Chap-2-Transient Over Voltages
Chap-2-Transient Over Voltages
2 2.
3.
Principles of Over Voltage Protection
Devices for Over Voltage Protection
Transient 4.
5.
Utility Capacitor Switching Transients
Utility System Lightning Protection
Over 6.
7.
Load Switching Transient Problems
Computer Tools for Transient Analysis
Voltages
1
switching a single capacitor
Capacitor switching switching back-to-back capacitors
transient “magnification”
Synchronous condenser
Other methods to improve
power electronics device
power factor (VSC/STATCOM)
1. Sources of transient over
voltages line energizing
Other switching transients
Faults
Lightning
2
1. Source of Transient Over Voltages
3
1. Source of Transient Over Voltages
5
1. Source of Transient Over Voltages
➢ Transient voltages are caused by the sudden release of stored energy due to incidents such as
➢ External Cause
➢ lightning strikes,
➢ Internal Cause
➢ Capacitor switching
➢ Switching Operation – Contactor/Breaker /Loads
➢ power electronic devices when switched
➢ unfiltered electrical equipment,
➢ contact bounce,
➢ arcing, capacitor bank or
➢ generators being switched ON and OFF.
➢ Transient voltages differ from swells by being larger in magnitude and shorter in duration. 6
1. Source of Transient Over Voltages
8
Internal Cause : 1. Switching Surges
➢ Electrical breakdown is often associated with the failure of solid or liquid insulating materials used
inside HV transformers or capacitors in the electricity distribution grid, usually resulting in short
circuit or blown fuse.
10
Internal Cause : 3. Arcing Ground
12
Internal Cause : 3. Arcing Ground
➢ Some capacitors are energized all the time (a fixed bank), while others are switched
according to load levels;
➢ Various control means,
➢ including time,
➢ temperature,
➢ voltage, current, and
➢ reactive power,
➢ are used to determine when the capacitors are switched.
➢ It is common for controls to combine two or more of these functions
13
Internal Cause : 3. Arcing Ground
Equivalent Circuit
16
Magnification of capacitor switching transient by customer
➢ W.k.t a brief voltage transient of at least 1.3 to 1.4 pu when capacitor banks are
switched. The transient is generally no higher than 2.0 pu on the primary distribution
➢ This may require customer to install high energy MOV
system, although ungrounded capacitor banks may yield some what higher values. surge arresters
➢ customer may install a small inductor (called a
➢ customer’s capacitor bank on LV side of service transformer will see the voltage
reactor) in series with the capacitor bank
transient produced by utility capacitor switching (on MV or HV system). ➢ added advantage of improving harmonic
performance
➢ if the resonant frequency is close to the frequency produced by the utility capacitor,
➢ if a few drives are all that are affected , then
the customer’s capacitor bank will appear to magnify the oscillation locally. the inductor can be added there
17
Magnification of capacitor switching transient by customer
➢ When one or more capacitor banks are switch on when there are
others previously energized (Back-to-back), over voltages will
arise in local and remote buses.
➢ These over voltages are typically smaller than those obtained
when the circuit breaker of the first capacitor bank was closed.
19
Back-to-back capacitor switching
➢ This case occurs due to the switching of a capacitor bank in the presence of already
energized banks on the same bus.
➢ In this case, the transients mainly consist of interchange of current between the banks.
➢ These transient currents can be high in amplitude and frequency and may exceed the
capability of the circuit breaker.
➢ They may induce high over voltages and currents into secondary relaying and metering
circuits by transformation through current transformers and/or magnetic coupling
between busbars and unshielded secondary cables.
20
Ferro-resonance
➢ Ferro-resonance a nonlinear resonance is a type of resonance in electric circuits which occurs when a
circuit containing a nonlinear inductance is fed from a source that has series capacitance, and the
circuit is subjected to a disturbance such as opening of a switch.
➢ Common strategies for managing ferro-resonance include:
➢ Preventing open phase condition,
➢ limiting over voltages,
➢ damping resonance with secondary load,
➢ limiting cable length,
➢ switching at transformer terminals and
➢ grounding transformer primary
21
Ferro-resonance
22
Ferro-resonance
23
Ferro-resonance
24
Ferro-resonance
➢ strike to HV or MV (primary)
line supplying customer
26
External Cause - Lightning
27
External Cause - Lightning
28
External Cause - Lightning
The chief power quality problems with lightning stroke currents entering the
ground system are
➢ They raise the potential of the local ground above other grounds in the
vicinity by several kilovolts.
29
2. Principles of Over Voltage Protection
31
2. Principles of Over Voltage Protection
➢ The main function of surge arresters and transient voltage surge suppressors (TVSSs) is to limit the
voltage that can appear between two points in the circuit.
➢ This is an important concept to understand.
➢ One of the common misconceptions about varistors, and similar devices, is that they somehow are able
to absorb the surge or divert it to ground independently of the rest of the system.
32
2. Principles of Over Voltage Protection
➢ That may be a beneficial side effect of the arrester application if there is a suitable path for the surge
current to flow into, but the foremost concern in arrester application is to place the arresters directly
across the sensitive insulation that is to be protected so that the voltage seen by the insulation is limited
to a safe value.
➢ Surge currents, just like power currents, must obey Kirchoff’s laws.
➢ They must flow in a complete circuit, and they cause a voltage drop in every conductor through which
they flow.
➢ One of the points to which arresters, or surge suppressors, are connected is frequently the local ground,
but this need not be the case
33
3. Devices for Over Voltage Protection
The following points highlight the five main devices used for protection from over-voltage.
The devices are:
2. Isolation Transformers
3. Low-Pass Filters
https://unacademy.com/lesson/source-of-transients-overvoltage-capacitor-switching-and-
restrikes-during-capacitor-denergizing/3UTZWSL3
34
1. Surge Arresters and Transient Voltage Surge Suppressors(TVSS)
➢ Arresters and TVSS devices protect equipment from transient over voltages by limiting the maximum voltage, and the
terms are sometimes used interchangeably.
➢ However, TVSSs are generally associated with devices used at the load equipment.
➢ A TVSS will sometimes have more surge-limiting elements than an arrester, which most commonly consists solely of
MOV blocks.
➢ An arrester may have more energy-handling capability; however, the distinction between the two is blurred by
common language usage.
➢ The elements that make up these devices can be classified by two different modes of operation,
➢ crowbar and
➢ clamping.
35
Crow-Bar Over Voltage Protection
36
Clampers Over Voltage Protection
37
2. Isolation Transformers
➢ Figure.1 shows a diagram of an isolation transformer used to attenuate high frequency noise and transients as they
attempt to pass from one side to the other. However, some common mode and normal mode noise can still reach the
load. An electrostatic shield, as shown in Fig. 2 is effective in eliminating common mode noise.
➢ However, some normal mode noise can still reach the load due to magnetic and capacitive coupling.
38
The chief characteristic of isolation transformers for:
➢ Low-pass filters use the pi-circuit principle to achieve even better protection for high-frequency
transients.
➢ For general usage in electric circuits, low-pass filters are composed of series inductors and parallel
capacitors.
➢ This LC combination provides a low impedance path to ground for selected resonant frequencies.
➢ In surge protection usage, voltage clamping devices are added in parallel to the capacitors.
➢ In some designs, there are no capacitors.
40
3. Low-Pass Filters:
➢ Figure shows a common hybrid protector that combines two surge suppressors and a low-pass filter
to provide maximum protection.
➢ It uses a gap-type protector on the front end to handle high-energy transients.
➢ The low-pass filter limits transfer of high-frequency transients.
41
3. Low-Pass Filters:
➢ The inductor helps block high-frequency transients and forces them into the first suppressor.
➢ The capacitor limits the rate of rise, while the nonlinear resistor (MOV) clamps the voltage
magnitude at the protected equipment.
➢ Other variations on this design will employ MOVs on both sides of the filters and may have
capacitors on the front end as well.
42
4 Low-impedance power conditioners
as part of their design (Fig.) ➢ Note the new neutral-to-ground connection that can be made on
disturbances (i.e., noise and impulses). ➢ The transient can be magnified by the output filter capacitor.
43
https://www.youtube.com/watch?v=1k4ePyG7U2I
44
https://www.youtube.com/watch?v=1k4ePyG7U2I
45
4. Utility Capacitor Switching Transients (CST)
2. Pre-insertion resistors
3. Synchronous closing
4. Capacitor location
46
1. Switching times Capacitor
47
2. Pre-insertion resistors
48
2. Pre-insertion resistors
50
3. Synchronous closing
51
3. Synchronous closing
➢ To avoid pre-strikes, the dielectric strength of the gap between the circuit breaker contacts must exceed
the rate of the system voltage change, commonly identified as RDDS. (Fig.)
➢ However, it is frequently a cost-effective solution when capacitor switching transients are disrupting end-
user load.
52
4. Capacitor location
➢ For distribution feeder banks, a switched capacitor may be too close to a sensitive load or at a
location where the transient over voltages tend to be much higher.
➢ Often, it may be possible to move the capacitor downline or to another branch of the circuit and
eliminate the problem.
➢ The strategy is to either create more damping with more resistance in the circuit or to get more
impedance between the capacitor and the sensitive load.
➢ The success of this strategy will depend on a number of factors.
➢ Of course, if the capacitor is placed at a large load to supply reactive power specifically for that load,
moving the bank may not be an option.
53
5. Utility Lightening Protection
1. Shielding
2. Line arresters
3. Low-side surges
54
1. Shielding
55
1. Shielding
➢ One of the strategies open to utilities for lines that are particularly susceptible to lightning strikes is
to shield the line by installing a grounded neutral wire over the phase wires.
➢ This will intercept most lightning strokes before they strike the phase wires.
➢ This can help but will not necessarily prevent line flashovers because of the possibility of back
flashovers.
➢ Shielding overhead utility lines is common at transmission voltage levels and in substations but is
not common on distribution lines because of the added cost of taller poles and the lower benefit
due to lower flashover levels of the lines.
56
2. Line arresters
57
2. Line arresters
➢ Another strategy for lines that are struck frequently is to apply arresters periodically along the phase
wires.
➢ Normally, lines flash over first at the pole insulators.
➢ Therefore, preventing insulator flashover will reduce the interruption and sag rate significantly.
➢ Stansberry argues that this is more economical than shielding and results in fewer line flashovers.
➢ Neither shielding nor line arresters will prevent all flashovers from lightning.
➢ The aim is to significantly reduce flashovers in particular trouble spots.
➢ As shown in Fig. the arresters bleed off some of the stroke current as it passes along the line.
58
3. Low-side surges
59
3. Low-side surges
➢ Some utility and end-user problems with lightning impulses are closely related.
➢ One of the most significant ones is called the “low-side surge” problem by many utility engineers.
➢ The name was coined by distribution transformer designers because it appears from the
transformer’s perspective that a current surge is suddenly injected into the low-voltage side
terminals.
➢ Utilities have not applied secondary arresters at low-voltage levels in great numbers.
➢ From the customer’s point of view it appears to be an impulse coming from the utility and is likely to
be termed a secondary surge.
60
6. Switching Transient Problems with Loads
• Since transient voltages due to utility capacitor switching typically exceed 130
percent, the probability of nuisance tripping of the drive is high.
62
6. Switching Transient Problems with Loads
3 Transformer energizing
64
6. Switching Transient Problems with Loads
➢ Energizing a transformer produces inrush currents that are rich in harmonic components for a period
lasting up to 1 s.
➢ If the system has a parallel resonance near one of the harmonic frequencies, a dynamic overvoltage
condition results that can cause failure of arresters and problems with sensitive equipment.
➢ This problem can occur when large transformers are energized simultaneously with large power factor
correction capacitor banks in industrial facilities.
➢ The equivalent circuit is shown in Fig.
➢ A dynamic overvoltage waveform caused by a third harmonic resonance in the circuit is shown in Fig.
➢ This form of dynamic overvoltage problem can often be eliminated simply by not energizing the
capacitor and transformer together
65
7. Computer
Tools for
Transient
Analysis
66
67
68