Marine Certified System, MCS-3 Data Sheet: Generator Protection (ANSI) M-Logic (Micro PLC)

The Marine Certified System MCS-3 is a compact all-in-one control unit for protection and control of synchronous or asynchronous generators. It contains necessary functions like generator protection, busbar protection, engine control and protection, display, and communication features. Setup and configuration can be done via the display interface or USB connection to a PC.

Uploaded by

jordan navarro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
3K views11 pages

Marine Certified System, MCS-3 Data Sheet: Generator Protection (ANSI) M-Logic (Micro PLC)

The Marine Certified System MCS-3 is a compact all-in-one control unit for protection and control of synchronous or asynchronous generators. It contains necessary functions like generator protection, busbar protection, engine control and protection, display, and communication features. Setup and configuration can be done via the display interface or USB connection to a PC.

Uploaded by

jordan navarro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 11

Marine Certified System, MCS-3

DATA SHEET

Marine Certified System, MCS-3


DATA SHEET

Generator protection (ANSI) M-logic (Micro PLC)


 2 x reverse power (32)  Simple logic configuration tool
 5 x overload (32)  Selectable input/output events
 6 x overcurrent (50/51)
 2 x overvoltage (59) Engine control and protection
 3 x undervoltage (27)
 Engine start/stop
 3 x over-/underfrequency (81)
 Emergency stop
 Voltage-dependent overcurrent (51V)
 Current/voltage unbalance (60)  Shutdown channels with wire break supervision
 Loss of excitation/overexcitation  Back-up of shutdown channels
(40/32RV)  Shutdown override
 9 x NEL groups
Display
Busbar protection (ANSI)  Status texts
 3 x overvoltage (59)  Info messages
 4 x undervoltage (27)  Alarm indication
 3 x overfrequency (81)  Prepared for remote mounting
 4 x underfrequency (81)  Prepared for additional remote displays
 Voltage unbalance
 3 x NEL groups General
 USB interface to PC
 Free PC utility software for commissioning
 Programmable parameter, timer and alarms
 User-configurable texts

Document no.: 4921240363B


SW version 3.0x.x or later
Data sheet Marine Certified System, MCS-3
Application Self-test
The Marine Certified System (MCS-3) is a compact all The MCS-3 automatically carries out a cyclical self-test
in one microprocessor-based control unit containing all at start-up. If any errors are found, they will be
necessary functions for protection and control of a displayed in clear text in the display and indicated with
synchronous/asynchronous generator. It contains all a relay output (status output).
necessary galvanically separated 3-phase measuring
circuits. M-logic (Micro PLC)
This configuration tool is part of the PC utility software
The MCS-3 is intended for marine-based applications. It which is free of charge. With this tool, it is possible to
is designed for the following applications (can be customise the application to your needs. It is possible to
combined): dedicate specific functions or logical conditions to
different inputs and outputs.
1. Stand-alone
2. Parallel with other generators Engine control and protection
The MCS-3 will control the start and stop sequences of
The MCS-3 can synchronise the generator and after
the engine and furthermore provide full back-up of
synchronisation carry out all necessary generator
engine shutdown channels in case the main processor
control and protective functions. It is well-suited for
fails.
PLC-controlled systems, and the interfacing can be
done via binary and analogue I/Os or via serial
communication. Setup
Setup is easily done via a menu structure in the display
(password-protected) or via the USB PC connection.
Display unit
The display unit is separate and can be installed directly
on the main unit or in the front of the switchboard door
(3m display cable included). Up to two additional Approvals
displays can be installed within 200m. The MCS-3 is marine-approved by all major
classification societies and is UL/cUL listed.
The display unit shows all measured and calculated
values as well as alarms and data from the event log.

Operation modes
Four different regulation modes can easily be selected
through digital inputs on the standard MCS-3, and the
governor will be controlled accordingly:

1. Fixed frequency
2. Fixed power (base load)
3. Frequency droop
4. Load sharing

Page 2 of 11
Display layouts
Standard delivery
DEIF A/S
Data sheet Marine Certified System, MCS-3
Application examples

Engine and generator protection Synchronisation and load sharing

MCS MCS MCS

Loadsharing line

PLC-controlled system

PLC

Modbus

MCS MCS MCS

Loadsharing line

The MCS-3 can be used in simple or complex applications. The above shows some of the applications,
but due to the flexible mode selection, the MCS-3 can be used in all applications.

Page 4 of 11
Data sheet Marine Certified System, MCS-3
Available options
Option CAT part no. Description Slot Option Note
no. type
G Load sharing
G3 355-4035 Load sharing and synchronisation Software
H Serial communication
H7 355-4036 CANbus J1939 engine communication 7 Software

J Cables
J6 355-4037 Display cable with plugs, 1m UL94 (V1) Other One cable per MCS-3
approved unit is included as
standard
J7 355-4038 PC cable for utility software (USB) 3m Other
UL94-approved (V1)
X Display One display per MCS-
3 unit is included as
standard
X2 355-4040 Additional standard display. CANbus Other Two X2 options can be
comm. ordered for each PPU
unit

Page 5 of 11
Data sheet Marine Certified System, MCS-3
Hardware overview

Slot #4, term. 65-72 (std.) Slot #6, term. 90-97 (std.)
GOV/AVR/transducer output Analogue inputs

EF5: 1 x PWM governor output M15.6: 4 x 4…20mA inputs


1 x +/-20mA out for AVR
2 x relay outputs

Slot #2, term. 29-36 (std.) Slot #8, term. 126-133

90 91 92 93 94 95 96 97
65 66 67 68 69 70 71 72

Modbus communication (std.)


Analogue inputs
H2: Modbus RTU/ASCII (RS485) M13.8: 7 x digital inputs
51 52 53 54 55 56 57 58 59 60 61 62 63 64

Display

85 86 87 88 89
Service port

Slot #1, term. 1-28 (std.) Slot #7, term. 98-125 (std.)
USB Memory

Power supply Engine I/F


79 80 81 82 83 84
Ethernet

8-36V DC supply, 11W M4: 8-36V DC supply, 5W


37 38 39 40 41 42 43 44 45 46 47 48 49 50

1 x status output relay 1 x magnetic pick-up (MPU)


5 x relay outputs 3 x multi-inputs
7 x digital inputs
Self check ok

2 x pulse outputs (kWh, kVArh)


Alarm inhibit
Engine CAN
PMS CAN
Ethernet

4 x relay outputs
Power

5 x digital inputs
USB

73 74 75 76 77 78

H7: CANbus J1939 (requires M4)

Slot #3, term. 37-64 (std.) Slot #5, term. 73-89 (std.)
I/O and load sharing AC measuring

M12: 13 x digital inputs 3 x generator voltage


4 x relay outputs 3 x generator current
1 x P load sharing line 3 x busbar/mains voltage
1 x input for ext. setpoint LED & I/F (std.)
Display connection
Service port (USB)
Power LED
Self check LED
Alarm inhibit LED

Page 6 of 11
Data sheet Marine Certified System, MCS-3

Page 7 of 11
Data sheet Marine Certified System, MCS-3
Technical specifications
Accuracy: Class 1.0 Binary:
Max. resistance for ON
Fast overcurrent:
detection: 100
3% of 350%*In
Not galvanically separated
Analogue outputs:
PT100/1000:
Class 1.0 according to total
-40…250C, +/-1%
range
Not galvanically separated
To IEC/EN 60688 To IEC/EN 60751
VDO:
Operating temp.: -25…70C (-13...158 F)
0…1700, +/-2%
(UL/cUL Listed: Max. surround-
Not galvanically separated
ing air temp.: 55C/131F)
V DC:
Storage temp.: -40…70C (-40...158 F) 0…40V DC, +/-1%
Not galvanically separated
Climate: 97% RH to IEC 60068-2-30
Relay outputs: Electrical rating:
Meas. voltage: 100-690V AC +/-20% 250V AC/30V DC, 5A
(UL/cUL Listed: 480V AC phase- (UL/cUL Listed: 250V AC/24V DC,
phase) 2A resistive load)
Consumption: Max. 0.25VA/phase Thermal rating @ 50C:
2A: Continuously
Meas. current: -/1 or -/5A AC 4A: tON = 5 sec., tOFF = 15 sec.
(UL/cUL Listed: From CTs 1-5A)
(Unit status output: 1A)
Consumption: Max. 0.3VA/phase
Open collector
Current overload: 4 x In continuously outputs: Supply: 8…36V DC, max. 10mA
20 x In, 10 sec. (max. 75A)
80 x In, 1 sec. (max. 300A) Analogue outputs: 0(4)...20mA and +/-25mA
Galvanically separated
Meas. frequency: 30…70Hz Active output (internal supply)
Load max. 500
Aux. supply: Terminals 1 and 2: (UL/cUL Listed: Max. 20mA
12/24V DC (8...36V output)
continuously, 6V 1 sec.)
Max. 11W consumption Update rate:
Transducer output: 250ms
Terminals 98 and 99: Regulator output: 100ms
12/24V DC (8...36V
continuously, 6V 1 sec.) Analogue load
Max. 5W consumption sharing lines: -5…0…+5V DC,
The aux. supply inputs are to Impedance: 23.5 k
be protected by a 2A slow-blow
fuse
(UL/cUL Listed: AWG 24)

Binary inputs: Optocoupler, bi-directional


ON: 8…36V DC
Impedance: 4.7k
OFF: <2V DC

Analogue inputs: 0(4)…20mA


Impedance: 50
Not galvanically separated
RPM (MPU): 2…70V AC, 10…
10000Hz, 250…3000

Multi-inputs: 0(4)…20mA:
0-20mA, +/-1%
Not galvanically separated

Page 8 of 11
Galv. separation: Between AC voltage, AC (class 2)
current and other I/Os:
3250V AC, 50Hz, 1 min. Shock (base
mount): 10g, 11msec, half sine
Between analogue outputs To IEC 60255-21-2 Response
and other I/Os: (class 2)
500V DC, 1 min.
30g, 11msec, half sine
Between binary input groups To IEC 60255-21-2 Endurance
and other I/Os: (class 2)
500V DC, 1 min.
50g, 11msec, half sine
Response times: To IEC 60068-2-27
(Delay set to minimum)
Bump: 20g, 16msec, half sine
Busbar: To IEC 60255-21-2 (class 2)
Over-/undervoltage: < 50ms
Over-/underfrequency: < 50ms Material: All plastic materials are self-
Voltage unbalance: <200ms extinguishing according to UL94 (V1)
Generator:
Reverse power: <200ms Plug connec-
Overcurrent: <200ms tions: AC current:
Fast overcurrent: < 40ms 0.2-4.0 mm2 stranded wire
Over-/undervoltage: <200ms (UL/cUL Listed: AWG 18)
Over-/underfrequency: <300ms
Overload: <200ms
Current unbalance: <200ms AC voltage:
Voltage unbalance: <200ms 0.2-2.5 mm2 stranded wire
React. power import: <200ms (UL/cUL Listed: AWG 20)
React. power export: <200ms
Overspeed: <400ms Relays:
Digital inputs: <250ms (UL/cUL Listed: AWG 22)
Emergency stop: <200ms Terminals 98-116:
Multi-inputs: <800ms 0.2-1.5 mm2 stranded wire
Wire failure: <600ms (UL/cUL Listed: AWG 24)
Other:
Mounting: DIN-rail mount or base mount 0.2-2.5 mm2 stranded wire
with 6 screws (UL/cUL Listed: AWG 24)

Safety: To EN 61010-1, installation Display:


category (overvoltage 9-pole sub-D female
category) III, 600V, pollution Service port:
degree 2 USB A-B
To UL 508 and CSA 22.2 no.
14-05, overvoltage category Protection: Unit: IP20
III, 300V, pollution degree 2 Display: IP52 (IP54 with gasket:
Option L)
EMC/CE: To EN 61000-6-1/2/3/4 (UL/cUL Listed: Type Complete
IEC 60255-26 Device, Open Type)
DEIF A/S

IEC 60533 power distr. zone To IEC/EN 60529


IACS UR E10 power distr.
zone

Vibration: 3…13.2Hz: 2mmpp


13.2…100Hz: 0.7g
To IEC 60068-2-6 & IACS UR
E10
10…60Hz: 0.15mmpp
60…150Hz: 1g
To IEC 60255-21-1 Response
(class 2)
10…150Hz: 2g
To IEC 60255-21-1 Endurance
Data sheet Marine Certified System, MCS-3
Approvals: Marine-approved by all major
classification societies
UL/cUL Listed to UL508

UL markings: Wiring:
Use 60/75C copper conductors only
Mounting:
For use on a flat surface of type 1
enclosure
Installation:
To be installed in accordance with the
NEC (US) or the CEC (Canada)

Weight: Base unit: 1.6 kg (3.5 lbs.)


Display: 0.4 kg (0.9 lbs.)

Page 10 of 11
Data sheet Marine Certified System, MCS-3

Unit dimensions in mm (inches)