Vision™ OPLC™: General Description
Vision™ OPLC™: General Description
Vision™ OPLC™: General Description
Programming The Unitronics Setup CD contains VisiLogic software and other utilities
Software, VisiLogic
& Utilities Easily configure hardware and write both HMI and Ladder control
applications; the Function Block library simplifies complex tasks
such as PID. Write your application, and then download it to the
controller via the programming cable included in the kit.
Utilities
These include UniOPC server, Remote Access for remote
programming and diagnostics, and DataXport for run-time data
logging.
To learn how to use and program the controller, as well as use utilities such as
Remote Access, refer to the VisiLogic Help system.
Unitronics 1
Vision™ OPLC™,V1210-T20BJ Installation Guide
Removable Micro-SD card: store datalogs, Alarms, Trends, Data Tables; export to Excel;
Memory Storage backup Ladder, HMI & OS and use this data to ‘clone’ PLCs.
For more data, refer to the SD topics in the VisiLogic Help system.
Data Tables Data tables enable you to set recipe parameters and create datalogs.
Danger Symbols
When any of the following symbols appear, read the associated information carefully.
Symbol Meaning Description
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance
with the standards given in the product’s technical specification sheet.
Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Install at maximum distance from high-voltage cables and power equipment.
2 Unitronics
Vision™ OPLC™,V1210-T20BJ Installation Guide
Mounting
Dimensions
Note that the LCD screen may have a single pixel that is permanently either black or white.
Unitronics 3
Vision™ OPLC™,V1210-T20BJ Installation Guide
Panel Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
Note: For UL listed module, in order to meet the UL508 standard, panel-mount this device
on the flat surface of a Type 1 enclosure.
4 Unitronics
Vision™ OPLC™,V1210-T20BJ Installation Guide
Wiring
Do not touch live wires.
Install an external circuit breaker. Guard against short-circuiting in external wiring.
Use appropriate circuit protection devices.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any substance on stripped wire that might cause the wire
Caution
strand to break.
Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm 2–3.31 mm2).
1. Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Power Supply
The controller V1210-T20BJ requires either an external 12 or 24VDC power supply.
Permissible input voltage range: 10.2-28.8VDC, with less than 10% ripple.
The power supply must include double insulation. Outputs must be rated as
SELV/PELV/Class 2/Limited Power.
Do not connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to device’s 0V pin.
Install an external circuit breaker. Guard against short-
circuiting in external wiring.
Double-check all wiring before turning on the power
supply.
In the event of voltage fluctuations or non-conformity to
voltage power supply specifications, connect the device
to a regulated power supply.
Unitronics 5
Vision™ OPLC™,V1210-T20BJ Installation Guide
Communication Ports
This series comprises a USB port, 2 RS232/RS485 serial ports and a CANbus port. An additional
port may be ordered separately and installed. This port may be either Ethernet, or serial (COM 3).
For the most updated information regarding ports and their installation, please refer to the Technical
Library at www.unitronics.com.
Turn off power before making communications connections.
The USB port may be used for programming, OS download, and PC access.
Note that COM port 1 function is suspended when this port is physically connected to a PC.
The serial ports are type RJ-11 and may be set to either RS232 or RS485 via DIP switches, in
accordance with the table shown below.
Use RS232 to download programs from a PC, and to communicate with serial devices and
applications, such as SCADA.
Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show PLC port signals.
To connect a PC to a port that is set to RS485, remove the RS485 connector, and connect the PC to
the PLC via the programming cable. Note that this is possible only if flow control signals are not used
(which is the standard case).
RS232 RS485** Controller Port
Pin # Description Pin # Description
1* DTR signal 1 A signal (+)
2 0V reference 2 (RS232 signal)
3 TXD signal 3 (RS232 signal)
4 RXD signal 4 (RS232 signal) Pin #1
5 0V reference 5 (RS232 signal)
6* DSR signal 6 B signal (-)
*Standard programming cables do not provide connection points for pins 1 and 6.
**When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,
and Pin 6 (DSR) signal is used for signal B.
RS232 to RS485: Changing DIP Switch Settings
The ports are set to RS232 by factory default.
To change the settings, first remove the Snap-in I/O Module, if one is installed, and then set the
switches according to the following table.
6 Unitronics
Vision™ OPLC™,V1210-T20BJ Installation Guide
Unitronics 7
Vision™ OPLC™,V1210-T20BJ Installation Guide
CANbus
These controllers comprise a CANbus port. Use this to create a decentralized control network using
one of the following CAN protocols:
CANopen: 127 controllers or external devices
CANLayer 2
Unitronics’ proprietary UniCAN: 60 controllers, (512 data bytes per scan)
The CANbus port is galvanically isolated.
CANbus Wiring
Use twisted-pair cable. DeviceNet® thick shielded twisted pair cable is recommended.
Network terminators: These are supplied with the controller. Place terminators at each end of the
CANbus network.
Resistance must be set to 1%, 121Ω, 1/4W.
Connect ground signal to the earth at only one point, near the power supply.
The network power supply need not be at the end of the network.
CANbus Connector
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising
out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other
third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
DOC16001-B8 03/14