500 User Manual
500 User Manual
Operation Manual
Contents
Preface................................................................................................................................................ 4
2.1 Nameplate................................................................................................................... - 17 -
4.1Operation Panel.................................................................................................................44
-2-
6.1 Standard Function Parameters.................................................................................... 58
PE group reserved..................................................................................................................143
A1 ~A4group reserved...........................................................................................................147
-3-
7.1 Routine Repair and Maintenance of the 500 Series............................................ 163
Preface
Thank you for purchasing the 500Series AC Drive. The 500Series AC Drive is a
general-purpose high performance Current vector control AC Drive. Mainly used to
control and adjust the three-phase AC asynchronous motor speed and torque.
500 series uses high-performance vector control technology, Low speed high
torque output, Has good dynamic characteristics, Super overload capacity, rich and
powerful functions, stable performance. It is used to drive various automation
production equipment involving Textile, Paper-making, Wire-drawing, Machine tool,
Packing, Food, Fan and Pump.
This manual describes the correct use of the 500Series AC Drive, including
selection, parameter setting, commissioning, maintenance & inspection. Read and
understand the manual before use and forward the manual to the end user.
Notes
The drawings in the manual are sometimes shown without covers or protective
guards, to explain the details of the product.
Remember to install the covers or protective guards as specified first, and then
perform operations in accordance with the instructions.
The drawings in the manual are shown for description only and may not match
the product you purchased.
-4-
500 series User-Manual Preface
Contact our agents or customer service center if you have problems during the
use.
When unpacking, please confirm carefully: The model name of the machine
and the AC Drive rating are the same as your order. The packing containing
your ordered machine (with product certification), user manual (with product
warranty card).
If the product is damaged during transport, If you find that there is some
omission or damage, please promptly contact with our company or your
supplier for solution.
-5-
500 series User-Manual Safety Information & Precautions
Chapter 1
Definition of security:
In this manual, the notices are graded based on the degree of danger:
DANGER :indicates that failure to comply with the notice will result in severe
personal injury or even death.
WARNING :indicates that failure to comply with the notice will result in personal
injury or property damage.
Read this manual carefully so that you have a thorough understanding. Installation,
commissioning or maintenance may be performed in conjunction with this chapter.
500 SERIES will assume no liability or responsibility for any injury or loss caused by
improper operation.
Using Safety
precautions
stage grade
Do not install the equipment if you find water
seepage,component missing or damage upon unpacking.
danger
Do not install the equipment if the packing list does not
conform to the product you received.
-7-
500 series User-Manual Safety Information & Precautions
When two AC drives are laid in the same cabinet, arrange the
installation positions properly to ensure the cooling effect.
Ensure that the power supply is cut off before wiring. Failure to
comply may result in electric shock.
During
Tie the AC drive to ground properly by standard. Failure to
installati
comply may result in electric shock.
on
Never connect the power cables to the output terminals (U,V,
W) of the AC drive. Pay attention to the marks of the wiring
terminals and ensure correct wiring. Failure to comply will result
Termin in damage to the AC drive.
als
Never connect the braking resistor between the DC bus
WARNING (+) and (-). Failure to comply may result in a fire.
-8-
500 series User-Manual Safety Information & Precautions
Use a shielded cable for the encoder, and ensure that the
shielding layer is reliably grounded.
on result in accidents.
Warnin Do not touch the rotating part of the motor during the motor
g auto-tuning or running. Failure to comply will result in
-9-
500 series User-Manual Safety Information & Precautions
accidents.
- 10 -
500 series User-Manual Safety Information & Precautions
The AC drive generates high leakage current during running, which flows through
the protective earthing (PE) conductor. Thus install a type-B RCD at primary side of
the power supply. When selecting the RCD, you should consider the transient and
steady-state leakage current to ground that may be generated at startup and during
running of the AC drive. You can select a specialized RCD with the function of
suppressing high harmonics or a general-purpose RCD with relatively large residual
current.
The AC drive generates high leakage current during running, which flows through
the PE conductor. Earth connection must be done before connection of power
supply. Earthing shall comply with local regulations and related IEC standards.
Perform the insulation test when the motor is used for the first time, or when it is
reused after being stored for a long time, or in a regular check-up, in order to
prevent the poor insulation of motor windings from damaging the AC drive. The
motor must be disconnected from the AC drive during the insulation test. A 500-V
mega-Ohm meter is recommended for the test. The insulation resistance must not
be less than 5 MΩ.
- 11 -
500 series User-Manual Safety Information & Precautions
If the rated capacity of the motor selected does not match that of the AC drive,
especially when the AC drive's rated power is greater than the motor's, adjust the
motor protection parameters on the operation panel of the AC drive or install a
thermal relay in the motor circuit for protection.
5) Running at over 50 Hz
The AC drive may encounter the mechanical resonance point at some output
frequencies, which can be avoided by setting the skip frequency.
The output of the AC drive is pulse width modulation (PWM) wave with certain
harmonic frequencies, and therefore, the motor temperature, noise, and vibration
are slightly greater than those when the AC drive runs at power frequency (50 Hz).
Do not install the capacitor for improving power factor or lightning protection
voltage-sensitive resistor on the output side of the AC drive because the output of
- 12 -
500 series User-Manual Safety Information & Precautions
the AC drive is PWM wave. Otherwise, the AC drive may suffer transient over-current
or even be damaged.
When a contactor is installed between the input side of the AC drive and the power
supply, the AC drive must not be started or stopped by switching the contactor on
or off. If the AC drive has to be operated by the contactor, ensure that the time
interval between switching is at least one hour since frequent charge and discharge
will shorten the service life of the capacitor inside the AC drive.
When a contactor is installed between the output side of the AC drive and the motor,
do not turn off the contactor when the AC drive is active. Otherwise, modules inside
the AC drive may be damaged.
- 13 -
500 series User-Manual Safety Information & Precautions
The AC drive must not be used outside the allowable voltage range specified in this
manual. Otherwise, the AC drive's components may be damaged. If required, use a
corresponding voltage step-up or step-down device.
Do not change the three-phase input of the AC drive into two-phase input.
Otherwise, a fault will result or the AC drive will be damaged.
The AC drive has a built-in voltage dependent resistor (VDR) for suppressing the
surge voltage generated when the inductive loads (electromagnetic contactor,
electromagnetic relay, solenoid valve, electromagnetic coil and electromagnetic
brake) around the AC drive are switched on or off. If the inductive loads generate a
very high surge voltage, use a surge suppressor for the inductive load or also use a
diode.Do not connect the surge suppressor on the output side of the AC.
The regular using temperature of this 500 series AC Drive is -10℃~+50℃ When
the temperature more than 50 need to de-rate using,The temperature rises by 1.5%
degrees centigrade.
In places where the altitude is above 1000 m and the cooling effect reduces due to
thin air, it is necessary to de-rate the AC drive. Contact 500 SERIES for technical
support.
If wiring that is not described in this manual such as common DC bus is applied,
contact the agent or 500 SERIES for technical support.
16) Disposal
- 14 -
500 series User-Manual Safety Information & Precautions
The electrolytic capacitors on the main circuits and PCB may explode when they are
burnt. Poisonous gas is generated when the plastic parts are burnt. Treat them as
ordinary industrial waste.
• The cooling fan and rotor shaft of non-variable-frequency motor are coaxial,
which results in reduced cooling effect when the rotational speed declines. If
variable speed is required, add a more powerful fan or replace it with variable-
frequency motor in applications where the motor overheats easily.
• The standard parameters of the adaptable motor have been configured inside
the AC drive. It is still necessary to perform motor auto-tuning or modify the default
values based on actual conditions. Otherwise, the running result and protection
performance will be affected.
- 15 -
500 series User-Manual Product Information
Chapter 2
Product Information
- 16 -
500 series User-Manual Product Information
500 SERIES AC Drive s have been tested and inspected before leaving the
manufacturer. Before unpacking the product, please check product packaging for
shipping damage caused by careless transportation and whether the specifications
and type of the product complies with the order. If any questions, please contact the
supplier of 500 SERIES products, or directly contact the company.
※Inspect that the contents are complete (500 series AC Drive , operation manual,
warranty card, keyboard extension line every each unit.)
※Check the nameplate on the side of the AC Drive to ensure that the product you
have received is the right one you ordered.
2.1 Nameplate
Model
Special model
Date of model
Date of manufacture
Fig. 2.1
- 17 -
500 series User-Manual Product Information
Fig. 2.1
- 18 -
500 series User-Manual Product Information
Y0110G1 11 15 45 004
Y0150G1 15 20 60 004
Y0185G1 18.5 25 75 004
Y0220G1 22 30 90 005
Y0300G1 30 40 110 005
Y0370G1 37 50 150 006
Y0450G1 45 60 170 006
Y0550G1 55 70 210 007
Y0750G1 75 100 300 007
Y0930G1 93 125 340 008
Y1100G1 110 150 380 008
Y1320G1 132 175 470 008
Y1600G1 160 210 600 009
Y1850G1 185 250 650 009
Y2000G1 200 260 725 009
Table 2.2.1
- 19 -
500 series User-Manual Product Information
Y0370G3 37 50 75 004
Y0450G3 45 60 90 005
Y0550G3 55 70 110 005
Y0750G3 75 100 150 006
Y0930G3 93 125 170 006
Y1100G3 110 150 210 007
Y1320G3 132 175 250 007
Y1600G3 160 210 300 007
Y1850G3 185 250 340 008
Y2000G3 200 260 380 008
Y2200G3 220 300 415 008
Y2500G3 250 350 470 008
Y2800G3 280 370 520 008
Y3150G3 315 400 600 009
Y3550G3 355 420 650 009
Y4000G3 400 530 725 009
Y4500G3 450 600 800 009
Y5000G3 500 700 920 009
Table 2.2.2
Fig. 2.3.1.1
- 20 -
500 series User-Manual Product Information
Fig. 2.3.1.2
Fig. 2.3.2.1
- 21 -
500 series User-Manual Product Information
Fig. 2.3.2.2
Fig. 2.3.3
- 22 -
500 series User-Manual Product Information
0.4kw-2.2kw 220v Single Phase /Three Phase Input & Three Phase Output
AC Drive
W W1 L3 L2 H H1 Hole N.W. G.W.
model Case
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg)
M0.4kw-220v
M0.75kw-220v 85.5 74 141.5 132 113 123 Ø2 0.8 1 00
M1.5kw-220v
0.75kw-220v
1.5kw-220v 100 92 152 143 116.5 127 Ø2 0.9 1.1 001
2.2kw-220v
4kw 220v Single Phase /Three Phase Input & Three Phase Output
AC Drive
models W W1 H H1 D D1 N.W. G.W.
Case
(mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg)
5.5kw-200kw 220v Single Phase /Three Phase Input & Three Phase Output
AC Drive
H W D H1 W1 R1 N.W. G.W.
model Case
(mm) (mm) (mm) (mm) (mm) (mm) (kg) (kg)
5.5kw-220v
397.1 212 190.9 378.2 156.5 Ø7 9.5 11.5 003
7.5kw-220v
11kw-220v
15kw-220v 463 285 217 447 235 Ø7 11.9 17.8 004
18.5kw-220v
22kw-220v
600.1 385.4 267 580 260 Ø9 27 39 005
30kw-220v
37kw-220v
700 473 311 678 343 Ø10 43 58 006
45kw-220v
55kw-220v
849 480 389 822.1 369 Ø10 85 98 007
75kw-220v
93kw-220v
110kw-220v 1060 650 381 1030 420 Ø12 110 132 008
132kw-220v
160kw-220v
185kw-220v 1361 800 392.5 1300 520 Ø12 230 250 009
200kw-220v
Chart 2.4.1
- 23 -
500 series User-Manual Product Information
45kw-380v
600.1 385.4 267 580 260 Ø9 27 39 005
55kw-380v
75kw-380v
700 473 311 678 343 Ø10 43 58 006
93kw-380v
110kw-380v
132kw-380v 849 480 389 822.1 369 Ø10 85 98 007
160kw-380v
185kw-380v
200kw-380v
1060 650 381 1030 420 Ø12 110 132 008
220kw-380v
250kw-380v
280kw-380v
315kw-380v
355kw-380v 1361 800 392.5 1300 520 Ø12 230 250 009
400kw-380v
450kw-380v
- 24 -
500 series User-Manual Product Information
500kw-380v
Chart 2.4.2
Item Specifications
Control High performance of current vector control technology to realize 3
system phase asynchronous motor control
Drive
High efficiency driving for induction motor and synchronous motor
performance
Maximum
Vector control:0~500Hz V/F control:0~500Hz
frequency
Carrier 0.5kHz~16kHz; the carrier frequency will be automatically adjusted
frequency according to the load characteristics
Input
Digital setting: 0.01Hz
frequency
Analog setting: maximum frequency ×0.025%
resolution
Open loop vector control(SVC)
Control mode Closed loop vector control(FVC)
Basic function
V/F control
Startup torque G type:0.5Hz/150%(SVC);0Hz/180%(FVC) P type:0.5Hz/100%
Speed range 1:100(SVC) 1:1000(FVC)
Speed
stabilizing ±0.5%(SVC) ±0.02%(FVC)
precision
Torque control
±5%(FVC)
precision
G type:150% rated current 60 seconds; 180% rated current 3
Over load
seconds;
capability
P type:120% rated current 60 seconds; 150% rated current 3 seconds
Torque boost Auto torque boost function;Manual torque boost 0.1%~30.0%
Linear V/F, multi-point V/F and square V/F curve (power of 1.2, 1.4,
V/F curve
1.6, 1.8, 2)
V/F separation In 2 ways:separation ,semi separation
Acc. / dec Straight line or S curve acceleration and deceleration mode.
curve Four kinds of acceleration and deceleration time. Acceleration and
- 25 -
500 series User-Manual Product Information
- 26 -
500 series User-Manual Product Information
ra
d
b
p
o
ti
o
n
e
e
y
- 27 -
500 series User-Manual Product Information
OLED display Optional device, which can offer Chinese / English operating content
Keyboard
Equipped with keyboard potentiometer or coding potentiometer
potentiometer
Parameter
Realize parameter rapid copy through OLED operation panel
copy
Key lock &
Realize button locking, define operation range for part of buttons to
function
prevent operation fault.
selection
It can implement power-on motor short-circuit detection, input /
Protection output phase loss protection, over current protection, over voltage
function protection, under voltage protection, overheating protection and
overload protection.
OLED operation panel, brake component, multi-function extended
card 1.IO extended card 2.user programmable card, RS485
communication card,.communication card, CANlink communication
Optional parts
card, CANopen communication card, differential input PG card, UVW
differential input PG card, rotating AC Drive PG card, OC input PG
card.
Indoor, and be free from direct sunlight, dust, corrosive gas,
Using place
combustible gas, oil smoke, vapor, drip or salt.
Altitude Below 1000m
Environment
Chart 2.5
- 28 -
500 series User-Manual Product Information
- 29 -
500 Series AC Drive User Manual Installation & Wiring
Chapter 3
- 30 -
500 Series AC Drive User Manual Installation & Wiring
1) Ambient temperature-10℃~50℃.
2) Avoid electromagnetic interference and keep the unit away from the source of
interference.
3) Prevent dropping water, steam, dust powder, cotton fiber or fine metal powder
from
invasion.
4) Prevent oil, salt and corrosive gas from entering it.
5) Avoid vibration. Vibration should be less than 0.6G. Keep away from punching
machine etc.
6) Avoid high temperature, moisture or being wetted due to raining, with the
humidity
below 95%RH (non-condensing).
7) Prohibit the use in the dangerous environment where inflammable or
combustible or
explosive gas, liquid or solid exists.
The clearance that needs to be reserved varies with the power class of the 500 Series, as
shown in the following figure.
Figure 3.1.2.1 Clearance around the 500 Series for installation
Hot wind
- 31 -
500 Series AC Drive User Manual Installation & Wiring
Fig. 3.1.2.2
- 32 -
500 Series AC Drive User Manual Installation & Wiring
Fig. 3.1.2.3
1) Mounting space is shown in chart 3.1.2, which could ensure the heat sinking
space of the AC Drive . However, the heat sinking of other devices in the cabinet
shall also be considered.
2) Install the AC Drive vertically so that the heat may be expelled from the top.
However, the equipment cannot be installed upside down. If there are multiple
up-down installation is required, please install the thermal insulating guide plate
- 33 -
500 Series AC Drive User Manual Installation & Wiring
referring to the Fig. 3.2.1.2 and 3.1.2.3 for standalone installation and up-down
installation.
4) It is suggested that cooling cabinet be put outside at places where powder dust
exists. Space inside the sealed cabinet shall be large as much as possible.
PE Earth terminal
Chart . 3.2.1
The specifications and installation methods of the external power wiring should
comply with the local regulations and related IEC standards.
Recommen Recommend
Recommend
ded Recommend ed input Recommend
AC Drive ed output
breaker ed contactor side main ed control
Model side main
specificatio specification loop wire loop wire(㎡)
loop wire(㎡)
ns (㎡)
Single 0.4KW 16 10 2.5 2.5 1.5
Phase 0.75KW 16 10 2.5 2.5 1.5
- 34 -
500 Series AC Drive User Manual Installation & Wiring
Chart 3.2.2.1
The reference value of the brake resistance selection and the line distance should
be less than 5m.Otherwise, the AC Drive may be damaged.
The specifications and installation methods of the external power wiring should
comply with the local regulations and related IEC standards.
For power cable wiring, please refer to the wiring shown in Figure 3.2.3.
The AC Drive side can not be connected to the capacitor or surge absorber,
otherwise it will be caused to protect and even damage.
When the motor cable is too long, because of the influence of distributed
capacitance, it is easy to generate electric resonance, resulting in the insulation
failure of motor, or the large leakage current, which makes the AC Drive
overcurrent protection. When the length of the motor cable is more than 100m,
the AC output reactor must be installed near the frequency converter.
The terminals must be reliably grounded, and the grounding wire must be less
than 10 Omega. Otherwise, it will result in abnormal or even damage to the
equipment work.
- 35 -
500 Series AC Drive User Manual Installation & Wiring
Can not share the ground terminal and the power zero line N terminal.
When selecting protective devices, factors such as power cable current capacity,
system overload capacity and short-circuit capability of equipment before power
distribution should be considered. Generally, please choose according to
recommended values in 3.2.3 table recommendation.
T/A T/B T/C AO1 DI5 DI4 DI3 DI2 DI1 COM GND AI2 AI1 AM 10V
Chart 3.2.3.1
T/A T/B T/C DI1 DI2 DI3 DI4 DI5 AO1 COM 10V AM AI1 AI2 - + GND
Chart 3.2.3.2
T/A1 T/B1 T/A T/B T/C A01 AO2 DI1 DI2 DI3 DI4 DI5 OP
Chart 3.2.3.3
- 36 -
500 Series AC Drive User Manual Installation & Wiring
Termin Terminal
Type al sign Function Description
Name
- 37 -
500 Series AC Drive User Manual Installation & Wiring
- 38 -
500 Series AC Drive User Manual Installation & Wiring
interf interface
ace PG card 14 needle terminals , for selectable card please
J13
interface refer to interface configuration, table 3-3.3.
External
J7 keyboard External keyboard.
interface
3.4 Terminal wiring diagram
Fig. 3.4.1
- 39 -
500 Series AC Drive User Manual Installation & Wiring
Fig. 3.4.2.1
- 40 -
500 Series AC Drive User Manual Installation & Wiring
Fig. 3.4.2.2
- 41 -
500 Series AC Drive User Manual Keyboard Operation Instructions
Chapter 4
You can modify the parameters, monitor the working status and start or stop the
500 series by operating the operation panel, as shown in the following figure.
Function indicator
Shortcut key
Increase/decrease Keyboard/Exit key
key
Enter key
Shift key
Fig. 4.1.1
- 43 -
500 Series AC Drive User Manual Keyboard Operation Instructions
Notes:When operating on the three level menu, the Level II can be returned by
PRGM or ENT. The difference between them is: according to ENT, set the
parameters into the control panel, then return to the level II, and automatically
transfer to the next function code: PRGM directly returns to the level II, does not
store parameters, and stays in the current function code.
- 44 -
500 Series AC Drive User Manual Keyboard Operation Instructions
Fig. 4.2.1
In the state of the level III, if the parameter does not have a flashing bit, it
indicates that the function code can not be modified,This may be because:
1.Such a function code is only readable, such as, AC drive model, actually
detected parameter and running record parameter.
2,Such a function code cannot be modified in the running state and can only be
changed at stop.
- 45 -
500 Series AC Drive User Manual Keyboard Operation Instructions
The self - learning operation steps of the motor parameters are as follows:
The 1st step:If the motor can completely disconnect with the load, in the case of
power failure, the motor will be detached from the mechanical motor and the load
part, so that the motor can be freely rotated.
The 2nd step:After power-on, the AC Drive command source (P0-02) is selected as
the command channel of the operation panel.
The 3rd step:Input the nameplate parameters of the motor (such as P1-00 to P1-05)
correctly, please input the following parameters according to the actual parameters
of the motor:
Parameter
Input
P1-00: motor type select P1-01: motor rated power
according to
P1-02: motor rated voltage P1-03: motor rated current
the motor
P1-04: motor rated power P1-05: motor rated revolving
nameplate
speed
Chart 4.2.2
The 4th step: if it is asynchronous motor, then P1-37 please select 2 (complete
tuning of the asynchronous machine), press ENTER key,meanwhile the keyboard
displays TUNE. Then press the RUN key on the keyboard panel, the AC Drive will
drive the motor to increase or decelerate, and turn it into operation. The running
indicator lights up, and the tuning operation duration is about 2 minutes. When the
above display information is gone, it returns to the normal parameter display state,
indicating that the tuning is completed.
After this complete tuning, the AC Drive automatically calculates the following
parameters of the motor:
Motor Parameter
- 46 -
500 Series AC Drive User Manual Keyboard Operation Instructions
If the motor can not be completely removed from the load,parameter P1-37
please choose 3(asynchronous motor Static tuning 2),Then press the RUN key
on the keyboard panel to start the tuning of the motor parameters.
- 47 -
500 Series AC Drive User Manual Operation Cases and Descriptions
Chapter 5
Parameter Settings:
Parameter Settings:
Start, stop: press "RUN" key FWD indicator light On to Run; press "STOP /
RESET" key to stop;
If you want the keyboard to Forward and Reverse, set P7-01 = 2 and press the
(REV / JOG) key. REV indicator light On.
Parameter Settings:
- 49 -
500 Series AC Drive User Manual Operation Cases and Descriptions
P0-02=1 P0-03=2
The AC Drive stops when the DI1-DI2 terminal is disconnected from COM.
Parameter Settings:
P0-02=1 P0-03=2
The AC Drive stops when the DI1-DI2 terminal is disconnected from COM.
Speed control: Analog voltage signal (AI1 GND- "0-10V or 0-5V voltage signal)
Analog voltage signal linearity adjustment parameters in the P4-13 --- P4-17,
generally do not need to adjust
Parameter Settings:
P0-02=1 P0-03=3
- 50 -
500 Series AC Drive User Manual Operation Cases and Descriptions
The AC Drive stops when the DI1-DI2 terminal is disconnected from COM.
Speed control: Analog current signal (AI2 GND- "4-20MA analog current signal)
Analog current signal linearity adjustment parameters in the P4-18 --- P4-22,
generally do not need to adjust.
Panel Start:
Parameter Settings:
Start and stop: Press "RUN" key FWD operation indicator light On, press (REV /
JOG) key REV indicator light (set P7-01 = 2); Press (STOP / RESET) to stop the AC
Drive.
Speed control: (DI1 --- COM) Short-circuit speed increases, (DI2-COM) short-
circuit speed decreases
External start:
Parameter Settings:
Start, stop: "DI3-COM" shorted FWD indicator light On, the AC Drive is running;
"DI4-COM" shorted REV indicator light On, the AC Drive is running; otherwise
the AC Drive stops.
- 51 -
500 Series AC Drive User Manual Operation Cases and Descriptions
Panel Start:
Start, stop: press "RUN" key, FWD indicator light On, AC Drive run; press
REV/JOG key, REV indicator light on, (Set P7-01=2); Press STOP/RESET key, AC Drive
stops.
External start:
Speed control: Define the multi-speed terminal and COM short circuit, AC Drive
display frequency.
Multi-speed table:
Corresponding
K4 K3 K2 K1 Instruction set
parameters
- 52 -
500 Series AC Drive User Manual Operation Cases and Descriptions
Chart 5.7.1
Acceleration or
Terminal 2 Terminal 1 Corresponding parameters
deceleration time selection
Acceleration or
Terminal 2 Terminal 1 Corresponding parameters
deceleration time selection
- 53 -
500 Series AC Drive User Manual Operation Cases and Descriptions
Chart 5.7.2
Parameter settings:
PA-01 (PID Given value---- Set according to the size of the pressure gauge or
transmitter range and the actual needs)
Wiring:
Remote pressure gauge: 10V AI1 GND
Pressure Transmitters: 10V AI2 or 24V AI2; Shor circuit COM and GND
Parameter setting:
Note: This parameter sets the display status of the AC Drive in the running state
(BIT00-----BIT15, total 16 states), With 4 hexadecimal representation, One bit
hexadecimal means 4-bit binary(2 is represented by 0 1, 0 indicates that this state
is not displayed,1 indicates that this status is displayed.)
- 54 -
500 Series AC Drive User Manual Operation Cases and Descriptions
converter in the running state shows the operating frequency, set frequency, bus
voltage, output voltage.
Parameter setting:
P7-03=H.4000
Note:
2. Because we drag the motor is generally asynchronous motor, there is a slip or the
load itself involves a change in the speed ratio, so the P7-06 parameter settings are
generally set to a few points, let it more accurately reflect the actual load speed.
- 55 -
500 Series AC Drive User Manual Function Code Table
Chapter 6
Group P and Group A are standard function parameters. Group U includes the
"☆": The parameter can be modified when the AC drive is in either stop or running
state.
"★": The parameter cannot be modified when the AC drive is in the running state.
"●": The parameter is the actually measured value and cannot be modified.
"*": The parameter is factory parameter and can be set only by the manufacturer.
Function Factory
Name Setting Range property
code Setting
P0 Standard Function Parameters
P0-00 GP type display - - ★
0:Speed sensorless vector control
(SFVC)
Motor control
P0-01 1:Closed-loop vector control 2 ★
mode
(CLVC)
2:Voltage/Frequency (V/F)
0: Speed sensorless vector control
It refers to the open-loop vector control that is generally applied to high performance
control field. One inverter can only drive one motor. E.g.:machine tool, centrifugal machine,
fiber drawing machine, injection
molding machine’ load etc.
1: Speed sensor vector control
It refers to the closed-loop vector control and encoder must be added to the motor end.
Inverter must be matching with the same type PG card of the encoder. This control mode is
- 57 -
500 Series AC Drive User Manual Function Code Table
suitable for high precision speed control or torque control field. One inverter can only drive
one motor. E.g.:high speed papermaking machinery , hoisting machinery , elevator’ load
etc.
2: V/F control
V/F control mode is suitable for fields that load demand is not high or one inverter can
drive multiple motors. E.g.:draught fan, pump’ load etc.
Tips:Motor parameters must be indentified before choosing vector control mode. Only
accurate motor parameters can play the advantage of vector control mode. Users can get
better performance by adjusting speed regulator group P2 parameters(motor 2,motor 3,motor
4 respectively for group A2,A3,A4)
FVC is generally used for permanent magnet synchronous motor, while part of the small
power applications can select V/F control mode. 500 series support specific models of
permanent magnet synchronous motor sensorless vector control mode. Please refer to 500
users manual and 500S dedicated users manual for using method.
0:Operation panel control (LED
off)
Command
P0-02 1:Terminal control (LED on) 0 ☆
source selection
2:Communication control (LED
blinking)
Inverter control commands include : run, stop, forward rotation (FWD), reverse rotation
(REV), forward jog (FJOG), reverse jog (RJOG), etc.
0: Operation panel command channel (“LOCAL/REMOT” LED off);
Perform running command control with RUN, MF.K and STOP/RESET keys on the
operation panel.
1: Terminal command channel (“LOCAL/REMOT” LED on);
Perform running command control with multifunctional input terminals such as FWD, REV,
FJOG, RJOG, and so on.
2: Serial port communication command channel (“LOCAL/REMOT” LED flashing).
The running command is given by the host computer via the communication mode. When
the item is chosen, it must be equipped with communication card(Modbus RTU、Profibus DP
card、CANlink card、 users programmable control card or CANopen card and so on).
For the communication protocol, please refer to “ PD communication function group ”
and supplementary explanation of corresponding communication card for details.
Supplementary explanation for communication card is allotted with communication card. This
manual contains a brief description of communication card.
Main frequency 0:Digital setting (non-retentive at
P0-03 4 ★
source X power failure)
- 58 -
500 Series AC Drive User Manual Function Code Table
- 59 -
500 Series AC Drive User Manual Function Code Table
Function code P4-33 is used to set AI1~AI3 3-channel analog input. Choose 1 curve among
the 5 respectively. For specific correspondence please refer to P4、A6 groups.
5: Pulse setup(DI5) Pulse setup is set through terminal pulse. Signal standard:voltage
range 9V~30V, frequency range 0kHz~100kHz. Set pulse can be only input through multi-
function input terminal DI5. Relationship between DI5 input pulse frequency and
corresponding settings is set through P4-28~P4-31. It is linear relationship(2-point
correspondence). Pulse input 100.0% refers to the percentage of P0-10 .
6: MS command MS command running mode is set through different combination mode
of digital input DI terminal. There are 4 MS command terminals with 16 status of 500 series.
PC group function codes correspond to 16 “MS command”. “MS command” is
percentage relativing to P0.10 ( maximum frequency). When digital input terminal DI is used
as MS command terminal, user should set through P4 group. For specifications please refer to
P4 group.
7: Simple PLC When frequency source is set to 7, running frequency source can be
switched to any frequency command during 1~16.
User can set frequency command retention time and acceleration/deceleration time
respectively. For specifications please refer to PC group .
8: PID Running frequency is the output of PID control process. Generally used for field
process closed-loop control.
When PID is chosen, user should set relevant parameters of PA group “PID function”.
9: Communication setup Communication setup refers to main frequency source that
setting through communication method of position machine. 500 series support 4 kinds of
communication modes:Modbus、Profibus DP、CANopen、CANlink. 4 kinds of
communication can not be used at the same time. Communication card should be installed
during the use of communication.4 kinds of communication cards are optional. User can select
to buy according to the needs, and set parameter P0-28 correctly.
0:Digital setting (non-retentive at
power failure)
1:Digital setting(Pre-frequency
as P0-08,UP/DOWN could be
Auxiliary changed,retentive at power
P0-04 frequency source failure) 0 ★
Y selection 2:AI1
3:AI2
4:Keyboard potentiometer
5:reserved
6:Multi-reference
- 60 -
500 Series AC Drive User Manual Function Code Table
7:simple PLC
8:PID
9:Communication setting
When the auxiliary frequency source is used as independent frequency reference channel
(i.e. frequency source switching from X to Y), it is used in the same way as the relative
specifications of P0-03.
When the auxiliary frequency source is used as overlap reference (i.e. frequency source
selection switching from X plus Y or X to X plus Y), it has special points as follows:
When the auxiliary frequency source is digital reference, the preset frequency (P0-08) is
nonsensical, and it needs to adjust the main reference frequency through the keys “∧”and
“∨” of the keyboard (or UP and DOWN of multifunctional input terminals).
When the auxiliary frequency source is analog input reference (AI1、AI2、AI3) or pulse
input reference, 100% of input setup is relative to the auxiliary frequency source range, and
can be set through P0-05 and P0-06.
When the frequency source is pulse input reference, it is similar to the analog value.
Prompt: There is difference between the auxiliary frequency source Y selection and the main
frequency source X setup value. That is to say, P0.03 and P0.04 cannot use the same frequency
reference channel.
Auxiliary
frequency 0:Relative to maximum frequency
P0-05 0 ☆
source Y range 1:Relative to frequency source X
selection
Auxiliary
P0-06 frequency 0% ~ 150% 100% ☆
source Y range
When the frequency source selection is frequency overlap reference(P0-07 is set to 1、3
or 4), it is used to determine the adjustment range of auxiliary frequency source. P0-05 is used
to determine the relative object within the range. If it is relative to main frequency, that range
will vary with the main frequency X.
Unit's digit Frequency source
selection
Frequency
0:Main frequency source X.
P0-07 source stacking 00 ☆
1:Main / auxiliary operation result
selection
(10bit determine operation
relationship)
- 61 -
500 Series AC Drive User Manual Function Code Table
- 62 -
500 Series AC Drive User Manual Function Code Table
frequency through P0-21. By stacking offset frequency on main & auxiliary operation result, it
could flexible cope with all kinds of needs .
- 63 -
500 Series AC Drive User Manual Function Code Table
frequency reaches value of upper limit , inverter maintains operation at the upper limit
frequency.
P0-12 Frequency upper Frequency lower limit (P0-14) to 50.00H ☆
limit maximum frequency (P0-10) z
Frequency upper 0.00Hz ~Max frequency (P0-10)
P0-13 0.00Hz ☆
limit offset
When upper limit is set through analog value or PULSE setup, P0-13 will be used as
analog value offset. The addition of offset frequency and analog setup value of frequency
upper limit is used as the final setup value of frequency upper limit.
Frequency lower 0.00Hz ~frequency upper limit (P0-
P0-14 0.00Hz ☆
limit 12)
When the running frequency of the inverter is lower than the frequency lower limit, it can
select to run at frequency lower limit or stop the inverter. Refer to P8-14 function code for
details.
P0-15 Carrier frequency 0.5kHz ~ 16.0kHz 6 ☆
This function is used to adjust the carrier frequency of the inverter. By adjusting the carrier
frequency, the motor noise can be reduced, the resonance of the mechanical system can be
avoided, so that the leakage current to the ground and the interference of the inverter can be
reduced.
When the carrier wave frequency is low, the output current higher harmonic component will
be increased, the motor loss will be increased, and the motor temperature rise will also be
increased. When the carrier wave frequency is high, the motor loss is reduced, and the motor
temperature rise is reduced, but the inverter loss and inverter temperature rise will be
increased, and thus the interference will be increased.
The adjustment of carrier frequency will influence the following items on the performance:
Different power of inverter is set with different carrier frequency by the factory. Though
user could modify it , attention should be paid:if carrier frequency is set higher than the
- 64 -
500 Series AC Drive User Manual Function Code Table
factory set value, it will lead to inverter radiator temperature rise increasing. User should take
inverter derating use, or there will be danger of overheating alarm.
Carrier frequency 0:NO
P0-16 adjusting with 1:YES 1 ☆
temperature
Carrier frequency adjusting with temperature refers to the detecting of radiator
temperature. When the temperature is high , carrier frequency automatically decreased to
reduce the inverter temperature rise. On the contrary , when the temperature is low, carrier
frequency gradually restored to the set value. This function could help to reduce the chance of
inverter overheating alarm.
Acceleration time
P0-17 0.0s ~ 6500.0s 20 ☆
1
Deceleration
P0-18 0.0s ~ 6500.0s 20 ☆
time 1
The acceleration time means the time t1 needed for the inverter to accelerate from 0Hz to
the reference frequency (P0-25).
The deceleration time means the time t2 needed for the inverter to decelerate from the
reference frequency (P0-25) to 0Hz.
The description of acceleration and deceleration time are as shown in Fig.6-1:
500 totally offers 4 groups of speed-up/speed-down time for selection, you can shift
through digital input terminal DI, 4 groups of them are shown as follows:
GROUP 1:P0-17、P0-18;
GROUP 2:P8-03、P8-04;
GROUP 3:P8-05、P8-06;
- 65 -
500 Series AC Drive User Manual Function Code Table
GROUP 4:P8-07、P8-08.
0:1 s
Acc./dec. time
P0-19 1:0.1 s 1 ★
unit
2:0.01 s
500 offers 3 kinds of speed-up /speed down time unit to meet the need of all kinds of scene.
Respectively for 1 second、0.1 seconds and 0.01 seconds.
Caution:Decimal places as well as corresponding acceleration/deceleration time of the 4
groups may be changed when modifying this function parameter, special attention should be
paid in the process of application.
Auxiliary
P0-21 frequency source 0.00Hz ~Max frequency( P0-10) 0.00Hz ☆
offset frequency
It is valid only at the time of main/auxiliary operation is chosen. When frequency source is
main / auxiliary operation(P0-21 as offset frequency) ,it could make frequency set more flexible
by stacking offset frequency on main & auxiliary operation as the final frequency set value.
Frequency 1:0.1HZ
P0-22 command 2:0.01Hz 2 ★
resolution
This parameter is used to determine all the function code resolution which is relevant to
frequency. Frequency resolution is 0.1Hz , 500 maximum output frequency can reach 3200Hz.
While frequency resolution is 0.01Hz, 500 maximum output frequency is 320.00Hz.
Caution:Parameter (relating to frequency ) decimal digits and corresponding frequency
value will change through modifying P0-22. Special attention should be paid during operation.
Digital setup 0:Without memory
frequency 1:memory
P0-23 memory 0 ☆
selection upon
stop
This function is only valid when frequency source is digital setup.
0: Without memory Upon power fault or stop of the inverter, set the frequency value back
to the setup value of “Preset Frequency” (P0-08). Frequency modification which set through
keyboard “∧”、“∨” or terminal UP、DOWN is cleared.
1: Memory Digital setup frequency is the retention that reserved at last stop time.
Keyboard “∧”、“∨” or terminal UP、DOWN to make the correction valid.
P0-24 - - - -
P0-25 Acceleration / 0: Maximum frequency(P0.10) 0 ★
- 66 -
500 Series AC Drive User Manual Function Code Table
- 67 -
500 Series AC Drive User Manual Function Code Table
- 68 -
500 Series AC Drive User Manual Function Code Table
motor parameter. The accuracy of the regulation results has intimate relationship with the
accuracy of set motor nameplate parameters.
0.001Ω~65.535Ω
Asynchronous Model
(AC drive power≤55kW
P1-06 motor stator depende ★
0.0001Ω~6.5535Ω
resistance nt
(AC drive power>55kW)
0.001Ω~65.535Ω
Asynchronous Model
(AC drive power≤55kW)
P1-07 motor rotor depende ★
0.0001Ω~6.5535Ω
resistance nt
(AC drive power>55kW)
0.01mH~655.35mH
Asynchronous Model
(AC drive power≤ 55kW)
P1-08 motor leakage depende ★
0.001mH~65.535mH
inductance nt
(AC drive power> 55kW)
0.1mH~6553.5mH
Asynchronous Model
(AC drive power≤ 55kW)
P1-09 motor mutual depende ★
0.01mH~655.35mH
inductance nt
(AC drive power> 55kW)
0.01A~P1-03
Asynchronous Model
(AC drive power≤ 55kW)
P1-10 motor no load depende ★
0.1A~P1-03
current nt
(AC drive power > 55kW)
P1-06~P1-10 are parameters for asynchronous motor. Generally, motor nameplate
doesn’t contain such parameters, users can get them through inverter auto tuning. Among
them, 3 parameters (P1-06~P1-08) can be get through “ asynchronous motor static tuning”,
while all the 5 parameters as well as encoder phase , current loop PI etc can be get through
“asynchronous motor complete tuning”. When change the motor rated power (P1-01) or
motor rated voltage (P1-02), inverter would automatically modify the P1-06~P1-10 parameter
value and restore them to common standard of Y series motor parameter. If the asynchronous
motor is unable to be tuned, users could input above parameters with factory offered motor
value.
P1-11 P1-11~P1-36 - - -
0:Without operation
1:Asynchronous static tuning 1
P1-37 Tuning selection 0 ★
2:Asynchronous complete tuning
3:Synchronous static tuning 2
- 69 -
500 Series AC Drive User Manual Function Code Table
Users can adjust vector control speed dynamic response characteristics through setting
proportional coefficient and integration time of the speed regulator. Both increasing
proportional gain and reducing integration time can accelerate the speed loop dynamic
- 70 -
500 Series AC Drive User Manual Function Code Table
response. But excessive proportional gain or insufficient integration time may led to system
oscillation.
Suggestions for regulating method:If the factory parameters can not meet the
requirements, users can fine-tuning it on the basis of factory value parameters. First increase
the proportional gain to restrain system oscillation, then reduce integration time so that
system has fast response characteristic and smaller overshoot.
Notice:Improper PI parameter setting may lead to excessive speed overshoot , even
voltage fault during overshoot drop.
- 71 -
500 Series AC Drive User Manual Function Code Table
- 72 -
500 Series AC Drive User Manual Function Code Table
the entire control loop circuit. If current oscillation or torque fluctuation is relatively big, users
could manually turn down the PI proportional gain or integration gain.
Speed loop Unit's digit: integral separation
P2-17 integration 0:Invalid 0 ☆
attribute 1:Valid
P3 group V/F control parameter
Function Factory propert
Name Setting Range
code Setting y
0:Linear V/F
1:Multi-point V/F
2:Square V/F
3:Power of 1.2 V/F
4:Power of 1.4 V/F
P3-00 V/F curve setting 6:Power of 1.6 V/F 0 ★
8:Power of 1.8 V/F
9:reserved
10:VF complete separation
mode
11:VF semi separation mode
This parameter defines the V/F setup mode so as to meet the requirements of various load
characteristics.
0: Linear V/F. It is suitable for the ordinary constant torque load.
1: Multi-point V/F It is suitable for special loads such as dehydrator and centrifugal
machine. It can be self-defined. Refer to the description of functional codes of Group F1-07 to
F1-12 for details.
2: Square V/F It is suitable for centrifugal loads such as fan and pump.
3~8: These are relation curve situated between linear V/F curve and square V/F
curve.
9: Reserved
10: VF complete separation mode ,Inverter output frequency and output voltage are
mutually independent. Output frequency is decided by frequency source, while output voltage
is decided by P3.13 (VF separation voltage source). VF complete separation mode is generally
applied in induction heating, inverter power supply, torque motor control fields etc.
11: VF semi separation mode In this case, V is proportional to F. Proportional
relationship can be set by the voltage source P3-13. The relationship between V&F is
connected with P1 group(motor rated voltage and rated frequency).
- 73 -
500 Series AC Drive User Manual Function Code Table
Suppose that voltage source input is X (X from 0~100%), the V,F relationship is:
V/F=2*X*(Motor rated voltage)/(Motor rated frequency)
0.0%:(automatically Torque Model
P3-01 Torque boost value boost ) depende ☆
0.1% ~ 30.0% nt
Torque boost cut- 0.00Hz ~Max frequency
P3-02 50.00Hz ★
off frequency
- 74 -
500 Series AC Drive User Manual Function Code Table
- 75 -
500 Series AC Drive User Manual Function Code Table
The slip compensation gain adjustment may be performed referring to the following
principle: When the load is rated load, and the slip compensation coefficient is set to 100%,
the rotary speed of the motor is close to the reference speed.
V/F over-excitation 0 ~ 200
3-10 64 ☆
gain
The role of over excitation gain function is to suppress the rise of bus voltage during the
inverter deceleration process, thus avoiding occurrence of over voltage fault due to bus
voltage exceeding over voltage protection limitation value. The higher the over excitation gain
is, more powerfully the suppression effect is. The setting is described as follows:
In the applications where over-voltage alarm easily occurs, it needs to improve the over-
excitation gain. Excessive over-excitation gain easily lead to increasing of output current .Users
should keep the balance during operation. In the applications where the inertia is very low, the
over excitation gain is set to 0, while in the applications where there is brake resistor ,the over
excitation gain is set to 0 as well.
V/F oscillation 0 ~ 100
P3-11 40 ☆
suppression gain
When the motor has no oscillation, please select this gain to 0. Only when the motor has
obvious oscillation and does not run normally can the gain be properly increased. The bigger
the gain is, the better oscillation suppression result will be. The gain shall be set as small as
possible under the condition that the oscillation is suppressed effectively so as to avoid high
influences on the V/F operation. Accurate motor rated current and no-load current parameters
are required during using oscillation suppression function, or VF oscillation suppression effect
will not be excellent.
3-12 - - - -
0:Digital setting(P3-14)
1:AI1
2:AI2
3:AI3(Potentiometer)
4:reserved
V/F separation
P3-13 5:MS command 0 ☆
voltage source
6:Simple PLC
7:PID
8:Communication setup
Note:100.0% corresponding to
the rated motor voltage
P3-14 V/F separation 0V ~rated voltage 0V ☆
- 76 -
500 Series AC Drive User Manual Function Code Table
voltage digital
setup
VF separation is generally applied to induction heating control, inverter power supply
control and torque motor control etc.
In VF separation control mode, output voltage can be set through function code P3-14,
analog value, MS command , PLC, PID or communication setup. When P3-13 is nonnumeric
setup, each 100% of the setting corresponds to rated motor voltage. When output setting
percentage is negative, it’s absolute value is the valid setting value.
0: Digital setup
(P3-14)Voltage is directly set through P3-14.
1: AI1
2: AI2
3: AI3(Potentiometer)
Voltage is set through analog input terminal.
4: PULSE
pulse setup(DI5) voltage set through terminal pulse. Pulse setup signal specification:
voltage range 9V~30V, frequency range 0kHz~100kHz.
5: MS command
voltage source is MS command. Corresponding relationship between set signal and set
voltage is determined through P4 group and PC group.
6: Simple PLC
When voltage source is simple PLC, output voltage is set through PC group parameters.
7: PID
Output voltage through PID closed loop. For specifications please refer to PA group for
PID detailed description.
8: Communication setup
Communication setup refers to voltage that set by position machine through
communication mode. When the above voltage source selection is 1~8, 0~100% corresponds
to output voltage 0V~motor rated voltage.
0.0s ~ 1000.0s
Voltage rise
P time Note:It indicates the time for the
0.0s
3-15 of V/F separation voltage rising from 0 V to rated
motor voltage.
P3-15 refers to the time that needed for output voltage varying from 0V to motor rated
voltage. As shown in fig.6-5.
- 77 -
500 Series AC Drive User Manual Function Code Table
0.0s ~ 1000.0s
Voltage decline
Note:It indicates the time for the
P3-16 time of V/F 0.0s ☆
voltage rising from 0 V to rated
separation
motor voltage.
0:Frequency and voltage
Stop mode
declining to 0 independently
P3-17 selection upon V/F 0 ☆
1:Frequency declining after
separation
voltage declines to 0
Over current stall
P3-18 50~200% 150% ★
current
0 :invalid
P3-19 Overflow stall 1 ★
1 :valid
Over current stall
P3-20 0~100 20 ☆
inhibition gain
Speed flow
compensation
P3-21 50~200% 50% ★
coefficient stall
action current
Over voltage stall
P3-22 650.0V~800.0V 730.0V ★
voltage
- 78 -
500 Series AC Drive User Manual Function Code Table
frequency gain
- 79 -
500 Series AC Drive User Manual Function Code Table
- 80 -
500 Series AC Drive User Manual Function Code Table
Corresponding
K4 K3 K2 K1 Instruction set
parameters
Chart 6-1
- 81 -
500 Series AC Drive User Manual Function Code Table
Acceleration or Corresponding
Terminal 2 Terminal 1
deceleration time selection parameters
Acceleration or Corresponding
Terminal 2 Terminal 1
deceleration time selection parameters
Chart 6-2
interference ,users could increase the parameter value to enhance the interference
immunity. However, this operation may cause reduced sensitivity of the DI terminal.
0:2-line type 1
Terminal
1:2-line type 2
P4-11 command 0 ★
2:3-line type 1
mode
3:3-line type 2
- 82 -
500 Series AC Drive User Manual Function Code Table
This parameter defines four different ways of controlling the AC Drive to run via external
terminals.
0:Two-wire mode 1: This mode is the most commonly used two-wire mode. The
terminals DI1, DI2 are used to determine the forward and reverse run of the motor. The
function code is set as follows:
Chart 6-3
K1 K2 Running Command
0 0 stop
DI1 FWD running
0 1 fwd
DI2 REV Running
1 0 rev
COM Digital Common
1 1 stop
As Figure 6-5 shows, in this control mode, K1 close, the AC Drive is running forward. K2 close,
reverse run. K1, K2 are closed or disconnected at the same time, the AC Drive stop running.
1: Two-wire mode 2: In this mode, the DI1 terminal function is the run enable terminal,The
DI2 terminal function determines the direction of running. The function code is set as follows:
- 83 -
500 Series AC Drive User Manual Function Code Table
Chart 6-5
K1 K2 Running
Command
DI1 Running Enable
0 0 stop
DI2 FWD/REV
0 1 fwd Running direction
1 1 stop
1: This mode DI3 is the enable terminal, the directions are controlled by DI1,DI2. The
function code is set as follows:
- 84 -
500 Series AC Drive User Manual Function Code Table
selection
Chart 6-7
3. Three - wire control mode 2: In this mode, DI3 is the enable terminal, and the run
command is given by DI1, The direction is determined by the state of DI2. The function code
is set as follows:
Functio
Name Settings Function description
n code
- 85 -
500 Series AC Drive User Manual Function Code Table
Chart 6-8
0 FWD
COM Digital Common
1 REV
Terminal
P4-12 UP/DOWN 0.001Hz/s ~ 65.535Hz/s 1.00Hz/s ☆
variation rate
It is used to set the frequency variation rate (frequency variation per second) when
adjusting the set frequency with terminals UP/DOWN. When P0-22 (frequency decimal
AI curve 1
P4-13 0.00V ~ P4-15 0.00V ☆
minimum input
AI curve 1
minimum input
P4-14 -100.0% ~ +100.0% 0.0% ☆
corresponding
setup
AI curve 1
P4-15 P4-13 ~ +10.00V 10.00V ☆
maximum input
- 86 -
500 Series AC Drive User Manual Function Code Table
AI curve 1
maximum input
P4-16 -100.0% ~ +100.0% 100.0% ☆
corresponding
setup
The parameters mentioned above define the relationship between analog input
When analog input voltage exceeds the setup “maximum input” limit, analog
- 87 -
500 Series AC Drive User Manual Function Code Table
than the setup “minimum input”, analog voltage is calculated as minimum input or
AI input filtering time is used to set AI1 software filtering time. When field analog
quantity is vulnerable, please increase the filtering time so that analog quantity tends
to be stable. But excessive filtering time will lead to slow response time to analog
reference will be different. Refer to specific application description for the specific
value.
AI curve 2
P4-18 0.00V ~ P4-20 0.00V ☆
minimum input
AI curve 2
minimum input
P4-19 -100.0% ~ +100.0% 0.0% ☆
corresponding
setup
AI curve 2
P4-20 P4-18 ~ +10.00V 10.00V ☆
maximum input
AI curve 2
maximum input
P4-21 -100.0% ~ +100.0% 100.0% ☆
corresponding
setup
P4-23—P-32
P4-23 Reserved Reserved
reserved
Unit digit:AI1 curve selection
P4-33 AI curve 321 ☆
- 88 -
500 Series AC Drive User Manual Function Code Table
- 89 -
500 Series AC Drive User Manual Function Code Table
Only DI1, DI2, DI3 are able to set equipment delay time.
They are used to set delay time to inverter DI terminal state change.
0:high level valid
1:low level valid
DI terminal valid Unit’s digit:DI1
P4-38 mode Ten’s digit:DI2 00000 ★
selection 1 Hundred’s digit:DI3
Thousand’s digit:DI4
Ten thousand’s digit:DI5
It is used to set digital input terminal effective mode.
High level valid:Connection between COM and corresponding DI is valid, disconnection
invalid.
Low level valid:Connection between COM and corresponding DI is
invalid,disconnection valid.
- 90 -
500 Series AC Drive User Manual Function Code Table
0:No output
1: AC Drive in operation
2: Output fault(Stop fault)
3: Frequency level detection
AO1 selection (open FDT1 output
P5-01 collector output 4: Frequency arrival 0 ☆
terminal) 5: Null speed operation (stop
without output)
6: Motor overload pre-alarm
7: AC Drive overload pre-alarm
8: Setup counting value arrived
9:Designated counting value
arrived
Relay output
10: Length arrived
11: PLC circulation end
P5-01 selection 0 ☆
12: Total running time arrived
13: Frequency limit
(TA1.TB1.TC1)
14: Torque limit
15: RUN ready
Expansion card relay 16: AI1>AI2
output 17: Frequency upper limit
P5-02 0 ☆
selection(TA2.TB2.TC arrived
2) 18: Frequency lower limit arrived
DO1 output (stop without output)
selection(open 19:Undervoltage state output
P5-03 0 ☆
collector output 20: Communication setup
terminal) 21: Reserved
22: Reserved
23:Null speed operation 2 (Stop
with output)
24: Total power-on time arrival
Expansion card DO2 25: Inspection level of FDT2
P5-04 0 ☆
output selection frequency
26: Frequency 1 arrival output
27: Frequency 2 arrival output
28: Current 1 arrival output
29: Current 2 arrival output
- 91 -
500 Series AC Drive User Manual Function Code Table
0:running frequency
1:setting frequency
2:output current
AM output function
P5-07 3:output torque ( Absolute 0 ☆
selection
value of torque )
4:output power
5:output voltage
6:reserved
7:AI1
8:AI2
9:reserved
10:length
FM output function 11:Counting value
P5-08 1 ☆
selection 12:Communication setup
13:Motor revolving speed
14:Output current (100.0%
means 1000.0A)
15:output voltage (100.0%
means 1000.0V)
- 92 -
500 Series AC Drive User Manual Function Code Table
and also be used to define required AO output curves. If b represents zero offset, k
represents gain, Y represents actual output, and X represents standard output, the actual
output is calculated as follows: Y=kX+b .AO1, AO2 zero offset coefficient 100%
For example, if the analog output is the running frequency, and it is expected to output
8V (16mA) when the frequency is 0, and output 3V (6mA) at the maximum frequency, the
standard output 0V to 10V shall be modified to 8V to 3V output. As per the above formula,
AO zero offset coefficient shall be set to“80%”, while A0 gain shall be set to “-0.50”.
- 93 -
500 Series AC Drive User Manual Function Code Table
FM output delay
P5-21 0.0s ~ 3600.0s 0.0s ☆
time
Set output terminal FMR, relay 1, relay 2, DO1 and DO2 delay time that begins from
0:Positive logic
1:Negative logic
Unit’s digit:AO1
AO output terminal
P5-22 Ten’s digit:delay 1 00000 ☆
valid state selection
Hundred’s digit:relay 2
Thousand’s digit:AO2
Ten thousand’s digit:reserved
Define output terminal FMR、Relay 1、Relay 2、DO1 and DO2 output logic.
0: Positive logic Digital output terminals and the corresponding public end connected
1: Negative logic Digital output terminals and the corresponding public end connected
P5-23 - - - ★
When the DC brake time is non-zero value, it can perform DC brake before start. It is
suitable for the applications where small inertia may cause reverse rotation at the time of
- 94 -
500 Series AC Drive User Manual Function Code Table
startup.
The inverter firstly judges the revolving speed and direction of the motor and then starts
at the frequency corresponding to the tracked rotation velocity of the motor, and performs
smooth startup of the motor in rotation without impact. It is suitable for the applications
where large inertia is restarted due to transient power shutdown. In order to ensure the
performance of the rotation velocity tracking startup, motor parameters (Group P1) should
be set correctly.
It is only valid for asynchronous motor , and is used to establish magnetic field before
motor operation. For pre-excitation current, pre-excitation time please refer to function code
If pre-excitation time is set to 0, the pre-excitation process will be cancelled ,and start
with start frequency. If pre-excitation time is not set to 0, inverter first pre-excitation then
0: Track downward from the frequency at the time of stop, which is generally selected
at first.
1: Track upward from zero frequency, which is used when the inverter is restarted upon
2: Track downward from the maximum frequency, which is generally used for power
generating load.
- 95 -
500 Series AC Drive User Manual Function Code Table
Revolving speed
P6-02 1-200 20 ☆
tracking mode
In the mode of revolving speed tracking startup, it is used to select the speed of rotation
tracking. The higher the parameter value is, the faster the tracking velocity is, but too higher
addition, in order to set up magnetic flux when waiting for the startup of the motor, the
startup frequency shall remain for a certain period of time before accelerating to the setup
frequency. Start frequency P6-03 is not affected by the lower frequency limit. If the
frequency reference value (frequency source) is lower than the startup frequency, the
inverter cannot start and will be in standby status. In positive&negative switching process,
start frequency holding time does not work. Start frequency holding time is not included in
the acceleration time, but included in the simple PLC running time.
Example 1:
P0-03 = 0 means the frequency source is digital reference. P0-08 = 2.00Hz means the
digital setup frequency is 2.00Hz. P6-03 = 5.00Hz means the start frequency is 5.00Hz. P6-
In this case, the inverter will be in the standby status and its output frequency is 0Hz.
Example 2:
P0-03 = 0 means the frequency source is digital reference. P0-08 = 10.00Hz means the
digital setup frequency is 10.00Hz. P6-03=5.00Hz means the start frequency is 5.00Hz. P6-
In this case, the inverter accelerates to 5.00 Hz and remains for 2 seconds, and then
- 96 -
500 Series AC Drive User Manual Function Code Table
Start dc braking
P6-05 current /pre- 0% ~ 100% 50% ★
excitation current
Start dc braking
P6-06 time /pre-excitation 0.0s ~ 100.0s 0.0s ★
time
Pre-excitation is used to establish asynchronous motor magnetic field before startup,
which would improve response speed. Start dc current braking is only valid when it is direct
startup. Inverter first carries out dc braking according to the setup of start dc current
braking , and then carries out operation after start dc braking time. If dc braking time is set
to 0, inverter directly start without dc braking. The bigger the dc braking current is , the
greater the braking force is. If start mode is asynchronous motor pre-excitation start,
inverter first establish magnetic field through pre-excitation current setup, then start to run
after pre-excitation time. If set pre-excitation time to 0, inverter would directly start without
The output frequency increases or decreases along the straight line. 500 series inverter
The output frequency increases or decreases along the straight line. S curve is generally
used in the applications where start and stop processes are relatively gentle, such as
elevator and conveyor belt. The acceleration / deceleration time is consistent with the
straight acceleration/ deceleration time. Function codes of P6.08 and P6.09 can be
- 97 -
500 Series AC Drive User Manual Function Code Table
In the acceleration/ deceleration curve, the motor rated frequency fb is always the point
of inflexion on S-curve. As shown in 5-12. S curve is generally used in the applications where
the high-speed area above the rated frequency as well as short-time acceleration/
deceleration. When set frequency is above the rated frequency, acceleration/ deceleration
time is:
Initial-segment
P6-08 time proportion of 0.0% ~ (100.0%-P6-09) 30.0% ★
S-curve
Finishing-segment
P6-09 time proportion of 0.0% ~ (100.0%-P6-08) 30.0% ★
S-curve
Function code of P6-08 and P6-09 can be respectively defined the time proportion
t1 in the Fig.6-10 is the parameter defined by P6-08, in this period of time which the
parameter P6-09, in this period of time which the changing slope of output frequency
change to zero. The changing slope of output frequency is fixing within the time of t1 and
t2.
- 98 -
500 Series AC Drive User Manual Function Code Table
0:decelerating stop
P6-10 Stop mode 0 ☆
1:free stop
0: Deceleration to stop When the stop command is valid, the inverter will
1 : Free stop When the stop command is valid, the inverter will terminate the output
immediately and the load will coast to stop according to the mechanical inertia.
- 99 -
500 Series AC Drive User Manual Function Code Table
frequency at stop
DC braking waiting
P6-12 0.0s ~ 100.0s 0.0s ☆
time at stop
DC braking current
P6-13 0% ~ 100% 0% ☆
at stop
DC braking time at
P6-14 0.0s ~ 100.0s 0.0s ☆
stop
DC brake initial frequency at stop : During the process of decelerating to stop, when
the running frequency at stop reaches this frequency, it will start the process of DC brake. DC
brake waiting time at stop : Prior to the beginning of DC brake at stop, the inverter will
terminate the output, and then start DC brake after this delay time. It is used to prevent over
current fault due to DC brake which starts at the time of higher velocity. DC brake current at
stop: The DC brake quantity added shall be set according to the percentage setting of the
rated current of the inverter. The higher the brake current is, more powerful the brake effect
is. DC brake time at stop: It refers to the continuous DC brake time. If this DC brake time is
set to 0, it indicates that there is no DC brake process, and the inverter will stop according to
the setting process of decelerating to stop. The process of DC brake at stop is as shown in
Figure below:
- 100 -
500 Series AC Drive User Manual Function Code Table
Brake utilization
P6-15 0% ~ 100% 100% ☆
ratio
It is only valid for the inverter with built-in brake unit. It is used to adjust the duty ratio of
the brake unit. When the brake utilization ratio is high, then the duty ratio of brake unit
action is high, braking effect is strong. But there will be big fluctuation of inverter bus
voltage.
pro
Function Factory
Name Setting Range pert
code Setting
y
0: invalid
1:Switching between operation
panel command channel & the
remote command channel
(terminal command channel or
P7-01 REV/JOG selection 0 ★
serial port command channel)
2:Switching between FWD &
REV rotation
3:Forward jog command
4:Reverse jog command
- 101 -
500 Series AC Drive User Manual Function Code Table
0: Invalid function
keyboard control.
2 : Switching between forward & reverse rotation. Switch the rotary direction of the
motor via the MF/REV key on the keyboard is only enabled when the command source is
3: Forward jog. It can perform forward jog (FJOG) operation via the MF/REV key on the
keyboard.
4: Reverse jog. It can perform reverse jog (RJOG) operation via the MF/REV key on the
keyboard.
- 102 -
500 Series AC Drive User Manual Function Code Table
Bit11: reserved
Bit12: Counter
Bit13: Length
Bit14: Load speed display
Bit15: PID setting
If the above parameters need to be displayed during the operation, users can set their
corresponding positions to 1 and then convert this binary number into decimal number and
set it to P7-03.
0000 ~ PPPP
Bit00:PID feedback
Bit01:PLC phrase
Bit02:reserved
Bit03:running frequency 2(Hz)
Bit04:The left running time
Bit05:AI1 Pre-correction voltage
(V)
Bit06:AI2 Pre-correction voltage
(V)
LED running Bit07:reserved
P7-04 displayed Bit08:line speed H.0000 ☆
parameter 2 Bit09:currently power-on time
(Hour)
Bit10:currently running time
(Min)
Bit11:reserved
Bit12:communication setting
value
Bit13:reserved
Bit14:Main frequency X display
(Hz)
Bit15:Auxiliary Y display (Hz)
If the above parameters need to be displayed during the operation, users can set their
corresponding positions to 1 and then convert this binary number into decimal number and
set it to P7-04. Running display parameter is used to set paratermers which can be seen
under inverter running state. 32 state parameters can be checked at most,you could choose
the needed state parameter through
- 103 -
500 Series AC Drive User Manual Function Code Table
P7-03、P7-04 binary digit, display sequence starts from P7-03 lowest digit order.
0000 ~ PPPP
Bit00:setting frequency (Hz)
Bit01: Bus. voltage (V)
Bit02:DI input state
Bit03:AM output state
Bit04:AI1 voltage (V)
LED stopped
Bit05:AI2 voltage (V)
P7-05 displayed H.0033 ☆
Bit06:reserved
parameter
Bit07:Counter
Bit08:Length
Bit09:PLC phrase
Bit10:Load speed
Bit11:PID setting
Bit12:reserved
If the above parameters need to be displayed at the time of stop, it can set their
corresponding positions to 1 and then convert this binary number into decimal number and
set it to P7-05.
Load speed
P7-06 displayed 0.0001 ~ 6.5000 1.0000 ☆
coefficient
When display of the load speed is necessary, P7-06 is used to adjust the corresponding
relationship between inverter frequency output and load speed. For details please refer to
P7-12.
AC Drive module
P7-07 radiator 0℃~ 120℃ - ●
temperature
It is used to display IGBT temperature. Different model ’ s inverter module is set with
different IGBT over temperature protection value.
Rectifier module
P7-08 radiator - - ●
temperature
It is used to display rectifier module temperature.Different model’s rectifier module is set
with different over temperature protection value.
Accumulative
P7-09 0h ~ 65535h - ●
running time
- 104 -
500 Series AC Drive User Manual Function Code Table
It is used to display the accumulated running time of the inverter. When the accumulated
running time.reaches P8-17 setup running time, the multifunctional digital output
terminal(12) will output ON signal.
P7-10 Product ID - - ●
Software version
P7-11 - - ●
No.
Unit’s digit:U0-14 number of
decimal place
0:0 decimal place
1:1 decimal place
Load speed display 2:2 decimal place
P7-12 21 ☆
decimal digits 3:3 decimal place
Ten’s digit:U0-19/U0-29
number of decimal place
1:1 decimal place
2:2 decimal place
Decimal point position: It is used to set the number of decimal places of the load
speed.For example, if the Load speed display coefficient P7-06 is 2.000,load speed display
decimal digits is 2(Two decimal places),when inverter running frequency is 40.00Hz,the load
speed will be : 40.00*2.000=80.00(2 decimal digit display). If the inverter is in stopped
state, then load speed displays as corresponding set frequency speed.Take set frequency of
50.00Hz as an example, the stop state load speed is: 50.00*2.000=100.00(Two decimal
places).
Accumulative
P7-13 0 ~ 65535 h - ●
power-on time
It displays accumulative power-on time since leaving the factory. When it reaches the set
power-on time (P8-17) , multi-function digital output (24) ON signal.
Accumulative
P7-14 0 ~ 65535 kw/h - ●
power
It displays the inverter accumulative power consumption.
- 105 -
500 Series AC Drive User Manual Function Code Table
JOG acceleration
P8-01 0.0s ~ 6500.0s 20.0s ☆
time
JOG deceleration
P8-02 0.0s ~ 6500.0s 20.0s ☆
time
It defines the reference frequency and acc. / dec. time of the inverter at the time of
jogging. The jog process is started and stopped according to direct startup mode(P6-00=0)
and decelerate to stop mode(P6-10=0).
Hopping frequency
P8-09 0.00Hz ~MAX frequency 0.00Hz ☆
1
Hopping frequency
P8-10 0.00Hz ~MAX frequency 0.00Hz ☆
2
Hopping frequency
P8-11 0.00Hz ~MAX frequency 0.01Hz ☆
amplitude
- 106 -
500 Series AC Drive User Manual Function Code Table
When set frequency is within the range of hopping frequency, the actual running
frequency will run close to the set frequency of hopping frequency. Inverter can avoid load
mechanical resonance by setting hopping frequency.
500 can set 2 hopping frequency points, if both of them are set to 0, then the hopping
frequency function is canceled. Hopping frequency and hopping frequency amplitude
schematic is shown in Fig 6-13.
- 107 -
500 Series AC Drive User Manual Function Code Table
It refers to the transit time at the 0Hz output point when the inverter switches between
forward rotation and reverse rotation. As shown in figure 6-14.
the frequency lower limit. 500 offers 3 kinds of running mode to meet all kinds of
applications.
It is used for load distribution when multiple motors drive the same load.
- 108 -
500 Series AC Drive User Manual Function Code Table
Droop control refers to inverter output frequency decreasing with added load. In this way,
motor with heavy load output frequency decrease more, which could decrease the motor
load to realize multiple motor load uniformity . This parameter is the output frequency
Accumulative
P8-16 power-on time 0h ~ 65000h 0 ☆
arrival setup
When the accumulative power on time (P7-13) reaches the P8-16 set value, inverter multi-
When accumulative power-on time reaches 100 hours, inverter outputs fault number 26=
E.ArA.
Accumulative
P8-17 running time arrival 0h ~ 65000h 0 ☆
setup
When the accumulated running time (P7-09) reaches this set running time, the digital
command power on), inverter will not respond to the running command. Users should first
- 109 -
500 Series AC Drive User Manual Function Code Table
cancel running command, after running command coming into valid again, the inverter then
responds. If running command is valid upon inverter fault reset, inverter will not respond to
the running command. Running protection status can be eliminated after cancelling the
running command. This can prevent the dangers caused by the automatic running of the
Frequency
P8-19 detection value 0.00Hz ~MAX frequency 50.00Hz ☆
(FDT1)
Frequency
P8-20 detection hysteresis 0.0% ~ 100.0%(FDT1 level) 5.0% ☆
value (FDT1)
When the running frequency is higher than the frequency detection value,multi-function
is less than a certain value of the detection value. It is used to set the detection value of the
- 110 -
500 Series AC Drive User Manual Function Code Table
output frequency and the hysteresis value upon release of the output action.P8-20 is the
Frequency arrival
0.0% ~ 100.0%(MAX
P8-21 detection 0.0% ☆
frequency)
amplitude
When inverter running frequency is in certain target frequency ,multi-function terminal
acceleration/deceleration. P8-22 =1: Actual running frequency will skip the setting
- 111 -
500 Series AC Drive User Manual Function Code Table
- 112 -
500 Series AC Drive User Manual Function Code Table
During acceleration process, if running frequency is less than P8-25 ,then choose acc. time2.
If running frequency is greater than P8-25, choose acc. time 1. During deceleration process, if
running frequency is greater than P8-26, then choose dec. time 1. If running frequency is less
than P8-26 , choose dec. time 2.
Terminal jog 0:invalid
P8-27 0 ☆
priority 1:valid
It is used to set if terminal jog function has the highest priority. When P8-27 is valid, if jog
command occurring during running , inverter will switch to jog running mode.
Frequency
P8-28 detection value 0.00Hz ~MAX frequency 50.00Hz ☆
(FDT2)
Frequency
P8-29 detection hysteresis 0.0% ~ 100.0%(PDT2 level) 5.0% ☆
value(FDT2)
This frequency detection function and FDT1 function are exactly the same, for details
Random frequency
P8-30 arrival detection 0.00Hz ~MAX frequency 50.00Hz ☆
value1
Random frequency
0.0% ~ 100.0%(MAX
P8-31 arrival detection 0.0% ☆
frequency)
range1
Random frequency
P8-32 arrival detection 0.00Hz ~MAX frequency 50.00Hz ☆
value2
Random frequency
0.0% ~ 100.0%(MAX
P8-33 arrival detection 0.0% ☆
frequency)
range2
- 113 -
500 Series AC Drive User Manual Function Code Table
When inverter output frequency is within the positive & negative detection range of
Zero-current
P8-35 detection delay 0.01s ~ 600.00s 0.10s ☆
time
- 114 -
500 Series AC Drive User Manual Function Code Table
When inverter output current is less than or equals to zero-current detection level, and
the lasting time exceeds zero-current detection delay time, inverter multi-function terminal
0.0%(No detection)
Output current
P8-36 0.1%~300.0%(Motor rated 200.0% ☆
overlimit value
current)
Output current
P8-37 overlimit detection 0.00s ~ 600.00s 0.00s ☆
delay time
- 115 -
500 Series AC Drive User Manual Function Code Table
When inverter output current is larger than output current overlimit value(P8-36) ,and
lasting time exceeds the software overlimit detection delay time ,inverter multi-function
detection.
- 116 -
500 Series AC Drive User Manual Function Code Table
500 offers two groups of random current arrival range detection parameters ,as shown in
fig. 6-22..
- 117 -
500 Series AC Drive User Manual Function Code Table
This group of function codes are used to realize sleep and wake up function.
During operation:when set frequency is less than or equals to sleep frequency(P8-51),
inverter would step into sleep state and stop after sleep delay time(P8-52). If inverter is in
sleep state and current running command is valid, when set frequency is no less than P8-49
wake-up frequency, inverter will start to run after P8-50 wake-up delay time. Generally,
please set wake-up frequency no less than sleep frequency. Sleep function and wake-up
function are valid when both wake-up frequency and sleep frequency are set to 0.00 Hz.
When enabling sleep function(frequency source : PID) , PID calculation selection in sleep
state is influenced by function code PA-28(PA-28=1).
The running time
P8-53 0.0 ~ 6500.0 Min 0.0Min ☆
arrival
- 118 -
500 Series AC Drive User Manual Function Code Table
Output power
P8-54 correction 0.00% ~ 200.0% 100.0% ☆
coefficient
When the running time reached the P8-53 set value, inverter multi-function DO output
P9-00=1 : The inverter has overload protection function for the motor according to
motor overload protection inverse time limit curve. Motor overload protection inverse time
limit curve: 220%×(P9-01)× motor rated current, it will report motor overload fault after it
lasts for one minute. When the operating current of the motor reaches the current of 150%×
(P9-01)times the rated current of the motor, it will report motor overload after it lasts 60
minutes. Users can set value of P9-01 according to the motor actual overload ability. If the
parameter is set too big, it may cause danger of motor overheating damage without inverter
fault report.
Motor overload
P9-02 pre-alarm 50% ~ 100% 80% ☆
coefficient
This function is used before motor overload fault by giving pre-alarm signal through
multi-function terminal DO. This pre-alarm coefficient is used to determine the warning
timing before motor overload protection. The higher the value, the shorter the warning
timing will be. When the inverter output current is accumulated more than the product of
- 119 -
500 Series AC Drive User Manual Function Code Table
inverse time limit curve with P9-02, multi-function terminal DO output “ Motor overload
pre-alarm”ON signal.
Over-voltage stall
P9-03 0 ~ 100 30 ☆
gain
Over-voltage stall
P9-04 650V-800V 730V ☆
protection voltage
Over-voltage stall gain : It adjusts the inverter ’ s capacity in suppressing the current
stall. The bigger the value is, the stronger the capacity is. For the load with small inertia, the
value should be small. Otherwise, the dynamic response of the system would be slow. For
the load with large inertia, the value should be large. Otherwise, the suppressing result will
be poor, and over voltage fault may be caused. Over voltage stall protection voltage : It
selects the protection point for over voltage stall function. When the value is exceeded, the
stall protection current (P9-06), if the inverter is running with acceleration speed, it will stop
acceleration. When the inverter is running with constant speed, it will reduce the output
frequency. When the inverter is running with deceleration speed, it will stop deceleration
and the operating frequency will not recover normally till the current is less than the current
stall protection current (P9-06). Over current stall protection current: It selects the
protection point for over current stall function. When the value is exceeded, the inverter
starts to execute the over current stall protection function. This value is relative to the
percentage of rated current of the motor. Over current stall gain:It adjusts the inverter’s
capacity in suppressing the over current stall. The bigger the value is, the stronger the
capacity is.
- 120 -
500 Series AC Drive User Manual Function Code Table
Ground short
0:Invalid
P9-07 circuit protection 1 ☆
1:valid
upon power-on
It determines whether the motor has ground short circuit fault upon power-on. If this
function is valid, the inverter UVW end will output voltage within the period of time after
power-on.
Braking unit initial
P9-08 650 ~ 800V 680V ☆
voltage
Note:Please set the true parameters ,otherwise it will abnormal of the built-in braking unit.
500 series inverter above 18.5kW (type G) has input phase fault protection function.
For the inverter below 18.5kW (type P), the input phase fault protection function is
- 121 -
500 Series AC Drive User Manual Function Code Table
0:No fault
1:reserved
2:Acceleration over current
3:Deceleration over current
4:Constant speed over current
P9-14 The 1ST fault type - ●
5:Acceleration over voltage
6:Deceleration over voltage
7:Constant speed over voltage
8:Control power supply fault
9:Undervoltage fault
10:AC Drive overload
11:Motor overload
12:Input phase lack
13:Output phase lack
14:Module overheating
15:External equipment fault
- 122 -
500 Series AC Drive User Manual Function Code Table
- 123 -
500 Series AC Drive User Manual Function Code Table
- 124 -
500 Series AC Drive User Manual Function Code Table
Transient stop
60%~10
P9-62 action judgment 80% ★
0%
voltage
The function defines when instant outage or voltage suddenly drops, inverter
compensating dc busvoltage decrease by load feedback energy through decreasing output
- 125 -
500 Series AC Drive User Manual Function Code Table
P9-72 Reserved - - ☆
- 126 -
500 Series AC Drive User Manual Function Code Table
Instantaneous stop
P9-73 action deceleration 0~300.0s 20.0s ★
time
It is used to select target parameter reference channel of process PID. Set target value of
process PID is a relative value, set range is 0.0%~100.0%. PID feedback value is a relative
value as well,PID play the role of making the two relative value the same.
0:AI1
1:AI2
2:Potentiometer
3:AI1-AI2
PA-02 PID feedback source 4:reserved 0 ☆
5:Communication
6:AI1+AI2
7:MAX(|AI1|, |AI2|)
8:MIN(|AI1|, |AI2|)
It is used to select the feedback channel of PID Feedback value of process PID is a relative
value, set range is 0.0%~100.0%.
0:Positive action
PA-03 PID action direction 0 ☆
1:Negative action
Positive action: If the feedback signal is smaller than the PID reference signal, it is required
to boost the output frequency of the inverter to make PID reach balance. The winding
tension PID control is such a case.
Negative action: If the feedback signal is smaller than the PID reference signal, it is
required to decrease the output frequency of the inverter to make PID reach balance. The
- 127 -
500 Series AC Drive User Manual Function Code Table
Proportional gain Kp1: the parameter determines the adjustable strength of PID
regulator. The larger P is, the greater the adjustable strength will be. When the parameter is
set to 100.0, it means that when the deviation between PID feedback value and reference
value is 100.0%, the range for the PID regulator to regulate the output frequency commands
is the maximum frequency (integration effect and differential effect are omitted).
Integration time Ti1: determines the strength of PID integration regulation. The shorter
the integration time , the greater adjustable strength will be. Integration time means that
when the deviation between PID feedback value and reference value is 100%, the adjustment
by the integration regulator (proportional effect and differential effect are omitted) after
continuous adjustment in this period reaches the maximum frequency.
Differential time Td1: determines the degree of adjustment that PID regulator
performs on the derivation between PID feedback value and reference value. Differential
time means that if the feedback value changes 100% within this time, the adjustment by the
differential regulator (proportional effect and differential effect are omitted) will reach the
maximum frequency. The longer differential time is, the higher the degree of adjustment will
be.
PID cutoff frequency
PA-08 0.00 ~MAX frequency 2.00Hz ☆
of reverse rotation
In some cases, only when the frequency of the PID output is negative (i.e., frequency
inversion ) could PID put the reference and feedback to the same state. High inversion
frequency is not allowed in some certain cases, PA-08 is used to determine reverse
- 128 -
500 Series AC Drive User Manual Function Code Table
It is used to set the maximum allowable deviation between the system feedback value
and reference value. When the deviation between the PID feedback and reference is within
this range, the PID stops adjustment. The deviation limit is calculated according to the
percentage of the PID setup source (or feedback source). When deviation between reference
value and the feedback value is small, output frequency is stability constant. It’s especially
PID differential
PA-10 0.00% ~ 100.00% 0.10% ☆
amplitude limit
In PID regulation, the role of differential is relatively sensitive that system oscillation may
be easily caused. Therefore, range of PID differential regulation has been limited to a small
When PID reference changed, PID given value linear changes in accordance with given
time, which can reduce system adverse effect caused by given mutation.
PA-12 is used for filtering of PID feedback. The filtering helps to reduce the influence of
the feedback interference, but brings response performance of process closed-loop system.
PA-13 is used for filtering of PID output frequency. The filtering helps to reduce the
mutations of the output frequency, but brings response performance of process closed-loop
- 129 -
500 Series AC Drive User Manual Function Code Table
system.
PA-14 - - - ☆
Proportional gain
PA-15 0.0 ~ 100.0 20.0 ☆
Kp2
This group of function codes is used to switch 2 groups of PID parameters. Regulator
parameters PA-15~PA-17 and parameter PA-05~PA-07 have the same setting method.
Two groups of PID parameters can be switched through multi-function digital DI terminal
- 130 -
500 Series AC Drive User Manual Function Code Table
parameter group 1(PA-05~PA-07) when terminal invalid, while valid please choose
reference and feedback is less than PA-19 set value, PID parameters select parameter group
1. When deviation absolute value between reference and feedback is greater than PA-20 set
value, PID parameters select group 2. When deviation absolute value between reference and
feedback is within the range of switching deviation 1 & 2 , PID parameters select linear
This function is used to limit difference between the PID output two beats (2ms / beat ),
which suppressing rapid change of PID output, so that the inverter operation tends to be
stable.
- 131 -
500 Series AC Drive User Manual Function Code Table
Output deviation
PA-23 forward maximum 0.00% ~ 100.00% 1.00% ☆
value
Output deviation
PA-24 reverse maximum 0.00% ~ 100.00% 1.00% ☆
value
PA-23 and PA-24 correspond to the output deviation maximum absolute value of forward
Unit’s digit:Integration
separation
0:invalid
1:valid
PID integration
PA-25 Ten’s digit:Whether stop 00 ☆
attribute
integration when reaching
output limit
0 : Continue to integration
1:Stopping integration
1bit :Integration separation
suspended (function 22) effective, the PID integration stop operation, and only proportion
When PID operation output reaches the maximum or minimum value, user could choose
If you choose to stop integration, then the PID integration stops calculation, which may
- 132 -
500 Series AC Drive User Manual Function Code Table
When PID feedback value is less than PA-26 set value, and lasted for more than PA-27 set
Swing frequency
Pb-01 0.0% ~ 100.0% 0.0% ☆
amplitude
Jump frequency
Pb-02 0.0% ~ 50.0% 0.0% ☆
amplitude
It is used to determine the amplitude value and the jump frequency value. Swing relative
to the center frequency (variable swing, select Pb-00=0): Swing (AW) =frequency source
P0-07 setup times swing amplitude Pb-01. Swing relative to the maximum frequency (fixed
swing, Pb-00=1) : Swing (AW) = maximum frequency P0-10 times swing amplitude Pb-
01. When the swing is running, the jump frequency
- 133 -
500 Series AC Drive User Manual Function Code Table
relative to the swing= Swing (AW) times jump frequency amplitude P0-02. If “Swing
relative to the center frequency (variable swing amplitude, Pb-00=0)” is selected, the
jump frequency is variable value. If “Swing relative to the maximum frequency (fixed
swing, Pb-00=1)” is selected, the jump frequency is fixed value. The swing operation
frequency is constrained by upper frequency limit and lower frequency limit.
Swing frequency
Pb-03 0.1s ~ 3000.0s 10.0s ☆
cycle
Triangle wave rise
Pb-04 0.1% ~ 100.0% 50.0% ☆
time coef.
Swing frequency cycle: It defines the time of a whole cycle for rising and falling of the
swing frequency. The coefficient of triangle wave rising time is Pb-04,it is time percentage
of triangle rising time relativing to swing frequency cycle Pb-03. Triangle wave rising time=
Swing frequency cycle Pb-03 times triangle wave rising time coefficient Pb-04 (unit: s)
Triangle wave falling time= Swing frequency cycle Pb.03 times (1-triangle wave rising time
coefficient Pb.04) (unit: s)
Counting value
Pb-08 1 ~ 65535 1000 ☆
setup
Designated
Pb-09 1 ~ 65535 1000 ☆
counting value
Counting value should be collected through multi-function digital input terminal.
Corresponding input terminal should be set to the function of “counter input”(function
- 134 -
500 Series AC Drive User Manual Function Code Table
25) in application. DI5 terminal should be used when pulse frequency is high. When
counting value reaches Pb-08 set value, multi-function digit DO output “setup counting
value arrival” ON signal, then stop counting. When counting value reaches Pb-09 set value,
multi-function digit DO output “designated counting value arrival”ON signal, then
continues to count until reaching “setup counting value”.Specified counting value should
not be greater than setup counting value Pb-08.
- 135 -
500 Series AC Drive User Manual Function Code Table
PLC has 3 running modes as frequency source (VF separation voltage source is not
provided with the 3 modes):
0: Single running stop Upon completion of one single cycle of the inverter, it will stop
automatically and will not start until running command is given again.
1: Single running end remaining final value Upon completion of one single cycle of the
inverter, the inverter will remain the running frequency and direction of last one phase.
After the inverter restarted upon stop, it will run from the initial status of PLC.
2: Continuous circulation Upon completion of one single cycle of the inverter, it will
enter next cycle and not stop until stop command is given.
- 136 -
500 Series AC Drive User Manual Function Code Table
- 137 -
500 Series AC Drive User Manual Function Code Table
PLC 0segment
PC-18 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 0segment
PC-19 0 ~ 3 0 ☆
acc./dec. time
PLC 1segment
PC-20 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 1segment
PC-21 0 ~ 3 0 ☆
acc./dec. time
PLC 2 segment
PC-22 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PC-23 PLC 2 segment
0 ~ 3 0 ☆
acc./dec. time
PLC 3 segment
PC-24 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 3 segment
PC-25 0 ~ 3 0 ☆
acc./dec. time
PLC 4 segment
PC-26 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 4 segment
PC-27 0 ~ 3 0 ☆
acc./dec. time
PLC 5 segment
PC-28 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 5 segment
PC-29 0 ~ 3 0 ☆
acc./dec. time
PLC 6 segment
PC-30 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 6 segment
PC-31 0 ~ 3 0 ☆
acc./dec. time
PLC 7 segment
PC-32 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 7 segment
PC-33 0 ~ 3 0 ☆
acc./dec. time
PLC 8 segment
PC-34 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 8 segment
PC-35 0 ~ 3 0 ☆
acc./dec. time
- 138 -
500 Series AC Drive User Manual Function Code Table
PLC 9 segment
PC-36 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 9 segment
PC-37 0 ~ 3 0 ☆
acc./dec. time
PLC 10 segment
PC-38 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 10 segment
PC-39 0 ~ 3 0 ☆
acc./dec. time
PLC 11 segment
PC-40 0.0s(h) ~ 6553.5s(h) 0.0sh) ☆
running time
PLC 11 segment 0 ~ 3
PC-41 0 ☆
acc./dec. time
PLC 12 segment
PC-42 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 12 segment
PC-43 0 ~ 3 0 ☆
acc./dec. time
PLC 13 segment
PC-44 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 13 segment
PC-45 0 ~ 3 0 ☆
acc./dec. time
PLC 14 segment
PC-46 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 14 segment
PC-47 0 ~ 3 0 ☆
acc./dec. time
PLC 15 segment
PC-48 0.0s(h) ~ 6553.5s(h) 0.0s(h) ☆
running time
PLC 15 segment
PC-49 0 ~ 3 0 ☆
acc./dec. time
Running time 0:seconds
PC-50 0 ☆
unit 1:hours
0:Function code PC-00 setting
1:AI1
MS command 0 2:AI2
PC-51 0 ☆
reference mode 3:Potentiometer
4:served
5:PID
- 139 -
500 Series AC Drive User Manual Function Code Table
6:Pre-frequency(P0-08)
UP/DOWN modified
It is used to select the reference channel of MS speed 0. Besides choosing PC-00, MS
command 0 has many other options, which is convenient for switching between MS
command and other set modes. Both MS command and simple PLC used as frequency
source can easily realize switching between the two frequency sources.
- 140 -
500 Series AC Drive User Manual Function Code Table
Unit’s digit:MODBUS
0:Non-standard MODBUS
protocal
Data 1:Standard MODBUS protocal
Pd-05 transformat Ten’s digit:Profibus-DP 30 ☆
selection 0:PPO1 format
1:PPO2 format
2:PPO3 format
3:PPO5 format
Communication 0:0.01A
Pd-06 read current 1:0.1A 0 ☆
resolution
PE group reserved
0:No function
1:Restore to factory default
Parameter value, motor parameter not
PP-01 0 ★
initialization included
2:Clear memory
0: No function
1: Restore to factory default value, motor parameter not included The inverter
restores all the parameters excluding the following parameters of the factory default
- 141 -
500 Series AC Drive User Manual Function Code Table
values: Motor parameters, P0-22, fault record information, P7-09, P7-13, P7-14.
2: Clear memory The inverter clears the fault records , P7-09, P7-13 and P7-14 to zero.
The establishment of parameter display selection is basically convenient for the users
viewing the different arrangement forms of function parameters according to the actual
needs. Three display methods are offered as below:
Name Description
User change parameter mode Parameters which are different from factory default.
Chart 6-10
When existing display for PP-03, user could switch into different display mode through
QUICK key. Function parameter display mode as default.
- 142 -
500 Series AC Drive User Manual Function Code Table
Chart 6-10
500 series offers two groups of personalized parameter display mode:user customization
function mode, user change parameter mode. In user customization parameter mode, sign u is
added to the user customization function code as default. In user change parameter mode,
sign c is added to the user customization function code as default. E.g.:P1-00 is displayed as
cP1-00 .
PP-04=1:All the function codes can only be viewed, but not modified.
Multi-function digit DI terminal of 500 is equipped with two functions relating torque
control :Torque control banned(Function29), speed control/torque control switching
(function 46). The two terminals should be matched with A0-00 to realize switching
- 143 -
500 Series AC Drive User Manual Function Code Table
between speed control and torque control. A0-00 sets the control mode when
speed/torque control switching terminal is invalid. If the speed/ torque control switching
terminal is valid, control mode is equivalent to the inversion of A0-00 value. When function
29 is valid, speed control mode is fixed for the inverter.
Torque set is a relative value, which 100% corresponds to inverter rated torque. Set
range: 200.0%~200.0%. Maximum torque is 2 times than the inverter rated torque.
When the torque is set by selection 1~7, 100% of communication ,analog input, pulse
input corresponding to A0-03.
A0-04 - - -
Torque control
forward 50.00H
A0-05 0.00Hz ~MAX frequency ☆
maximum z
frequency
Torque control
reverse 50.00H
A0-06 0.00Hz ~MAX frequency ☆
maximum z
frequency
A0-05, A0-06 are used to set forward or reverse maximum running frequency in torque
control mode. In inverter toque control mode, if load torque is less than motor output
toque, the motor revolving speed would speed up. In case of galloping or other accidents
- 144 -
500 Series AC Drive User Manual Function Code Table
Upper torque
A0-07 0.00s ~ 65000s 0.00s ☆
filter time
Lower torque
A0-08 0.00s ~ 65000s 0.00s ☆
filter time
In torque control mode , rate of speed change of motor and load is decided by the
difference between motor output toque and load torque. Therefore, motor speed may
change fast, causing noise or excessive mechanical stress problems. By setting the torque
control acc./dec. time, can make the motor speed changes smoothly. A0-07 and A0-08
should be set to 0.00s in situations where torque rapid response is needed. E.g.:Two
motors drive the same load, to make sure of load uniform distribution , one is set as host
inverter(speed control mode) and another is the slave one(torque control mode). Actual
output torque of the host inverter is the torque command of the slave, and slave torque is
required to quickly follow the host torque, then torque control acc./dec. time is set to 0.00s
for the slave inverter.
A1 ~A4group reserved
PWM
0:Asynchronous modulation
A5-01 modulation 0 ☆
1:Synchronous modulation
mode
- 145 -
500 Series AC Drive User Manual Function Code Table
This parameter is only valid for VF control mode. Asynchronous modulation refers to
carrier frequency that linear changes with output frequency, and ensure that the ratio of
them (carrier ratio) remains the same. Generally high output frequency is benefit for
output voltage quality. Generally, synchronous modulation is not needed at low
frequencies ( below 100Hz), because the ratio of carrier frequency and output frequency is
relatively high, asynchronous modulation advantage is more obvious. When running
frequency is greater than 85Hz, synchronous modulation is valid. And fixed as
asynchronous modulation mode when below this frequency.
the heterogeneous and soft, the external electromagnetic interference can be effectively
reduced. 0 indicates that the PWM is invalid. Different random PWM depth represents
protection fault and make the inverter work normally. If the inverter long time continuous
staying in rapid current-limiting state, it may occur overheating fault, which is not allowed
during operation. Fault alarm of long time rapid current-limiting is 40= E.CbC , which refers
Current
A5-05 0 ~ 100 5 ☆
detection
- 146 -
500 Series AC Drive User Manual Function Code Table
compensation
It is used to set inverter current detection compensation. Excessive setting may lead to
Under-voltage
A5-06 210 ~ 420V 350V ☆
point setup
A5-06 is used to set value of inverter under-voltage fault 9= E.LU. Different voltage level
requirements.
improve the voltage effective use rate. Users are not suggested to modify.
Over-voltage Model
A5-09 200.0V ~ 2500.0V ★
point setup dependant
A5-09 is overvoltage point set through software, which is not related to hardware
overvoltage point.
Functio Communicatio
Parameter name MIN unit
n code n address
- 147 -
500 Series AC Drive User Manual Function Code Table
- 148 -
500 Series AC Drive User Manual Function Code Table
Communication
U0-28 0.01% 701CH
setting value
U0-29 Reserved Reserved Reserved
U0-30 Main frequency X 0.01Hz 701EH
U0-31 Auxiliary frequency Y 0.01Hz 701PH
View any memory
U0-32 1 7020H
address value
U0-33 U0-33—U0-38 Reserved Reserved
Target voltage upon
U0-39 1V 7027H
V/F separation
Output voltage upon
U0-40 1V 7028H
V/F separation
U0-41 DI state visual display 1 7029H
AO state visual 702AH
U0-42 1
display
DI function state
U0-43 1 702BH
visual display 1
DI DI function state
U0-44 visual display 2 1 702CH
- 149 -
500 Series AC Drive User Manual Function Code Table
500 series communication data can be divided into function code data, non
functional code data, and the latter includes operation command, running state,
running parameter, alarm information ,etc.
P group P0、P1、P2、P3、P4、P5、P6、P7、P8、P9、PA、
500-series
(read-write) PB、PC、PD、PE、PP
function code
A group A0、A1、A2、A5、A6、A7、A8、A9、AA、AB、
data
(read-write) AC、AD、AE、AP
Definition of the communication address as follows:
For P0~PP and A0~AP group function code data, Its functional group number if its
communication address is sixteen bits high,If lower sixteen bit is directly used for
function code in function group.
E.G.:
For P0~PP group data, its communication address is sixteen bits, it is divided into
00~0P or P0~PP according to whether it is written to EEPROM, and the low sixteen
bit is directly used for function code in function group serial number.
- 150 -
500 Series AC Drive User Manual Function Code Table
E.G.:
For A0~AP group data, its communication address is sixteen bits. it can be divided
into 40~4P or A0~AP According to whether to write EEPROM. The low sixteen bit is
directly used for function code in function group.
E.G.:
statue data divided into U group、AC Drive fault description、AC Drive running
statue
1) U group
The details descriptions of the U group data please reference to the 5th & 6th chapter
its communication address as follows:
U0~UP,Its communication address is sixteen bits 70~7P, and the lower sixteen is
the number of the monitoring parameters in the group,
- 151 -
500 Series AC Drive User Manual Function Code Table
E.G.:
When the communication reads the AC Drive running state, the communication
address is fixed to 3000H, and the upper machine can read the address data by
reading the address data, and it can get the information of the current AC Drive
running state. It is defined as follows:
1)control order
When P0-02( order source ) is 2:In communication control, the upper computer
can control the switching and stop of the AC Drive through the communication
address. The control commands are defined as follows:
- 152 -
500 Series AC Drive User Manual Function Code Table
4:Reverse jog
5:Free stop
6:Decelerate stop
7:Fault reset
2)communication setting value
Communication set points, main users, 500 Series intermediate frequency source,
torque upper limit source, V/F separation voltage source, PID given source and PID
feedback source are selected as the given data communicated to timing. The
communication address is 1000H, and when the upper computer sets the
communication address value, the data range is -10000~10000, corresponding to
the relative given value -100.00%~100.00%.3)digit output terminal control
The function of the digital output terminal is selected as 20: communication control,
the host computer can control the digital output terminal of the AC Drive through
the communication address. It is defined as follows:
The function of the analog output terminal AM,FM is selected as 20: communication
control, the host computer can control the analog terminal of the AC Drive through
the communication address. It is defined as follows:
- 153 -
500 Series AC Drive User Manual Function Code Table
AO1 AO1
0 ~ 7FFF means 0%~ 100%
AO2 AO2
5)parameter initialization
This function needs to be used when the parameter initialization operation of the
frequency converter is needed through the upper computer.
If the PP-00 (user password) is not 0, then we first need to check the password
through communication. After passing the check, the PC initialization operation in
30 seconds.
The communication address of the user password verification is 1F00H, and the
correct user password is written to the address. Then the password can be
completed. The address initialization of communication is 1F01H, and the data
content is defined as follows:
The function code group number and label parameter address rules:
Low byte:00~PP
Note:
- 154 -
500 Series AC Drive User Manual Function Code Table
1)For achieve this P group,change its high byte P of this function code to 0.
2)For achieve this A group,change its high byte A of this function code to 4.
Low byte:00~PP
Function code A0-05 not to be stored into EEPROM ,the address is 4005;
For all the parameters can also use the command code 07H to realize.
Parameter Parameter
Parameter description Parameter set
address address
1000H * Communication set 1010H PID set
- 155 -
500 Series AC Drive User Manual Function Code Table
value(Decimal system)
–10000 ~ 10000
1001H Running frequency 1011H PID feedback
1002H Busbar voltage 1012H PLC produce
1003H Output voltage 1013H Reserved
1004H Output current 1014H Reserved
1005H Output power 1015H The left running time
AI1 Pre-correction
1006H Output torque 1016H
voltage
AI2 Pre-correction
1007H Running speed 1017H
voltage
AI3 Pre-correction
1008H DI input mark 1018H
voltage
1009H DO output mark 1019H Reserved
100AH AI1 voltage 101AH Power-on time currently
100BH AI2 voltage 101BH Running time currently
100CH Reserved 101CH Reserved
Communication setting
100DH Count value input 101DH
value
100EH Length value input 101EH Reserved
100PH Overload speed 101PH Main frequency X display
– – 1020H Main frequency Y display
Note:
1) The set value of the communication is the percentage of the relative value,
10000 means 100.00%,-10000 means -100.00%。
2) For the data of frequency dimension, the percentage is the percentage of the
relative maximum frequency (P0-10). For the torque dimension data, the percentage
is P2-10 and A2-48 (the upper limit of the torque is digitally set, corresponding to
the first, second motor).
- 156 -
500 Series AC Drive User Manual Function Code Table
- 157 -
500 Series AC Drive User Manual Function Code Table
AC Drive fault
AC Drive fault information
address
0000:No fault
0001:Reserved 0015:Parameter read-write
0002:Accelerate over abnormal
current 0016:AC Drive hardware fault
0003:Decelerate over 0017:Motor to ground short
current circuit fault
0004:Constant over 0018:Reserved
current 0019:Reserved
0005:Accelerate over 001A:Running time arrival
voltage 001B:User custom fault 1
0006:Decelerate over 001C:User custom fault 2
voltage 001D:Power-on time arrival
0007:Constant over 001E:Load off
8000H voltage 001P:PID feedback lost when
0008:Buffer resistance running
overload fault 0028:Fast current limiting fault
0009:Undervoltage fault 0029:Fault of switching motor
000A:AC Drive overload at run time
000B:Motor overload 002A:Excessive velocity
000C:Input phase losing deviation
000D:Output phase losing 002B:Reserved
000E:Module overheating 002D:Reserved
000P:External fault 005A:Reserved
0010:Communication 005B:Reserved
abnormal 005C:Reserved
0011:Contactor abnormal 005E:Reserved
0012:Current detecting
- 158 -
500 Series AC Drive User Manual Function Code Table
fault
0013:Motor tuning fault
0014:Reserved
- 159 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
Chapter 7
The influence of the ambient temperature, humidity, dust and vibration will cause
the aging of the devices in the AC drive, which may cause potential faults or reduce
the service life of the AC drive. Therefore, it is necessary to carry out routine and
periodic maintenance.
2) Remove the dust, especially metal powder on the surface of the AC drive, to
prevent the dust from entering the AC drive.
- 161 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
The vulnerable components of the AC drive are cooling fan and filter electrolytic
capacitor. Their service life is related to the operating environment and maintenance
status. Generally, the service life is shown as follows:
1) Cooling Fan
● Judging Criteria: Whether there is crack on the blade, whether there is abnormal
vibration noise upon startup.
- 162 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
● Possible damage reason: Input power supply in poor quality, high ambient
temperature, frequent load jumping, electrolytic aging.
● Judging Criteria: Whether there is liquid leakage, whether the safe valve has
projected, measure the static capacitance, measure the insulating resistance.
After purchasing AC drive, for temporary storage and long-term storage, pay
attention to the following two aspects:
1) Pack the AC drive with the original box provided by 500 SERIES.
2) Long-term storage degrades the electrolytic capacitor. Thus, the AC drive must be
energized once every 2 years, each time lasting at least 5 hours. The input voltage
must be increased slowly to the rated value with the regulator.
2) 500 SERIES will provide 18-month warranty (Starting from the leave-factory date
as indicated on the barcode) for the failure or damage under normal use conditions.
If the equipment has been used for over 18 months, reasonable repair expenses will
be charged.
3) Reasonable repair expenses will be charged for the damages due to the following
causes:
- 163 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
500 Series AC drive provide a total Fault information and protective functions. After
a fault occurs, the AC drive implements the protection function, and displays the
fault code on the operation panel (if the operation panel is available). The
corresponding fault types and common solutions for faults are shown in the
following table. The table lists only for reference, please do not repair, transform, if
can not rule out the fault, please contact our company or agents for technical
support.
Display
Fault Name Fault investigation Fault countermeasures
- 164 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
- 165 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
- 166 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
- 167 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
- 168 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
- 169 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
1. The load is too heavy 1. Reduce the load and check the
Pulse-by-
or locked-rotor occurs motor and mechanical condition
pulse
Err40 on the motor 2. Select an AC drive of higher
current limit
2. The AC drive model is power class
fault
of too small power class
1. Change the selection 1. Perform motor switchover after
Motor
of the motor via terminal the AC drive stops
switching Err41
during running of the AC
fault
drive
1、Improper set 1、Set inspection parameters
inspection parameters properly according to actual
Excessive
P9-69、P9-60 situation
speed Fault
2、Wrongly set encoder 2、Set motor encoder parameters
deviation No.42
parameters correctly
fault
3、No parameter 3、Motor parameter
identification identification
No parameter 1、Motor parameter
identification identification
Motor 2、Wrongly set encoder 2、Set motor encoder parameters
Fault
overspeed parameters correctly
No.43
fault 3、Improper set 3、Set inspection parameters
inspection parameters properly according to actual
P9-69、P9-60 situation
Temperature sensor Check sensor wiring and eliminate
Motor wiring loose fault
Fault
overtempera Motor overtemperature 2、Reduce carrier frequency or
No.45
ture fault take other cooling measures for
the motor
Excessive deviation Reconfirm motor parameter
Initial
Fault between motor settings, pay attention to the
position
No.51 parameters and the rated current value
fault
practical value
- 170 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
You may come across the following faults during the use of the AC drive. Refer to
the following table for simple fault analysis.
- 171 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
- 172 -
500 Series AC Drive User Manual Maintenance & Troubleshooting
- 173 -
500 Series AC Drive User Manual Memo
power-on
- 174 -
500 Series AC Drive User Manual Memo
Memo
- 175 -