up to (8) List 90 or 91 temperature probes for each concentrator.
Page 61 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Anderson Battery Connector
Features
♦ Includes the components necessary to assemble an Anderson
connector onto a battery cable.
Restrictions
Appropriate battery post mating lugs must be ordered separately.
Ordering Notes
Order Anderson connector housings and lugs per the following table.
Page 62 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Digital Input and Relay Output Cables
Features
♦ Lists 5 and 6: Two sets of customer wiring cables are available. One set for the Digital Inputs and
another set for the Relay Outputs. One half of the Relay Outputs Cable is provided and factory
connected in the shelf. The other half (includes mating connector on one end and un-terminated on the
other end) must be ordered separately. Both halves of the Digital Inputs Cable must be ordered
separately. When ordered, one half of the Digital Inputs Cable is factory connected in the shelf. The
other half has a mating connector on one end and is un-terminated on the other end.
♦ Lists 1 and 2: One set of customer wiring cables is available (Digital Inputs and Relay Outputs). One
half of the cable is provided and factory connected in the shelf. The other half (includes mating connector
on one end and un-terminated on the other end) must be ordered separately.
Ordering Notes
1) Lists 5 and 6: For the Relay Outputs Cable, P/N 541308 (shelf side) is provided and factory connected
in the List 5 and 6 shelf, and P/N 541309 or P/N 545644 (customer side) must be ordered separately.
For the Digital Inputs Cable, order both P/Ns 541310 (shelf side) and P/N 541311 (customer side).
Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory
installed only.
2) Lists 1 and 2: For the Digital Inputs and Relay Outputs Cable, P/N 545494 (shelf side) is provided and
factory connected in the List 1 and 2 shelf and P/N 545495 (customer side) must be ordered separately.
Replacement Modules
Ordering Notes
1) Refer to Table 5.
Page 63 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Wiring Notes
Refer also to the next section, Wiring Illustrations.
Illustrations
For correct AC input wire size, use the appropriate AC Input Cable Assembly/Line Cord for each AC input
branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORY DESCRIPTIONS section of this
document.
Page 64 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
to these terminals. The other half includes a mating connector on one end and is un-terminated
on the other end.
♦ List 1 and 2: Relay output and digital input leads are connected to screw-type terminals located on the
SCU+ Controller Module mounted inside the shelf. One half of a Digital Input/Relay Output Cable is
factory connected to these terminals. The other half (includes mating connector on one end and un-
terminated on the other end) is ordered separately.
Restrictions
Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of
fuse amperage sizes, and that two different types of receptacles are provided.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse connector, and
are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and
are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco
350537-3 [reel].
Page 65 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) List 60 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s GMT fuse connector, and are left un-terminated
at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)
Features
♦ Load distribution (circuit breakers) and load return leads terminated in two-hole lugs are connected to
threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed
from the front) of the shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 6 AWG when all four (4) circuit breaker
positions are used and 2 AWG when only two (2) are used. When using lugs for #4 and #2 AWG wire,
recommended to use a customer supplied flat washer between the lug and the nut supplied on the
termination.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug
selection, refer to Table 6.
Page 66 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
2) For other available lugs, refer to drawings 031110100 through 031110300.
Page 67 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (GMT Fuses) (List KG)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to terminal blocks located on the front
of the assembly.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 26 to 14 AWG.
CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA)
Features
♦ Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring.
Restrictions
Recommended CO ground wire size is 6 AWG.
Recommended lug is 245346500 (2-hole, 10-32 clearance holes, 5/8” centers).
Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA)
Features
♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located
inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 6 AWG when all four (4) circuit breaker
positions are used and 2 AWG when only two (2) are used. When using lugs for #4 and #2 AWG wire,
Page 68 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
recommended to use a customer supplied flat washer between the lug and the nut supplied on the
termination.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug
selection, refer to Table 6.
2) For other available lugs, refer to drawings 031110100 through 031110300.
Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC)
Features
♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located
inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the front of the shelf.
Restrictions
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width, 0.61 inches.
Ordering Notes
1) Battery wire size varies depending on load, therefore no specific information is provided for wire size.
When making connections, observe correct polarity.
2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables.
Page 69 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Wiring Illustrations
Shelf Frame Grounding Stud (List 1 and 2 Only)
Rear View
Page 70 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Wiring (Lists 1 and 2)
List 1 List 2
Front Front
Rectifiers are numbered left to
right as viewed from the front.
AC input connections are AC input connections are
made using the supplied AC made using the supplied AC
input cable assemblies/ input cable assemblies/
line cords connected here. line cords connected here.
L1 Brown* Black*
* color of AC Input Cable
Assembly/Line Cord lead.
Page 71 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Wiring (Lists 5 and 6)
List 5 List 6
Front Front
3 3
4 4
6
AC input connections are 1 AC input connections are 2 1
2 5
made using the supplied AC made using the supplied AC
input cable assemblies/ input cable assemblies/
line cords connected here. line cords connected here.
Rectifiers are numbered as shown above Rectifiers are numbered as shown above
Front View
AC Input AC Input
Cable Assembly Line Cord
ENSURE THE PROPER VOLTAGE AC
BRANCH CIRCUIT AND LINE CORDS L2-N Blue* White*
WITH THE APPROPRIATE PLUG
ARE USED FOR YOUR APPLICATION. Ground Green/Yellow* Green*
L1 Brown* Black*
500W Rectifier: 120/208/240 VAC Input
1000W Rectifier: 120/208/240 VAC Input * color of AC Input Cable
Assembly/Line Cord lead.
Page 72 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
External Alarm and Monitoring Wiring (Lists 1 and 2)
SCU+
Controller
Notes
Relay Output/Digital Input Cable P/N 545494
is factory connected to terminals. Mating half
(w/ unterminated ends) available, P/N 545495.
A factory-connected jumper
supplies +BAT (Battery Return)
SCU+ Controller
to the positive side of Digital
(Top View)
Input #2.
When ordered, Temperature Probe
leads are factory connected
to SCU+ Connector Board
located in the Distribution Unit.
These are labeled T1 and T2.
NC = Normally Closed
COM = Common
NO = Normally Open
Page 73 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
External Alarm and Monitoring Wiring (Lists 5 and 6)
Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed
only.
Notes
Relay Output Cable P/N 541308 is factory connected to Relay Output terminals.
Mating half (w/ unterminated ends) available, P/N 541309.
If ordered, Digital Input Cable P/N 541310 is factory connected to Digital Input terminals.
Mating half (w/ unterminated ends) available, P/N 541311.
NC = Normally Closed
COM = Common
NO = Normally Open
ON
SW1
Switch settings must be in this position SCU+/ACU+ Customer Interface Board
to interface with the SCU+/ACU+ Controller (Top View)
* The SCU+/ACU+ relay assigned to "Major Summary" alarm (relay 1 by default) operates in the "Fail Safe Mode".
"Fail Safe Mode" means Relay 1 is de-energized during an alarm condition, opening contacts between
C and NO terminals, and closing contacts between C and NC terminals.
The remaining seven (7) relays of the SCU+/ACU+ energize during an alarm condition, closing contacts between
C and NO terminals, and opening contacts between C and NC terminals.
Page 74 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
EXTERNAL BATTERY
DISCONNECT UNIT
(Side cover removed in illustration
to show wiring details.)
Page 75 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Yellow Jumper/Alarm Yellow Alarm Lead
Lead (P/N 524384) (P/N 535294)
(Ordered separately (factory wired to
and supplied loose. circuit breaker
Must be wired
by the customer to
* No terminal alarm terminal)
on 524384
each circuit breaker jumper REMOVE
“C (Common)” COMPLETELY
alarm terminal) Connect to FROM ALL BATTERY
shelf per DISCONNECT UNITS
table below. AND DISCARD.
see
previous
page
see
previous
page
see
previous
1st EXTERNAL BATTERY page
DISCONNECT UNIT
Page 76 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Yellow Jumper/Alarm
Lead (P/N 524384)
(Ordered separately
and supplied loose.
Must be wired
by the customer to
each circuit breaker * No terminal
“C (Common)” on 524384
alarm terminal) jumper
Connect to
shelf per
table below.
see
previous
page
see
previous
page
see
1st BATTERY TRAY previous
BATTERY DISCONNECT page
CIRCUIT BREAKER
Page 77 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Yellow Jumper/Alarm
Lead (P/O Cabinet)
Orange Wire on
541434 not used
Connect to
shelf per
table below.
alarm
wire
alarm
wire
1st BATTERY CABINET
BATTERY DISCONNECT alarm
CIRCUIT BREAKER wire
Procedure
1. Remove quick connect terminal from YELLOW
battery cabinet alarm lead.
2. Wire per table below.
Page 78 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown)
Fuse Terminal
Position Load Return Load (-48V)
1 1 2
2 3 4
3 5 6
4 7 8
5 9 10
6 11 12
7 13 14
8 15 16
9 17 18
10 19 20
Page 79 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5
shown)
Front
Load Distribution
Leads Enter Here
GMT Fuse GMT Fuse Load GMT Fuse GMT Fuse Load
Positions Distribution Leads Positions Distribution Leads
(Max. 15A) Connect Here (Max. 10A) Connect Here
Page 80 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,
List 5 shown)
Front
Load Distribution
Leads Enter Here
Page 81 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module)
Page 82 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed
in a List 5 or 6, List 5 shown)
Front
Front
Page 83 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers),
and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)
Front
Front
Page 84 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (GMT Fuses) (List KG)
Loads
Loads
Loads
#1 - #5
#1 - #5
#1 - #5
"A" Side
"B" Side
"A" Side
#6 - #10
#6 - #10
"B" Side
"A" Side
#6 - #10
#6 - #10
Load Returns
Load Returns
Loads
#1 - #5
"B" Side
Connections are made to
screw compression terminal blocks.
Wire size range is 26 to 14 AWG.
Page 85 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown)
Rear View
Page 86 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown)
and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown)
List NF Distribution
Unit shown. List BF,
LF, BC, LC, and NC similar.
Front
OBSERVE PROPER
POLARITY WHEN
CO Ground Lead MAKING BATTERY
Right Side
CONNECTIONS
Page 87 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
SPECIFICATIONS
Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R48500/UM1R481000)
supplied with your Power System.
For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B)
supplied with your Power System.
For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (C-
drawing) supplied with your Power System.
1. SYSTEM
1.1 Environmental Ratings
1.1.1 Operating Ambient Temperature Range (Specification Compliant):
(A) -40°C (-40°F) to +65°C (+149°F) with derating output.
(B) -40°C (-40°F) to +40°C (+104°F) with full power performance.
1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +75°C (+167°F).
1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of
0% to 90%, non-condensing.
1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or
above a non-combustible surface.
This product must be located in a Controlled Environment with access to Craftspersons only.
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut,
or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic
equipment enclosure).
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the
relay rack and 2' for the rear of the relay rack.
Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4”
multiple drillings for the 2U shelf and 1-3/4" multiple drillings for the 1U shelf).
Mounting angles are positioned for a 5-inch front projection mounting only.
1.1.6 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be
blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient
Temperature Range stated above.
1.2 Compliance Information
1.2.1 Surge Protection: Refer to Paragraphs 2.3.6. and 3.3.6.
Note: This level of protection is a widely used standard for telecommunications power
equipment. As with all such equipment, it is the end user's responsibility to provide an
adequately sized Surge Suppression Device at the commercial power service entrance of
the building that reduces all incoming surges to levels below the classes/categories
stated for the equipment.
Page 88 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
1.2.2 Safety Compliance:
(A) This unit meets the requirements of UL 60950, Standard for Information Technology
Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data
Processing, or Information Processing Equipment.
(B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and
Certified by UL ("c UR") as a Component Type Power Supply.
1.2.3 EMC and Safety:
(A) Complies with the Low-Voltage Directive, 73/23/EEC. Complies with Emissions and
Immunity requirements as specified in GR-1089-Core Issue 4.
EMC
Emissions Test Level
EN 55022: 1998 Conducted Class B
CFR 47 – Part 15
GR-1089 Issue 4 Radiated Class B
Immunity
EN 61000-4-2 Electrostatic Discharge 8kV / 15kV
EN 61000-4-4 Electric Fast Transients 0.25kV / 0.5kV
GR-1089 Issue 4 Radiated Immunity 8.5V/m
Conducted Immunity 89dBuA
Surge IEEE C62.41 2kV / 6kV
SAFETY
Safety of Information Technology Equipment, including
EN 60950-1: 2001
Electrical Business Equipment
For NETSURE™ 211NGFB to remain compliant during a fan failure condition, the backup battery
connection must be utilized to provide sufficient power to the loads for up to eight (8) hours
when the system is operated at greater than 50% output power. If no backup battery
connection is used, the system must operate with a redundant module installed.
Page 89 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
1.3.3 Load Connections:
(A) List 1 and 2: Load and load return leads are connected to a screw-type terminal block
located on the front of the shelf.
(B) Lists 5 and 6: Load distribution (circuit breakers, if furnished) and load return leads
terminated in two-hole lugs are connected to threaded studs located inside the Distribution
Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and
are accessible from the front of the shelf.
Load distribution (GMT fuses) and load return leads are connected to receptacles located
inside the Distribution Unit. Load leads are brought into the right side (as viewed from the
front) of the shelf and are accessible from the front of the shelf.
1.3.4 Alarm and Monitoring Connections: Customer wiring cables are available.
(A) List 1 and 2: Relay output and digital input leads are connected to screw-type terminal
blocks located on the SCU+ located inside the shelf. These leads enter the rear of the shelf.
(B) Lists 5 and 6: Relay output and digital input leads are connected to screw-type terminal
blocks located on the Customer Interface Board located inside the shelf. These leads enter
the right side (as viewed from the front) of the shelf and are accessible from the front of the
shelf.
1.3.5 Dimensions and Weights: Refer to the PHYSICAL SIZE INFORMATION section of this
document.
2. DISTRIBUTION UNIT
2.1 List BG and NG in a List 1 and List 2 Shelf
2.1.1 Ratings: Refer to the Restrictions in the LIST DESCRIPTIONS section of this document.
2.1.2 Battery Connection
(A) 8 AWG cables (48” long) factory wired and terminated in an Anderson type connector.
2.1.3 Standard Features
(A) Provides ten (10) GMT load fuse positions (18/100A to 15A fuses).
(B) Provides front access screw-clamp type load and load return terminals.
(C) Provides the connections for system battery input.
(D) Equipped with an optional Low Voltage Battery Disconnect (LVBD) contactor.
(E) Provides a load fuse alarm indicator.
2.2 List 5 and 6 Shelves
2.2.1 Ratings: Refer to the Restrictions in the LIST DESCRIPTIONS section of this document.
2.2.2 Standard Features
(A) Lists BC, LC, and NC: Provides thirteen (13) GMT load distribution fuse positions.
(B) Lists BF, LF, and NF: Provides four (4) load distribution circuit breaker positions, and five
(5) GMT load distribution fuse positions.
(C) Lists BA, LA, and NA: Provides two (2) battery disconnect circuit breaker positions.
Provides two (2) load distribution circuit breaker positions. Provides five (5) GMT load
distribution fuse positions.
(D) Dimensions: 83mm (H) x 157mm (W) x 274mm (D).
3.25” (H) x 6.2” (W) x 10.8” (D).
(E) Weight (w/out LVD): 3 kg (7 lbs).
Page 90 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
3. GMT LOAD DISTRIBUTION FUSE PANEL (LIST KG)
3.1 Electrical
3.1.1 Input/Output Voltage: Nominal –48VDC
3.1.2 Current: 40A per side, 80A total (Note: The split (A/B) input bus feature provided on panel is
factory connected for single input only.)
3.1.3 Fuse Alarm Circuit: If one or more distribution fuses opens, one set of Form-C relay contacts
changes state, and resistive battery is provided to an alarm terminal. Alarm circuit is factory
connected to activate the Power System Controller fuse alarm.
Page 91 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
PHYSICAL SIZE INFORMATION
Overall Dimensions – List 1
Top View
5
Left Side View 17.3 0.5 12
18.3
19.0 Right Side View
Front View
1.25 1.72
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 16
Shipping:
Bottom View 3. Finish: Front Panels are Gray
Shelf is Galvaneal.
Page 92 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Overall Dimensions – List 2
Top View
Front View
1.25 1.72
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 20.5
Bottom View Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.
Page 93 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Overall Dimensions – List 5
Top View
17.3 5
Left Side View 0.5 12
18.3
19.0 Right Side View
19.4
Front View
3.00 3.46
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 30
Bottom View Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.
Page 94 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Overall Dimensions – List 6
Top View
21.3 5
Left Side View
22.3 0.5 12
23.0
23.4 Right Side View
Front View
3.00 3.46
Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 39
Bottom View Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.
Page 95 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Overall Dimensions – List KG
Notes:
1. Dimensions in inches
unless otherwise specified.
2. Finish: Gray 8.31
3. Weight:
Net: 10.00
Shipping:
5.05
Bottom View
R 0.125 (TYP)
Mounting Angle Detail
0.235 0.235
0.125 0.500 0.500 0.125
1.250 1.250
0.125 0.125
Page 96 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Overall Dimensions – 19” Battery Tray
Optional Battery Disconnect Circuit Breakers
(Shown on Right Side, Available on Either Side)
A
See
Note 3
10.50
12.25
14.00
(as ordered)
ISO View
Front View B
Notes:
See Note 3
1. All dimensions are in inches,
unless otherwise specified. Right Side View
2. P/N 541036 tray shown.
P/Ns 541034 and 540841 similar.
3.
Dimension Dimension
Tray P/N
A B
541036 7.03 16.47
541034 7.03 20.95
540841 6.90 12.50
4. Weight in LBS.
(per tray, less batteries).
With Circuit Without Circuit
Part No.
Breaker Option Breaker Option
541036 20.5 lbs 18.5 lbs
541034 25.3 lbs 23.3 lbs
540841 18.5 lbs 16.5 lbs
5. Finish: Gray
6. Maximum trays available per rack is three (3).
Page 97 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Overall Dimensions – 23” Battery Tray
Optional Battery Disconnect Circuit Breakers
(Shown on Right Side, Available on Either Side)
A
See
Note 3
10.50
12.25
14.00
(as ordered)
ISO View
B
Front View See Note 3
Notes:
1. All dimensions are in inches, Right Side View
unless otherwise specified.
2. P/N 528496 tray shown.
P/N 540842 similar.
3.
Dimension Dimension
Tray P/N
A B
528496 9.781 24.437
540842 6.90 12.50
4. Weight in LBS.
(per tray, less batteries).
With Circuit Without Circuit
Part No.
Breaker Option Breaker Option
528496 33 lbs 29 lbs
540842 20 lbs 18 lbs
5. Finish: Gray
6. Maximum trays available per rack is three (3).
Page 98 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
BATTERY MANUFACTURER INFORMATION
Some equipment described in this System Application Guide is designed to accommodate batteries from
various manufacturers. The following are referenced in this document.
C&D: C&D Technologies, Inc., Powercom Div., 1400 Union Meeting Road, Blue Bell, PA 19422-0858
Deka®: East Penn Mfg. Co., Inc., Lyon Station, PA 19536-0147
Douglas®: Douglas Battery Mfg. Co., 500 Battery Dr., Winston-Salem, NC 27117-2159
MarathonTM: GNB Industrial Power, a Division of Exide Technologies, Princeton, NJ 08543.
Northstar: NorthStar Battery Co. LLC, 4000 Continental Way, Springfield, MO 65803
RELATED DOCUMENTATION
Installation Instructions: Section 6031
User Instructions: Section 6032
Battery Cabinet Spec. No. 541434
Installation and User Instructions: Section 6023
Battery Cabinet Spec. No. 545534
Installation and User Instructions: Section 6033
Battery Cabinet Spec. No. 545506
Installation and User Instructions: Section 6036
Rectifier User Instructions: UM1R481000
SCU+ Controller User Instructions: UM1M521B
ACU+ Controller User Instructions: UM1M820B
Page 99 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
REVISION RECORD
Change
Issue Number Description of Change Date Approved
(ECO)
AA LLP212765 New 09/16/2009 John Jasko
List BC, LC, and NC RESTRICTIONS updated.
AB LLP213064 Reference to custom SCU+ configurations 10/09/2009 John Jasko
added. Custom digital input cable kit added.
Lists BF, LF, and NF now available (note
stating Lists were unavailable removed from
AC LLP213144 document). Restriction added to Battery 01/06/2010 John Jasko
Cabinet P/N 541434 that it can only be used
with List 1 and 2.
Added 545644, 58213660067, 545728,
540993, 545616, 547525, 548457, 541285,
545534, and 545506.
AD LLP213376 Updated breaker alarm wiring and system 05/19/2010 Shanon Ravacio
ratings and wiring information.
Changed input cord gauges per LLP213702
Add P/N 547645
Add AP6C57EA/EB Ring and Distribution
AE LLP214159 09/03/2010 Shanon Ravacio
Module
List LA now available (notes stating List was
unavailable removed from document). Added Tim Strouse
Dec 14, 2010
List KG, List 91, ACU+, and SiteWeb™ TEMP.
AF LLP214106 John Kirkpatrick
Removed Rectifier and Controller specification
Dec 14, 2010
information, and referenced the separate
Rectifier and Controller User Manuals.