SAG582136600

System Application Guide


Spec. No. 582136600 (Model 211NGFB)
Issue AF, December 9, 2010
Home
SYSTEM OVERVIEW
Description: The NETSURE™ 211NGFB DC Power System is a complete integrated power system
containing rectifiers, intelligent control, metering, monitoring, and distribution. This power
system consists of the following mounted in a 1RU or 2RU high by 19” or 23” wide shelf.
• 500W or 1000W Rectifier Modules
The 1RU high by 19” wide shelf accommodates
two (2) 500W or 1000W Rectifier Modules.
The 1RU high by 23” wide shelf accommodates
three (3) 500W or 1000W Rectifier Modules.
The 2RU high by 19” wide shelf accommodates
four (4) 500W or 1000W Rectifier Modules.
The 2RU high by 23” wide shelf accommodates
six (6) 500W or 1000W Rectifier Modules.
The Rectifier Modules provide load power, battery float current, and battery recharge
current during normal operating conditions. The Rectifier Modules are designed to
provide constant power. They are designed with the latest patented switch-mode
technology using DSP (Digital Signal Processing) functionality for efficient operation.
This means that, within the normal operating ambient temperature range and input
voltage range, the maximum available output power is a constant 500W or 1000W.
Within these ranges, the Rectifier Modules operate in one of three modes, depending
upon load demands. Transition between modes is completely automatic. If ambient
temperature rises above or input voltage falls below acceptable values, Rectifier
Modules continue to operate but at derated output power levels.
1) Constant Voltage Mode: For any initial output voltage setting from 42 to 58
volts, output voltage remains constant regardless of load. This is the normal
operating condition, in which loads are being supplied and batteries are float
charged. Rectifier Modules operate in the Constant Voltage Mode unless load
increases to the point where the product of load current and output voltage is
approximately 500W or 1000W.
2) Constant Power Mode: As
load increases above
approximately 500W or 1000W
(non-adjustable), output current
continues to increase, but
output voltage decreases as
required to maintain constant
output power. Rectifier
Modules operate in the List 1 (List 2 similar)
Constant Power Mode unless
load continues to increase to
the point where the current limit
setting is reached.
3) Constant Current Mode: If
load increases above the
current limit setting, output
voltage decreases linearly to
maintain output current at
current limit.
List 5 (List 6 similar)

Page 1 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
• ACU+ (Advanced Control Unit Plus)
The ACU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions,
monitoring functions, and local/remote alarms as well as PCU control, data
acquisition, system alarm management, and advanced battery and energy
management. The ACU+ contains an LCD display and keypad for local access. It
provides connection for binary inputs, programmable relay outputs, and a charge
control function. The controller also supports rectifier temperature compensation if
the system is equipped with a temperature probe (or multiple temperature probes
connected via Temperature Concentrators (SiteWeb™ TEMP), and ambient air
temperature monitoring if equipped with a second temperature probe. The ACU+
provides Ethernet connection and supports software upgrade via its USB port. It also
comes with a comprehensive web page and SNMP capability for remote system
management.
• SCU+ (Standard Control Unit Plus)
The SCU+ provides Rectifier Module and optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) control, metering functions,
monitoring functions, and local/remote alarms. The SCU+ contains an LCD display
and keypad for local access. It provides connection for binary inputs, programmable
relay outputs, and a charge control function. The controller also supports rectifier
temperature compensation if the system is equipped with a temperature probe (or
multiple temperature probes connected via Temperature Concentrators (SiteWeb™
TEMP), and ambient air temperature monitoring if equipped with a second
temperature probe. The SCU+ also provides Ethernet connection and SNMP
capability.
• Distribution Unit
Various Distribution Unit options are available, as described in this document. The
Distribution Unit can be equipped with an optional Low Voltage Battery Disconnect
(LVBD) or Low Voltage Load Disconnect (LVLD) contactor.

Family: NETSURE™
Spec. No.: 582136600
Model: 211NGFB
Input Voltage Nominal 120/208/240 volts AC, single phase, 3-wire, 50/60 Hz, with an
operating range of 100 to 250 volts. Acceptable input frequency range is
45 to 65 Hz.
Output Voltage: -48 Volts DC
Output Capacity:
Rectifier Module: 500W @ Vout >48Vdc (10.5A @ -48Vdc)
or
1000W @ Vout >48Vdc (20.9A @ -48Vdc)

Page 2 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
System: See the following table.

208/240VAC Input 120VAC Input


+40°C (+104°F) +65°C (+149°F) +40°C (+104°F) +65°C (+149°F)
System
500W 1000W 500W 1000W 500W 1000W 500W 1000W
Rect. Rect. Rect. Rect. Rect. Rect. Rect. Rect.
58213660001 20.8A 41.6A 12.6A 25A 20.8A 27.4A 12.6A 16.4A
58213660002 31.2A 62.4A 18.9A 37.5A 31.2A 41.1A 18.9A 24.6A
58213660005 41.6A 83.2A 25.2A 50A 41.6A 54.8A 25.2A 32.8A
58213660006 62.4A 124.8A 37.8A 75A 62.4A 82.2A 37.8A 49.2A

Agency Approval: UL 60950 Recognized, CAN/CSA 22.2


Framework Type: Relay Rack Mounted
Mounting Width: 19” or 23”, nominal
Mounting Depth: 12”
Mounting Height: 1.75” (1RU) or 3.5” (2RU)
Access: Front for Installation, Operation, and Maintenance
Control: Microprocessor
Color: Front Panels are Gray; Shelf is Galvaneal
List Options: 1RU High 19” Wide Shelf, 1RU High 23” Wide Shelf, 2RU High 19” Wide
Shelf, 2RU High 23” Wide Shelf, SCU + Controller, ACU+ Controller,
Rectifier Module (500W), Rectifier Module (1000W), Five (5) Load Lead
Assemblies for 10A GMT Fuse Positions, Eight (8) Load Lead
Assemblies for 10A GMT Fuse Positions, Five (5) Load Lead Assemblies
for 15A GMT Fuse Positions), Shelf Side Battery Cables, Battery Side
Battery Cables, Battery Cable, Optional External Battery Cables with
Anderson Connector for (1) Battery String, Optional External Battery
Cables with Anderson Connector for (2) Battery Strings, Relay Rack
Earthquake Anchor Kit, Optional Temperature Probes, Battery Tray for
23” Relay Rack, Battery Tray for 19” Relay Rack, 1RU High Distribution
Unit with (10) GMT Fuse Load Positions and with Low Voltage Battery
Disconnect (LVBD), 1RU High Distribution Unit with (10) GMT Fuse Load
Positions and w/out Low Voltage Disconnect, 2RU High Distribution Unit
with (5) GMT Fuse Load Positions, (2) Circuit Breaker Load Positions,
(2) Circuit Breaker Battery Disconnect Positions, and with Low Voltage
Battery Disconnect (LVBD), 2RU High Distribution Unit with (5) GMT
Fuse Load Positions, (2) Circuit Breaker Load Positions, (2) Circuit
Breaker Battery Disconnect Positions, and with Low Voltage Load
Disconnect (LVLD), 2RU High Distribution Unit with (5) GMT Fuse Load
Positions, (2) Circuit Breaker Load Positions, (2) Circuit Breaker Battery
Disconnect Positions, and w/out Low Voltage Disconnect, 2RU High
Distribution Unit with (5) GMT Fuse Load Positions, (4) Circuit Breaker
Load Positions, and with Low Voltage Battery Disconnect (LVBD), 2RU
High Distribution Unit with (5) GMT Fuse Load Positions, (4) Circuit
Breaker Load Positions, and with Low Voltage Load Disconnect (LVLD),
2RU High Distribution Unit with (5) GMT Fuse Load Positions, (4) Circuit
Breaker Load Positions, and w/out Low Voltage Disconnect, 2RU High

Page 3 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Distribution Unit with (13) GMT Fuse Load Positions and with
Low Voltage Battery Disconnect (LVBD), 2RU High Distribution
Unit with (13) GMT Fuse Load Positions and with Low Voltage Load
Disconnect (LVLD), 2RU High Distribution Unit with (13) GMT Fuse Load
Positions and w/out Low Voltage Disconnect, 1RU High Load Distribution
Panel with (20) GMT Fuse Load Positions
Accessory Options: Relay Racks, Mounting and Adapter Kits, Distribution Devices, AC Input
Cables and Line Cords, Ring & Distribution Module, External Battery
Disconnect Unit, Battery Cabinets, SiteWeb™ TEMP Temperature
Concentrator, Anderson Battery Connector, Digital Input and Relay
Output Cables, Replacement Modules, Wiring Notes, Wiring Illustrations
Environment: -40°C (-40°F) to +65°C (+149°F),
with deratings (see SPECIFICATIONS section)

Page 4 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
58213660001

Distribution Unit

SCU+ P/N 1M521BNA

Side AC Input Connectors Rectifier Module


(P/O List 1) and (500W)
AC Input Cables/Line Cords or
Rectifier Module
(1000W)

58213660002

Distribution Unit

SCU+ P/N 1M521BNA

Rectifier Module
Side AC Input Connectors (500W)
(P/O List 2) and or
AC Input Cables/Line Cords Rectifier Module
(1000W)

Page 5 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
58213660005

Distribution Unit

SCU+ P/N 1M521BNA


Side AC Input Connectors or
(P/O List 5) and Rectifier Module ACU+ P/N 1M820BNA
AC Input Cables/Line Cords (500W)
or
Rectifier Module
(1000W)
58213660006

Distribution Unit

SCU+ P/N 1M521BNA


Rectifier Module or
Side AC Input Connectors (500W) ACU+ P/N 1M820BNA
(P/O List 6) and or
AC Input Cables/Line Cords Rectifier Module
(1000W)

Page 6 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
DISTRIBUTION UNIT (Lists 1 and 2)

List BG: (10) GMT Fuse Load Positions


Low Voltage Battery Disconnect (LVBD)
(1) Set Battery Cables

List NG: (10) GMT Fuse Load Positions


NO Low Voltage Disconnect
(1) Set Battery Cables

DISTRIBUTION UNIT (Lists 5 and 6)

List BF: (13) GMT Fuse Load Positions


Low Voltage Battery Disconnect (LVBD)
(3) Battery Landing Points

List LF: (13) GMT Fuse Load Positions


Low Voltage Load Disconnect (LVLD)
(3) Battery Landing Points

List NF: (13) GMT Fuse Load Positions


NO Low Voltage Disconnect
(3) Battery Landing Points

List BC: (5) GMT Fuse Load Positions


(4) Bullet-Nose Circuit Breaker Load Positions
Low Voltage Battery Disconnect (LVBD)
(3) Battery Landing Points

List LC: (5) GMT Fuse Load Positions


(4) Bullet-Nose Circuit Breaker Load Positions
Low Voltage Load Disconnect (LVLD)
(3) Battery Landing Points

List NC: (5) GMT Fuse Load Positions


(4) Bullet-Nose Circuit Breaker Load Positions
NO Low Voltage Disconnect
(3) Battery Landing Points

List BA: (5) GMT Fuse Load Positions


(2) Bullet-Nose Circuit Breaker Load Positions
(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
Low Voltage Battery Disconnect (LVBD)

List LA: (5) GMT Fuse Load Positions


(2) Bullet-Nose Circuit Breaker Load Positions
(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
Low Voltage Load Disconnect (LVLD)

List NA: (5) GMT Fuse Load Positions


(2) Bullet-Nose Circuit Breaker Load Positions
(2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
NO Low Voltage Disconnect

Page 7 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Other List Options
List 60: Five (5) Load Lead Assemblies for 10A GMT Fuse Positions
(for use w/ Lists BC, LC, NC, BA, LA, and NA)
List 61: Eight (8) Load Lead Assemblies for 10A GMT Fuse Positions
(for use w/ Lists BF, LF, and NF)
List 62: Five (5) Load Lead Assemblies for 15A GMT Fuse Positions
(for use w/ Lists BF, LF, and NF)
List 65: Shelf Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 66: Battery Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 67: Battery Side Battery Cables
(for use w/ Lists BF, LF, NF, BC, LC, and NC)
List 71: Optional External Battery Cables with Anderson Connector
for (1) Battery String (for use w/ Lists BG and NG)
List 72: Optional External Battery Cables with Anderson Connector
for (2) Battery Strings (for use w/ Lists BG and NG)
List 89: Relay Rack Earthquake Anchor Kit
List 90: Temperature Probe (9 ft.)
List 91: Temperature Probe (30 ft.)
List 93: Battery Tray (23”)
List 94: Battery Tray (19”)
List KG: GMT Fuse Load Distribution Panel

Accessory Options SEE ALSO


Relay Racks System Overview
Mounting and Adapter Kits Table of Contents
Distribution Devices Ordering Information
AC Input Cables and Line Cords List Descriptions
Ring & Distribution Module Accessory Descriptions
External Battery Disconnect Unit Specifications
SiteWeb™ TEMP Temperature Physical Size Information
Concentrator
Related Documentation
Anderson Battery Connector
Digital Input/Relay Output Cables
Replacement Modules
Wiring Notes
Wiring Illustrations

Page 8 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010

TABLE OF CONTENTS

Ordering Information
System Physical Size Related
Picture Specifications
Overview List Accessory Information Documentation
Descriptions Descriptions

SYSTEM OVERVIEW.................................................................................................................................................1
58213660001.........................................................................................................................................................5
TABLE OF CONTENTS .............................................................................................................................................9
ORDERING INFORMATION ....................................................................................................................................12
List Options........................................................................................................................................................12
Accessory Options ............................................................................................................................................16
LIST DESCRIPTIONS ..............................................................................................................................................17
List 1: 1RU High by 19” Wide Shelf...............................................................................................................17
List 2: 1RU High by 23” Wide Shelf...............................................................................................................18
List 5: 2RU High by 19” Wide Shelf...............................................................................................................19
List 6: 2RU High by 23” Wide Shelf...............................................................................................................20
Rectifier Module (500W), P/N 1R48500 .........................................................................................................21
Rectifier Module (1000W), P/N 1R481000 .....................................................................................................21
ACU+ (Advanced Control Unit Plus), P/N 1M820BNA ..................................................................................21
SCU+ (Standard Control Unit Plus), P/N 1M521BNA ....................................................................................22
List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions ...................................22
List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions .................................22
List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions ...................................23
List 65: Shelf Side Battery Cables, P/N 540814 ...........................................................................................23
List 66: Battery Side Battery Cables, P/N 540954 ........................................................................................23
List 67: Battery Cable, P/N 545709 ................................................................................................................24
List 71: Optional External Battery Cable Assembly with Anderson Connector for (1) Battery String,
P/N 545493 ....................................................................................................................................................24
List 72: Optional External Battery Cable Assembly with Anderson Connector for (2) Battery
Strings, P/N 535124 .......................................................................................................................................24
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167 ........................................................................25
List 90: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04118247 (probe
side half, 9 ft. long) .........................................................................................................................................25
List 91: Optional Temperature Probe, P/N 04118246 (shelf side half) and P/N 04116740 (probe
side half, 30 ft. long) .......................................................................................................................................25
List 93: Battery Tray for 23” Relay Rack .......................................................................................................26
List 94: Battery Tray for 19” Relay Rack .......................................................................................................29
List BF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery
Disconnect (LVBD).........................................................................................................................................32
List LF: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Load
Disconnect (LVLD) .........................................................................................................................................33
List NF: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage
Disconnect......................................................................................................................................................34
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and with Low Voltage Battery Disconnect (LVBD) .....................................................35
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and with Low Voltage Load Disconnect (LVLD).........................................................36
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, and w/out Low Voltage Disconnect ............................................................................37

Page 9 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)

List BA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Battery
Disconnect (LVBD).........................................................................................................................................38
List LA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and with Low Voltage Load
Disconnect (LVLD) .........................................................................................................................................39
List NA: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker Load
Distribution Positions, Circuit Breaker Battery Disconnect Positions, and w/out Low Voltage
Disconnect......................................................................................................................................................40
List BG: Distribution Unit with GMT Fuse Load Distribution Positions and with Low Voltage Battery
Disconnect (LVBD).........................................................................................................................................41
List NG: Distribution Unit with GMT Fuse Load Distribution Positions and w/out Low Voltage
Disconnect......................................................................................................................................................42
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions ...............................................43
ACCESSORY DESCRIPTIONS ...............................................................................................................................44
Relay Racks .......................................................................................................................................................44
Mounting and Adapter Kits ..............................................................................................................................45
Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285 ....................................................................45
Optional 19” to 23” Rack Adapter Kit, P/N 540993 ........................................................................................45
Optional 19” to 23” Rack Adapter Kit, P/N 545728 ........................................................................................45
Rear Battery Cable Exit Kit P/N 547645 ........................................................................................................45
Distribution Devices ..........................................................................................................................................46
GMT Load Distribution Fuses ........................................................................................................................46
Bullet Nose-Type Circuit Breakers .................................................................................................................47
Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332 .................................................................48
Optional Bulk Output Busbar, P/N 535015 ....................................................................................................48
AC Input Cables and Line Cords .....................................................................................................................49
AC Input Cable Assembly, P/N 535232 .........................................................................................................49
AC Input Line Cord, 208/240VAC, P/N 540946 .............................................................................................49
AC Input Line Cord, 208/240VAC, P/N 545616 .............................................................................................50
AC Input Line Cord, 120VAC, P/N 545252 ....................................................................................................50
AC Input Line Cord, 120VAC, P/N 545478 ....................................................................................................51
AC Input Line Cord, 120VAC, P/N 545479 ....................................................................................................51
AC Input Line Cord, 208/240VAC, P/N 545480 .............................................................................................52
AC Input Line Cord, 120VAC, P/N 545481 ....................................................................................................52
AC Input Line Cord, 208/240VAC, P/N 545553 .............................................................................................53
AC Input Line Cord, 120VAC, P/N 547525 ....................................................................................................53
AC Input Line Cord, 120VAC, P/N 548457 ....................................................................................................54
AP6C57EA/EB Ring & Distribution Module ....................................................................................................55
External Battery Disconnect Unit, P/N 535282 ...............................................................................................57
NETSURE™ 201BC Battery Cabinet (Spec. No. 541434) ..................................................................................58
NETSURE™ 211BC Battery Cabinet (Spec. No. 545534) ..................................................................................59
NETSURE™ 211BC Battery Cabinet (Spec. No. 545506) ..................................................................................60
Site Web™ TEMP Temperature Concentrator (P/N 547490) .........................................................................61
Anderson Battery Connector ...........................................................................................................................62
Digital Input and Relay Output Cables ............................................................................................................63
Replacement Modules ......................................................................................................................................63
Wiring Notes ......................................................................................................................................................64
Shelf Frame Grounding Stud (List 1 and 2 Only) ...........................................................................................64
AC Input Branch Circuit Protection and Wiring ..............................................................................................64
External Alarm and Monitoring Wiring............................................................................................................64
Load Distribution Wiring (GMT Fuses) (Lists BG and NG only) ....................................................................65
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only) ..............................................................65
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA).................................................66
Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module) ...................................66

Page 10 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010

Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) ..........................................66
Load Distribution Wiring (GMT Fuses) (List KG) ...........................................................................................68
CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA) ............................................................68
Input Battery Wiring (List BG and NG) ...........................................................................................................68
Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) ..................................68
Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC) .............................................69
Wiring Illustrations ............................................................................................................................................70
Shelf Frame Grounding Stud (List 1 and 2 Only) ...........................................................................................70
AC Input Wiring (Lists 1 and 2) ......................................................................................................................71
AC Input Wiring (Lists 5 and 6) ......................................................................................................................72
External Alarm and Monitoring Wiring (Lists 1 and 2)....................................................................................73
External Alarm and Monitoring Wiring (Lists 5 and 6)....................................................................................74
Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown) ................79
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5 shown) ..........80
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,
List 5 shown) ..................................................................................................................................................81
Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module) ............................................82
Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed
in a List 5 or 6, List 5 shown) .........................................................................................................................83
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers), and CO Ground
Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)............................................................84
Load Distribution Wiring (GMT Fuses) (List KG) ...........................................................................................85
Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown) .............................................86
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown) and
CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown) .........................................87
SPECIFICATIONS....................................................................................................................................................88
1. System ...........................................................................................................................................................88
1.1 Environmental Ratings .............................................................................................................................88
1.2 Compliance Information ...........................................................................................................................88
1.3 Standard Features....................................................................................................................................89
2. Distribution Unit ............................................................................................................................................90
2.1 List BG and NG in a List 1 and List 2 Shelf ..............................................................................................90
2.2 List 5 and 6 Shelves .................................................................................................................................90
3. GMT Load Distribution Fuse Panel (List KG) .............................................................................................91
3.1 Electrical ...................................................................................................................................................91
PHYSICAL SIZE INFORMATION ............................................................................................................................92
Overall Dimensions – List 1 .............................................................................................................................92
Overall Dimensions – List 2 .............................................................................................................................93
Overall Dimensions – List 5 .............................................................................................................................94
Overall Dimensions – List 6 .............................................................................................................................95
Overall Dimensions – List KG ..........................................................................................................................96
Overall Dimensions – 19” Battery Tray ...........................................................................................................97
Overall Dimensions – 23” Battery Tray ...........................................................................................................98
BATTERY MANUFACTURER INFORMATION ......................................................................................................99
RELATED DOCUMENTATION................................................................................................................................99
REVISION RECORD ..............................................................................................................................................100

Page 11 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
ORDERING INFORMATION
List Options
Order the following by the items Part Number as specified in the following table.
When viewing electronically, click on the link to jump to the detailed description page.

List Part
Description
Number Number
Shelf Options
1RU 19” Mini Shelf.
1 58213660001 (Shelf requires one [1] AC Feed)
(Houses up to [2] Rectifiers, Controller, and Distribution Unit.)
1RU 23” Mini Shelf.
2 58213660002 (Shelf requires one [1] AC Feed)
(Houses up to [3] Rectifiers, Controller, and Distribution Unit.)
2RU 19” Mini Shelf.
5 58213660005 (Shelf requires two [2] AC Feeds)
(Houses up to [4] Rectifiers, Controller, and Distribution Unit.)
2RU 23” Mini Shelf.
6 58213660006 (Shelf requires two [2] AC Feeds)
(Houses up to [6] Rectifiers, Controller, and Distribution Unit.)
Controller Options
Order
1M820BNA ACU+ (Advanced Control Unit Plus)
by P/N
Order
1M521BNA SCU+ (Standard Control Unit Plus)
by P/N
Rectifier Options
Order
1R48500 Model R48-500 Rectifier Module (500W).
by P/N
Order
1R481000 Model R48-1000 Rectifier Module (1000W).
by P/N
Distribution Unit Options
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
• (13) GMT Fuse Load Positions
BF 582136600BF
(5) 0A to 15A
(8) 0A to 10A
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 5 AND 6.

Page 12 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010

List Part
Description
Number Number
Distribution Unit Options (Cont’d)
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
• (13) GMT Fuse Load Positions
LF 582136600LF
(5) 0A to 15A
(8) 0A to 10A
• Low Voltage Load Disconnect (LVLD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
• (13) GMT Fuse Load Positions
NF 582136600NF
(5) 0A to 15A
(8) 0A to 10A
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
BC 582136600BC • (5) GMT Fuse Load Positions (0A to 10A)
• (4) Bullet-Nose Circuit Breaker Load Positions
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
LC 582136600LC • (5) GMT Fuse Load Positions (0A to 10A)
• (4) Bullet-Nose Circuit Breaker Load Positions
• Low Voltage Load Disconnect (LVLD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (3) Battery Connection Points
NC 582136600NC • (5) GMT Fuse Load Positions (0A to 10A)
• (4) Bullet-Nose Circuit Breaker Load Positions
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.

Page 13 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)

List Part
Description
Number Number
Distribution Unit Options (Cont’d)
Distribution Unit w/
• (1) Battery Shunt
• (5) GMT Fuse Load Positions (0A to 10A)
BA 582136600BA • (2) Bullet-Nose Circuit Breaker Load Positions
• (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (5) GMT Fuse Load Positions (0A to 10A)
• (2) Bullet-Nose Circuit Breaker Load Positions
LA 582136600LA
• (2) Bullet-Nose Circuit Breaker
Battery Disconnect Positions
• Low Voltage Load Disconnect (LVLD)
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Battery Shunt
• (5) GMT Fuse Load Positions (0A to 10A)
NA 582136600NA • (2) Bullet-Nose Circuit Breaker Load Positions
• (2) Bullet-Nose Circuit Breaker Battery Disconnect Positions
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.
Distribution Unit w/
• (1) Set Battery Cables
BG 582136600BG • (10) GMT Fuse Load Positions (0A to 15A)
• Low Voltage Battery Disconnect (LVBD)
FOR USE WITH LISTS 1 AND 2.
Distribution Unit w/
• (1) Set Battery Cables
NG 582136600NG • (10) GMT Fuse Load Positions (0A to 15A)
• NO Low Voltage Disconnect
FOR USE WITH LISTS 1 AND 2.
Other Options
Five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
60 58213660060 Leads are 12’ long and 16 AWG.
For use with Lists BC, LC, NC, BA, LA, and NA.
Eight (8) Load Lead Assemblies for 10A GMT Fuses Positions.
61 58213660061 Leads are 12’ long and 16 AWG.
For use with Lists BF, LF, and NF.

Page 14 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010

List Part
Description
Number Number
Other Options (Cont’d)
Five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
62 58213660062 Leads are 12’ long and 14 AWG.
For use with Lists BF, LF, and NF.
Shelf Side Battery Cables. Cables are 3’ long and 2 AWG terminated in a
65 58213660065 2-position Anderson connector. Remaining end terminated in lugs for
connection to shelf. For use with Lists BF, LF, NF, BC, LC, and NC.
Battery Side Battery Cables. Cables are 12’ long and 2 AWG terminated in
66 58213660066 a 2-position Anderson connector. Remaining end un-terminated for
connection to batteries. For use with Lists BF, LF, NF, BC, LC, and NC.
Output Cable to Battery Cabinet – cables are 4’ long and 8 AWG
terminated in a 2-position Anderson connector. Remaining end terminated
67 58213660067
in lugs for connection to shelf. For Use with Lists BC, LC, NC, BF, LF, and
NF.
Optional External Battery Cables with Anderson Connector for (1) Battery
71 58213600071
String. For use with Lists BG and NG.
Optional External Battery Cables with Anderson Connector for (2) Battery
72 58213600072
Strings. For use with Lists BG and NG.
89 58213660089 Relay Rack Earthquake Anchor Kit.
90 58213660090 Temperature Probe, 9 ft long.
91 58213660091 Temperature Probe, 30 ft. long.
93 58213660093 Battery Tray (23”).
94 58213660094 Battery Tray (19”).
Distribution Panel w/
• (20) GMT Fuse Load Positions (0A to 15A)
KG 582136600KG
• NO Low Voltage Disconnect
FOR USE WITH LISTS 5 AND 6.

Page 15 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Accessory Options
Order the following by the items Part Number as specified in the following table.
When viewing electronically, click on the link to jump to the detailed description page.

Description Part Number


Relay Racks
Distribution Devices
AC Input Cables and Line Cords
Ring & Distribution Module
External Battery Disconnect Unit
Battery Cabinet See ACCESSORY
DESCRIPTIONS Section
SiteWeb™ TEMP Temperature Concentrator

Anderson Battery Connector


Digital Input and Relay Output Cables
Replacement Modules
Wiring Notes
Wiring Illustrations

Page 16 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
LIST DESCRIPTIONS
List 1: 1RU High by 19” Wide Shelf
Features
♦ Consists of a 1RU high by 19” wide shelf.
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are
terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery
connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.
♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.
A mating half is available.
♦ The shelf houses up to two (2) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 1 shelf holds up to two (2) Rectifier Modules.
Ordering Notes
1) Order List 1 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) per shelf. Also specify the appropriate configuration file
for your site.
3) Order up to two (2) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 1 shelf requires one (1) AC Input
Cable or Line Cord.
5) Order one (1) Distribution Unit (List BG or NG) per shelf.
6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
7) Order Relay Rack Anchor Kit(s) (List 89) as required.
8) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
9) Order Battery Trays (List 94) as required.
10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 17 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List 2: 1RU High by 23” Wide Shelf
Features
♦ Consists of a 1RU high by 23” wide shelf.
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are
terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery
connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Mounted to the side of the shelf is an AC input housing with plug-in connector for a single AC input feed.
♦ The “Digital Input and Relay Outputs Cable” P/N 545494 (shelf side) is factory connected inside the shelf.
A mating half is available.
♦ The shelf houses up to three (3) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 2 shelf holds up to three (3) Rectifier Modules.
Ordering Notes
1) Order List 2 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) per shelf. Also specify the appropriate configuration file
for your site.
3) Order up to three (3) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 2 shelf requires one (1) AC Input
Cable or Line Cord.
5) Order one (1) Distribution Unit (List BG or NG) per shelf.
6) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
7) Order Relay Rack Anchor Kit(s) (List 89) as required.
8) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
9) Order Battery Trays (List 93) as required.
10) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
11) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
12) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
13) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
14) Order Mating Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
15) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 18 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 5: 2RU High by 19” Wide Shelf
Features
♦ Consists of a 2RU high by 19” wide shelf.
♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.
♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.
♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is
available. A “Digital Input Cable” (shelf side and customer side) is also available.
♦ The shelf houses up to four (4) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 5 shelf holds up to four (4) Rectifier Modules.
Ordering Notes
1) Order List 5 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) or (1) ACU+ controller (P/N 1M820BNA) per shelf. Also
specify the appropriate configuration file for your site.
3) Order up to four (4) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 5 shelf requires two (2) AC Input
Cables or Line Cords.
5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf.
6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.
Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
7) Order one (1) List KG Distribution Fuse Panel per shelf, as required.
8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66)
for each List BC, LC, NC, BF, LF, or NF ordered.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order one (1) for each battery cabinet feed required.
11) Order Relay Rack Anchor Kit(s) (List 89) as required.
12) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
13) Order Battery Trays (List 94) as required.
14) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
15) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
16) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
17) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
18) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
19) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 19 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List 6: 2RU High by 23” Wide Shelf
Features
♦ Consists of a 2RU high by 23” wide shelf.
♦ Mounted to the side of the shelf is an AC input housing with plug-in connectors for two (2) AC input feeds.
♦ Includes the Customer Interface Board that provides additional Relay Outputs and Digital Inputs.
♦ The “Relay Outputs Cable” P/N 541308 (shelf side) is factory connected inside the shelf. A mating half is
available. A “Digital Input Cable” (shelf side and customer side) is also available.
♦ The shelf houses up to six (6) Rectifier Modules, one (1) Controller, and one (1) Distribution Unit.
Restrictions
Each List 6 shelf holds up to six (6) Rectifier Modules.
Ordering Notes
1) Order List 6 as required.
Also order the following as required.
2) Order one (1) SCU+ controller (P/N 1M521BNA) or (1) ACU+ controller (P/N 1M820BNA) per shelf. Also
specify the appropriate configuration file for your site.
3) Order up to six (6) Rectifier Modules per shelf: P/N 1R48500 (500W) or P/N 1R481000 (1000W).
4) Order AC Input Cables or Line Cords as required. Note that each List 6 shelf requires two (2) AC Input
Cables or Line Cords.
5) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) per shelf.
6) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA ordered.
Each List 60 provides five (5) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 61 for each List BF, LF, or NF ordered.
Each List 61 provides eight (8) Load Lead Assemblies for 10A GMT Fuse Positions.
Order one (1) List 62 for each List BF, LF, or NF ordered.
Each List 62 provides five (5) Load Lead Assemblies for 15A GMT Fuse Positions.
7) Order one (1) List KG GMT Distribution Fuse Panel per shelf, as required.
8) Order three (3) sets of Shelf Side and three (3) sets of Battery Side Battery Cables (List 65 and List 66)
for each List BC, LC, NC, BF, LF, or NF ordered.
9) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
10) Order Relay Rack Anchor Kit(s) (List 89) as required.
11) Order up to two (2) Temperature Probes (List 90) as required. One probe is used with the Battery Charge
Temperature Compensation feature, the other to monitor ambient air temperature.
12) Order Battery Trays (List 93) as required.
13) Order Relay Racks per ACCESSORY DESCRIPTIONS section.
14) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
15) Order External Battery Disconnect Unit per ACCESSORY DESCRIPTIONS section.
16) Order Battery Cabinet per ACCESSORY DESCRIPTIONS section.
17) Order Digital Input/Relay Output Cables per ACCESSORY DESCRIPTIONS section.
18) Order lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 20 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Rectifier Module (500W), P/N 1R48500
Features
♦ Provides one (1) Model R48-500, Spec. No. 1R48500,
500 watt / 48 volt Rectifier Module.
Restrictions
Each List 1 Shelf holds up to two (2) Rectifier Modules.
Each List 2 Shelf holds up to three (3) Rectifier Modules.
Each List 5 Shelf holds up to four (4) Rectifier Modules.
Each List 6 Shelf holds up to six (6) Rectifier Modules.
DO NOT install different wattage Rectifier Modules in same shelf.
Ordering Notes
1) Order by P/N (1R48500) as required.

Rectifier Module (1000W), P/N 1R481000


Features
♦ Provides one (1) Model R48-1000, Spec. No. 1R481000,
1000 watt / 48 volt Rectifier Module.
Restrictions
Each List 1 Shelf holds up to two (2) Rectifier Modules.
Each List 2 Shelf holds up to three (3) Rectifier Modules.
Each List 5 Shelf holds up to four (4) Rectifier Modules.
Each List 6 Shelf holds up to six (6) Rectifier Modules.
DO NOT install different wattage Rectifier Modules in same shelf.
Ordering Notes
1) Order by P/N (1R481000) as required.

ACU+ (Advanced Control Unit Plus), P/N 1M820BNA


Features
♦ Provides the ACU+ Controller.
♦ Factory programmed with the configuration file specified when ordered.
Restrictions
ACU+ is not available in List 1 or List 2 shelves.
Each List 5 or List 6 shelf must contain one (1) SCU+ or one (1) ACU+
Controller.
Ordering Notes
1) Order one (1) ACU+ (P/N 1M820BMA) or one (1) SCU+ Controller (P/N
1M521BNA) or for each shelf.

Page 21 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
SCU+ (Standard Control Unit Plus), P/N 1M521BNA
Features
♦ Provides the SCU+ Controller.
♦ Factory programmed with the configuration file specified when ordered.
Restrictions
Each shelf must contain one (1) SCU+ or one (1) ACU+ Controller.
Ordering Notes
1) Order one (1) SCU+ Controller (P/N 1M521BNA) or one (1) ACU+ (P/N
1M820BMA) for each shelf.
For the SCU+ controller, specify also one of the following configurations.
Note: For custom SCU+ configurations, contact Emerson.
a) List 1 and 2 with Low Voltage Disconnect: 545304.
b) List 1 and 2 without Low Voltage Disconnect: 545305.
c) List 5 and 6 with Low Voltage Disconnect: 545298.
d) List 5 and 6 without Low Voltage Disconnect: 545299.

List 60: Five (5) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated
on one end with the appropriate mating connector to plug into the system’s
10A GMT fuse connector on a List BC, LC, NC, BA, LA, or NA Distribution
Unit, and are left un-terminated at the remaining end for connection into
customer loads.
Restrictions
For use with List BC, LC, NC, BA, LA, and NA Distribution units only.
Ordering Notes
1) Order one (1) List 60 for each List BC, LC, NC, BA, LA, or NA Distribution Unit.
Each List 60 provides five (5) GMT fuse load lead assemblies, P/N 535206.

List 61: Eight (8) Load Lead Assemblies (P/N 535206) for 10A GMT Fuse Positions
Features
♦ Provides 12’ long, 16 AWG, load and load return leads that are terminated on
one end with the appropriate mating connector to plug into the system’s 10A
GMT fuse connector on a List BF, LF, or NF Distribution Unit, and are left un-
terminated at the remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 61 for each List BF, LF, or NF Distribution Unit.
Each List 61 provides eight (8) GMT fuse load lead assemblies, P/N 535206.

Page 22 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 62: Five (5) Load Lead Assemblies (P/N 540988) for 15A GMT Fuse Positions
Features
♦ Provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector to plug into the system’s 15A GMT fuse connector
on a List BF, LF, or NF Distribution Unit, and are left un-terminated at the
remaining end for connection into customer loads.
Restrictions
For use with List BF, LF, and NF Distribution units only.
Ordering Notes
1) Order one (1) List 62 for each List BF, LF, or NF Distribution Unit.
Each List 62 provides five (5) GMT fuse load lead assemblies, P/N 540988.

List 65: Shelf Side Battery Cables, P/N 540814


Features
♦ Provides two (2) 3’ long, 2 AWG, battery cables terminated in a 2-position Red
SB120 Anderson connector (mates with the Anderson connector on List 66).
Remaining end terminated in lugs for connection to shelf.
Restrictions
For use with List BF, LF, NF, BC, LC, and NC Distribution units only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery strings.

List 66: Battery Side Battery Cables, P/N 540954


Features
♦ Provides two (2) 12’ long, 2 AWG, battery cables terminated in a 2-position Red
SB120 Anderson connector (mates with the Anderson connector on List 65).
Remaining end un-terminated for connection to batteries.
Restrictions
For use with List BF, LF, NF, BC, LC, and NC only.
Ordering Notes
1) Order as required. Each shelf provides landings for up to three (3) battery
strings.

Page 23 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List 67: Battery Cable, P/N 545709
Features
♦ Provides two (2) 4’ long, 8 AWG, battery cables terminated in a 2-position Anderson
connector on the battery side. Remaining end terminated in lugs for connection to shelf.
Restrictions
For use with P/N 541434, P/N 545534 or P/N 545506 Battery cabinets only.
For use with List BF, LF, NF, BC, LC, and NC Distribution units only.
Ordering Notes
1) Order up to three (3) List 67 for each List BC, LC, NC, BF, LF, and NF ordered.
2) Order one (1) for each battery cabinet feed required.

List 71: Optional External Battery Cable Assembly


with Anderson Connector for (1) Battery String, P/N 545493
Features
♦ Provides two (2) 6’ long, 8 AWG, battery cables terminated in a Red SB50
Anderson connector for connecting one (1) battery string to the system.
♦ One end of the assembly connects to the Anderson connector factory wired to
the shelf’s battery connection points, and the other end contains two (2) un-
terminated cables for connection into a customer battery string.
Restrictions
For use with List BG and NG only.
Ordering Notes
1) Order if required.
2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

List 72: Optional External Battery Cable Assembly


with Anderson Connector for (2) Battery Strings, P/N 535124
Features
♦ Provides four (4) 6’ long, 10 AWG, battery cables terminated in a Red SB50
Anderson connector for connecting two (2) battery strings to the system.
♦ One end of the assembly connects to the Anderson connector factory wired to
the shelf’s battery connection points, and the other end contains four (4) un-
terminated cables for connection into customer battery strings.
Restrictions
For use with List BG and NG Distribution units only.
Ordering Notes
1) Order if required.
2) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 24 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 89: Relay Rack Earthquake Anchor Kit, P/N P0987167
Features
♦ Provides four (4) sets of hardware for anchoring the relay rack to the floor.
Ordering Notes
1) Order as required.

List 90: Optional Temperature Probe,


P/N 04118246 (shelf side half) and P/N 04118247 (probe side half, 9 ft. long)
Features
♦ Two Temperature Probes can be
connected to this system. One to provide
Battery Charge Temperature
Compensation and the other to monitor
ambient air temperature. Each probe plugs
into the IB2 Board.
♦ The Temperature Probe used for Battery Charge Temperature Compensation is mounted near the battery
to sense battery ambient temperature. This allows the SCU to automatically increase or decrease the
output voltage of the system to maintain battery float current as battery ambient temperature decreases
or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery
with respect to temperature is maintained.
♦ The Temperature Probe consists of two pieces that plug together to make a complete probe. When
ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04118247 (9 feet long) is shipped
loose.
Ordering Notes
1) Order up to two (2) Temperature Probes for each shelf, as required.
Each List 90 includes one (1) P/N 04118246 and one (1) P/N 04118247.
2) For a Temperature Probe with a longer cable see List 91.

List 91: Optional Temperature Probe,


P/N 04118246 (shelf side half) and P/N 04116740 (probe side half, 30 ft. long)
Features
♦ Two Temperature Probes can be
connected to this system. One to provide
Battery Charge Temperature
Compensation and the other to monitor
ambient air temperature. Each probe plugs
into the IB2 Board.
♦ The Temperature Probe used for Battery Charge Temperature Compensation is mounted near the battery
to sense battery ambient temperature. This allows the SCU to automatically increase or decrease the
output voltage of the system to maintain battery float current as battery ambient temperature decreases
or increases, respectively. Battery life can be extended when an optimum charge voltage to the battery
with respect to temperature is maintained.
♦ The Temperature Probe consists of two pieces that plug together to make a complete probe. When
ordered, P/N 04118246 (3 feet long) is pre-wired to the shelf and P/N 04116740 (30 feet long) is shipped
loose.

Page 25 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Ordering Notes
1) Order up to two (2) Temperature Probes for each shelf, as required.
Each List 91 includes one (1) P/N 04118246 and one (1) P/N 04116740.
2) For a Temperature Probe with a shorter cable see List 90.

List 93: Battery Tray for 23” Relay Rack


Features
♦ Provides one battery tray that mounts four (4) 12V
front terminal Valve Regulated Lead Acid (VRLA) P/N 362736700
batteries. Batteries are configured as one (1) 48V
string.
♦ Accepts various VRLA batteries. See Ordering
Notes below.
♦ See Overall Dimensions - 23” Battery Tray under
PHYSICAL SIZE INFORMATION for battery tray
dimensions and typical arrangement. Note that
two battery trays are available to accommodate
the various size batteries listed in the Ordering
Notes tables.
P/N 528496
♦ Trays can be ordered with or without battery
disconnect circuit breakers. When circuit
breakers are ordered, one is provided in the -48V
lead of each battery string (1 circuit breaker per
tray). P/N 362736700
♦ Battery cables are available terminated at the
power system end in an Anderson connector.
Battery lugs are available for the remaining end.
Restrictions
For 23” relay racks only.
Maximum number of List 93’s per rack is three (3).
A single List 93 must mount at bottom of rack.
Multiple List 93’s must mount starting at bottom of
rack and working upward. P/N 540842
Ordering Notes
1) Order multiples of List 93 for more than one (1) battery tray. See Restrictions above.
2) Order one (1) or more P/N 362736700 Cable Bracket(s) as required.
3) Order batteries separately. The following tables list batteries recommended for use with List 93.

Page 26 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home

Battery Tray P/N 528496


Emerson Weight
Rated 8-Hr. Dimension Required
Network (per
Manufacturer* Model Capacity WxLxH Tray
Power battery)
(Ah) (Inches) Spacing
P/N (lbs)
GNB Marathon M12V125FT -- 125 4.90 X 22.00 X 11.15 7U 105
GNB Marathon M12V155FT 112795 155 4.90 X 22.00 X 11.15 7U 119
Northstar NSB110FT -- 110 4.92 X 22.05 X 8.94 7U 91.3
Northstar NSB170FT -- 167 4.92 X 22.05 X 12.60 8U 131
Deka Unigy I 12AVR-150ET 122018 150 4.90 X 22.00 X 11.75 8U 115
C&D FA 12-150F FA12150 150 4.92 X 21.97 X 12.70 8U 131
Douglas DGS12-150F 125453 150 4.90 X 22.00 X 12.70 8U 137
Douglas DSN12-170F -- 170.8 4.92 X 22.05 X 12.60 8U 129.6
* See Battery Manufacturer Information located at the end of this document.

Battery Tray P/N 540842


Emerson Weight
Rated 8-Hr. Dimension Required
Network (per
Manufacturer* Model Capacity WxLxH Tray
Power battery)
(Ah) (Inches) Spacing
P/N (lbs)
GNB Marathon M12V35FT -- 35 4.21 X 11.02 X 7.44 6U 31
GNB Marathon M12V50FT -- 47 4.21 X 11.02 X 9.09 7U 40
GNB Marathon M12V60FT -- 59 4.21 X 11.02 X 10.35 7U 51
Northstar NSB40FT** -- 38.1 3.80 X 9.80 X 8.20 6U 34
Northstar NSB60FT** -- 57.9 4.20 X 11.30 X 10.40 7U 49
Douglas DGS12-25F -- 25 3.94 X 10.80 X 7.60 6U 27
Douglas DGS12-50F -- 50 3.94 X 10.80 X 11.60 8U 48
* See Battery Manufacturer Information located at the end of this document.
** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.

4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required
for battery clearance. See table above.

Page 27 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
5) Battery lugs are provided, as specified from the following table.

Battery Lug Kit Part Number


Battery (Kit provides two lugs for one tray.)
Specified
Lists 5 and 6 Lists 1 and 2
GNB Marathon M12V125FT
GNB Marathon M12V155FT
Northstar NSB110FT
528234
Northstar NSB170FT
Deka Unigy I 12AVR-150ET
C&D FA 12-150F 540989
Douglas DGS12-150F 528236 (for use with 10 AWG wire and List 72)
Douglas DSN12-170F
GNB Marathon M12V35FT 545581
GNB Marathon M12V50FT (for use with 8 AWG wire and List 71)
GNB Marathon M12V60FT
528234
Northstar NSB40FT
Northstar NSB60FT
Douglas DGS12-25F
Douglas DGS12-50F
6) Specify with or without battery disconnect circuit breakers. If ordering List 93 with circuit breakers, order
one (1) circuit breaker per List 93 from the following table. Also specify breaker mounting on left side of
tray, right side of tray, or remote mounting. Note: All List 93 trays in a rack will be furnished with or
without battery disconnect circuit breakers as specified for the first tray ordered.
Also order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3)
battery disconnect circuit breakers.

P/N P/N
Ampere Ampere
Electrical/Mechanical Trip1 Electrical/Mechanical Trip1
Rating Rating
(Black Handle) (Black Handle)
1 256690300 35 256693500
3 256690700 40 256693900
5 256691100 50 256694300
10 256691500 60 256694700
15 256691900 70 256695100
20 256692300 75 256695500
25 256692700 100 256695900
30 256693100
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or
manual trip condition.

Page 28 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List 94: Battery Tray for 19” Relay Rack
Features
♦ Provides one battery tray that mounts four (4) 12V front
terminal Valve Regulated Lead Acid (VRLA) batteries. P/N 362736700
Batteries are configured as one (1) 48V string.
♦ Accepts various VRLA batteries. See Ordering Notes
below.
♦ See Overall Dimensions - 19” Battery Tray under
PHYSICAL SIZE INFORMATION for battery tray
dimensions and typical arrangement. Note that three
battery trays are available to accommodate the various
size batteries listed in the Ordering Notes tables.
♦ Trays can be ordered with or without battery disconnect P/N 541036
circuit breakers. When circuit breakers are ordered, one
is provided in the -48V lead of each battery string (1 circuit
P/N 362736700
breaker per tray).
♦ Battery cables are available terminated at the power
system end in an Anderson connector. Battery lugs are
available for the remaining end.
Restrictions
For 19” relay racks only.
Maximum number of List 94’s per rack is three (3).
A single List 94 must mount at bottom of rack. Multiple List
94’s must mount starting at bottom of rack and working P/N 541034
upward.
Ordering Notes
1) Order multiples of List 94 for more than one (1) battery P/N 362736700
tray. See Restrictions above.
2) Order one (1) or more P/N 362736700 Cable Bracket(s)
as required.
3) Order batteries separately. The following tables list
batteries recommended for use with List 94.

P/N 540841

Page 29 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home

Battery Tray P/N 541036


Emerson Weight
Rated 8-Hr. Dimension Required
Network (per
Manufacturer* Model Capacity WxLxH Tray
Power battery)
(Ah) (Inches) Spacing
P/N (lbs)
Northstar NSB90FT -- 90 4.25 X 15.59 X 10.04 7U 70.6
Northstar NSB100FT -- 100 4.25 X 15.59 X 11.03 7U 78.5
GNB Marathon M12V90FT -- 90 4.13 X 15.55 X 10.63 7U 70
* See Battery Manufacturer Information located at the end of this document.

Battery Tray P/N 541034


Emerson Weight
Rated 8-Hr. Dimension Required
Network (per
Manufacturer* Model Capacity WxLxH Tray
Power battery)
(Ah) (Inches) Spacing
P/N (lbs)
GNB Marathon M12V105FT -- 105 4.33 X 20.12 X 9.37 7U 79
* See Battery Manufacturer Information located at the end of this document.

Battery Tray P/N 540841


Emerson Weight
Rated 8-Hr. Dimension Required
Network (per
Manufacturer* Model Capacity WxLxH Tray
Power battery)
(Ah) (Inches) Spacing
P/N (lbs)
GNB Marathon M12V35FT -- 35 4.21 X 11.02 X 7.44 6U 31
GNB Marathon M12V50FT -- 47 4.21 X 11.02 X 9.09 7U 40
GNB Marathon M12V60FT -- 59 4.21 X 11.02 X 10.35 7U 51
Northstar NSB40FT** -- 38.1 3.80 X 9.80 X 8.20 6U 34
Northstar NSB60FT** -- 57.9 4.20 X 11.30 X 10.40 7U 49
Douglas DGS12-25F -- 25 3.94 X 10.80 X 7.60 6U 27
Douglas DGS12-50F -- 50 3.94 X 10.80 X 11.60 8U 48
* See Battery Manufacturer Information located at the end of this document.
** Batteries MUST be equipped with front access terminal option. See Battery Manufacturer for ordering information.

4) Specify rack spacing of 6U (10.5”), 7U (12.25”), or 8U (14”) between trays and above top tray as required
for battery clearance. See table above.

Page 30 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
5) Battery lugs are provided, as specified from the following table.

Battery Lug Kit Part Number


Battery (Kit provides two lugs for one tray.)
Specified
Lists 5 and 6 Lists 1 and 2
Northstar NSB90FT
Northstar NSB100FT
GNB Marathon M12V90FT
GNB Marathon M12V105FT 540989
GNB Marathon M12V35FT (for use with 10 AWG wire and List 72)
GNB Marathon M12V50FT 528234
GNB Marathon M12V60FT 545581
Northstar NSB40FT (for use with 8 AWG wire and List 71)
Northstar NSB60FT
Douglas DGS12-25F
Douglas DGS12-50F
6) Specify with or without battery disconnect circuit breakers. If ordering List 94 with circuit breakers, order
one (1) circuit breaker per List 94 from the following table. Also specify breaker mounting on left side of
tray, right side of tray, or remote mounting. Note: All List 94 trays in a rack will be furnished with or
without battery disconnect circuit breakers as specified for the first tray ordered.
Also order Alarm Jumper P/N 524384 for each system to connect the alarm terminal of up to three (3)
battery disconnect circuit breakers.

P/N P/N
Ampere Ampere
Electrical/Mechanical Trip1 Electrical/Mechanical Trip1
Rating Rating
(Black Handle) (Black Handle)
1 256690300 35 256693500
3 256690700 40 256693900
5 256691100 50 256694300
10 256691500 60 256694700
15 256691900 70 256695100
20 256692300 75 256695500
25 256692700 100 256695900
30 256693100
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or
manual trip condition.

Page 31 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List BF: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage
Battery Disconnect (LVBD), a battery shunt, (3)
battery connection points, and thirteen (13) GMT
fuse load distribution positions.
♦ Five (5) 0A to 15A GMT fuse load distribution
positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT
fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value.
In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent
to a 10A fuse. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty
space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a
GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List BF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List BF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.

Page 32 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List LF: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery
connection points, and thirteen (13) GMT fuse load
distribution positions.
♦ Five (5) 0A to 15A GMT fuse load distribution
positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT
fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value.
In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent
to a 10A fuse. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty
space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a
GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List LF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List LF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.

Page 33 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List NF: Distribution Unit with GMT Fuse Load Distribution Positions
and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, (3) battery connection
points, and thirteen (13) GMT fuse load distribution
positions.
♦ Five (5) 0A to 15A GMT fuse load distribution
positions.
♦ Eight (8) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
The (13) Position GMT Fuse Printed Wiring Board is rated 100A at +40°C (+104°F) and 59.5A at 65°C
(+149°F).
In an ambient of 40°C (+104°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is not required between fuses of any value. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 40°C (+104°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. 15A GMT
fuses cannot be placed in adjacent fuseholders. An empty space is not required between fuses of any value.
In an ambient of 65°C (+149°F), fuseholders F1-F8 are rated for a 10A GMT fuse maximum and an empty
space is required between 10A fuses. A GMT fuse greater than 3A cannot be placed in a fuseholder adjacent
to a 10A fuse. GMT fuses load bottom to top / highest to lowest value.
In an ambient of 65°C (+149°F), fuseholders F9-F13 are rated for a 15A GMT fuse maximum. An empty
space is required between 15A GMT fuses. 10A GMT fuses cannot be placed in adjacent fuse holders and a
GMT fuse greater than 3A cannot be placed in a fuseholder adjacent to a 10A fuse.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 61 for each List NF. Each List 61 provides eight (8) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order one (1) List 62 for each List NF. Each List 62 provides five (5) GMT fuse load lead assemblies for
the 15A fuse blocks.
5) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.

Page 34 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List BC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, (3) battery
connection points, four (4) bullet nose-type circuit
breaker load distribution positions, five (5) GMT fuse
load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 35 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List LC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, (3) battery
connection points, four (4) bullet nose-type circuit
breaker load distribution positions, five (5) GMT fuse
load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List LC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 36 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List NC: Distribution Unit with GMT Fuse Load Distribution Positions, Circuit Breaker
Load Distribution Positions, and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, (3) battery connection
points, four (4) bullet nose-type circuit breaker load
distribution positions, five (5) GMT fuse load
distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List NC. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order Shelf Side, Battery Side Battery Cables or Output Cables (List 65, List 66 or List 67) as required.
List 65 and List 67 are factory installed.
5) Order circuit breaker load lugs per Wiring Notes under ACCESSORY DESCRIPTIONS section.

Page 37 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List BA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), a battery shunt, two (2) bullet
nose-type circuit breaker load distribution positions, two
(2) bullet nose-type circuit breaker battery disconnect
positions, five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List BA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.

Page 38 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List LA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and with Low Voltage Load Disconnect (LVLD)
Features
♦ Provides a Distribution Unit with Low Voltage Load
Disconnect (LVLD), a battery shunt, two (2) bullet
nose-type circuit breaker load distribution positions,
two (2) bullet nose-type circuit breaker battery
disconnect positions, five (5) GMT fuse load
distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List LA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.

Page 39 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List NA: Distribution Unit with GMT Fuse Load Distribution Positions,
Circuit Breaker Load Distribution Positions, Circuit Breaker Battery Disconnect Positions,
and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, two (2) bullet nose-type
circuit breaker load distribution positions, two (2) bullet
nose-type circuit breaker battery disconnect positions,
five (5) GMT fuse load distribution positions.
♦ Five (5) 0A to 10A GMT fuse load distribution
positions.
Restrictions
For use with List 5 and 6 only.
Maximum distribution current is 72A at @ +65°C (+149°F)
and 100A @ +40°C (+104°F).
The GMT fuse block has a 35A @ +40°C (+104°F) and a 21A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 10A. At +65°C (+149°F), a space is required between GMT fuses greater than
5A.
Maximum load distribution or battery circuit breaker size is 75A @ +65°C (+149°F).
Caution: In an ambient of +65°C (+149°F), a circuit breaker with a rating greater than 45 amperes
SHALL HAVE an empty mounting position between it and any other overcurrent protective
device. There are no restrictions in an ambient of +40°C (+104°F).
See also the Restrictions under “GMT Load Distribution Fuses” and “Bullet Nose-Type Circuit Breakers” in
the ACCESSORY DESCRIPTIONS section.
Ordering Notes
1) Order one (1) Distribution Unit (List BF, LF, NF, BC, LC, NC, BA, LA, or NA) for each List 5 or 6 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order one (1) List 60 for each List NA. Each List 60 provides five (5) GMT fuse load lead assemblies for
the 10A fuse blocks.
4) Order circuit breaker load lugs and battery input lugs per Wiring Notes under ACCESSORY
DESCRIPTIONS section.

Page 40 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List BG: Distribution Unit with GMT Fuse Load Distribution Positions
and with Low Voltage Battery Disconnect (LVBD)
Features
♦ Provides a Distribution Unit with Low Voltage Battery
Disconnect (LVBD), battery cables, and ten (10) GMT
fuse load distribution positions (15A maximum).
♦ Two (2) 8 AWG 48” long battery cables are factory
connected inside the shelf. These cables are
terminated at the customer end in a Red SB50
Anderson battery connector. A mating Anderson
battery connector is provided [Housing: Emerson P/N
138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602,
Anderson Power Products P/N 5952].
♦ Ten (10) 0A to 15A GMT fuse load distribution positions.
Restrictions
For use with List 1 and 2 only.
The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A
fuses.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 41 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
List NG: Distribution Unit with GMT Fuse Load Distribution Positions
and w/out Low Voltage Disconnect
Features
♦ Provides a Distribution Unit w/out low voltage
disconnect, a battery shunt, battery cables, and ten
(10) GMT fuse load distribution positions (15A
maximum).
♦ Two (2) 8 AWG 48” long battery cables are factory
connected inside the shelf. These cables are
terminated at the customer end in a Red SB50
Anderson battery connector. A mating Anderson
battery connector is provided [Housing: Emerson P/N
138922, Anderson Power Products P/N 992G1. Contacts (two provided): Emerson P/N 247109602,
Anderson Power Products P/N 5952].
♦ Ten (10) 0A to 15A GMT fuse load distribution positions.
Restrictions
For use with List 1 and 2 only.
The Distribution Unit has a 50A @ +40°C (+104°F) and 40A @ +65°C (+149°F) maximum capacity.
Maximum GMT fuse size is 15A. In an ambient of +65°C (+149°F), an empty space is required between 15A
fuses.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) Distribution Unit (List BG or NG) for each List 1 or 2 shelf.
Also order the following as required.
2) Order Distribution Devices per ACCESSORY DESCRIPTIONS section.
3) Order Optional External Battery Cables with Anderson Connector for one (1) to two (2) Battery Strings per
List 71 or 72.
4) Order Spare Anderson Battery Connector per ACCESSORY DESCRIPTIONS section.

Page 42 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
List KG: Distribution Panel with (20) GMT Fuse Load Distribution Positions
Features
♦ 1U-high GMT fuse panel that provides Single Load
Distribution (-48V)
♦ Provides twenty (20) 0A to 15A GMT fuse load
distribution positions.
♦ Maximum Capacity: 80A @ +40°C and 80A @ +65°C
♦ Factory mounted and connected to List 5 or 6 shelf.
Restrictions
For use with List 5 and 6 only.
Mounts only immediately above List 5 or 6 shelf.
For use with List BA, BC, BF, NA, NC and NF only.
Maximum distribution current is 80A.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Ordering Notes
1) Order one (1) List KG GMT Distribution Fuse Panel Assembly for each List 5 or 6 shelf as required.
Also order the following as required.
2) Order GMT Load Distribution Fuses per ACCESSORY DESCRIPTIONS section.

Page 43 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
ACCESSORY DESCRIPTIONS
Relay Racks
Features
♦ The following relay racks are available.
Restrictions
Customer must mount Power/Distribution Shelf in relay rack. If battery trays are ordered, they are factory
mounted in the relay rack.
Ordering Notes
1) Order from relay racks listed in Table 1.

Part Available Mounting


Size Notes
Number Positions (1RU = 1-3/4”)
23” Relay Racks
543156 51-3/8” H x 23” W 28RU Welded
543161 6’0” H x 23” W 37RU Welded
Seismic
543160 7’0” H x 23” W 45RU
(Note 1)
543162 7’0” H x 23” W 45RU Welded
543163 7’6” H x 23” W 48RU Welded
543164 8’0” H x 23” W 51RU Welded
19” Relay Racks
525003 51-3/8” H x 19” W 28RU Welded
Seismic
534653 6’0" H x 19” W 37RU
(Note 1)
524961 6’0” H x 19” W 37RU Welded
Seismic
534654 6’6” H x 19” W 41RU
(Note 1)
534651 6’6” H x 19” W 41RU Welded
Seismic
528183 7’0” H x 19” W 45RU
(Note 1)
524988 7’0” H x 19”W 45RU Welded
524963 7’6” H x 19” W 48RU Welded
534652 8’0" H x 19” W 51RU Welded
Note 1: Complies with Bellcore Seismic Zone 4 requirements.
Table 1
Available Relay Racks

Page 44 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Mounting and Adapter Kits
Optional Wall Mount Bracket Kit for Lists 1 and 2, P/N 541285
Features
♦ Allows for horizontal or vertical wall mounting.
Restrictions
For use with List 1 or 2 only.
Customer must supply mounting fasteners for attaching the Wall
Mount Bracket to the wall.
Ordering Notes
1) Order P/N 541285, which consists of two (2) P/N 545701 horizontal wall mounting brackets and two (2)
P/N 541284 vertical wall mounting brackets, and eight (8) 12-24 x ½” screws for attaching the brackets to
the shelf.

Optional 19” to 23” Rack Adapter Kit, P/N 540993


Features
♦ Allows for 23” relay rack mounting
Restrictions
For use with List 1 only.
Ordering Notes
1) Order P/N 540993, which consists of two (2) P/N 540994 adapters and four (4) 12-24 x 1/”2 thread
forming screws.

Optional 19” to 23” Rack Adapter Kit, P/N 545728


Features
♦ Allows for 23” relay rack mounting
Restrictions
For use with List 5 only.
Ordering Notes
1) Order P/N 545728, which consists of two (2) P/N 545727 adapters and four (4) 12-24 x 1/”2 thread
forming screws.

Rear Battery Cable Exit Kit P/N 547645


Features
♦ Provides 12” battery cables exiting rear of shelf
Restrictions
For use with List 5 only.
Ordering Notes
1) For use with Battery Cabinets only.

Page 45 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Distribution Devices
GMT Load Distribution Fuses
Features
♦ Each List BF, LF, NF Distribution Unit holds up to five (5) 0-15A GMT load distribution fuses and eight (8)
0-10A GMT load distribution fuses.
♦ Each List BC, LC, NC, BA, LA, NA Distribution Unit holds up to five (5) 0-10A GMT load distribution fuses.
♦ Each List BG and NG Distribution Unit holds up to ten (10) 0-15A GMT load distribution fuses.
♦ Each List KG Distribution Panel holds up to twenty (20) 0-15A GMT load distribution fuses.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 ampere
fuses, for which load should not exceed 70% of device rating.
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (GMT Fuses) (Lists BG and NG only), Load Distribution Wiring (GMT
Fuses) (Lists BF, LF, and NF only), and Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA,
and NA) under WIRING NOTES for additional wiring restrictions.
Ordering Notes
1) Order GMT fuses per Table 2.

Ampere Rating P/N Fuse Color


18/100 GMT-A 248610301 --
1/4 248610200 Violet
1/2 248610300 Red
3/4 248610500 Brown
1-1/3 248610700 White
2 248610800 Orange
3 248610900 Blue
5 248611000 Green
7-1/2 248611300 Black-White
10 248611200 Red-White
15 248611500 Red-Blue
Replacement
248872600 ---
Dummy Fuse
Lists BF, LF, NF,
Replacement Safety BC, LC, NC, 102774
BA, LA, NA and KG --
Fuse Cover
Lists BG and NG 248898700
Table 2
GMT Fuses

Page 46 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Bullet Nose-Type Circuit Breakers
Features
♦ Each List BC, LC, and NC Distribution Unit holds up to four (4) bullet nose-type load distribution circuit
breakers.
♦ Each List BA, LA, and NA Distribution Unit holds up to two (2) bullet nose-type battery disconnect circuit
breakers and up to two (2) bullet nose-type load distribution circuit breakers.
Restrictions
See also the Restrictions for each Distribution Unit in the LIST DESCRIPTIONS section.
See also Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA) and Input Battery
Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA) under WIRING NOTES for additional
wiring restrictions.
Ordering Notes
1) Order circuit breakers per Table 3.

P/N
Ampere Electrical/
Rating Electrical Trip1
Mechanical Trip2
(White Handle)
(Black Handle)
1 102272 101596
3 102273 101597
5 102274 101598
10 102275 101599
15 102276 101600
20 102277 101601
25 102278 101602
30 102279 101603
35 102280 101604
40 102281 101605
45 121998 121997
50 102282 101606
60 102283 101607
70 102284 101608
75 102285 101609
80 121996 121995
100 102286 101610
See Table 6 for recommended wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Note that Electrical Trip only circuit breakers are not typically used for battery
disconnect circuit breakers.
Table 3
Bullet Nose-Type Circuit Breakers

Page 47 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Optional Bullet Nose 6-Position GMT Fuse Module, P/N 545332
Features
♦ Factory installed in a List BC, LC, NC, BA, LA,
and NA Distribution Unit.
♦ Provides six (6) 0A to 15A GMT fuse load
distribution positions.
♦ Screw clamp type load and load return terminals
provided.
♦ Includes six (6) dummy fuses equipped with
safety fuse covers.
Restrictions
For use with Lists BC, LC, NC, BA, LA, and NA.
Terminal block wire size capacity: 24 to 14 AWG.
Requires two (2) bullet device mounting positions.
Fuse Module has a 30A @ +40°C (+104°F) and +65°C (+149°F) maximum capacity. Maximum GMT fuse
size is 15A. Fuses are to be loaded from bottom to top with highest value in the lowest position.
Caution: A fuse with a rating greater than 10 amperes SHALL HAVE an empty mounting position
between it and any other overcurrent protective device.
See also the Restrictions under “GMT Load Distribution Fuses” in the ACCESSORY DESCRIPTIONS
section.
Factory installed only.
Ordering Notes
1) Order optional Bullet Nose-Type 6-Position GMT Fuse Module (P/N 545332) as required.
2) Order GMT fuses as required per Table 2.

Optional Bulk Output Busbar, P/N 535015


Features
♦ Each Bulk Output Busbar installs in a single circuit breaker
position in a List BC, LC, NC, BA, LA, and NA Distribution Unit.
Restrictions
For use with Lists BC, LC, NC, BA, LA, and NA.
Ordering Notes
3) Order by P/N 535015 as required.

Page 48 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Cables and Line Cords
AC Input Cable Assembly, P/N 535232
Features
♦ Provides one (1) 30” long, 8 AWG, AC Input Cable Assembly;
♦ terminated on one end with a Molex plug which mates with AC
input receptacle on the Power/Distribution Shelf,
♦ and the remaining end un-terminated.
Restrictions
Rated for 30A.
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

AC Input Line Cord, 208/240VAC, P/N 540946


Features
♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-30P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 30A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

Page 49 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Line Cord, 208/240VAC, P/N 545616
Features
♦ Provides one (1) 6’ long, 8 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-30P twist-lock plug.
Restrictions
For 208/240 VAC only (rated for 30A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

AC Input Line Cord, 120VAC, P/N 545252


Features
♦ Provides one (1) 14’ long, 8 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-30P twist-lock plug.
Restrictions
For 120 VAC only (rated for 30A at 120VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

Page 50 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Line Cord, 120VAC, P/N 545478
Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 5-15P plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 equipped with R48-500 Rectifier Modules.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

AC Input Line Cord, 120VAC, P/N 545479


Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-15P twist-lock plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 equipped with R48-500 Rectifier Modules.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

Page 51 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Line Cord, 208/240VAC, P/N 545480
Features
♦ Provides one (1) 14’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-15P twist-lock plug.
Restrictions
For 240 VAC only (rated for 15A at 208/240VAC).
For use with List 1 and 5.
For use with List 2 and 6 with R48-500 Rectifiers.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

AC Input Line Cord, 120VAC, P/N 545481


Features
♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-20P twist-lock plug.
Restrictions
For 120 VAC only (rated for 20A at 120VAC).
For use with List 1 and 5.
For use with List 2 and 6 with R48-500 Rectifiers.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

Page 52 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Line Cord, 208/240VAC, P/N 545553
Features
♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on
the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L6-20P twist-lock plug.
Restrictions
For 240 VAC only (rated for 20A at 208/240VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

AC Input Line Cord, 120VAC, P/N 547525


Features
♦ Provides one (1) 14’ long, 12/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input receptacle on the
Power/Distribution Shelf,
♦ and on the remaining end with a NEMA L5-30P twist-lock plug.
Restrictions
For 120 VAC only (rated for 30A at 120VAC).
For use with List 1, 2, 5, and 6.
Each List 1 and 2 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 and 6 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 and 2 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 and 6 ordered.

Page 53 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Line Cord, 120VAC, P/N 548457
Features
♦ Provides one (1) 6’ long, 14/3 AWG, AC Input Line Cord;
♦ terminated on one end with a Molex plug which mates with AC input
receptacle on the Power/Distribution Shelf,
♦ and on the remaining end with a NEMA 5-15P plug.
Restrictions
For 120 VAC only (rated for 15A at 120VAC).
For use with List 1 and 5 with R48-500 Rectifiers.
Each List 1 requires one (1) AC Input Cable Assembly/Line Cord.
Each List 5 requires two (2) AC Input Cable Assemblies/Line Cords.
Ordering Notes
1) Order one (1) AC Input Cable Assembly/Line Cord as required for each List 1 ordered.
2) Order two (2) AC Input Cable Assemblies/Line Cords as required for each List 5 ordered.

Page 54 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AP6C57EA/EB Ring & Distribution Module
Features
♦ When used with List 5 or 6, this module is designed to
supply a filtered and regulated –48 VDC source and a
continuous 20 Hz ringing supply source to imbedded
subscriber loop carrier telecommunication systems
(such as SLC-96 or SLC Series-5) requiring up to 45 A
of load capacity.
♦ Designed to mount in a 23” relay rack, the module is
one rack unit high, with 5” front projection.
♦ Includes two (2) 50VA ringers with automatic transfer
capability (N+1 redundancy).
♦ Provides 35 DC distribution fuse positions, configured
in five groups of seven, feeding five channel banks. Includes 35 dummy fuses.
♦ Connectorized cables are available for SLC-96 or SLC Series-5 applications. Required DC distribution
fuses are included with each cable assembly ordered.
♦ An Order Wire Option provides a connection interface for an analog communication link over a metallic
pair, with surge protection.
♦ See Ring & Distribution Module Installation and User Manuals (IM6C57E and UM6C57E) for complete
specifications.
Restrictions
Cannot be used with Distribution units List BF, LF, or NF.
Ordering Notes
1) For a Ring & Distribution Module equipped with two (2) 50VA ringers only, order AP6C57EA (A7000626).
2) For a Ring & Distribution Module equipped with two (2) 50VA ringers and the Order Wire option, order
AP6C57EB (A7000796).
3) Order distribution cable assemblies as required, from the following table. Order up to five (5) cable
assemblies (one per channel bank). Required fuses are included with each cable assembly. Cable
assemblies can be mixed.
ORDERING CODE DESCRIPTION
P7000858 Cable assy for one SLC96 channel bank (8 ft.)
P7001139 Cable assy for one SLC96 channel bank (20 ft.)
P7000859 Cable assy for one SLC5 channel bank (8 ft.)
P7001136 Cable assy for one SLC5 channel bank (20 ft.)
P7000937* Cable assy for one channel bank, generic applications (8 ft.)
*Note: Each channel bank position on the panel has a maximum capacity of 11A.

4) Order Part No. 547491 DC power cable kit, as required. Provides two (2) 9” long cables to connect
between a power shelf and the DC input terminals of one (1) Ring & Distribution Module.

Page 55 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
5) For SLC-96 or SLC Series-5 applications, order battery cable kits as required, from the following
table.
ORDERING DESCRIPTION
CODE
Battery cable kit for SLC96 legacy power shelf (Tyco Mate-N-Lock connectors) - for 2
battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution
547646
units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use
a flat washer, not provided.)
Battery cable for SLC5 legacy power shelf (Tyco Mate-N-Lock connectors) - for
2 battery strings, Up to 3 cable kits can be installed in the power shelf with Distribution
547647
units BC, LC, and NC. Two cable kits can be installed in DU Lists BA, LA, and NA. (Use
a flat washer, not provided.)

6) Spare parts for the AP6C57EA/EB Ring & Distribution Module can be ordered as required from the
following table.
ORDERING CODE DESCRIPTION
A0885525 1.33A Alarm SAN-O Fuse
A0885530 3A Alarm SAN-O Fuse
A0885531 5A Alarm SAN-O Fuse
A0885532 10A Alarm SAN-O Fuse
A7000627 (AP8C55AA) 50VA Ring Generator

Page 56 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
External Battery Disconnect Unit, P/N 535282
Features
♦ Battery Disconnect Unit with mounting tabs.
♦ Two 1/4-20 studs w/hardware provided for installation of single hole
battery lugs.
♦ One (10’ long) alarm lead provided.
Restrictions
Circuit breakers are ordered separately.
Maximum number of Battery Disconnect Units per system is three (3).
Ordering Notes
1) Order by P/N 535282 as required.
2) Order a circuit breaker for each Battery Disconnect Unit from Table 4.
3) Also order the following lug kits for each battery disconnect circuit
breaker ordered: 545581(for use with 8 AWG wire and List 71) or
540989 (for use with 10 AWG wire and List 72) and 541031 (wire with
lugs for connection from battery disconnect to battery string).
4) Also order P/N 524384 Jumper/Alarm Lead if more than one (1) Battery
Disconnect Units are to be used (daisy-chains the alarm terminal of up Yellow Jumper/Alarm Lead (P/N 524384)
to three [3] Battery Disconnect Units). (Section of alarm lead between (for use when more than one Battery
Battery Disconnect Units is 30”, section of alarm lead between Battery Disconnect Units are ordered)
Disconnect Unit and system’s alarm terminal is 84”.)

P/N P/N
Ampere Electrical/Mechanical Ampere Electrical/Mechanical
Rating Trip1 Rating Trip1
(Black Handle) (Black Handle)
1 256690300 35 256693500
3 256690700 40 256693900
5 256691100 50 256694300
10 256691500 60 256694700
15 256691900 70 256695100
20 256692300 75 256695500
25 256692700 100 256695900
30 256693100
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
Table 4
Battery Disconnect Unit Circuit Breakers

Page 57 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
NETSURE™ 201BC Battery Cabinet (Spec. No. 541434)
Features
♦ The NETSURE™ 201BC Battery Cabinet can be
mounted in a 19” or 23” nominal relay rack, or
mounted to a suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere
battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided
to tie into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery
cable terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in
the table under Order Notes) into the Battery
Cabinet provided.
♦ Battery Cabinets can be paralleled to provide
greater reserve time. Battery cabinets contain a
second Anderson battery connector for plugging
one cabinet into another.
Ordering Notes
1) Order by Spec. No. 541434 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.

Battery Manufacturer Emerson Capacity Amp-Hours Weight (lb)


Manufacturer P/N P/N (8Hr rate) per Battery
Hawker SBS 15 139091 14 12.50
Fiamm 12SLA12 139092 12 12.35
EaglePicher HE-12V7.7FR 139094 6.9 5.94
EaglePicher HE-12V12.7FR 139093 11.6* 9.68
Enersys NP18-12FR 139774 16 * 13.60
* 10Hr rate

3) When ordering 139774 batteries, also order 545427 Battery Connection kit.

Page 58 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
NETSURE™ 211BC Battery Cabinet (Spec. No. 545534)
Features
♦ The NETSURE™ 211BC Battery Cabinet can be mounted
in a 19” or 23” nominal relay rack, or mounted to a
suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere battery
disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie into
the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the table
under Ordering Notes) into the Battery Cabinet provided.
♦ Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet into
another.

Ordering Notes
1) Order by Spec. No. 545534 as required.
2) Also order two (2) batteries per Battery Cabinet per the following table.

Battery Manufacturer Emerson P/N Capacity Amp-Hours Weight (lb)


Manufacturer P/N (8Hr rate) per Battery
Enersys SBS B10 140553 38 28.20
C&D / Dynasty TEL12-30 140455 30.5 26.70

Page 59 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
NETSURE™ 211BC Battery Cabinet (Spec. No. 545506)
Features
♦ The NETSURE™ 211BC Battery Cabinet can be
mounted in a 23” nominal relay rack, or mounted to a
suitable wall.
♦ The Battery Cabinet contains one (1) 40 ampere
battery disconnect circuit breaker.
♦ Battery circuit breaker alarm leads are provided to tie
into the power system’s alarm circuit.
♦ The Battery Cabinet is equipped with a battery cable
terminated in an Anderson connector.
♦ Cables to connect the batteries (as specified in the
table under Ordering Notes) into the Battery Cabinet
provided.
♦ Battery Cabinets can be paralleled to provide greater
reserve time. Battery cabinets contain a second
Anderson battery connector for plugging one cabinet
into another.
Ordering Notes
1) Order by Spec. No. 545506 as required.
2) Also order four (4) batteries per Battery Cabinet per the following table.

Battery Manufacturer Emerson P/N Capacity Amp-Hours Weight (lb)


Manufacturer P/N (8Hr rate) per Battery
Enersys SBS B10 140553 38 28.20
Enersys SBS 40 140581 38 28.00
C&D/ Dynasty TEL12-30 140455 30.5 26.70
C&D/ Dynasty TEL12-45 140454 46 26.70

Page 60 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Site Web™ TEMP Temperature Concentrator (P/N 547490)
Features
♦ Allows for multiple temperature probes to be used for temperature
compensation. Compensation can be based on highest probe
temperature or average probe temperature.
♦ Provides (8) temperature probe inputs per SiteWeb™ TEMP.
♦ Can be cascaded up to (8) SiteWeb™ TEMP modules,
connecting up to 64 temperature probes.
♦ Provides CAN output for ACU+ and analog output for all
controllers.
Restrictions
Concentrator needs to plug into analog temp input on IB2 board.
Ordering Notes
1) Order P/N 547490.
2) Order up to (8) List 90 or 91 temperature probes for each concentrator.

Page 61 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Anderson Battery Connector
Features
♦ Includes the components necessary to assemble an Anderson
connector onto a battery cable.
Restrictions
Appropriate battery post mating lugs must be ordered separately.
Ordering Notes
Order Anderson connector housings and lugs per the following table.

Single Part Number for a Housing and Lugs


Emerson Anderson
Description
P/N P/N
(not available (not available
For a single string (spare for List 71). in kit form, in kit form,
order order
Consists of two (2) lugs (Anderson P/N 5952) and one (1) Red
components components
Connector (Anderson P/N 992G1). Lugs accept 8 AWG wire.
individually individually
Allows for the connection of one (1) battery string (both polarities) per the per the
(one wire per lug). second half second half
of this table) of this table)
For a double string (spare for List 72).
Consists of two (2) lugs (Anderson P/N 5900) and one (1) Red
Connector (Anderson P/N 992G1). Lugs accept 6 AWG wires. 133196 6331G1
Allows for the connection of two (2) battery strings (both polarities)
(two [10 AWG] wires per lug).
Individual Housing and Lugs Part Numbers
(spare for List 1, 2, and 71)
Emerson Anderson
Description
P/N P/N
Housing 138922 992G1
Lug (accepts 8 AWG wire) (2 required per housing) 247109602 5952

Page 62 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Digital Input and Relay Output Cables
Features
♦ Lists 5 and 6: Two sets of customer wiring cables are available. One set for the Digital Inputs and
another set for the Relay Outputs. One half of the Relay Outputs Cable is provided and factory
connected in the shelf. The other half (includes mating connector on one end and un-terminated on the
other end) must be ordered separately. Both halves of the Digital Inputs Cable must be ordered
separately. When ordered, one half of the Digital Inputs Cable is factory connected in the shelf. The
other half has a mating connector on one end and is un-terminated on the other end.
♦ Lists 1 and 2: One set of customer wiring cables is available (Digital Inputs and Relay Outputs). One
half of the cable is provided and factory connected in the shelf. The other half (includes mating connector
on one end and un-terminated on the other end) must be ordered separately.
Ordering Notes
1) Lists 5 and 6: For the Relay Outputs Cable, P/N 541308 (shelf side) is provided and factory connected
in the List 5 and 6 shelf, and P/N 541309 or P/N 545644 (customer side) must be ordered separately.
For the Digital Inputs Cable, order both P/Ns 541310 (shelf side) and P/N 541311 (customer side).
Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory
installed only.
2) Lists 1 and 2: For the Digital Inputs and Relay Outputs Cable, P/N 545494 (shelf side) is provided and
factory connected in the List 1 and 2 shelf and P/N 545495 (customer side) must be ordered separately.

Replacement Modules
Ordering Notes
1) Refer to Table 5.

Item Part Number


500W Rectifier Module 1R48500
1000W Rectifier Module 1R481000
Rectifier Module Fan 32010156
1M521BNA*
* Also specify the appropriate SCU+
SCU+ Controller Module configuration file. Refer to the
configuration file label on your
existing SCU+ Controller.
1M820BNA*
* Also specify the appropriate ACU+
ACU+ Controller Module configuration file. Refer to the
configuration file label on your
existing ACU+ Controller.
Order per List 90 (9 ft. long)
or List 91 (30 Ft. long)
Temperature Probe (or if only one piece of the two piece
probe is needed, see the List 90 or 91
description for part numbers)
Table 5
Replacement Module Part Numbers

Page 63 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Wiring Notes
Refer also to the next section, Wiring Illustrations.
Illustrations

Shelf Frame Grounding Stud (List 1 and 2 Only)


Features
♦ An M5 frame grounding stud with hardware is provided on the rear of the shelf
Restrictions
Recommended frame ground wire size is 6 AWG.

AC Input Branch Circuit Protection and Wiring


Features
♦ Each shelf contains one (1) or two (2) side mounted plug-in AC input connector(s).
♦ AC Input Cable Assemblies/Line Cords are available that plug into the shelf’s AC input connector.
Restrictions
Lists 1 and 2 require one (1) AC input branch circuit.
The AC input branch circuit feeds two (2) (List 1) or three (3) (List 2) rectifiers.
Refer to the following table for recommended branch circuit protection.
Lists 5 and 6 require two (2) AC input branch circuits.
Each AC input branch circuit feeds two (2) (List 5) or three (3) (List 6) rectifiers.
Refer to the following table for recommended branch circuit protection.

AC Input Branch Circuit Protection


208/240VAC Input 120VAC Input
System
500W Rect. 1000W Rect. 500W Rect. 1000W Rect.
58213660001
58213660005 15A 15A 15A 20A
(2-Rectifiers per AC Feed)
58213660002
58213660006 15A 20A 20A 25A / 30A
(3-Rectifiers per AC Feed)

For correct AC input wire size, use the appropriate AC Input Cable Assembly/Line Cord for each AC input
branch circuit. Refer to AC Input Cables and Line Cords in the ACCESSORY DESCRIPTIONS section of this
document.

External Alarm and Monitoring Wiring


Features
♦ List 5 and 6: Relay output and digital input leads are connected to screw-type terminal blocks located on
the Customer Interface Board mounted inside the shelf. One half of a Relay Outputs Cable is factory
connected to these terminals. The other half (includes mating connector on one end and un-terminated
on the other end) is ordered separately. If ordered, one half of a Digital Input Cable is factory connected

Page 64 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
to these terminals. The other half includes a mating connector on one end and is un-terminated
on the other end.
♦ List 1 and 2: Relay output and digital input leads are connected to screw-type terminals located on the
SCU+ Controller Module mounted inside the shelf. One half of a Digital Input/Relay Output Cable is
factory connected to these terminals. The other half (includes mating connector on one end and un-
terminated on the other end) is ordered separately.
Restrictions
Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.

Load Distribution Wiring (GMT Fuses) (Lists BG and NG only)


Features
♦ Load and load return leads are connected to a screw-type terminal block located on the front of the
Distribution Unit.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 20 to 12 AWG.

Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF only)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf. Note that the GMT distribution fuse block accepts two ranges of
fuse amperage sizes, and that two different types of receptacles are provided.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) Lists 61 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s lower amperage rating GMT fuse connector, and
are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].
2) Lists 62 provides 12’ long, 14 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s higher amperage rating GMT fuse connector, and
are left un-terminated at the remaining end for connection into customer loads.
* Consists of housing Tyco P/N 350777-1 and terminals Tyco P/N 350551-3 [loose] or Tyco
350537-3 [reel].

Page 65 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to receptacles located inside the
Distribution Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and are
accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Ordering Notes
1) List 60 provides 12’ long, 16 AWG, load and load return leads that are terminated on one end with the
appropriate mating connector* to plug into the system’s GMT fuse connector, and are left un-terminated
at the remaining end for connection into customer loads.
* Consists of housing Molex P/N 39-01-2025 and terminals P/N 44476-3112 [loose] or 44476-3111
[reel].

Load Distribution Wiring (Optional Bullet-Nose-Type 6-Position GMT Fuse Module)


Features
♦ Load and load return leads are connected to a screw-type terminal block located on the front of the Fuse
Module.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 24 to 14 AWG.

Load Distribution Wiring (Circuit Breakers) (Lists BC, LC, NC, BA, LA, and NA)
Features
♦ Load distribution (circuit breakers) and load return leads terminated in two-hole lugs are connected to
threaded studs located inside the Distribution Unit. Load leads are brought into the right side (as viewed
from the front) of the shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 6 AWG when all four (4) circuit breaker
positions are used and 2 AWG when only two (2) are used. When using lugs for #4 and #2 AWG wire,
recommended to use a customer supplied flat washer between the lug and the nut supplied on the
termination.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug
selection, refer to Table 6.

Page 66 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
2) For other available lugs, refer to drawings 031110100 through 031110300.

Circuit Recm 90°C Wire Size (1)


Breaker
14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 2 AWG
Amperage (2)
Loop Length (feet)
1, 3, 5,
37 (3, 4, 5) 58 (3, 4, 5) 93 (3, 4, 5) 148 (3, 4, 5) 236 (3, 4, 5) -- --
10A
15A 24 (3, 4) 39 (3, 4, 5) 62 (3, 4, 5) 99 (3, 4, 5) 157 (3, 4, 5) -- --
20A -- 29 (3, 4) 46 (3, 4, 5) 74 (3, 4, 5) 118 (3, 4, 5) -- --
25A -- -- 37 (3, 4,) 59 (3, 4, 5) 94 (3, 4, 5) -- --
30A -- -- 31 (3, 4) 49 (3, 4, 5) 78 (3, 4, 5) -- --
35A -- -- -- 42 (3, 4) 67 (3, 4, 5) 107 (3, 4) --
40A -- -- -- 37 (3, 4) 59 (3, 4, 5) 94 (3, 4) --
45A -- -- -- 33 (3, 4) 52 (3, 4) 83 (3, 4) --
50A -- -- -- 29 (3) 47 (3, 4,) 75 (3, 4) --
60A -- -- -- -- 39 (3, 4) 62 (3, 4) 99 (3, 4)
70A 53 (3, 4) 85 (3, 4)
75A 50 (3, 4) 79 (3, 4)
80A 47 (3, 4) 74 (3, 4)
90A 41 (3) 66 (3, 4)
100A -- 59 (3, 4)
Recommended Crimp Lug (6)
2-hole 245390100 245390100 245390100 245346600 245346500 245346800 245346900
1
Wire sizes are based on recommendations of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16
for wire rated at 90°C conductor temperature operating in ambient temperatures of 40°C, 50°C, and
65°C was used. For other operating ambient temperatures, refer to the NEC. For operation in
countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current
for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 50°C Ambient Operating Temperature.
5
Wire Size / Loop Length Combination Calculated using 65°C Ambient Operating Temperature.
6
Two-hole lugs are 10-32 bolt clearance on 5/8" centers. Refer to drawing 031110100 for lug crimping
information.
Table 6
Recommended Battery and Load Distribution Wire Size and Lug Selection
(Bullet Nose-Type Circuit Breaker)

Page 67 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (GMT Fuses) (List KG)
Features
♦ Load distribution (GMT fuses) and load return leads are connected to terminal blocks located on the front
of the assembly.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
Terminal block wire size capacity is 26 to 14 AWG.

CO Ground Wiring (Lists BF, LF, NF, BC, LC, NC, BA, LA, and NA)
Features
♦ Two 10-32 studs on 5/8” centers with hardware are provided on the Return Bus for CO Ground wiring.
Restrictions
Recommended CO ground wire size is 6 AWG.
Recommended lug is 245346500 (2-hole, 10-32 clearance holes, 5/8” centers).

Input Battery Wiring (List BG and NG)


Features
♦ Two (2) 8 AWG 48” long battery cables are factory connected inside the shelf. These cables are
terminated at the customer end in a Red SB50 Anderson battery connector. A mating Anderson battery
connector is provided [Housing: Emerson P/N 138922, Anderson Power Products P/N 992G1. Contacts
(two provided): Emerson P/N 247109602, Anderson Power Products P/N 5952].
♦ Additional strings of battery may be connected to the system using the available battery cable kits (see
List 71 and List 72).
Restrictions
Battery leads are NOT internally fused.

Input Battery Wiring (to Battery Disconnect Circuit Breakers) (Lists BA, LA, and NA)
Features
♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located
inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the front of the shelf.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 6 AWG when all four (4) circuit breaker
positions are used and 2 AWG when only two (2) are used. When using lugs for #4 and #2 AWG wire,

Page 68 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
recommended to use a customer supplied flat washer between the lug and the nut supplied on the
termination.
Ordering Notes
1) The rating of the distribution device determines the wire size requirements. For wire size and lug
selection, refer to Table 6.
2) For other available lugs, refer to drawings 031110100 through 031110300.

Input Battery Wiring (to Battery Busbars) (Lists BF, LF, NF, BC, LC, and NC)
Features
♦ Battery and battery return leads terminated in two-hole lugs are connected to threaded studs located
inside the Distribution Unit. Battery leads are brought into the right side (as viewed from the front) of the
shelf and are accessible from the front of the shelf.
Restrictions
All lugs for customer connections must be ordered separately. Mounting hardware is factory supplied.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width, 0.61 inches.
Ordering Notes
1) Battery wire size varies depending on load, therefore no specific information is provided for wire size.
When making connections, observe correct polarity.
2) List 65 and List 66 provide 2 AWG “shelf side” and “battery side” (respectively) battery cables.

Page 69 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Wiring Illustrations
Shelf Frame Grounding Stud (List 1 and 2 Only)

Rear View

Connect a frame grounding


lead to this stud, if required.

Stud is a Size M5.

Page 70 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
AC Input Wiring (Lists 1 and 2)

List 1 List 2

Front Front
Rectifiers are numbered left to
right as viewed from the front.
AC input connections are AC input connections are
made using the supplied AC made using the supplied AC
input cable assemblies/ input cable assemblies/
line cords connected here. line cords connected here.

Front View AC Input AC Input


Cable Assembly Line Cord

L2-N Blue* White*


Ground Green/Yellow* Green*

L1 Brown* Black*
* color of AC Input Cable
Assembly/Line Cord lead.

ENSURE THE PROPER VOLTAGE AC


Nominal 120/208/240V BRANCH CIRCUIT AND LINE CORDS
AC Input for Rectifier Module: WITH THE APPROPRIATE PLUG
List 1 (19” Shelf): #1 and #2 ARE USED FOR YOUR APPLICATION.
List 2 (23” Shelf): #1, #2, and # 3
500W Rectifier: 120/208/240 VAC Input
1000W Rectifier: 120/208/240 VAC Input

“WARNING - HIGH LEAKAGE CURRENT.”


* AC Input Cable Assembly / Line Cords An industrial style plug is required when
Part Number Customer End providing power to three (3) or more Rectifier
545232 unterminated (List 1 & 2) Modules with a flexible cord. Plug and
540946 L6-30P (List 1 & 2) outlet types 1-15, 2-15, 2-20, 5-15, and 5-20
545252 L5-30P (List 1 & 2) as specified in IEC 60083 are considered
545478 5-15P (List 1 w/ R48-500) to be NON-INDUSTRIAL within the meaning
545479 L5-15P (List 1 w/ R48-500) of this standard.
545480 L6-15P (List 1; List 2 w/ R48-500)
545481 L5-20P (List 1; List 2 w/ R48-500)
545553 L6-20P (List 1 & 2)
545616 L6-30P (List 1 & 2)
547525 L5-30P (List 1 & 2)
548457 5-15P (List 1 w/ R48-500)

Page 71 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
AC Input Wiring (Lists 5 and 6)

List 5 List 6

Front Front
3 3
4 4
6
AC input connections are 1 AC input connections are 2 1
2 5
made using the supplied AC made using the supplied AC
input cable assemblies/ input cable assemblies/
line cords connected here. line cords connected here.
Rectifiers are numbered as shown above Rectifiers are numbered as shown above

Front View
AC Input AC Input
Cable Assembly Line Cord
ENSURE THE PROPER VOLTAGE AC
BRANCH CIRCUIT AND LINE CORDS L2-N Blue* White*
WITH THE APPROPRIATE PLUG
ARE USED FOR YOUR APPLICATION. Ground Green/Yellow* Green*

L1 Brown* Black*
500W Rectifier: 120/208/240 VAC Input
1000W Rectifier: 120/208/240 VAC Input * color of AC Input Cable
Assembly/Line Cord lead.

Nominal 120/208/240V Nominal 120/208/240V


AC Input for Rectifier Module: AC Input for Rectifier Module:
List 5 (19” Shelf): #1 and #2 List 5 (19” Shelf): #3 and #4
List 6 (23” Shelf): #1, #2, and #5 List 6 (23” Shelf): #3, #4, and #6

* AC Input Cable Assembly / Line Cords “WARNING - HIGH LEAKAGE CURRENT.”


An industrial style plug is required when
Part Number Customer End providing power to three (3) or more Rectifier
545232 unterminated (List 5 & 6) Modules with a flexible cord. Plug and
540946 L6-30P (List 5 & 6) outlet types 1-15, 2-15, 2-20, 5-15, and 5-20
545252 L5-30P (List 5 & 6) as specified in IEC 60083 are considered
545478 5-15P (List 5 w/ R48-500) to be NON-INDUSTRIAL within the meaning
545479 L5-15P (List 5 w/ R48-500) of this standard.
545480 L6-15P (List 5; List 6 w/ R48-500)
545481 L5-20P (List 5; List 6 w/ R48-500)
545553 L6-20P (List 5 & 6)
545616 L6-30P (List 5 & 6)
547525 L5-30P (List 5 & 6)
548457 5-15P (List 5 w/ R48-500)

Page 72 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
External Alarm and Monitoring Wiring (Lists 1 and 2)

SCU+
Controller
Notes
Relay Output/Digital Input Cable P/N 545494
is factory connected to terminals. Mating half
(w/ unterminated ends) available, P/N 545495.

Digital Input 1 is factory wired to


Load Breaker / Fuse Alarm.

Digital Input 2 default is External Battery


Disconnect Circuit Breaker Alarm.

A factory-connected jumper
supplies +BAT (Battery Return)
SCU+ Controller
to the positive side of Digital
(Top View)
Input #2.
When ordered, Temperature Probe
leads are factory connected
to SCU+ Connector Board
located in the Distribution Unit.
These are labeled T1 and T2.

NC = Normally Closed
COM = Common
NO = Normally Open

Major Minor All relay contacts are shown


Summary Summary with the relay deenergized.
(48/24V) Relay Outputs
Alarm Alarm
Digital Inputs

Page 73 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
External Alarm and Monitoring Wiring (Lists 5 and 6)
Note: A custom digital input cable and internal wiring kit is available, P/N 545594. This kit is factory installed
only.
Notes
Relay Output Cable P/N 541308 is factory connected to Relay Output terminals.
Mating half (w/ unterminated ends) available, P/N 541309.

If ordered, Digital Input Cable P/N 541310 is factory connected to Digital Input terminals.
Mating half (w/ unterminated ends) available, P/N 541311.

Digital Input 1 is factory wired to Load Breaker / Fuse Alarm.


Digital Input 2 is reserved for External Battery Breaker Alarm.
A factory connected jumper supplies +BAT (Battery Return) to the positive
side of digitla Input #2.

Digital Inputs 3 through 7 are User defined.


Digital Input 8 is reserved for Emergency Stop.
Digital Input 9 is not available in this system.
When ordered, Temperature Probe leads
are factory connected to J11 and J12. These
are labeled 1 and 2.

NC = Normally Closed
COM = Common
NO = Normally Open

All relay contacts are shown RS-485 Connection


with the relay deenergized. SCU+/ACU+ Customer for SM AC, SM BAT,
Interface Board SITEWEB™ BRC, or SM IO
Supervisory Modules.
Relay Outputs See module data
Digital Inputs
7 5 3 1* sheets. (Functional
8 7 6 5 4 3 2 1 with ACU+ Only.)
J9 J8 J7 J6
NO C NC NO C NC NO C NC NO C NC J5 J4 J3
5 3 1 5 3 1 5 3 1 5 3 1 5 3 1 5 3 1 5 3 1
-
+
6 4 2 6 4 2 6 4 2 6 4 2 6 4 2 6 4 2 6 4 2
NO C NC NO C NC NO C NC NO C NC J12 Temp. Probe #2
8 6 4 2 or
SiteWeb™ TEMP

J11 Temp. Probe #1


or
SiteWeb™ TEMP

ON

SW1
Switch settings must be in this position SCU+/ACU+ Customer Interface Board
to interface with the SCU+/ACU+ Controller (Top View)
* The SCU+/ACU+ relay assigned to "Major Summary" alarm (relay 1 by default) operates in the "Fail Safe Mode".
"Fail Safe Mode" means Relay 1 is de-energized during an alarm condition, opening contacts between
C and NO terminals, and closing contacts between C and NC terminals.

The remaining seven (7) relays of the SCU+/ACU+ energize during an alarm condition, closing contacts between
C and NO terminals, and opening contacts between C and NC terminals.

Page 74 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home

Yellow Alarm Lead


(P/N 535294)
(factory wired to
circuit breaker
alarm terminal)

Alarm Wiring to a Single Torque to 84 in-lbs


using supplied hardware
External Battery Disconnect Unit
To
To Connect to shelf
Procedure Power
per table below.
System Battery
1. Connect YELLOW lead exiting top of Remove quick
Battery Disconnect Unit per table below. connect terminal
Remove quick connect terminal first. first.
The YELLOW lead is factory connected
to circuit breaker “C (Common)” alarm
terminal in the Battery Disconnect Unit.
2. There is NO connection to the circuit
breaker “NO (Normally Open)”
alarm terminal.
3. Connect loose end of Jumper factory
connected to bottom terminal on
circuit breaker to circuit breaker
“NC (Normally Closed)” alarm
terminal.

EXTERNAL BATTERY
DISCONNECT UNIT
(Side cover removed in illustration
to show wiring details.)

External Battery Disconnect Circuit Breaker Alarm Input:


A battery disconnect circuit breaker alarm is activated when the circuit
breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

BREAKER ALARM CONNECTION


Alarm Cable
Shelf List CONNECT YELLOW WIRE TO:
on shelf
NO Must order Cable 545495
1 or 2 545495
YES R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
NO Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
5 or 6 541311
YES O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 75 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Yellow Jumper/Alarm Yellow Alarm Lead
Lead (P/N 524384) (P/N 535294)
(Ordered separately (factory wired to
and supplied loose. circuit breaker
Must be wired
by the customer to
* No terminal alarm terminal)
on 524384
each circuit breaker jumper REMOVE
“C (Common)” COMPLETELY
alarm terminal) Connect to FROM ALL BATTERY
shelf per DISCONNECT UNITS
table below. AND DISCARD.
see
previous
page

see
previous
page

see
previous
1st EXTERNAL BATTERY page
DISCONNECT UNIT

(Side cover removed in illustration


to show wiring details.)
2nd EXTERNAL BATTERY
DISCONNECT UNIT

Alarm Wiring to (2) to (3)


3rd EXTERNAL BATTERY
External Battery Disconnect Units
DISCONNECT UNIT
Procedure
1. Completely remove YELLOW lead exiting top of 3. There is NO connection to the circuit
ALL Battery Disconnect Units and discard. breaker “NO (Normally Open)”
alarm terminal.
2. Connect separately ordered YELLOW jumper/alarm
lead (P/N 524384) to circuit breaker “C (Common)” 4. In ALL Battery Disconnect Units,
alarm terminals in ALL Battery Disconnect Units. connect loose end of Jumper factory
Connect remaining end per table below. connected to bottom terminal on
circuit breaker to circuit breaker
“NC (Normally Closed)”
alarm terminal.

External Battery Disconnect Circuit Breaker Alarm Input:


A battery disconnect circuit breaker alarm is activated when the circuit
breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

BREAKER ALARM CONNECTION

Shelf List Alarm Cable CONNECT YELLOW WIRE TO:


on shelf
NO Must order Cable 545495
1 or 2 545495
YES R-BK Lead of 545495. Splice and heat shrink tubing included with 545495

NO Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)


5 or 6 541311
YES O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 76 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home

Yellow Jumper/Alarm
Lead (P/N 524384)
(Ordered separately
and supplied loose.
Must be wired
by the customer to
each circuit breaker * No terminal
“C (Common)” on 524384
alarm terminal) jumper

Connect to
shelf per
table below.
see
previous
page

see
previous
page

see
1st BATTERY TRAY previous
BATTERY DISCONNECT page
CIRCUIT BREAKER

(Side cover removed in illustration


to show wiring details.) 2nd BATTERY TRAY
BATTERY DISCONNECT
CIRCUIT BREAKER
(if furnished)

Alarm Wiring to Battery Disconnect Circuit 3rd BATTERY TRAY


Breakers when (1) to (3) Battery Trays are Used BATTERY DISCONNECT
CIRCUIT BREAKER
Procedure (if furnished)
1. Connect kit-supplied YELLOW jumper/alarm lead
(P/N 524384) to circuit breaker “C (Common)” 3. On ALL Battery Disconnect circuit
alarm terminals on ALL Battery Disconnect Circuit breakers, there should be a factory
Breakers. Connect remaining per table below. connected Jumper connected from
the bottom terminal on the circuit
2. There is NO connection to the circuit breaker to the circuit breaker “NC
breaker “NO (Normally Open)” (Normally Closed)” alarm terminal.
alarm terminal.

External Battery Disconnect Circuit Breaker Alarm Input:


A battery disconnect circuit breaker alarm is activated when the circuit
breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

BREAKER ALARM CONNECTION

Shelf List Alarm Cable CONNECT YELLOW WIRE TO:


on shelf
NO Must order Cable 545495
1 or 2 545495
YES R-BK Lead of 545495. Splice and heat shrink tubing included with 545495

NO Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)


5 or 6 541311
YES O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 77 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home

Yellow Jumper/Alarm
Lead (P/O Cabinet)

Orange Wire on
541434 not used
Connect to
shelf per
table below.

alarm
wire

alarm
wire
1st BATTERY CABINET
BATTERY DISCONNECT alarm
CIRCUIT BREAKER wire

2nd BATTERY CABINET


BATTERY DISCONNECT
CIRCUIT BREAKER
3rd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Alarm Wiring to Battery Cabinets

Procedure
1. Remove quick connect terminal from YELLOW
battery cabinet alarm lead.
2. Wire per table below.

External Battery Disconnect Circuit Breaker Alarm Input:


A battery disconnect circuit breaker alarm is activated when the circuit
breaker is in the OFF position, and provides -48VDC to Digital Input # 2.

BREAKER ALARM CONNECTION

Shelf List Alarm Cable CONNECT YELLOW WIRE TO:


on shelf
NO Must order Cable 545495
1 or 2 545495
YES R-BK Lead of 545495. Splice and heat shrink tubing included with 545495
NO Pin 3 of J3 on customer interface BD (negative side of Digital Input # 2)
5 or 6 541311
YES O-R Lead of 541311. Splice and heat shrink tubing included with 541311

Page 78 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (GMT Fuses) (Lists BG and NG installed in a List 1 or 2, List 1 shown)

Connect to Front Terminal Block

Load Return -48V Distribution


Leads Leads

Fuse Terminal
Position Load Return Load (-48V)
1 1 2
2 3 4
3 5 6
4 7 8
5 9 10
6 11 12
7 13 14
8 15 16
9 17 18
10 19 20

Page 79 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (GMT Fuses) (Lists BF, LF, and NF installed in a List 5 or 6, List 5
shown)

Front

Load Distribution
Leads Enter Here

GMT Fuse GMT Fuse Load GMT Fuse GMT Fuse Load
Positions Distribution Leads Positions Distribution Leads
(Max. 15A) Connect Here (Max. 10A) Connect Here

Mating Connectors and 12' Mating Connectors and 12'


Leads provided with List 62. Leads provided with List 61.

-48V on Left (Black Lead), -48V on Left (Black Lead),


Return on Right (White Lead) Return on Right (White Lead)

Page 80 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (GMT Fuses) (Lists BC, LC, NC, BA, LA, and NA installed in a List 5 or 6,
List 5 shown)

Front

Load Distribution
Leads Enter Here

GMT Fuse Load


GMT Fuse Distribution Leads
Positions Connect Here

Mating Connectors and 12'


Leads provided with List 60.

-48V on Left (Black Lead),


Return on Right (White Lead);
as viewed from side with door
closed.

Page 81 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (Optional Bullet Nose 6-Position GMT Fuse Module)

-48V Distribution Load Return


Leads Leads

Page 82 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (Circuit Breakers) and CO Ground Wiring (Lists BC, LC, and NC installed
in a List 5 or 6, List 5 shown)

Front

Circuit Breaker Load


Distribution and
CO Ground Leads
Load Distribution Enter Here
Circuit Breakers

Front

Portion of shelf removed


in illustration for clarity. Load Return Leads
Leads are brought into CO Ground Lead
side of shelf, and tools
to secure lugs from
front of shelf. 10-32 studs (w/ hardware)
-48V Load
on 5/8" centers for installation
Distribution
of customer provided two hole lugs.
Leads

Page 83 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Load Distribution Wiring (Circuit Breakers), Input Battery Wiring (Circuit Breakers),
and CO Ground Wiring (Lists BA, LA, and NA installed in a List 5 or 6, List 5 shown)

Front

Load Distribution CO Ground, Circuit Breaker


Circuit Breakers Load Distribution, and Circuit
Breaker Battery Leads
Battery Disconnect
Enter Here
Circuit Breakers

Front

Portion of shelf removed


in illustration for clarity.
Leads are brought into Battery Return Leads
side of shelf, and tools Load Return Leads
to secure lugs from CO Ground Lead
front of shelf.
OBSERVE PROPER -48V Load
Distribution 10-32 studs (w/ hardware)
POLARITY WHEN on 5/8" centers for installation
MAKING BATTERY Leads
of customer provided two hole lugs.
CONNECTIONS -48V Battery
Leads

Page 84 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Load Distribution Wiring (GMT Fuses) (List KG)
Loads

Loads
Loads
#1 - #5

#1 - #5
#1 - #5
"A" Side

"B" Side
"A" Side

#6 - #10
#6 - #10

"B" Side
"A" Side

#6 - #10
#6 - #10

Load Returns
Load Returns

Loads
#1 - #5
"B" Side
Connections are made to
screw compression terminal blocks.
Wire size range is 26 to 14 AWG.

Page 85 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Input Battery Wiring (Lists BG and NG installed in a List 1 or 2, List 1 shown)

Rear View

Connect battery leads to factory installed


leads exiting the shelf here. These leads
are factory terminated in an Anderson
connector. A mating half to this connector
is provided for connection to customer battery
leads. External battery cables are also
available to connect 1 (List 71) or 2 (List 72)
strings of batteries to the system.

OBSERVE PROPER POLARITY.


LEADS AND CONNECTORS ARE
MARKED WITH A PLUS AND MINUS
SYMBOL OR TEXT.

Minus (-48V Battery)


Plus (Battery Return)

Page 86 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Input Battery Wiring (Lists BF, LF, NF, BC, LC, and NC installed in a List 1 or 5, List 5 shown)
and CO Ground Wiring (Lists BF, LF, and NF installed in a List 1 or 5, List 5 shown)

List NF Distribution
Unit shown. List BF,
LF, BC, LC, and NC similar.

Front

List 65 provides 3' long, 2 AWG, battery cables


terminated on one end with lugs to connect to
the input battery landings and on the other end Distribution Battery, Battery Return,
Unit and CO Ground Leads
with an Anderson connector.
Enter Here
List 66 provides 12' long, 2 AWG, battery cables
terminated on one end in an Anderson connector
and left unterminated at the remaining end for
connection of battery lugs. List BC, LC, and NC
Distribution Unit
Battery: 1/4-20 studs (w/hardware)
on 5/8" centers for installation
of customer provided two hole lugs.

CO Ground: 10-32 studs (w/hardware)


on 5/8" centers for installation
of customer provided two hole lugs.

CO Ground Lead Right Side


List BF, LF, and NF
Distribution Unit
Battery Return Leads -48 Battery Leads

OBSERVE PROPER
POLARITY WHEN
CO Ground Lead MAKING BATTERY
Right Side
CONNECTIONS

Battery Return Leads -48 Battery Leads

Page 87 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
SPECIFICATIONS
Note: For all rectifier specifications, refer to the separate Rectifier User Manual (UM1R48500/UM1R481000)
supplied with your Power System.

For all controller specifications, refer to the Controller User Manual (UM1M521B or UM1M820B)
supplied with your Power System.

For factory settings of all configurable Controller parameters, refer to the Configuration Drawing (C-
drawing) supplied with your Power System.
1. SYSTEM
1.1 Environmental Ratings
1.1.1 Operating Ambient Temperature Range (Specification Compliant):
(A) -40°C (-40°F) to +65°C (+149°F) with derating output.
(B) -40°C (-40°F) to +40°C (+104°F) with full power performance.
1.1.2 Storage Ambient Temperature Range: -40°C (-40°F) to +75°C (+167°F).
1.1.3 Humidity: This Power System is capable of operating in an ambient relative humidity range of
0% to 90%, non-condensing.
1.1.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
1.1.5 Mounting: This product is intended only for installation in a Restricted Access Location on or
above a non-combustible surface.
This product must be located in a Controlled Environment with access to Craftspersons only.
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut,
or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic
equipment enclosure).
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the
relay rack and 2' for the rear of the relay rack.
Separate shelves are available for mounting in either a 19" or 23" wide relay rack (1” or 1-3/4”
multiple drillings for the 2U shelf and 1-3/4" multiple drillings for the 1U shelf).
Mounting angles are positioned for a 5-inch front projection mounting only.
1.1.6 Ventilation Requirements: Rectifier and mounting shelf ventilating openings must not be
blocked and temperature of air entering rectifiers must not exceed rated Operating Ambient
Temperature Range stated above.
1.2 Compliance Information
1.2.1 Surge Protection: Refer to Paragraphs 2.3.6. and 3.3.6.
Note: This level of protection is a widely used standard for telecommunications power
equipment. As with all such equipment, it is the end user's responsibility to provide an
adequately sized Surge Suppression Device at the commercial power service entrance of
the building that reduces all incoming surges to levels below the classes/categories
stated for the equipment.

Page 88 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
1.2.2 Safety Compliance:
(A) This unit meets the requirements of UL 60950, Standard for Information Technology
Equipment, and is UL Recognized as a power supply for use in Telephone, Electronic Data
Processing, or Information Processing Equipment.
(B) This unit meets the requirements of CAN/CSA 22.2, No. 60950-00 and is tested and
Certified by UL ("c UR") as a Component Type Power Supply.
1.2.3 EMC and Safety:
(A) Complies with the Low-Voltage Directive, 73/23/EEC. Complies with Emissions and
Immunity requirements as specified in GR-1089-Core Issue 4.

EMC
Emissions Test Level
EN 55022: 1998 Conducted Class B
CFR 47 – Part 15
GR-1089 Issue 4 Radiated Class B

Immunity
EN 61000-4-2 Electrostatic Discharge 8kV / 15kV
EN 61000-4-4 Electric Fast Transients 0.25kV / 0.5kV
GR-1089 Issue 4 Radiated Immunity 8.5V/m
Conducted Immunity 89dBuA
Surge IEEE C62.41 2kV / 6kV
SAFETY
Safety of Information Technology Equipment, including
EN 60950-1: 2001
Electrical Business Equipment

1.2.4 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory


(NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS
compliance reports.

For NETSURE™ 211NGFB to remain compliant during a fan failure condition, the backup battery
connection must be utilized to provide sufficient power to the loads for up to eight (8) hours
when the system is operated at greater than 50% output power. If no backup battery
connection is used, the system must operate with a redundant module installed.

1.3 Standard Features


1.3.1 AC Input Connections: AC input cable assemblies and line cords are available.
(A) List 1 and 2: Mounted to the side of the shelf is an AC input housing with one (1) plug-in
connector for one (1) AC input feed.
(B) List 5 and 6: Mounted to the side of the shelf is an AC input housing with two (2) plug-in
connectors for two (2) AC input feeds.
1.3.2 Battery Connections: Battery cables are available.
(A) List 1 and 2: Battery leads are connected to an Anderson connector exiting the rear of the
unit.
(B) Lists 5 and 6: Battery and battery return leads terminated in two-hole lugs are connected to
threaded studs located inside the Distribution Unit. Battery leads are brought into the right
side (as viewed from the front) of the shelf.

Page 89 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
1.3.3 Load Connections:
(A) List 1 and 2: Load and load return leads are connected to a screw-type terminal block
located on the front of the shelf.
(B) Lists 5 and 6: Load distribution (circuit breakers, if furnished) and load return leads
terminated in two-hole lugs are connected to threaded studs located inside the Distribution
Unit. Load leads are brought into the right side (as viewed from the front) of the shelf and
are accessible from the front of the shelf.
Load distribution (GMT fuses) and load return leads are connected to receptacles located
inside the Distribution Unit. Load leads are brought into the right side (as viewed from the
front) of the shelf and are accessible from the front of the shelf.
1.3.4 Alarm and Monitoring Connections: Customer wiring cables are available.
(A) List 1 and 2: Relay output and digital input leads are connected to screw-type terminal
blocks located on the SCU+ located inside the shelf. These leads enter the rear of the shelf.
(B) Lists 5 and 6: Relay output and digital input leads are connected to screw-type terminal
blocks located on the Customer Interface Board located inside the shelf. These leads enter
the right side (as viewed from the front) of the shelf and are accessible from the front of the
shelf.
1.3.5 Dimensions and Weights: Refer to the PHYSICAL SIZE INFORMATION section of this
document.
2. DISTRIBUTION UNIT
2.1 List BG and NG in a List 1 and List 2 Shelf
2.1.1 Ratings: Refer to the Restrictions in the LIST DESCRIPTIONS section of this document.
2.1.2 Battery Connection
(A) 8 AWG cables (48” long) factory wired and terminated in an Anderson type connector.
2.1.3 Standard Features
(A) Provides ten (10) GMT load fuse positions (18/100A to 15A fuses).
(B) Provides front access screw-clamp type load and load return terminals.
(C) Provides the connections for system battery input.
(D) Equipped with an optional Low Voltage Battery Disconnect (LVBD) contactor.
(E) Provides a load fuse alarm indicator.
2.2 List 5 and 6 Shelves
2.2.1 Ratings: Refer to the Restrictions in the LIST DESCRIPTIONS section of this document.
2.2.2 Standard Features
(A) Lists BC, LC, and NC: Provides thirteen (13) GMT load distribution fuse positions.
(B) Lists BF, LF, and NF: Provides four (4) load distribution circuit breaker positions, and five
(5) GMT load distribution fuse positions.
(C) Lists BA, LA, and NA: Provides two (2) battery disconnect circuit breaker positions.
Provides two (2) load distribution circuit breaker positions. Provides five (5) GMT load
distribution fuse positions.
(D) Dimensions: 83mm (H) x 157mm (W) x 274mm (D).
3.25” (H) x 6.2” (W) x 10.8” (D).
(E) Weight (w/out LVD): 3 kg (7 lbs).

Page 90 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
3. GMT LOAD DISTRIBUTION FUSE PANEL (LIST KG)
3.1 Electrical
3.1.1 Input/Output Voltage: Nominal –48VDC
3.1.2 Current: 40A per side, 80A total (Note: The split (A/B) input bus feature provided on panel is
factory connected for single input only.)
3.1.3 Fuse Alarm Circuit: If one or more distribution fuses opens, one set of Form-C relay contacts
changes state, and resistive battery is provided to an alarm terminal. Alarm circuit is factory
connected to activate the Power System Controller fuse alarm.

Page 91 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
PHYSICAL SIZE INFORMATION
Overall Dimensions – List 1

Top View

5
Left Side View 17.3 0.5 12
18.3
19.0 Right Side View

Front View
1.25 1.72

Rear View 0.23

Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 16
Shipping:
Bottom View 3. Finish: Front Panels are Gray
Shelf is Galvaneal.

Page 92 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Overall Dimensions – List 2

Top View

Left Side View 5


21.3 0.5 12
22.3
23.0 Right Side View

Front View
1.25 1.72

Rear View 0.23

Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 20.5
Bottom View Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.

Page 93 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Overall Dimensions – List 5

Top View

17.3 5
Left Side View 0.5 12
18.3
19.0 Right Side View
19.4
Front View

3.00 3.46

Rear View 0.23

Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 30
Bottom View Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.

Page 94 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Overall Dimensions – List 6

Top View

21.3 5
Left Side View
22.3 0.5 12
23.0
23.4 Right Side View

Front View

3.00 3.46

Rear View 0.23

Notes:
1. All dimensions are in inches,
unless otherwise specified.
2. Weight in LBS.
Net: 39
Bottom View Shipping:
3. Finish: Front Panels are Gray
Shelf is Galvaneal.

Page 95 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Overall Dimensions – List KG

Notes:
1. Dimensions in inches
unless otherwise specified.
2. Finish: Gray 8.31
3. Weight:
Net: 10.00
Shipping:
5.05

See Mounting Top View


Angle Detail 0.92

Left Side 17.25 1.75 Right Side


View View
18.25
19.25
22.31
23.25
Front View

Bottom View

R 0.125 (TYP)
Mounting Angle Detail
0.235 0.235
0.125 0.500 0.500 0.125

1.250 1.250

0.125 0.125

Page 96 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
Overall Dimensions – 19” Battery Tray
Optional Battery Disconnect Circuit Breakers
(Shown on Right Side, Available on Either Side)

A
See
Note 3

10.50
12.25
14.00
(as ordered)

ISO View
Front View B
Notes:
See Note 3
1. All dimensions are in inches,
unless otherwise specified. Right Side View
2. P/N 541036 tray shown.
P/Ns 541034 and 540841 similar.
3.
Dimension Dimension
Tray P/N
A B
541036 7.03 16.47
541034 7.03 20.95
540841 6.90 12.50
4. Weight in LBS.
(per tray, less batteries).
With Circuit Without Circuit
Part No.
Breaker Option Breaker Option
541036 20.5 lbs 18.5 lbs
541034 25.3 lbs 23.3 lbs
540841 18.5 lbs 16.5 lbs
5. Finish: Gray
6. Maximum trays available per rack is three (3).

Page 97 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
Overall Dimensions – 23” Battery Tray
Optional Battery Disconnect Circuit Breakers
(Shown on Right Side, Available on Either Side)

A
See
Note 3

10.50
12.25
14.00
(as ordered)

ISO View
B
Front View See Note 3
Notes:
1. All dimensions are in inches, Right Side View
unless otherwise specified.
2. P/N 528496 tray shown.
P/N 540842 similar.
3.
Dimension Dimension
Tray P/N
A B
528496 9.781 24.437
540842 6.90 12.50

4. Weight in LBS.
(per tray, less batteries).
With Circuit Without Circuit
Part No.
Breaker Option Breaker Option
528496 33 lbs 29 lbs
540842 20 lbs 18 lbs

5. Finish: Gray
6. Maximum trays available per rack is three (3).

Page 98 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Application Guide SAG582136600
Spec. No. 582136600 (Model 211NGFB) Issue AF, December 9, 2010
Home
BATTERY MANUFACTURER INFORMATION
Some equipment described in this System Application Guide is designed to accommodate batteries from
various manufacturers. The following are referenced in this document.
C&D: C&D Technologies, Inc., Powercom Div., 1400 Union Meeting Road, Blue Bell, PA 19422-0858
Deka®: East Penn Mfg. Co., Inc., Lyon Station, PA 19536-0147
Douglas®: Douglas Battery Mfg. Co., 500 Battery Dr., Winston-Salem, NC 27117-2159
MarathonTM: GNB Industrial Power, a Division of Exide Technologies, Princeton, NJ 08543.
Northstar: NorthStar Battery Co. LLC, 4000 Continental Way, Springfield, MO 65803

RELATED DOCUMENTATION
Installation Instructions: Section 6031
User Instructions: Section 6032
Battery Cabinet Spec. No. 541434
Installation and User Instructions: Section 6023
Battery Cabinet Spec. No. 545534
Installation and User Instructions: Section 6033
Battery Cabinet Spec. No. 545506
Installation and User Instructions: Section 6036
Rectifier User Instructions: UM1R481000
SCU+ Controller User Instructions: UM1M521B
ACU+ Controller User Instructions: UM1M820B

Page 99 of 100
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SAG582136600 System Application Guide
Issue AF, December 9, 2010 Spec. No. 582136600 (Model 211NGFB)
Home
REVISION RECORD
Change
Issue Number Description of Change Date Approved
(ECO)
AA LLP212765 New 09/16/2009 John Jasko
List BC, LC, and NC RESTRICTIONS updated.
AB LLP213064 Reference to custom SCU+ configurations 10/09/2009 John Jasko
added. Custom digital input cable kit added.
Lists BF, LF, and NF now available (note
stating Lists were unavailable removed from
AC LLP213144 document). Restriction added to Battery 01/06/2010 John Jasko
Cabinet P/N 541434 that it can only be used
with List 1 and 2.
Added 545644, 58213660067, 545728,
540993, 545616, 547525, 548457, 541285,
545534, and 545506.
AD LLP213376 Updated breaker alarm wiring and system 05/19/2010 Shanon Ravacio
ratings and wiring information.
Changed input cord gauges per LLP213702
Add P/N 547645
Add AP6C57EA/EB Ring and Distribution
AE LLP214159 09/03/2010 Shanon Ravacio
Module
List LA now available (notes stating List was
unavailable removed from document). Added Tim Strouse
Dec 14, 2010
List KG, List 91, ACU+, and SiteWeb™ TEMP.
AF LLP214106 John Kirkpatrick
Removed Rectifier and Controller specification
Dec 14, 2010
information, and referenced the separate
Rectifier and Controller User Manuals.

Emerson Network Power, Energy Systems, North America, Inc.


4350 Weaver Parkway, Warrenville, IL 60555

Toll Free: 800-800-1280 (USA and Canada)


Telephone: 440-246-6999 Fax: 440-246-4876
Web: EmersonNetworkPower.com/EnergySystems
EnergyNet: Secure.EmersonNetworkPower.com

Page 100 of 100