Glazed Elements - Fenestration Performance Requirements

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Glazed Elements - Fenestration Performance Requirements 19-2-2012 v1

Thermal Bridges: for all new air conditioned buildings, Thermal


Plot No.
Glazed Elements - Fenestration Performance Light Bridges, such as connection points between concrete or steel
Thermal Shading beams, external walls and columns and around doors and
Project Requirements as per Green Building Regulations & Transmittance -
Transmittance -U Coefficient - SC windows, which enable the flow of heat from outide into the
Specifications LT
Consultant W/m2 K building, must be eliminated or insulated to reduce the amount of
heat transfer
(1) If percentage of total area of external walls that let
Glazed Elements - Fenestration Percentage Orientation of Glazed Facades
lights to the external wall area is:
Wall Glazing Elements Percentage to the Glazing Portion of a Roof Percentage to the 1-1 Equal or less than 40% 2.10 (max) 0.40 (max) 0.25 (min) Perdominately North
External Wall Area Total Roof Area 1-2 Between 40% - 60% 1.90 (max) 0.32 (max) 0.10 (min) Orientation Percentage Is:
32%
Total Glass Area 282.37 m2 Total Glass Area m2 1-3 Equal or greater than 60% 1.90 (max) 0.25 (max) 0.10 (min)
Total External wall (2) For shopfronts and showrooms, other than those at
1607.44 m2 Total Roof Area 902.92 m2 1.90 (max) 0.76 (max)
Area ground floor level: For new buildings, other than villas and industrial
(3) If percentage of glazing portion of a roof to the roof buildings, at least 50% of the total glazed surface area of
18% area is: the building,(excluding glazed area with back insulated
3-1 Equal or less than 10% 1.90 (max) 0.32 (max) 0.40 (min) panels), must have a north orientation which include 150
degree angle started from east to northwest.
3-2 Greater than 10% 1.90 (max) 0.25 (max) 0.30 (min)

Hide Empty Rows

No. of Windows on the Exposed Orientation


Glazed Elements Thermal Light
Height Width Item Area Shading
Perdominately North Orientation No. of Glass Layers Transmittance - U Transmittance - Color Type Note
SE S SW W H Coefficient - SC
LT
Reference Name/No. m m m2 NW N NE E Horizontal W/m2 K
W-01 1.20 0.77 0.92 7.00 2.00 1.90 0.32 0.25 L
W-02 1.35 1.20 1.62 14.00 2.00 1.90 0.32 0.25 L
W-03 2.65 2.50 6.63 7.00 7.00 2.00 1.90 0.32 0.25 L
W-04 2.31 2.00 4.62 3.00 2.00 1.90 0.32 0.25 L
D-05 2.20 3.00 6.60 14.00 2.00 1.90 0.32 0.25 L
D-06 2.20 3.52 7.74 7.00 2.00 1.90 0.32 0.25 L
Total Glazed Area at the Corresponding Orintation (m2): 89.38 192.98

Wall Consultant Comments:


Height Width Total Area Light Reflective Value
No.
Reference Name/No. m m m2 LRV (%)
WALL-1 1.00 1607.44 1.00 1607.44 45.00 Light Colors on the Outside of Buildings: For all new buildings, at least 75% of the area
of externally painted walls must have a minimum Light Reflective (LRV) Value of 45%

Roof
Length Width Total Area Roof Solar Reflective Urban Heat Island Effect: All opaque external roofing surfaces must comply with a
Type of Roof
Reference Name/No. m m m2 Index - SRI minimum Roof Solar Reflective Index (SRI) Value according to table below for a minimum
ROOF 1.00 902.92 902.92 Flat & or Low 78.00 of 75% of the roof area:
Type of Roof Min. Roof SRI
Steep Sloped Roofs (slopes steeper than
≥ 29.00
1:6)
Flat and Low Sloped Roofs ≥ 78.00