Series DS-1 – 5.6 K-factor, Dry-type Sprinklers


Pendent, Upright, and Horizontal Sidewall
Standard Response, Standard Coverage
General NOTICE
Series DS-1 Dry-type Sprinklers
Description described herein must be installed
and maintained in compliance with this
TYCO Series DS-1 5.6K Pendent, document, as well as with the applica-
Upright, and Horizontal Sidewall, Stan- ble standards of the NATIONAL FIRE
dard Response (5 mm bulb), Standard PROTECTION ASSOCIATION (NFPA),
Coverage Dry-type Sprinklers are dec- in addition to the standards of any other
orative glass bulb automatic sprinklers authorities having jurisdiction. Failure
typically used where: to do so may impair the performance
• pendent sprinklers are required of these devices.
on dry pipe systems that are The owner is responsible for main-
exposed to freezing temperatures taining their fire protection system
(for example, sprinkler drops from and devices in proper operating con-
unheated portions of buildings) dition. Contact the installing contrac-
• sprinklers and/or a portion of the tor or product manufacturer with any
connecting piping may be exposed questions.
to freezing temperatures (for Series DS-1 Dry-type Sprinklers must
example, sprinkler drops from wet only be installed in fittings that meet
systems into freezers, or horizontal the requirements of the Design Crite-
piping extensions through a wall to ria section.
protect unheated areas of a building
such as loading docks, overhangs,
and building exteriors) Sprinkler
• sprinklers are used on systems that
are seasonably drained to avoid
Identification
freezing (for example, vacation
resort areas)
Numbers (SINs)
TY3255 – Pendent
TY3155 – Upright
TY3355 – Horizontal Sidewall
Discharge Coefficient
Technical K=5.6 gpm/psi½ (80,6 lpm/bar½)

Data Temperature Ratings


See Tables A and B.
Approvals Finishes
UL and C-UL Listed Sprinkler: See Table D.
FM Approved Escutcheon: See Table D.
NYC Approved Physical Characteristics
• under MEA 352-01-E Inlet ���������������������������������������������������������� Copper
IMPORTANT LPCB Approved Plug ���������������������������������������������������������� Copper
Refer to Technical Data Sheet • Reference No. 094a/11 Yoke. . . . . . . . . . . . . . . . . . . . . . . . Stainless Steel
TFP2300 for warnings pertaining to Casing. . . . . . . . . . . . . . Galvanized Carbon Steel
CE Certified
Insert ���������������������������������������������������������Bronze
regulatory and health information. • Certificate of Conformity Bulb Seat �������������������������������������� Stainless Steel
No.2831-CPR-S2015
Always refer to Technical Data Bulb (5 mm dia.) ����������������������������������������� Glass
Sheet TFP700 for the “INSTALLER See Tables A and B for details. Compression Screw ���������������������������������Bronze
Deflector ���������������������������������������������������Bronze
WARNING” that provides cautions Maximum Working Pressure Frame �������������������������������������������������������Bronze
with respect to handling and instal- 175 psi (12,1 bar) Guide Tube ���������������������������������� Stainless Steel
lation of sprinkler systems and com- Water Tube ���������������������������������� Stainless Steel
ponents. Improper handling and Inlet Thread Connections Spring. . . . . . . . . . . . . . . . . . . . . . Stainless Steel
1 in. NPT Sealing Assembly. . Beryllium Nickel w/TEFLON
installation can permanently damage ISO 7-R 1 Escutcheon. . . . Carbon Steel or Stainless Steel
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 10 DECEMBER 2020 TFP500


TFP500
Page 2 of 10

SPRINKLER FINISH
SPRINKLER ESCUTCHEON TEMPERATURE BULB
TYPE TYPE RATING COLOR CODE NATURAL CHROME POLYESTER*
BRASS PLATED
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow 1, 2, 3, 4, 5 1, 2, 4, 5
STANDARD
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 1, 2, 3 1, 2
135°F (57°C) Orange
155°F (68°C) Red
1, 2, 3, 5 1, 2, 5
175°F (79°C) Yellow
RECESSED
200°F (93°C) Green
286°F (141°C) Blue 1, 2

PENDENT 360°F (182°C) Mauve N/A


(TY3255) 135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
DEEP
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 1, 2, 3, 4, 5 1, 2, 4, 5
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
WITHOUT
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 1, 2, 3 1, 2
135°F (57°C) Orange
155°F (68°C) Red

UPRIGHT 175°F (79°C) Yellow 1, 2, 3, 4, 5 1, 2, 4, 5


WITHOUT
(TY3155) 200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 1, 2, 3 1, 2
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL), maximum order length of 48 in.
2. Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 in.
3. Approved by FM Global (FM Approvals), maximum order length of 48 in.
4. Loss Prevention Certification Board (LPCB) and CE conformity apply to these temperature ratings only
5. Approved by the City of New York under MEA 352-01-E
* Frame and deflector only
N/A – Not Applicable
TABLE A
SERIES DS-1 PENDENT & UPRIGHT DRY-TYPE SPRINKLERS, 5.6K, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP500
Page 3 of 10

SPRINKLER FINISH
SPRINKLER ESCUTCHEON TEMPERATURE BULB
TYPE TYPE RATING COLOR CODE NATURAL CHROME POLYESTER***
BRASS PLATED
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
STANDARD
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve
135°F (57°C) Orange
155°F (68°C) Red

HSW* 175°F (79°C) Yellow 1**, 2**, 3***, 4, 5 1**, 2**, 4, 5


(TY3355) DEEP
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
WITHOUT
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 1**, 2**, 5 1**, 2**
Notes:
1. Listed by Underwriters Laboratories, Inc. (UL), maximum order length of 48 in.
2. Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 in.
3. Approved by FM Global (FM Approvals), maximum order length of 48 in.
4. Loss Prevention Certification Board (LPCB) and CE conformity apply to these temperature ratings only
5. Approved by the City of New York under MEA 352-01-E
* Horizontal sidewall with top of deflector-to-ceiling distance of 4 to 12 in. (100 to 300 mm)
** Light and ordinary hazard occupancies only
*** Light hazard occupancies only
**** Frame and deflector only
TABLE B
SERIES DS-1 HORIZONTAL SIDEWALL (HSW) DRY-TYPE SPRINKLER, 5.6K, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS

PLUG WITH INLET


SEALING
ASSEMBLY
WRENCH
YOKE RECESS

SPRING
INLET
BAND
WATER WRENCH
TUBE FLAT
CASING

GUIDE INSERT PUSH WRENCH


TUBE IN TO ENSURE
ENGAGEMENT
BULB WITH SPRINKLER
FRAME SEAT WRENCHING AREA
FIGURE 2
5 mm BULB W-TYPE 7
VENT HOLE WRENCH

COMPRESSION
DEFLECTOR SCREW

FIGURE 1
SERIES DS-1 DRY-TYPE SPRINKLER, 5.6K, STANDARD RESPONSE
ASSEMBLY
TFP500
Page 4 of 10

SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING


(REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN
CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION)

FACE OF FACE OF FACE OF


SPRINKLER SPRINKLER SPRINKLER
FITTING FITTING FITTING

ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2" DIA.


2-3/4" to 48" 3-3/4" to 48" 1/2" to 46" (88,9 mm)
1-3/4" DIA. (12,7 to 1168,4 mm)
(69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm) 2-1/2" DIA.
IN 1/4" (6,4 mm) IN 1/4" (6,4 mm) 2-1/4" DIA. IN 1/4" (6,4 mm)
(63,5 mm)
INCREMENTS INCREMENTS (57,2 mm) INCREMENTS
FACE OF
CEILING FACE OF
FACE OF CEILING
CEILING
4-1/4" ± 1/8"
(108,0 ± 3,2 mm)
2-3/16" ± 1/8" 3" DIA. 1-3/8" ± 1/8" 2-7/8" DIA.
(55,6 ± 3,2 mm) (76,2 mm) (34,9 ± 3,2 mm) (73,0 mm)

FIGURE 4
FIGURE 3 PENDENT (TY3255) FIGURE 5
PENDENT (TY3255) WITH STANDARD PENDENT (TY3255)
WITH STANDARD ESCUTCHEON RECESSED ESCUTCHEON WITH DEEP ESCUTCHEON

SPRINKLER FITTING
(REFER TO DESIGN TOP OF
CRITERIA SECTION) DEFLECTOR

FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
5" to 48"
(127,0 to 1219,2 mm)
ORDER LENGTHS: IN 1/4" (6,4 mm)
5" to 48" INCREMENTS
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS
FACE OF
SPRINKLER
FITTING
MINIMUM
1-3/4" (44,5 mm)
DEFLECTOR
TO CEILING SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 6 FIGURE 7
PENDENT (TY3255) UPRIGHT (TY3155)
WITHOUT ESCUTCHEON WITHOUT ESCUTCHEON
TFP500
Page 5 of 10

ORDER LENGTHS:
2-3/4" to 48" (69,9 to 1219,2 mm)
Operation
IN 1/4" (6,4 mm) INCREMENTS When TYCO Series DS-1 5.6K Pendent,
2-3/8" ± 1/8"
Upright, and Horizontal Sidewall, Stan-
(60,3 ± 3,2 mm)
dard Response, Standard Coverage
FACE OF FACE OF
SPRINKLER MOUNTING
Dry-type Sprinklers are in service,
FITTING SURFACE
water is prevented from entering the
assembly by the Plug with Sealing
Assembly (see Figure 1) in the Inlet of
the sprinkler.
3" DIA.
(76,2 mm) The glass bulb contains a fluid that
expands when exposed to heat. When
3.5° the rated temperature is reached, the
SPRINKLER FITTING
1-3/4" DIA. fluid expands sufficiently to shatter
(REFER TO DESIGN
(44,5 mm)
CENTERLINE 5/16"
the glass bulb, and the Bulb Seat is
CRITERIA SECTION) OF WATERWAY (7,9 mm)
released.
FIGURE 8 The compressed Spring is then able
to expand and push the Water Tube as
HORIZONTAL SIDEWALL (TY3355) well as the Guide Tube outward. This
WITH STANDARD ESCUTCHEON action simultaneously pulls inward on
the Yoke, withdrawing the Plug with
ORDER LENGTHS: Sealing Assembly from the Inlet, allow-
1/2" to 45-3/4" (12,7 to 1162,1 mm) ing the sprinkler to activate and flow
IN 1/4" (6,4 mm) INCREMENTS water.
4-1/4" ± 1/8"

FACE OF
2-1/2" DIA. FACE OF
MOUNTING
(108,0 ± 3,2 mm)
Design
Criteria
(63,5 mm)
SPRINKLER SURFACE
FITTING
TYCO Series DS-1 5.6K Pendent,
Upright, and Horizontal Sidewall, Stan-
3-1/2" DIA. dard Response, Standard Coverage
(88,9 mm) Dry-type Sprinklers are intended for
3.5° use in fire sprinkler systems designed
in accordance with the standard instal-
SPRINKLER FITTING lation rules recognized by the appli-
(REFER TO DESIGN CENTERLINE 5/16" cable listing or approval agency (for
CRITERIA SECTION) OF WATERWAY (7,9 mm) example, UL Listing is based on NFPA
FIGURE 9 13 requirements). For more information
HORIZONTAL SIDEWALL (TY3355) on LPCB Approval, contact Johnson
WITH DEEP ESCUTCHEON Controls at the following office:
Kopersteden 1
ORDER LENGTHS: 7547 TJ Enschede
5-1/2" to 48" (139,7 to 1219,2 mm) The Netherlands
IN 1/4" (6,4 mm) INCREMENTS Tel: +31-(0)53-428-4444
MINIMUM
2-1/4" (57,2 mm)
Fax: +31-(0)53-428-3377

FACE OF DEFLECTOR TO Sprinkler Fittings


SPRINKLER MOUNTING Install 1 in. NPT Series DS-1 Dry-type
FITTING SURFACE Sprinklers in the 1 in. NPT outlet or run
of the following fittings:
• malleable or ductile iron threaded
tee fittings that meet the dimen-
sional requirements of ANSI B16.3
3.5° (Class 150)
5/16"
(7,9 mm) • cast iron threaded tee fittings that
SPRINKLER FITTING
(REFER TO DESIGN CENTERLINE meet the dimensional requirements
CRITERIA SECTION) OF WATERWAY of ANSI B16.4 (Class 125)
FIGURE 10 Do not install Series DS-1 Dry-type
HORIZONTAL SIDEWALL (TY3355) Sprinklers into elbow fittings. The Inlet
WITHOUT ESCUTCHEON of the sprinkler can contact the interior
of the elbow.
The unused outlet of the threaded tee is
plugged as shown in Figure 12.
TFP500
Page 6 of 10

Drainage
Temperatures for Heated Area(1)
In accordance with the minimum
40°F 50°F 60°F requirements of the NATIONAL FIRE
Ambient Temperature
Exposed to (4°C) (10°C) (16°C) PROTECTION ASSOCIATION for dry
Discharge End of Sprinkler pipe sprinkler systems, branch, cross,
Minimum Exposed Barrel Length(2), and feed-main piping connected to Dry
in.
(mm) Sprinklers and subject to freezing tem-
peratures must be pitched for proper
40°F 0 0 0 drainage.
(4°C)
Exposure Length
30°F 0 0 0 When using Dry Sprinklers in wet pipe
(-1°C) sprinkler systems to protect areas
20°F 4 subject to freezing temperatures, use
0 0 Table C to determine a sprinkler’s
(-7°C) (100)
appropriate exposed barrel length to
10°F 8 1 prevent water from freezing in the con-
0
(-12°C) (200) (25)
necting pipes due to conduction. The
0°F 12 3 exposed barrel length measurement
0
(-18°C) (305) (75) must be taken from the face of the
sprinkler fitting to the surface of the
-10°F 14 4 1
(-23°C) (355) (100) (25) structure or insulation that is exposed
to the heated area. See Figure 11 for
-20°F 14 6 3 an example.
(-29°C) (355) (150) (75)
For protected area temperatures
-30°F 16 8 4 between those given above, the
(-34°C) (405) (200) (100) minimum recommended length from
-40°F 18 8 4 the face of the fitting to the outside of
(-40°C) (455) (200) (100) the protected area may be determined
by interpolating between the indicated
-50°F 20 10 6 values.
(-46°C) (510) (255) (150)
Clearance Space
-60°F 20 10 6 In accordance with NFPA 13, when
(-51°C) (510) (255) (150)
connecting an area subject to freez-
Notes: ing and an area containing a wet pipe
1. For protected area temperatures that occur between values listed above, use the next cooler temperature.
2. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).
sprinkler system, the clearance space
around the sprinkler barrel of dry-type
TABLE C sprinklers must be sealed. Due to tem-
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS perature differences between two
MINIMUM RECOMMENDED LENGTHS areas, the potential for the formation
of condensation in the sprinkler and
You can also install Series DS-1 Dry- For dry pipe system installations, subsequent ice build-up is increased. If
type Sprinklers in the 1 in. NPT outlet use only the side outlet of maximum this condensation is not controlled, ice
of a GRINNELL Figure 730 Mechanical 2 1/2 in. reducing tee when locat- build-up can occur that might damage
Tee and GRINNELL G-FIRE Figure 522; ing Series DS-1 Dry-type Sprinklers the dry-type sprinkler and/or prevent
however, the use of the Figure 730 Tee directly below the branchline; other- proper operation in a fire situation.
and Figure 522 for this arrangement is wise, use the configuration shown in
limited to wet pipe systems. Figure 12 to assure complete water Use of the Model DSB-2 Dry Sprinkler
drainage from above Series DS-1 Boot, described in technical data sheet
The configuration shown in Figure 13 TFP591 and shown in Figures 14 and
Dry-type Sprinklers and the branch-
is only applicable for wet pipe systems 15, can provide the recommended seal.
line. Failure to do so may result in pipe
where the sprinkler fitting and water-
freezing and water damage.
filled pipe above the sprinkler fitting
are not subject to freezing and where
the length of the dry-type sprinkler has NOTICE
the minimum exposure length depicted Do not install Series DS-1 Dry-type
in Figure 11. See the Exposure Length Sprinklers into any other type fitting.
section. Failure to use the appropriate fitting
For wet pipe system installations of may result in one of the following:
1 in. NPT Series DS-1 Dry-Type Sprin- • failure of the sprinkler to operate
klers connected to CPVC piping, use properly due to formation of ice
only the following TYCO CPVC fittings: over the Inlet Plug or binding of the
• 1 in. x 1 in. NPT Female Adapter Inlet Plug
(P/N 80145) • insufficient engagement of the
• 1 in. x 1 in. x 1 in. NPT Sprinkler Head Inlet pipe-threads with consequent
Adapter Tee (P/N 80249) leakage
TFP500
Page 7 of 10

RUN
FACE OF OUTLET TO WET SIDE
SPRINKLER PLUGGED SYSTEM OUTLET
FITTING SPRINKLER PLUGGED
FITTING HEATED
HEATED EXPOSURE TO DRY (SEE DESIGN
SYSTEM AREA
AREA LENGTH CRITERIA
(SEE DESIGN SECTION)
DSB-2 CRITERIA AREA DSB-2 SPRINKLER
INTENDED SECTION) SUBJECT DSB-2 INTENDED FITTING
TO INTENDED (SEE DESIGN
FOR FREEZER FOR FREEZER
STRUCTURES FREEZING FOR FREEZER STRUCTURES CRITERIA
STRUCTURES SECTION)

FIGURE 12 FIGURE 13
FIGURE 11 SPRINKLER FITTING SPRINKLER FITTING
EXPOSURE LENGTH UNHEATED AREA HEATED AREA

STRAP TIES 1-3/4" DIA.


(ENDS ON (44,5 mm)
OPPOSING CLEARANCE INSULATED
SIDES OF HOLE FREEZER
BOOT) ADHESIVE STRUCTURE
DSB-2 BOOT
DSB-2
ADHESIVE BOOT

1-3/4" DIA.
(44,5 mm)
CLEARANCE
HOLE
INSULATED
FREEZER
STRUCTURE
STRAP TIES
DS-1
DS-1 (ENDS ON
SHOWN WITH
SHOWN WITH OPPOSING
STANDARD
STANDARD SIDES OF
ESCUTCHEON
ESCUTCHEON BOOT)
FIGURE 14 FIGURE 15
MODEL DSB-2 DRY SPRINKLER MODEL DSB-2 DRY SPRINKLER
BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES
DS-1 DRY-TYPE SPRINKLER DS-1 DRY-TYPE SPRINKLER
TFP500
Page 8 of 10

Installation Note: If sprinkler removal becomes


necessary, remove the sprinkler using
have not operated, should be replaced
if they cannot be completely cleaned
TYCO Series DS-1 5.6K Pendent, the same wrenching method noted by wiping the sprinkler with a cloth or
Upright, and Horizontal Sidewall, Stan- above. Sprinkler removal is easier when by brushing it with a soft bristle brush.
dard Response, Standard Coverage a non-hardening sealant was used Care must be exercised to avoid
Dry-type Sprinklers must be installed and torque guidelines were followed. damage to the sprinklers before,
in accordance with this section. After removal, inspect the sprinkler for during, and after installation. Sprin-
damage. klers damaged by dropping, striking,
General Instructions
Step 3. After installing the ceiling or wrench twist/slippage, or the like, must
Series DS-1 Dry-type Sprinklers must be replaced. Also, replace any sprinkler
wall and applying a ceiling finish, slide
only be installed in fittings that meet that has a cracked bulb or that has lost
on the outer piece of the escutch-
the requirements of the Design Cri-
eon until it comes in contact with the liquid from its bulb. See the Installation
teria section. See the Design Criteria
ceiling/wall. Do not lift the ceiling panel section.
section for other important require-
out of its normal position. The owner is responsible for the
ments regarding piping design and
sealing of the clearance space around When using the Deep Escutcheon, inspection, testing, and maintenance of
the Sprinkler Casing. hold the outer piece in contact with the their fire protection system and devices
mounting surface (ceiling or wall). Then in compliance with this document, as
Do not install any bulb-type sprinkler
rotate the inner piece approximately 1/4 well as with the applicable standards
if the bulb is cracked or there is a loss
turn with respect to the outer piece, of the NATIONAL FIRE PROTECTION
of liquid from the bulb. With the sprin-
to hold the Deep Escutcheon firmly ASSOCIATION, such as NFPA 25, in
kler held horizontally, a small air bubble
together. addition to the standards of any other
should be present. The diameter of the
authorities having jurisdiction. Contact
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) rating to Care and the installing contractor or product
manufacturer with any questions.
Maintenance
1/8 in. (3,2 mm) for the 360°F (182°C)
rating. Automatic sprinkler systems are rec-
ommended to be inspected, tested,
Obtain a leak-tight 1 in. NPT sprinkler TYCO Series DS-1 5.6K Pendent, and maintained by a qualified Inspec-
joint by applying a minimum-to-maxi- Upright, and Horizontal Sidewall, tion Service in accordance with local
mum torque of 20 to 30 lb-ft (26,8 to Standard Response, Standard Cover- requirements and/or national codes.
40,2 N·m). Higher levels of torque may age Dry-type Sprinklers must be main-
distort the sprinkler Inlet with conse- tained and serviced in accordance with
quent leakage or impairment of the this section.
sprinkler.
Before closing a fire protection system
Do not attempt to compensate for main control valve for maintenance
insufficient adjustment in an Escutch- work on the fire protection system
eon Plate by under or over-tightening that it controls, obtain permission to
the Sprinkler. Re-adjust the position of shut down the affected fire protection
the sprinkler fitting to suit. systems from the proper authorities
Notes: and notify all personnel who may be
• Install pendent sprinklers only in affected by this action.
the pendent position; install upright Absence of the outer piece of an
sprinklers only in the upright posi- escutcheon, which is used to cover a
tion. The deflector of a pendent or clearance hole, may delay the time to
upright sprinkler is to be parallel to sprinkler operation in a fire situation.
the ceiling.
A Vent Hole is provided in the Bulb
• Install horizontal sidewall sprinklers Seat (see Figure 1) to indicate if the Dry
in the horizontal position with their Sprinkler is remaining dry. Evidence of
centerline of waterway perpendicu- leakage from the Vent Hole indicates
lar to the back wall and parallel to potential leakage past the Inlet seal
the ceiling. Ensure the word “TOP” and the need to remove the sprinkler
on the Deflector faces the ceiling. to determine the cause of leakage;
Step 1. With a non-hardening pipe- for example, an improper installation
thread sealant such as TEFLON applied or an ice plug. Close the fire protec-
to the inlet threads, hand-tighten the tion system control valve and drain the
sprinkler into the sprinkler fitting. system before removing the sprinkler.
Step 2. Wrench-tighten the sprinkler Sprinklers which are found to be
using either: leaking or exhibiting visible signs of
corrosion must be replaced.
• a pipe wrench on the Inlet Band or
the Casing, see Figure 1 Automatic sprinklers must never be
painted, plated, coated, or other-
• the W-Type 7 Sprinkler Wrench on wise altered after leaving the factory.
the Wrench Flat, see Figure 2 Modified sprinklers must be replaced.
Apply the wrench recess of the W-Type Sprinklers that have been exposed to
7 Sprinkler Wrench to the wrench flat. corrosive products of combustion, but
TFP500
Page 9 of 10

P/N* 60 – XXX – X – XXX

SPRINKLER ESCUTCHEON
SIN FINISH FINISH(1)
Pendent with TY3255 SIGNAL WHITE
96 CHROME
Standard Escutcheon (1 in. NPT) (Figure 3) 0 (RAL9003)
PLATED POLYESTER
Pendent with TY3255
93 Deep Escutcheon (1 in. NPT) (Figure 5) SIGNAL WHITE
NATURAL
1 (RAL9003)
Pendent with TY3255 BRASS
97 POLYESTER
Recessed Escutcheon (1 in. NPT) (Figure 4)
Pendent without TY3255 NATURAL BRASS
92 2
Escutcheon (1 in. NPT) (Figure 6) BRASS PLATED

SIGNAL WHITE SIGNAL WHITE


Sidewall with TY3355 4 (RAL9003) (RAL9003)
94 Standard Escutcheon (1 in. NPT) (Figure 8) POLYESTER POLYESTER
Sidewall with TY3355
53 CHROME STAINLESS
Deep Escutcheon (1 in. NPT) (Figure 9) 8 PLATED STEEL
Sidewall without TY3355
54 Escutcheon (1 in. NPT) (Figure 10) CHROME CHROME
9 PLATED PLATED
Upright without TY3155
98 Escutcheon (1 in. NPT) (Figure 7)
TEMPERATURE ORDER
RATING(2) LENGTH(3)
Notes:
1. Escutcheon Finish applies to sprinklers provided with escutcheons.
2. 360°F (182°C) temperature rating applies to non-recessed sprinkler
0 135°F (57°C) 055 5.50 in.
assemblies.
3. Dry-type Sprinklers are furnished based upon “Order Length” as mea- 1 155°F (68°C) 082 8.25 in.
sured per Figures 3 through 10, as applicable, and for each individual
sprinkler where it is to be installed. After the measurement is taken,
round it to the nearest 1/4 in. increment. 2 175°F (79°C) 180 18.00 in.
* Use Prefix “I” for ISO 7-R 1 Connection (for example, I-60-961-1-180).
3 200°F (93°C) 187 18.75 in.

4 286°F (141°C) 372 37.25 in.

5 360°F (182°C) 480 48.00 in.

TABLE D
SERIES DS-1 DRY-TYPE SPRINKLERS, 5.6K, STANDARD RESPONSE
PART NUMBER SELECTION

Limited • SIN: • P/N from Table D


TY3255 – Pendent Part numbers are for 1 in. NPT stan-
dard order sprinklers. Orders for
Warranty TY3155 – Upright
TY3355 – Horizontal Sidewall all other sprinkler assemblies must
be accompanied by a complete
For warranty terms and conditions, visit • Order Length: description.
www.tyco-fire.com. Dry-type Sprinklers are furnished
based upon Order Length as mea- Sprinkler Wrench
Ordering sured per Figures 3 through 10, as
applicable. After the measurement is
Specify W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Procedure taken, round it to the nearest 1/4 in.
increment.
Sprinkler Boot
Specify Model DSB-2 Dry Sprinkler
Contact your local distributor for avail- • Inlet Connections: Boot, P/N 63-000-0-002
ability. When placing an order, indi- 1 in. NPT
cate the full product name, including This part number includes one (1) Boot,
(Standard) two (2) Strap Ties, and 1/3 oz of Adhe-
description and part number (P/N).
ISO 7-R 1 sive (a sufficient quantity for installing
Dry-type Sprinklers (For information on ISO Inlet Thread one boot).
When ordering Series DS-1 5.6K Connections, contact your Johnson
Pendent, Upright, and Horizontal Side- Controls Sales Representative.)
wall, Standard Response, Standard
Coverage Dry-type Sprinklers, specify • Temperature Rating
the following information: • Sprinkler Finish
• Escutcheon Type and Finish, as
applicable
TFP500
Page 10 of 10

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont