Distance Protection With Tele-Protection On An OHL Feeder
Distance Protection With Tele-Protection On An OHL Feeder
Distance Protection With Tele-Protection On An OHL Feeder
tele-protection
on an OHL feeder
www.siemens.com/siprotec5
SIPROTEC 5 Application
Distance protection with tele-protection (pilot protection) on an OHL feeder
SIPROTEC 5 Application
Distance protection with tele-protection (pilot
protection) on an OHL feeder
APN-016, Edition 2012-04-10
Content
The applicable SIPROTEC5 device Manual should be consulted for detailed information.
This application example covers the details with regard to distance protection only. Related subjects such as e.g. auto re-
close, sync check and breaker fail are covered in separate application descriptions.
1.2 Overview
Every protection engineer has his own preference when calculating settings. Some prefer calculations in primary, others
secondary and some in per unit quantities. The finer details of distance protection setting co-ordination are also not
addressed here as this is typically obtained with special software tools. The zone reaches are therefore predefined in Table
1 without further calculation.
Single pole tripping will be permitted for faults cleared by the under-reaching zone 1 and the tele-protection.
For the tele-protection the forward over-reaching time delayed Zone 2 will be applied with a POTT scheme.
Bus1
Bus3
LS1 VT1
Leitung 2
CT1
ISO1
Leitung 1
VT2 Leitung 3
CT2
LS2
ISO2
Abzweig 2
CT3 VT3
LS3
Bus2
VT4
The distance protection is applied to protect Line1 in Figure 1 above with the zone reaches defined in Table 1 below.
The values given in the table below are typically obtained by protection co-ordination studies using software tools (e.g.
PSS®SINCAL). For this application example the zone reaches as defined below will be used:
Zone 1 Fast underreach protection for Line 1 80% Line 1 0.00 sec
Zone 2 Forward time delay backup, overreach 20% less than Z1 1 time step
reach on Line 3
Table 1
Although the configuration in Figure 1 shows a breaker-and-a-half application, this has no significant impact on the
general application of distance protection as explained in this example. For this general case it is assumed that the two
CT’s are identical so that they may be replaced by a single CT which is equivalent to the double busbar application with
only one CT. The allocation of the CT’s and VT’s to the various measuring points as well as the circuit breakers to the
relevant function groups is covered in a separate application description.
Parameter Value
Line 1 - length 80 km
Based on the source and line impedance, the following minimum fault current levels can be calculated for faults on Line 1:
U source
I fault = with U source = 400 kV
3 ⋅ Z tot
If fault resistance is neglected for 3 phase faults:
Z tot = sum of positive sequence source and line impedance (as only current magnitudes are being calculated, only the
magnitude of the impedance is relevant)
400kV
I 3 phmin =
3 ⋅ 117.4
I 3 phmin = 1967 A
Z tot = 1/3 (sum of positive, negative and zero sequence source and line impedance)
400kV
I1 phmin =
3 ⋅ 167.3
I1 phmin = 1380 A
Z tot_R = Z tot + R F
Z tot _ R = RF + Z tot
Z tot = 250 + 19.8 + j166.1
Z tot = 316.8
The minimum single phase fault current with high resistance is therefore:
400kV
I1 phmin_ R =
3 ⋅ 316.8
I1 phmin_ R = 729 A
The minimum operating time has a default setting of 0 s. This does not have to be changed. Only in applications where
the “operate” of a protection function is intentionally not associated with a configured Circuit Breaker can this time be
changed to obtain a defined minimum operate time. The minimum tripping time for the trip command to the circuit
breaker is set in the FG Circuit breaker.
For the distance protection the residual compensation factors “Kr and Kx” must be set for the ground loop measurement.
The default setting format “Kr, Kx” is used in this application note. Alternatively the complex “K0” factor may also be used.
The setting of “Block monitoring dir.” should remain “off”. It can be changed to “on” during testing and commissioning to
avoid a flood of test related signals arriving in the control centre. This blocking can also be activated via binary input.
he setting mask for the CT parameters (e.g. Meas. Point I-3ph 1) is as follows (refer to the comment above regarding “Edit
mode” – it is recommended to be in “secondary” when changing CT ratio parameters):
a fixed number of samples per cycle are available. Although the distance protection does not use re-sampling the tracking
is set to “active” for the line current measurement because other functions in the device may use frequency tracking.
The rated primary and secondary current are set according to the application data given in Table 2.
The Current range setting for distance protection is fixed at 100 x IR.
The CT polarity is selected by correct application of the star point. This is done with the selection of the CT neutral point
direction which may be towards the protected object (line) or not. The correct setting must be checked during
commissioning or with “on-load” direction check.
The setting “Inverted phases” is only relevant when a there is the possibility of reversed phase rotation. For example the
phase sequence in the generator bay of a pumped storage plant has a phase sequence change when it switches from
pumping to generating. In this application the phase sequence is fixed so that this parameter is set to “none”
The other settings such as e.g. CT error are not applicable to this application. For Line Differential protection these have
significance.
The settings for the 2nd CT, Meas.point I-3ph 2, are exactly the same as the CT’s are identical.
1.4.3 Recording
The fault recording in SIPROTEC 5 is in the first place provided by the fault log. In the Information Routing the selection for
the fault log can be applied. The oscillographic recording (records) also contain bimary traces that are selectable in the
Information Routing matrix. The following settings cn be applied for the Fault recorder:
The SIPROTEC 5 devices can store long records in the internal memory so that in general all events (even those that do not
result in a trip output) are stored. If the risk exists that, due to high fault incidence or long intervals before extracting the
records from the device, records that resulted in trip and reclose are overwritten by other events, the storage mode can
be changed to “with trip” instead of “always”. Alternatively the sampling rate can be reduced to less than 8kHz for longer
fault recordings – refer to manual for details on the storage capacity.
General
The further settings in this window should be set according to the line data. The line capacitance (C1 and C0) are only
required if 2-ended fault location or charge compensation are applied together with line differential protection. The X per
length unit is also required by the fault location and should be set according to the line data in Table 2.
The Line angle setting is calculated from the positive sequence line impedance data. In this example:
Z1 = 0.025 + j0.21
X
Line _ angle = arctan L
RL
Although the residual compensation factors can be set for each zone separately, the setting based on the line data should
be set here.
R E 1 R0 XE 1 X0
= ⋅ − 1 = ⋅ − 1
RL 3 R1 X L 3 X1
RE 1 0.13 X E 1 0.81
= ⋅ − 1 = ⋅ − 1
RL 3 0.025 X L 3 0.21
RE XE
= 1.4 = 0.95
1116
RL XL
If the fault current (with transients) can cause CT saturation, the setting for CT saturation detection should be set to yes.
This ensures that appropriate stabilization measures are applied to prevent mal-operation due to CT saturation during
faults. When this setting is “yes” the CT saturation threshold must be set. This current level can be calculated with the
given CT data:
n'
CT _ Saturation _ Threshold = ⋅ I nom
5
PN + Pi
with: n' = n ⋅ = actual _ overcurrent _ factor
P'+ Pi
In this example only the 7SA52 relay is connected to the CT, so that the relay burden is 0.05 VA per phase. Due to the
Holmgreen connection, the maximum burden for earth currents is therefore twice 0.05VA =0.1VA.
2 ⋅ l cable ⋅ ρ CU
Rcable =
a cable
lcable = 50 m
ρcu = 0,0179 Ωmm2/m
acable = 2,5 mm2
therefore:
2 ⋅ 50 ⋅ 0.0179
Rcable =
2.5
Rcable = 0.72
20 + 3
n' = 20 ⋅
0.82 + 3
n' = 120
Process monitor
The 1-pole open detection is important when single pole tripping is possible. During the single pole dead time some
protection functions are blocked (stabilized). The default setting “with measurement” is recommended. In this context the
settings for the Voltage Criterion arise. To illustrate this the following diagram from the manual is shown below:
X Z2 Z4
I2
R R
nce
I1
da
mpe
Z1
line i
weak I1 I2
strong
source
relay Fault source
resistance
Figure 11: Example, sequential tripping with back-up stage during remote faults
Although the fault is in the Zone 2 range (according to reach co-ordination) it is initially not seen in zone 2 due to the
fault resistance and strong remote infeed. The remote end with strong infeed will trip according to its setting (reach and
time delay). When the remote infeed is open the current (I2) resets so that the fault impedance is seen in Zone 2. With
the applied setting, the zone 2 timer was already started on distance pickup, and zone 2 will trip in the desired time
although the fault was initially outside zone 2.
The Line Angle setting must be calculated from the positive sequence line parameters:
Z1 = 0.025 + j0.21
X
Line _ angle = arctan L
RL
The remaining settings in Figure 10 can remain on the default values. For details refer to the manual or online help
function.
For the distance protection a minimum current is required for operation. It is typically left unchanged on the default value
corresponding to 10% of secondary nominal current. As this setting is not relevant for the reach grading and is generally
much smaller than typical load current it is not based on a fault current calculation. If however weak in-feed conditions
exist which may result in internal faults having fault current flow below this threshold, a special “Weak In-Feed” protection
may have to be applied.
The load cut-out is typically only required on long lines where the set zone reaches may include load impedances. If this is
the case the load cut-out should be activated – not the case in this example.
X
Z poly
Maximum Zphi
Load Load
area area R
Minimum Zload
Zone 2 20% less than Z1 reach on Line 3 20% less than Z1 1 time step
reach on Line 3
Table 3
The applied template is pre-configured with the following distance protection zones:
Z1, Z1B, Z3 and Z4. These can be renamed, deleted or supplemented with additional inserted stages. In this case the
zones will be renamed by entering the desired name in the “Details” window as shown below:
This is converted to a secondary value by multiplying with the conversion factor in Table 2:
A separate resistance reach setting is available for ph-ph measured loops and ph-g measured loops. With the “Distance
characteristic angle” under General above the angle of inclination of the distance characteristic is set equal to the line
angle. The resistance settings of the individual zones therefore only have to cover the fault resistance at the fault location
(faults on the protected line). For the Z1 setting only arc faults will be considered. For this purpose the arc resistance will
The length of the arc is greater than the spacing between the conductors (ph-ph) because the arc is blown into a curve
due to thermal and magnetic forces. For estimation purposes it is assumed that l arc is 1.5 times the conductor spacing. To
obtain the largest value of R arc , which is required for the setting, the smallest value of fault current must be used
(calculated earlier):
For the earth fault, not only the arc voltage must be considered, but also the tower footing resistance. From the graph in
Figure 20 it is apparent that although the individual tower footing resistance is 15 Ω (Table 2) the resultant value due to
the parallel connection of multiple tower footing resistances is less than 1.5 Ω.
I2
RTF = 1 + ⋅ effective _ tower _ footing _ R
I1
RTF = (1 + 3) ⋅ 1.5
RTF = 6Ω( prim)
To obtain the largest value of R arc , which is required for the setting, the smallest value of fault current must be used
(calculated earlier):
18.75kV
Rarc =
1380 A
Rarc = 13.6Ω
The total resistance that must be covered during earth faults is the sum of R arc and R TF . A safety factor of 20% is included
and the result is converted to secondary values (division by factor (1 + RE/RL) because R arc and R TF appear in the loop
measurement while the setting is done as phase impedance or positive sequence impedance). :
The phase to phase fault resistance reach is calculated along the same lines as the setting for ph-ph resistance. Initially
calculate the ph-ph arc resistance
By addition of a 20% safety margin and conversion to secondary impedance (factor from Table2) the following minimum
setting is calculated (division by 2 because R arc appears in the loop measurement while the setting is done as phase
impedance or positive sequence impedance):
1.2 * 23 * 0.2632
R ( Z1) =
2
R ( Z1) = 3.63Ω(sec)
X reach Calculation
Ohm (sec)
Z2 0.8 x (Xline1 + 0.8 x Xline3) 0.8 x( 80 x 0,21 + 0.8 x 4.606) x 0.2632 6,485
The resistance reaches are simply increased proportional to the resistance reaches calculated for Zone Z1:
Ohm (sec)
Ohm
(sec)
For the Z2 zone specific residual compensation factors will be used. If the parameter is selected for this purpose, the
required settings are accessible:
( X 21 − X Line1 )
R 21 = R Line1 + ⋅ R Line 3
X Line 3
24.64 − 80 ⋅ 0.21
R 21 = 80 ⋅ 0.025 + ⋅ 1.5
17.5
R 21 = 2.672
( X 2 − X Line1 ) ( X 2 − X Line1 )
X 2 0 = X 0 Line1 + ⋅ X 0 Line 3 R 2 0 = R 0 Line1 + ⋅ R0 Line 3
X Line 3 X Line 3
24.64 − 80 ⋅ 0.21 24.64 − 80 ⋅ 0.21
X 2 0 = 80 ⋅ 0.81 + ⋅ 86.5 R 2 0 = 80 ⋅ 0.13 + ⋅ 7.5
17.5 17.5
X 2 0 = 103.4 R 2 0 = 13.76
Figure 19: Graphic illustration of positive and zero sequence impedance for Z2
The Kr and Kx factors for Z2 can then be directly calculated using the above results:
1 R0 1 X0
Kr = ⋅ − 1 Kx = ⋅ − 1
3 R1 3 X1
1 13.76 1 103.4
= ⋅ − 1 = ⋅ − 1
3 2.672 3 24.64
= 1.38 = 1.07
As the application is not on a parallel line the transient blocking does not need special consideration. The default settings
can be left unchanged.
The 85-21 is a selective protection, clearing internal faults without delay. It should therefore be set to trip single pole is
single pole auto re-closure is possible.
The 85-21 is generally set without any intentional operate delay. Only special back-up constellations require a time delay
setting here.
If the 85-67N scheme is sharing the same communication channel with 85-21, the transient block condition from 85-67N
should be applied to prevent maloperation of the 85-21 when there is a ground fault on a parallel line followed by current
reversal. As there is no parallel line in this application this selection is not made.
Closed Closed Normal Operation with both Close with set dead Run normal dead time
CB closed prior to fault time as leader and then wait for release by
then release Follower leader before AR close
Closed Open Tie breaker (follower) is open Close with set dead AR detects CB open and
prior to fault time as leader and does not start = no AR
then release Follower close
Open Closed Bus breaker (leader) is open AR detects CB open Close with set dead time as
prior to fault and does not start = leader does not block the
no AR close follower
Closed Closed Normal Operation with both Close with set dead Run normal dead time
CB closed prior to fault – AR time - Trip – definite then wait – no release by
not successful – permanent trip no further AR Leader – then new trip
fault indication – no AR and
definite trip
Table 4
A simple logic will be applied in the Function charts to achieve the above response:
When the Flip-flop is set, the output sets (via the Build SPS block) the signal Delay Close Command in CB2 the Follower.
The AR function in CB2 will go through all the normal states until the AR Close command is due. If the signal Delay Close
Command is active the AR close will not be issued until this signal resets. If the maximum dead time extension (Setting
Parameter) has expired before the release is given the AR will be terminated with a definite trip.
The Leader will reset the Flip-Flop when the leader Cycle is successful. This is indicated with the Remote Close Command
from CB1 which is issued when there is no further protection operation within a set time after the re-close of CB1.
In the Follower the “Max. dead time extension” must be set longer than the release delay from the leader as set above.
1.9 Conclusion
The breaker-and-a-half application with SIPROTEC5 can be achieved with flexible combination of the available functions. A
logical grouping of protection and control functions is possible to cover the special requirements of all users.
www.siemens.com/siprotec
Email: [email protected]
© 2016 Siemens. Subject to changes and errors. For all products using security features of OpenSSL, the
The information given in this document only contains following shall apply:
general descriptions and/or performance features which This product includes software developed by the OpenSSL
Project for use in the OpenSSL Toolkit.
may not always specifically reflect those described, or
(http://www.openssl.org/ )
which may undergo modification in the course of further
This product includes cryptographic software written by
development of the products. The requested performance
Eric Young ([email protected] )
features are binding only when they are expressly agreed This product includes software written by Tim Hudson
upon in the concluded contract. ([email protected])
This product includes software developed by Bodo Moeller.