Analysis of Ce Inter-Area Oscillations of 1 December 2016
Analysis of Ce Inter-Area Oscillations of 1 December 2016
Analysis of Ce Inter-Area Oscillations of 1 December 2016
ANALYSIS OF CE INTER-AREA
OSCILLATIONS OF
1ST DECEMBER 2016
13.07.2017
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
1 INTRODUCTION ........................................................................................................ 5
4 CONCLUSIONS ....................................................................................................... 13
Page 2 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
EXECUTIVE SUMMARY
On 1st December 2016, at 11:18 CET, an unexpected opening of a line in the French system
(on the western 400 kV interconnection corridor with the Spanish system) triggered an
oscillatory incident in Continental Europe electricity system (CE).
The opening of the line increased the impedance between the Iberian Peninsula and France
during high power flows between some relevant areas in the system as shown in Figure 4:
• export flows from the south western part to the centre of the system (3.100 MW from
Portugal to Spain and 2.250 from Spain to France),
• net importing position of France,
• export flows from central Europe to neighbouring areas, and
• import flows in the eastern part of CE.
All these elements caused a large voltage phase angle difference in the system and
decreased the general damping that triggered a permanent oscillation. Undamped
oscillations at 0.15 Hz appeared: Iberian Peninsula was swinging in anti-phase with the rest
of the CE system (East-Centre West mode) and with a certain participation of Turkey (around
70° voltage phase angle difference to the Iberian Peninsula). The biggest amplitude of the
oscillation was registered on the Iberian Peninsula.
The mode excited in this oscillation has already been identified in studies (E. Grebe et al. 1);
see the mechanical analogy and the mode shape in Figure 1.
Figure 1. East-Centre-West mode. Mechanical analogy and mode shape (E. Grebe et al.)
1
Low frequency oscillations in the interconnected system of Continental Europe. E. Grebe, J.
Kabouris, S. López Barba, W. Sattinger, W. Winter. Power and Energy Society General Meeting, 2010
IEEE
Page 3 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
Three minutes after the reduction of the Spain to France schedule exchange from 2.250 MW
to 1.000 MW, agreed by REE and RTE operators, the oscillations were totally damped.
These oscillations lasted for about five minutes (11:18 to 11:23 CET).
The oscillatory phenomenon is very well known in CE region. In the past, some important
events happened and it is a major concern when enlargements of the CE system are studied
or carried out (Centrel, IPS-UPS, Tunisia-Libya, Turkey, Ukraine-Moldova, etc.).
RTE and REE had performed some simulations2 and concluded that the reactive power
modulation on the HVDC line between France and Spain contributed to damping of the
oscillations but with a low influence. REE and RTE are currently working on the possibilities
of the HVDC active and reactive power controls to optimise their effect on the damping of
inter-area oscillations.
• In 2008, REE commissioned a study to check and retune the PSS of the combined
cycle power plants aiming to damp the 0.2-0.3 Hz East-West mode. REE is has
launched a revision of the 2008 PSS study, with the purpose of checking the
performance of PSS for damping oscillations in frequencies down to 0.12 Hz.
• The PSS settings in France seem to be well-tuned and no additional adjustments are
needed.
• In 2001, REN also commissioned a study to check and retune the already installed
PSS and tune the future ones to damp the oscillations found in future grid scenarios.
In 2005, the results of this study were provided to power plants for implementation.
Apart of some old ones, all new conventional power plants have PSS installed since
2000 at least.
• In parallel to the REE studies, the SPD group will further improve the dynamic model,
investigate the PSS settings of the important power stations in CE and support TSOs
affected by inter-area oscillations in order to better fine-tune the PSS settings.
2
Simulations were carried out based on ENTSO-E initial model and TSOs’ network simulators.
Page 4 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
Since the 2nd of December, PMU data is available in REE control rooms. The event has
confirmed the need for improving our knowledge of the oscillatory properties of the CE
system (i.e. impact of flow patterns, contingencies, topology and generation mix effect, etc.).
For this purpose, sharing PMU data between CE regions is a key activity.
Dispatchers of REE can now see the raw frequency signal from eight substations. In
addition, REE and RTE are working on defining damping and amplitude thresholds to
generate alarms to the control room and mitigation actions related to these alarms.
The Initial Dynamic Model created by SPD proved to be a pragmatic tool for dynamic studies
(transient and eigenvalue analyses), although some modelling improvements are needed to
facilitate the analysis and its accuracy.
Finally, as dynamic stability limits get closer to static limits, N-1 power flow analyses might
become insufficient to ensure secure system operation. For this reason, Dynamic Security
Assessment (DSA) close to real time could become necessary.
1 INTRODUCTION
The objective of this report is to describe and analyse the inter-area oscillation incident
occurred on 1st December 2016 at 11:18 CET within the Continental Europe (CE) electricity
system.
The incident was triggered by an unexpected tripping of a line in the French system, on the
western 400 kV interconnection corridor with the Spanish system. This event excited the
East-Centre-West oscillation sub mode of CE system; therefore, the Iberian Peninsula
system oscillated almost in phase with Turkish system and in anti-phase with the central part
of the CE system.
These oscillations lasted for about five minutes (11:18 to 11:23 CET), and were damped in
three minutes, after mitigation measures had been taken by REE.
Page 5 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
The export from Portugal to Spain (3.100 MW approx.) was almost as much high as the
export from Spain to France (2.250 MW approx.). The west part of the interconnection was
transmitting more than a half of this power to France (1.450 MW approx., see Figure 3):
Page 6 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
The physical international exchanges of 1st Dec. 2016 for the hour H12 taken from the
ENTSO-E transparency platform are depicted in Figure 4 (some values missing due to data
unavailability):
st
Figure 4: Main power flows in CE. 1 Dec. 2016 at 12h00 CET
Page 7 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
The power flow depicted for Spain-France in Figure 4 (1.547 MW) is less than the real flow
before the incident (2.250 MW) due to the power reduction applied by the REE operators
after the event.
• 11:18 am CET: The circuit breaker in substation Cantegrit 400 kV Argia bay opens
unexpectedly causing the opening of the 400 kV line Argia-Cantegrit. The tripping and
the topological situation in that area cause the separation of the Spanish and French
system at the Western side. The Spanish system continues supplying approximately
260 MW to the load of three French substations, Argia 400, Agria 220 kV and
Mouguerre 220 kV, through the 400 kV line Hernani-Argia and 220 kV line Arkale-
Argia.
The Iberian Peninsula system remains connected to CE by the rest of the
interconnections with France, i.e. 220 kV line Biescas-Pragnères, 400 kV line Vic-
Baixas and HVDC Links 1 and 2 Sta. Llogaia-Baixas, which transmit approx. 1.770
MW.
In total, after the incident, Spain continued delivering some 2.000 MW out of the
scheduled 2.250 MW (Figure 5).
Page 8 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
Page 9 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
• 11:20 am CET: REE and RTE operators agree on reducing the Spain to France
exchange from scheduled 2.250 MW to 1.000 MW to restore N-1 security. FRR
(Automatic Frequency Restoration Reserve) providers in Spain start activating the
reduction of the actual exchange between Spain and France.
• 11:21 am CET: the damping starts to be positive.
• 11:24 am CET: the oscillations are totally damped.
• 11:45 am CET: RTE operators close the line 400 kV Argia-Cantegrit.
Figure 8. Frequency in Spain and active power through 400 kV Vic-Baixas tie line.
Page 10 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
Figure 9: Phase to ground voltages in the Spanish system referred to the pre-incident values.
Figure 10 clearly shows that the Iberian Peninsula oscillated in phase opposition to the rest
of Continental Europe and around 70° degrees against Turkey and Greece.
Figure 10: Voltage angle differences to the slack node for different European locations in the
beginning of the incident.
Page 11 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
Figure 11 shows the damping and oscillation frequency during the incident. This Prony3
analysis clearly shows that the dominant frequency oscillation is fully correlated with the
described events.
3
as one of the currently successfully used methods for damping analysis, FFT or Kalman filtering
deliveris similar results.
Page 12 of 13
ENTSO-E • Boulevard Saint-Michel, 15 • 1040 Brussels • Belgium • Tel +32 2 737 15 80 • Fax +32 2 741 69 49 • [email protected] • www.entsoe.eu
European Network of
Transmission System Operators
INTER-AREA OSCILLATIONS IN THE CONTINENTAL EUROPE for Electricity
SYNCHRONOUS AREA
4 CONCLUSIONS
The event demonstrates that coincidence and combination of different factors can influence
the system stability. Each factor may not normally be critical in itself, but in this particular
case the combined effect decreased the general damping. The physical aspects and root
causes of phenomena are clear and as demonstrated in the present report. In fact this event
shows that power transport over long distances together with too high impedance can cause
a too low system damping with respect to inter-area oscillations and should, therefore, be
treated carefully.
Aspects such as HVDC influence and PSS settings across the CE system will be further
investigated by SPD and concerned TSOs. As foreseen in network codes on Operational
Security, it is evident that dynamic evaluations on the system behavior become more and
more necessary.
It is also important to note that prompt coordination between the TSOs played a vital role in
the mitigation of the transient.
Page 13 of 13